HomeMy WebLinkAboutOrdinance 10327s
~~
L r~f~ ~j-$
ORDINANCE NO
~ .. ~`j 1t ^~ ~ 1L
AN ORDINANCE ADOPTING THE 1988 UNIFORM BUILDING CODE
WITH AMENDMENTS BY AMENDING SECTION 7-46, 7-47, 7-48,
RND 7-49 OF THE CODE OF THE CITY OF FORT WORTH (1986),
REGULATING THE ERECTION, CONSTRUCTION, ENLARGEMENT,
ALTERATION, REPAIR, MOVING, REMOVAL, DEMOLITION,
CONVERSION, OCCUPANCY, EQUIPMENT, USE, HEIGHT, AREA,
AND MAINTENANCE OF BUILDINGS AND STRUCTURES IN THE CITY
OF FORT WORTH; PROVIDING FOR THE ISSUANCE OF PERMITS
AND THE COLLECTION OF FEES THEREOF; PROVIDING FOR THE
INSPECTION OF BUILDINGS; PROVIDING PENALTIES FOR THE
VIOLATION THEREOF; PROVIDING THAT THIS ORDINANCE SHALL
BE CUMULATIVE; PROVIDING A SEVERABILITY CLAUSE;
PROVIDING A SAVINGS CLAUSE; PROVIDING FOR PUBLICATION
IN PAMPHLET FORM; PROVIDING FOR PUBLICATION IN THE
OFFICIAL NEWSPAPER; PROVIDING FOR ENGROSSMENT AND
ENROLLMENT; AND PROVIDING AN EFFECTIVE DATE
~sE iT ORDAINED BY THE CITY COUNCIL OF THE CITY OF FORT
WORTH, TEXAS
SECTION 1
Section 7-46 to the Code of the City of Fart Worth {1986) is
amended to read as follows ~ ~
Sec 7-46 1988 EDITION OF THE UNIFORM BUILDING CODE
ADOFTED
(a) The Building Code of the City of
revised and amended to conform to the 1988
Buildings Code of the International Confere
officials, as amended hereby, and the same
hereby adopted as the Building Code of the
from the effective date thereof
Fort Worth is hereby
edition ~~f the Uniform
nce ~~f Building
as amended hereby is
City of Fort Worth
(b) The following provisions of the Appendix to the 1988
edition of the Uniform Building Code, as amended hereby, are
i~tereby specifically adopted as part of the Building Code of the
City of Fort Worth Chapter 1, Division 1, Life Safety
Requirements for Existing Buildings other t.h.an High-Rise
Buildings; Division 2, Existing High-Rise Buildings as amended;
Chapter 7 Aviation Control Tower; Chapters-2.3, Division 1,
Alternate Snow Load Design; Chapter 32, Re-roofing, Chapter 38,
Basement. Pipe Inlets; Chapter 49, Patio Covers; Chapter 51
Elevators, D~~mbwaiters, and Escalators; Chapter 55, Membrane
Structures; Chapter 56. Piers and Boathouses; and Chapter 70,
Excavation and Grading as amended
0
(c) The 1988 edition of the Uniform Building Code Standards
of the International Conference of Building Officials, amended
hereby, is hereby adopted as a part of the Building Code of the
City of Fort Worth, as more specifically set forth in Chapter 60
of this Code
(d) Three copies of the 1988 edition of the Uniform
Building Code, including the Appendix thereto, marked Exhibit
"A", and three copies of the 1988 edition of the Uniform Building
Code standards, marked Exhibit "B", are incorporated herein by
refe-rence and shall be filed in the office of the City Secretary
for permanent record and inspection
SECTION 2
Section 7-47 of the Code of the City of Fort Worth (1986) is
amended to read as follows
Sec 7-47 Amendments.
(a) The 1988 edition of the Uniform Building Code,
including the Appendix thereto (Exhibit "A") and the 1988 edition
to the uniform Building Standards (Exhibit "B") are hereby
amended as provided in this Section Three copies of such
amendments are specifically incorporated herein by reference and
shall be filed in the office of the City Secretary for permanent
record and inspection
(b) The 1988 edition of the Uniform Building Code is hereby
amended by revising the following sections as follows
SECTION 104
Section 104 (a) unchanged.
Bbl Additions, Alterations, or Repairs. Additions,
ait.eratlons ar repairs may be made to any building or structure
without ~equirir:g the existing building or structure to comply
with all the requirements of this code, provided the addition,
alteration, or repair conforms to the requirements for a new
building or structure Additions, alterations, or repairs shall
not be made to an existing building or structure which will ~~ause
the existing building or structure to be in violation of any of
the provisions of this code nor shall such additions or
alterations cause the existing structure to become unsafa An
unsafe condition shall be deemed to have been created if an
addition or alteration will cause the existing building or
structure tc~ become structurally unsafe or overloaded or will
not provide adequate egress in compliance with the provisions of
this ~~ode or will obstruct. existing exits; or will create a fire
hazard, will reduce required fire resistance or will otherwise
~~
n
-3-
create conditions dangerous for occupancy, shall not exceed the
height, number of stories and area permitted for new buildings
Any building plus new additions shall not exceed the height,
number of stories, and area specified for new buildings.
Additions or alterations shall not be made to an existing
building or structure when such existing building or structure is
not in full compliance with the provisions of this code except
when such addition or alteration will result in the existing
building or structure being no more hazardous based on life
safety, fire safety, and sanitation, than before such additions
or alterations are undertaken [See also Section 911 (c) for
Group H, Division 6 Occupancies 1
The second paragraph is unchanged.
(c) Existing Installations. Except as provided in Section
610, 809, 1009, 1202, and 1210 of this Code, buildings in
existence at the time of the adoption of this code may have their
existing use or occupancy continued, if such use or occupancy was
legal at the time of the adoption of this code, provided such
continued use is not dangerous to life
Any change in the use or occupancy of any existing building
or structure shall comply with the provisions of Section 307 and
502 of this code
For existing buildings, See Appendix Chapter
In addition to Appendix Chapter 1, the following sections
shall apply
Sec 502; Sec 510 (a) & (b); Sec 1204; Sec 1205 (a)
& (b); Sec 1206 (a) & (b); Sec 1207 (a), (b), & (c);
Sec 1707 (a), (b), (c), & (d); Sec 2303 (a); Sec
2307; Sec 2309 (a) & (b);
Sec 2311 (a); Sec 2403 (a); Sec 2501 (a), (b), &
(c); Sec 2516; Sec 2601; Sec 2701; Sec 2801 (a);
Sec 2907 (a), (b), (c), & (f); Sec 3001 (a) & (b);
Sec 3201 and Sec 3313 (a) & (b)
(d), (e), and (f) are unchanged except (f)2 reads:
Any unsafe conditions as described in this code are
corrected The Building Official shall use Appendix
Chapter 1 as a guideline to determine unsafe
conditions Unsafe conditions to be corrected shall
include but not be limited to those provisions
specified for existing buildings in Appendix Chapter 1
~~ _
-4-
SECTION 108
Section 108 Registration of
Remodeling Work. Permits shall be
which has a valid registration with
where the purpose is to add, alter,
buildings or structures within the
Contractors Performing
issued only to a business
the City of Fort Worth, and
or repair residential
city limits of Fort Worth
(a) Registration. Each business shall list its principals
and an official, in its employ, who will be designated as
controlling officer The controlling officer shall be
responsible for all permits obtained by him or any employee of
his business. Each registered business shall notify the City of
Fort Worth, in writing, of its permanent business and residential
address and its designated official Permits shall not be issued
where a registration does not exist or has been revoked
(b) Fees. A one hundred dollar ($100,00) fee will be paid
in order to register a business An annual renewal fee of one
hundred dollars will be paid thereafter
(c) Contractor Identification. Each job site will be
identified with a sign located in the front yard, or on the
structure front so as to be visible to the street The sign may
not be larger than two (2) feet by two (2) feet and no smaller
than one and one-half (1-1/2) feet by one and one-half (1-1/2)
feet and must display the contractor's business name and the
contractor's registration number The registration number shall
be no smaller than two and one-half (2-1/2) inches high
(d) Homeowner Permits Homeowners are exempt from the
registration requirement However, a building Permit will be
secured where required by the Building Code
(e) Registration may be revoked by the Building Official
for due cause The Construction and Fire Prevention Board of
Appeals may hear revocation appeals by applicants desiring
reinstatement
SECTION 204
Sec 204 The Construction and Fire Prevention Board of
Appeals shall act on Building Code related matters commensurate
with the provision of Ordinance Number 9282 of the City of Fort
Worth
SECTION 301
Sec 301 (a) unchanged.
(b) Exempted work A building permit shall not be required
for the following
.~
x
s.r,,..
-5-
1 Fences not over 6 feet high.
2 Oil Derricks
3 Water tanks.
4 Painting, papering, and similar work provided that the
paper meets the thickness and flame spread requirements
of Chapter 42.
5 Temporary motion picture, television, and theater
stage sets and scenery
6 Collapsible window awnings in Group R, Division 3 and
Group M Occupancies
7 All roof repairs on Group R, Division 3 and Group M
Occupancies
8 Movable cases, counters, and partitions not over 5 feet
9 inches high.
Unless otherwise exempted, separate plumbing, electrical,
and mechanical permits will be required for the above exempted
items
Exemption for the permit requirements of this code shall not
be deemed to grant authorization for any work to be done in any
manner in violation for the provisions of this code or any other
laws or ordinances of this jurisdiction
SECTION 302
Sec 302 (a) unchanged.
(b) Plans and specifications. With each application for a
building permit, and when required by the Building official for
enforcement of any provisions of this code or any other City of
For Worth Ordinance, two sets of plans and specifications shall
be submitted When circulation of the site plan to other
departments is required, a minimum of nine copies of the site
plan shall be submitted along with plans and specifications The
Building Official shall require plans and specifications to be
prepared and designed by an engineer or architect licensed by the
State of Texas to practice as such
For plumbing, electrical, and mechanical design sheets and
calculations, the following code sections are applicable
(1) Fort Worth Plumbing Code, Section 1 11
(2) Fort Worth Electrical Code, Section 302
(3? Fort Worth Mechanical Code, Section 302
EXCEPTIONS When authorized by the Building Official, plans
and specifications sealed by an architect or engineer need not be
submitted for the following
(1) any private dwelling or apartments not exceeding eight
units per building for one story buildings, or apartments
not exceeding four units per building and having a maximum
height of two stories, or garages other structures
pertinent to such buildings
n.
-6-
(2) private buildings which are to be used exclusively for
farm, ranch, or agricultural purposes, or used exclusively
for storage of raw agricultural commodities
(3) other buildings, except public buildings, having no more
than one story and containing no clear span between
supporting structures greater than 24 feet on the narrow
side and having a total floor area not in excess of five
thousand square feet On unsupported spans greater than 24
feet on such buildings, only the trusses, or other roof
supporting members need to be engineered or pre-engineered
and properly sealed
l4) a shell building in excess of five thousand square feet
that does not include interior design and layout, requires
only an engineering seal The tenant spaces within a shell
building (after the shell is constructed) shall require an
architect's seal when the space exceeds five thousand
square feet
(5) unless exempted above, site plans for all buildings will be
sealed with either an engineer or an architect stamp unless
a drainage study is involved at which time an engineer's
seal is required
(6) Small and unimportant work
The Building Official, when he deems necessary, may require
engineering calculations
(c) & (d) unchanged.
SECTION 303
Sec 303 (a), (b), and (c) unchanged
:d) Expiration. Every permit issued by the Building
Official under the provisions of this code shall expire ley
limitation and become null and void if the building or work
authorized by such permit is not commenced within 180 days from
the date of such permit, or if the building or work authorized by
such permit is suspended or abandoned for 180 days at any time
after the work is commenced, or if the owner shown on the permit
application is changed Before such work can be recommenced, a
new permit shall be first obtained to do so, and the fee thereof
shall be one-half the amount required for a new permit for such
work, provided no changes have been made or will be made in the
original plans and specification for such work; and provided
farther that such suspension or abandonment has not exceeded one
1~ear Any permittee holding an unexpired permit may apply for an
extension for the time within which he may commence work under
that permit when he is unable to commence work with the time
~~equired by this section for good and satisfactory reasons The
Building Official may extend the time for action by the permittee
for a period not exceeding 180 days upon written request
;`i ,.
-7-
SECTION 304
Sec 304 (a) Permit Fees.
be set forth in Table No 3-A
The fee for each permit shall
The determination of value or valuation under any other
provisions of this code shall be made by the Building Official
The value to be used in computing the building permit fee shall
be the total value of all construction work for which the permit
is issued as well as all finished work, painting, roofing,
electrical, plumbing, heating, air conditioning, elevators, fire
extinguishing systems, and any other permanent equipment A
building permit issuance fee of ten (10) dollars shall be
required upon issuance of a permit
EXCEPTION These provisions shall apply to new construction
and additions Separate permits shall be required for
remodeling Where work for which a permit is required by
this code is started or commenced prior to obtaining said
permit or permission from the Building Official, the fees
specified in Table No 3-A shall be doubled The payment of
such double fee shall not relieve any person from fully
complying with the requirements of this Code in the
execution of the work, nor from any other penalties
prescribed herein
(h) Plan Review Fees A plan review fee shall be submitted
with each application for a permit in the amount as follows
(1) Plans requiring review without circulation X75 00
(2) Plans requiring circulation $200 00
The review fee will be credited to the cost of the building
permit at the time the building permit fee is paid
EXCEPTION The Building Official may waive the plan review
fees on Group R-3 and M Occupancies
(c~ Inspection Fees Tn addition to the fees charged in
Table 3-A, the following inspection fee shall be charged
(1) Demolition and moving inspection fee, based upon
total square footage, as follows
-~
~.4~
-8-
1 thru 1,000 - $ 40
1,001 thru 2,000 80
2,001 thru 3,000 150
3,001 thru 5,000 225
5,001 thru 10,000 300
10,001 thru 20,000 400
20,001 and above 800
EXCEPTIONS:
1. Buildings ordered demolished by the City of
Fort Worth
2 No permit or permit fee shall be required for
' the demolition of structures by the State of
Texas for highway widening purposes
3 Those inspection fees specified in Chapter 46
for the permanent or temporary use of public
property
t2) A fee of $50 shall be charged for a change of
occupancy permit where an occupancy permit is required
by this code An occupancy permit fee shall not be
required for new construction where a building permit
fee has been paid
(3) For billing changes or meter changes as required
by the electrical code involving all commercial or
industrial occupancies, an ordinance inspection by a
mechanical, electrical, plumbing, and building
inspector will be made where there is a necessity for
one or more such inspectors because of the nature of
the existing equipment or proposed use to be made of
the existing building or space The fee for this
inspection is $20.00 per inspector or $80 00 maximum
This ordinance inspection shall include billing and
meter changes for gas and water services
The inspections covered by this section shall
include, but not be limited to the following
Annual Inspection Fee
Dance Halls
Mobile Home Parks
Night Clubs
Day Care
Rest Homes
Auto Junk Yards
Inspection for Licensing
Dance Halls
Night Clubs
Day Care
Rest Homes
Auto Junk Yards
}
l
~ f`K~'
Miscellaneous Ordinance and Occupancy Inspection
All Users
Meter Changes
House Moving and Demolition Permits
(4) A fee of $25 shall be charged for all
encroachment variance letters
(5) A fee of $10 shall be charged for all zoning
verification letters
(e) Fee Refunds remains the same except (f)2 which reads
-9-
2 The Building Official may authorize the refunding
of not more than 80 percent of the permit fee paid when
no work has been done under a permit issued in
accordance with this code Where no work has commenced
for a period exceeding 180 days from the issuance of
the permit, one-half of the fee may be refunded
provided that not less than $50 shall be retained by
the Building Official
(f) (added) A fifty dollar ($50) annual registration fee
shall be charged f.or all group homes, halfway houses,
and Group I and Group II care facilities
SECTION 306
Sec 306 (a) General remains the same except for the
exceptions which read
1 Concrete On concrete work when structural design is
based on f'c in excess of 2,500 pounds
Masonry Masonry work shall have special inspection
when required in Chapter 24
3 Welding On all structural welding
4 Reinforced Gypsum Concrete When cast-in-place Class B
reinforced gypsum is being mixed or deposited
5 Special Cases On special construction or work
involving unusual hazards or requiring constant
.inspection
cb), (c) (d), ~e), (f), and (g) unchanged.
SECTION 307
Sec 307 (a) and (b) unchanged.
r}, ~'Prs
-10-
tc) Certificate Issued. Upon final inspection and at the
request of the owner after he has certified that he has complied
with all code provisions, a Certificate of Occupancy shall be
issued by the Building Official or his deputies The Certificate
of Occupancy shall show the following:
1 The building permit number
2 Address and legal description
3. The zoning
4. The occupancy classification
5 The occupant load
6 The type of construction
7 The name of the Building Official
8 Owner's name and address
9 For B 2 storage, annotation on the Certificate of
Occupancy will be as approved by the administrative
authority
(d) unchanged.
te) Posting. The Certificate of Occupancy shall be posted
in a conspicuous place on the premises and shall not be removed
except by the Building Official. Those premises not posting a
Certificate of Occupancy shall be required to comply with this
section upon notification by any inspection agent of the City of
Fort Worth A Certificate of Occupancy shall not be withheld
based on non-compliance when a building meets the ordinance under
which it was constructed
(f) unchanged.
(q) Special Provisions. A Temporary Certificate of
Occupancy for a period not to exceed 24 months may be issued by
the Building Official for a structure not in compliance with this
Code (exiting excluded), provided:
The location and utilities meet all other ordinances of
the City
The area of the structure does not exceed 2,500 square
feet
The Temporary Certificate of Occupancy is issued to a
specific applicant and is not transferable
Upon separate application, the Construction and Fire
Prevention Board of Appeals may extend the Temporary Certificate
of Occupancy originally granted beyond the 24-month period of
time, not exceeding a time period of 12 months, provided the
Building Official has certified that the structure is being
maintained as approved under the original conditions of the
Temporary Certificate of Occupancy
.~, .:
-11-
The Building Official may revoke any permanent or temporary
Certificate of Occupancy for noncompliance with any provisions of
the certificate or this Code In addition, where any unsafe
condition results 'from the use of any utilities in noncompliance
with said certificate of occupancy or this Code, the Building
Official may order in writing that such utilities be
disconnected
(h) The issuance of any certificate of occupancy shall not
be construed to permit or sanction any violation of the
provisions of this code or any other ordinances, rules, or
regulation The issuance of a Certificate of Occupancy shall not
prevent the Building Official from thereafter requiring the
correction of such violations or from revoking the Certificate or
preventing building operations from being carried on thereunder
when in violation of this code or any other ordinances, rules, or
regulations
SECTION 403 (added)
Baby Sitting Service The care of six (6) or less children
for a part of the twenty-four (24) hour day that meets the
requirements of and either licensed or registered by the State of
Texas
SECTION 405 (added)
Day Care Home A place where more than six (6) non-related
children are cared for a part of the twenty-four (24) hour day
that meets the requirements of and licensed by the State of
Texas This definition does not include the foster care program
cr baby sitting for six (6) or less pre-kindergarten age
children
SECTION 409 (added)
Highrise Building A highrise building is a building having
floors used for human occupancy located more than 75 feet above
the lowest level of Fire Department vehicle access
SECTION 503
Sec 503 (a), (b), (c), and (d) 1 and 2 unchanged.
(d)3 In the one-hour separation between a Group R3, and M
Occupancy, the separation may be limited to the installation of
not less than one-half inch thickness gypsum board construction
on the garage side and a weather-stripped door will be permitted
in lieu of a one-hour fire assembly Fire dampers shall not be
required in ducts piercing this separation for ducts constructed
of not less than No 26 gauge galvanized steel
-12-
(d)4 Two-family dwelling units shall be separated by two
one-hour occupancy separation walls that are carried to the roof
deck Existing two-family dwelling that are subdivided into
separate ownerships shall provide one-hour occupancy separation
that extends to the roof deck
SECTION 506
Sec 506. (a), (b), and (c) unchanged except (c) 1, 2, 3,
and 4 are replaced with
1 Section 3802(f) for Group H, Divisions 1, 2, and 3
Occupancies
SECTION 507
Sec 507 remains the same except for items under the second
paragraph which are changed to read
1 Section 3802(f) for Group H, Divisions 1, 2, 3, 6, and 7
Occupancies
2 Section 3802(8) for Group I, Division 1 Occupancies used
for hospitals or nursing homes in Type II one-hour; Type
III one-hour; Type IV or Type V one-hour construction
See chapters 6 to 12 inclusive for special occupancy
provisions
SECTION 508
Sec 508 remains the same except for exceptions 1 and 2
EXCEPTION No 1 Such substitution shall not waive nor
reduce required fire-resistive construction for
1 Occupancy separations [Section 503(c)]
2 Exterior wall protection due to proximity of property
lines [Section 504(b)]
3 Area Separations [Section 505(e)]
4 Shaft enclosures [Section 1706]
5 Dwelling units Separations [Section 1202(b))
6 Corridors except as specifically exempted in Sec 3305
(g) and (h)
7 Stair enclosures [Section 3309]
8 Exit passageways [Section 3312(a))
9 Type of construction separation [Section 1701]
10 Atriums constructed in accordance with Section 1715
fa a
-13-
EXCEPTION No 2 (added) In Type II fire resistive
structures which are not required to comply with Section
1807, those assemblies required by Table 17-A to be two-hour
fire resistive may be reduced to one hour
SECTION 510
Sec 510 Remains the same except the following is added
(c) The use of ventless fans are allowed where one commode
and one lavatory meet the Code and are located in an enclosure
SECTION 511
Sec 511 Remains the same except the following is added
(e) Where there are State of Texas handicapped requirements
that conflict with this code, the most restrictive standards
shall prevail
SECTION 601
Sec 601 Group A Occupancies.
Divisions 1, 2, 2 1, 3, and 4 unchanged.
Division 5 Buildings and structures located on race track
site, such as auto and horse racing tracks, shall be constructed
of at least Type II-N construction Such facilities shall be
sprinklered as required by Chapter 38 Division 4 building area
requirements shall apply
SECTION b10
Sec 610 Fire Alarms Fire alarms shall be provided for
all new and existing Group A, Divisions 1, 2, and 2 1 Occupancies
with an occupant load greater than 300, and restaurants and night
clubs where alcohol is consumed with an occupant load greater
than 200 as required by the Fire Code
EXCEPTION Churches, when used primarily for worship
SECTION 709
Sec 709 Construction Construction shall be of
non-combustible materials Open parking garages shall meet the
design requirements of Chapter 23 Ramp access open parking
garages in which motor vehicles are parked above ground level
shall be provided with steel or concrete guardrails not less than
twenty-four (24) inches in height and designed to withstand a
static load of six (6) tons applied at any point on the
-14-
guardrail Such guardrails shall be located and adjacent to all
outer walls and along the periphery of all above ground level
open decks, floors, and roofs used for parking Mechanical-
access parking garages shall be provided with curb guards not
less than eight (8) inches in height approximately three (3) feet
from the outer edge of each above ground level deck Ground
level parking areas shall be provided with wheel guards not less
than six (6) inches in height so located as to prevent
automobiles from encroaching on adjacent public or private
property
SECTION 901
Sec 901 (a) Division 1 and 2 unchanged except 6,
Exception 1 reads
EXCEPTIONS 1 Rooms or areas used for woodworking that do
not exceed 1500 square feet in area may be classified as
Group B, Division 2 Occupancies, provided dust-producing
machines are equipped with approved dust collectors
Sec 901 (a) Divisions 3, 4, 5, 6, and 7 unchanged.
TABLE 9-A
Add the following paragraph to Footnote Number 1
Automotive battery charging equipemnt with a
capacity of not more than ten (10) batteries and having
an exhaust ventilation system when containing more than
four (4) batteries shall not be considered a control
area provided that
1) A business using more than one (1) such grouping
shall separate such groupings by a distance of 100
feet, and
2) that any such grouping placed within an enclosed
space that has an area less in size than ten (10)
times the area required by the chargers shall be
considered a control area, and
3) that such uses shall be considered to be a Group H
Occupancy when they cannot meet these provisions
~~ ~
-15-
SECTION 1202
Sec 1202 (a) unchanged.
(b) Special Provisions. Walls and Floors separating
dwelling units in the same building shall be of not less than
one-hour fire-resistive construction
Group R, Division 1, Occupancies more than two stories in
height or having more than 3000 square feet of floor area above
the first story shall not be less than one-hour fire-resistive
construction throughout except as provided in Section 1705(b)2
Storage or laundry rooms that are within Group R, Division
1, Occupancies that are used in common by tenants shall be
separated from the rest of the building by not less than one-hour
fire-resistive occupancy separation
An approved fire alarm system shall installed in Group R
occupancies in accordance with the City of Fort Worth Fire Code.
For Group R, Division 1, Occupancies with a Group B,
Division 1, parking garage in the basement of first floor, see
Section 702(a)
For one- and two-family dwellings and apartment buildings,
open metal carport structures may be constructed within zero (0)
feet of the property line when the location of such is approved
as required by other City ordinances
SECTION 1204
Sec 1204 Unchanged except for adding Note 3 to last
paragraph
3 A permit is obtained to install approved systems
SECTION 1210
Sec 1210 (a) 1, 2, 4, & 5 unchanged.
Sec 1210 (a)3, add Exception 1
EXCEPTION NO 1 When a building is gutted for
remodeling purposes or the entire electrical system is
remodeled, the smoke detectors shall be hard wired and
detectors shall be interconnected
Sec 1210 (b) unchanged.
~,
-16-
SECTION 1704
Table 17-A Add the following as a footnote
In those cases where it proves necessary to replace all
or part of an ordinary wood shingle roof, Class A, B, or C
singles may be overlaid on the wood shingles if permitted by
Appendix Chapter 32
Ordinary wood shingle or shake roofs located on Group
R, Division 1, Occupancies at the time of adoption of this
ordinance shall be required to be removed and replaced with
a Class C roofing material or covered with Class C shingles
at the end of their 80~ amortization of life expectancy or
February 11, 1988, whichever is later The 80$ life
expectancy of ordinary wood singles is 14 4 years for Number
1, 12 years for Number 2, and 9 6 years for Number 3 The
time clock countdown for such life expectancy starts on the
date the building upon which the roof is installed received
final inspection from the Building official or his
representative All ordinary wood shake roofs located on
Group R, Division 1, Occupancies now in existence shall be
required to be removed and replaced with a Class C roofing
material or covered with Class C shingles prior to February
11, 1988 Buildings which are not in compliance with this
provision shall be vacated until made to conform
EXCEPTION A wood shingle roof may be treated to
provide a reduced fire hazard or extend the fire
retardant life of the roof The roof shingle coating
is required to meet all testing listed in the Uniform
Building Code Standard 32-7 Tests may be accomplished
by an approved testing facility The maximum time
frame allowed to extend fire retardant life of the roof
shingles is limited to that time frame certified by an
approved testing facility
Skylights shall be constructed as required in Chapter
34
Penthouses shall be constructed as required in Chapter
36
For attics, access, and area, see Section 3205
For roof damage, see Chapter 3207
.SECTION 1706
Sec 1706 (a) is unchanged except for exceptions 1 and 5
which read
-17-
EXCEPTIONS: 1. In other than Groups H, I, and R-1
Occupancies, an enclosure will not be required for openings
which serve only an adjacent floor and are not connected
with opening serving other floors and which are not
concealed within the building construction. For enclosure
of stairways and ramps see Section 3309
5 In one- and two-story buildings other than Group H, I,
and R-1 Occupancies, shafts for gas vents and ducts or
piping which extend through not more than two floors need
not comply with Table No 17-A In Group R, Division 3
Occupancies, less than three stories in height, shafts for
gas vents and for ducts and piping which extend through not
more than two floors need not comply with Table No 17-A
SECTION 1709
Sec 1709 (a) General Parapets shall be provided on all
exterior walls of buildings
EXCEPTIONS 1 Walls which are not required to be of
fire-resistive construction
2 Walls which terminate at roofs of not less than two-hour
fire-resistive construction
3 Walls where, due to location on property, unprotected
opening are permitted
4 Walls on all buildings having a floor area of not more
than 1000 square feet per floor
5 Areas where a minimum ten-foot wide public easement is
dedicated on adjacent properties for maintenance and
restricting the space from construction except for cross
fences
6 An existing residential building changing in use to a
commercial use may have a non-combustible finish roof in
place of the required parapet
(b) unchanged.
SECTION 1807
Special Provisions for High-Rise Occupancies
Sec 1807 (a) Scope This section shall apply to all
occupancies having floors used for human occupancy located more
than 75 feet above the lowest level of fire department vehicle
access Such building shall be provided with an approved
automatic sprinkler system in accordance with Section 1807(c)
-18-
(b) through (e) unchanged
(f) Central Control Station. A central control station for
fire department operations shall be provided The location of
the central control station shall be approved by the fire
department The central control station room or area shall have
a minimum of 96 square feet with a minimum dimension of eight (8)
feet It shall contain the following as a minimum:
1 The voice alarm and public address system panels
2 The fire department communications panel
3 Fire detection and alarm system annunciator panels
4 Annunciator visually indicating the location of the
elevators and whether they are operational
5 Status indicators and controls for air-handling systems
6 Controls for unlocking all stairway doors
simultaneously
7 Sprinkler valve and water-flow detector display panels
8 Emergency and standby power controls and status
indicators
9 A telephone for fire department use with controlled
access to the public telephone system
10 Fire pump status indicators
it Schematic building plans indicating the typical floor
plan and detailing the building core, exit facilities,
fire protection systems, firefighting equipment, and
fire department access
12 Work table
All control panels in the central control section shall be
permanently identified as to function
(g) through (k) unchanged.
SECTION 1907
Sec 1907 Type II-FR buildings shall comply with the
special provisions on high-rise buildings in Section 1807
EXCEPTION The reduction provisions for roofs in Section
1807(c) Item No 2A, are not permitted
SECTION 2308
Sec 2308 (a) unchanged.
(b) Retaining Walls. Retaining walls shall be designed to
resist the lateral pressure of the retained material in
accordance with accepted engineering practice Walls retaining
drained earth may be designed for pressure equivalent to that
{
-19-
exerted by a fluid weighing not less than 30 pounds per cubic
foot and having a depth equal to that of the retained earth. Any
surcharge shall be in addition to the equivalent fluid pressure.
Retaining walls shall be designed to resist sliding or
overturning by at. least 1.5 times the lateral force or
overturning moment.
All retaining walls exceeding four (4) feet in height should
have an engineer's seal affixed to the plans. Retaining walls
constructed of railroad ties shall not exceed four (4) feet in
height
(c) and (d) unchanged.
SECTION 2516
Sec 2516 (a) through (m) unchanged except (c)11,
(f)4B(ii) and (g)4
Sec 2516 (c) 11 reads same with this exception added
EXCEPTION Where approved wood of natural resistance to
decay is not used, all wood exposed to the weather shall be
painted or treated with an approved treatment
Sec 2516(f)4B(ii) reads same with exception 2 changed as
follows
EXCEPTION 2 Attic draftstops may be omitted above one
tenant separation wall and intervening corridor walls
provided the area between draftstops does not exceed 3000
square feet and not more than two tenant spaces are directly
below any undivided attic area
Sec 2516 (g) 4 reads same with this exception added
EXCEPTION In other than 1- and 2-family dwellings, wood
shingles and shakes shall not be used as an exterior wall
covering within seven (7) feet of grade unless the area
immediately adjacent to the building is covered with
pavement a minimum of 20 feet in width As an alternative,
a five-foot green space followed by fifteen (15) feet of
pavement is permissible All wood shingle and shakes to be
used as an exterior wall covering must be Class C Rated for
roofing
SECTION 2517
Sec 2517 (g) 1 Unchanged.
-20-
Add the following to (g)2
Concrete wall panels used in
connected in such a manner as
case of fire The design for
accomplished and sealed by a
professional engineer
SECTION 2903
Sec 2903 (a) Unchanged.
construction shall be
to resist collapse in
this purpose shall be
State of Texas registered
(b) Drainage. Drainage from roofs of any commercial
building or structure shall be contained within property line and
shall not be allowed or caused to drain to adjacent properties
Drainage from downspouts or any commercial building or structure
shall be connected to lateral storm sewer piping or, in the
alternative, water therefrom shall be otherwise contained and
directed in accordance with accepted engineering practice as
approved by the Director of Transportation and Public Works
(c) Trench Safety. On all construction projects in which
trench excavations exceed five (5) feet, public or private,
within the corporate limits of the City, or within the
extraterritorial jurisdiction, the bid documents and contracts
for such projects shall contain
(1) detailed plans and specifications for adequate trench
safety systems that meet the Occupational Safety and
Health Act Standards; and
(2) a pay item for the trench safety system
This requirement shall not apply to persons subject to
safety standards adopted under Article 6053-1, V C T S and
subject to the administrative penalty provisions of Article
6053-2, V C T S
(d) Minimum distance of swimming pools from foundations.
Swimming pools may not be closer to a .building foundation than
one horizontal foot at finish grade for every vertical foot of
swimming pool depth
EXCEPTION A foundation designed by an engineer may be
placed closer to the pool
SECTION 2907
Sec 2907 (a), (b), (c), (d), and (e) unchanged.
(f) Foundation Plates or Sills. Foundation plates or sills
shall be bolted to the foundation or foundation wall with not
-21-
less than 1/2-inch nominal diameter steel bolts embedded at
least seven (7) inches into the concrete or masonry and spaced
not more than six (6) feet apart There shall be a minimum of
two bolts per piece with one bolt located within twelve (12)
inches of each end of each piece A properly sized nut and
washer shall be tightened on each bolt to the plate Foundation
plates and sills shall be the kind of wood specified in Section
251&(c) as approved by the Building Official
SECTION 3205
Sec 3205 (a), (b), and (c) unchanged, except the following
is added to (c)
Where eave or cornice vents are used to provide the
ventilation of combustible attic spaces, vent openings shall not
be located within three (3) feet measured laterally above the
window or door openings in the wall of the story immediately
below
` a _
7AbLE 32- A
TABLE 32-A MINIMUM ROOF CLASSES
ype of
Construction
I
FR
1-f~R I
N I
1-Hft d
N V
ii.T. V
1-HR y
N
Occupancy
IA.1 A 6 - -- - - - -
;A)2-Z.1 A B B - B - B B -
±A- 3
I
IA_a A
A B
B 6
B B
B B
B B
8 Q
B B
B B
B
B)1_z A B B B 8 B B B B
p)3_4 A G ! 6 B 6 G B B B
E A ~ B B B B B B B B
y_1 A A A A B d B B B
N)z_'~4 A B Q B B 6 B B B
)1-2 A B 8 - B - $ Q ~ -
L_3 A B B ~ - B - - B -
0 0 0 0 0 0 0 0 0
R- I A B B B B f3 C C C
Ott- 3 B Ol Ol Ol Ol Ol Ol Ol Ol
A Class A roofing
B Class B roofing
C ~ Class C roofing
0 = Ordinanry roof coverings
l~hen a parapet is not provided on the property Line of an attached duelling, a Class B
roof covering shall be used except where a pe!blie easement is dedicated as permitted by
Section 1709.(a). Exception ~.
Mote
Roof Coverings shall be as specified in Section 3204.
~~
-22-
SECTION 3206
Sec 3206(a) through (f) unchanged, except the exception is
added to (f) 3
EXCEPTION For sprinklered buildings, curtain boards are
required to be not less than four (4) feet in depth for all
occupancies
SECTION 3301
Sec 3301 (a) unchanged.
(b) Definitions. CORRIDOR, PUBLIC is an enclosed exitway
protected as required by Section 3305 (g) and (h) A public
corridor shall be required for any exit used by two or more
tenants on a floor of a building
CORRIDOR, PRIVATE is a corridor within a tenant space which
has exits leading to a public corridor or exit Private
corridors shall meet the requirements of Section 3305(b), (c),
(e), and (f)
SECTION 3304
Sec 3304 (a) through (d) and (f) through (k) unchanged
(e) Electronic Locking Device Alternatives. 1 Small
Rooms In rooms or areas having not more than 1500 square feet
of retail or commercial office floor area, an approved smoke
detection system shall be installed throughout the room or area
nerved by the electronic latch Doors which are electronically
latched shall swing freely when the electronic latch is
released The electronic latch shall
(A) Automatically release upon activation of the smoke
detection system, and
(B) Automatically release upon loss of electrical power to
the building, the electronic latch, the smoke detection
system, or the exit illumination system as required by
Section 3313, and
(C) Automatically release upon actuation of a release
button located adjacent to each door which is
electronically latched When pressed, the button shall
immediately release the latch The release button
shall have a minimum area of nine (9) square inches and
a minimum dimension of three (3) inches The button
shall be red and clearly state, "Push to Exit" in white
letters, and
-23-
(D) Be required to be relatched manually at the door
EXCEPTION: Latches may be relatched automatically when
the release was initiated by the push button, provided
all other release modes require manual relatching of
the door
2 Other Areas. In rooms or areas having more than 1500
square feet of retail or commercial office floor area, the
installation of electronic latches shall comply with all of the
provisions contained in subsection 1 above and shall meet the
following additional requirements
(A) The entire building shall be protected throughout by an
approved automatic sprinkler system, and
(B) Any waterflow alarm or trouble signal initiated by the
sprinkler system shall cause the latch to immediately
release
(1) Additional Doors. When additional doors are available
for human egress purposes, they shall conform to all provisions
of this chapter
EXCEPTION Approved revolving doors having leaves which
will collapse under opposing pressures may be used in exit
situations, provided
1 Such doors have a minimum width of six (6) feet
six (6) inches
2 At least one conforming exit door is located
adjacent to each revolving door
3 The revolving door shall not be considered to
provide any exit width
SECTION 3305
Sec 3305 (a) through (i) unchanged except (g) Add
exceptions 7 and 8 as follows
7 Except for Groups H, I, and R-1 Occupancies,
corridors serving only one tenant space shall be
equipped with an automatic extinguishing system The
sprinkler system, when in operation, must sound local
alarm systems and shut down the existing HVAC systems
8 Except for Groups H, I, and R-1 Occupancies, corridors
shall not be required to be protected when the building
is entirely protected by an approved automatic sprinkler
system The sprinkler system must sound an alarm and
shut down the existing HVAC
-24-
(j) Solid core wood or gasketed hollow metal doors shall be
provided in all interior corridors of R-1 Occupancies at a
spacing along the length of the corridor not to exceed a 100-foot
length of the corridor Such doors, when held in the open
position, shall be automatic closing and shall be activated by
smoke detectors
SECTION 3306
Sec 3306 (a) through (i) and (k) through (q) is
unchanged.
(j) Handrails. Stairways shall have handrails on each
side, and every stairway more than 88 inches in width shall be
provided with not less than one intermediate handrail for each 88
inches of width Intermediate handrails shall be spaced
approximately equally across the entire width of the stairway
The remainder of (j) remains the same
SECTION 3309
read
Sec 3309 remains the same except 3309 (a) is changed to
EXCEPTION In other than Group H, Group I, or Group R,
Division 1, Occupancies, an enclosure will not be required
for a stairway, ramp, or escalator serving only one adjacent
floor and not connected with corridors or stairways serving
other floors For enclosure of escalators serving Group B
Occupancies, see Chapter 17
SECTION _3801
Sec 3801 remains the same except definition of standpipe
~Iass I system which reads as follows
(c:) Definitions CLASS I is a standpipe system with a
water supply consisting of a one-inch water fill connection at
the top of the riser to maintain piping normally wet and a Fire
Department connection which is equipped with 2-1/2 inch outlets
for use by Fire Department or trained personnel
Also, 3801 (d) is changed to read
(d) Standards Fire-extinguishing systems shall comply
with rJ B C Standards Nos 38-1, 38-2, 38-4, and 38-5
EXCEPTIGNS ? Automatic fire-extinguishing systems not
covered by U B C Standard No 38-1, 38-2, 38-4, or 38-5
shall be approved and installed in accordance with the Fire
Code
-25-
2. Automatic sprinkler systems may be connected to the
domestic water-supply main when approved by the Building
Official, provided the domestic water supply is of adequate
pressure, capacity and sizing for the combined domestic and
sprinkler requirements. In such case, the sprinkler system
connection shall be made between the public water main or
meter and the building shutoff valve, and there shall not be
intervening valves or connections. The Fire Department
connection may be omitted when approved by the Fire
Department
3 Where sprinklers are installed in electrical rooms they
shall be separated from the building's main sprinkler system
by a preaction valve This valve shall be connected to fire
detection device(s) in the electrical room Sprinkler
piping shall remain dry until the fire detection device
activates and opens the preaction valve Sprinkler
head(s)shall be of a type to remain closed until sufficient
heat is present to open them Detection devices shall have
a minimum temperature rating of 165 degrees F The
sprinkler(s) shall have a minimum temperature rating of 212
degrees F Sprinkler heads in electrical rooms shall be
protected with a listed guard over the head
SECTION 3802
Sec 3802 (a) Where Required. An automatic fire-
extinguishing system shall be installed in the occupancies and
location as set forth in this section For special provisions on
hazardous chemicals, magnesium, calcium carbide, or high-piled
or rack storage in warehouse or speculative warehouse property,
see the Fire Code
Regardless of the provisions of 3802(b) through (f), all
occupancies four stories or more in height except open parking
garages, shall be sprinklered throughout the building
(b) unchanged.
(c) Group A Occupancies
Paragraphs 1, 2, 3, 4, and 5 unchanged.
6 Automatic sprinkler systems shall be installed in
barns, horse stalls, combustible storage rooms, or
buildings, bleachers, or any use connected to the
bleachers in any manner
(d) Group B, Division 2 Occupancies. An automatic
sprinkler system shall be installed in retail sales rooms classed
as Group B, Division 2, Occupancies where the floor area exceeds
12,000 square feet on any floor or 24,000 square feet on all
floors or in Group B, Division 2, retail sales occupancies more
than three (3) storaes in height The area of mezzanines shall
-26-
be included in determining the areas where sprinklers are
required
Speculative buildings over 12,000 square feet which measure
fifteen (15) feet or more from the floor to the bottom of the
roof structural system shall be protected as Class IV commodities
according to Article 81 of the Fire Code
For tire storage over six-feet high, see Fire Code Section
31 108
For high-pile storage of aerosols over six-feet high, see
Fire Code Section 9 103.
(e) through (h) unchanged.
SECTION 3804
Sec 3804, 4, D Other Approved Fire Protection Equipment.
SECTION 3805
Sec. 3805 (a) unchanged.
(b) Where required, standpipe systems shall be provided as
set forth in Table 38-A For the purposes of this table, a story
height shall be considered to be no more than twelve (12) feet
(c) Location of Class I Standpipes. There shall be a Class
I standpipe outlet connection at every floor level above the
first story of every required stairway above or below grade and
on each side of the wall adjacent to the exit opening of a
horizontal exit Outlets at stairways shall be located with the
exit enclosure or in the case of smokeproof enclosures, within
the vestibule or exterior balcony, giving access to the stairway
Risers and laterals of Class I standpipe systems not located
within an enclosed stairway or smokeproof enclosure shall be
protected by a degree of fire resistance equal to that required
for vertical enclosures in the building in which they are
located
EXCEPTION: In building equipped with an approved automatic
sprinkler system, risers and laterals which are not located
within an enclosed stairway or smokeproof enclosure need not
be enclosed within fire resistive construction
There shall be a two-way outlet above the roofline on
every standpipe when the roof has a slope of less than four
(4) inches in twelve (12) inches
ti
-27-
EXCEPTION Standpipes located in stairways conforming to
Section 3306(0) may have the two-way outlet located at the
topmost floor landing
In building where more than one standpipe is provided,
the standpipes shall be interconnected at the bottom
TABLE 42-B
Table 42-B is changed by changing R-1 Occupancy Group for
other exitways column to Class I
SECTION 4303
Sec 4303(b)6 Delete exception 2.
SECTION 4407
Sec 4407 (a) Protection Required Pedestrian traffic
shall be protected by a railing on the street side when the
walkway extends into the roadway, by a railing adjacent to
excavations and by such other protection as set forth in Table
No 44-A The construction of such protection devices shall be
in accordance with the provisions of this chapter
EXCEPTION In lieu of the above requirements, the Building
Official may permit a solid fence where there is pedestrian
access on the opposite side of the street away from the
construction site and more than half the length of the block
is to be used for construction purposes Where such use is
permitted, the Contractor shall place pedestrian warning
signs on each side of the barricade at corners occupied by
said barricades The pedestrian signs shall read as
`ollows
WARNING
"Pedestrians are required by law to use the opposite
side of the street "
The Contractor shall also provide signs located
approximately every fifty t50) feet horizontally along with
such barricade that reads as follows
WARNING
"No Parking or Standing of Vehicles "
Where one-half or less of a block is to be used for
:onstruction purposes, pedestrian walkways shall be
provided
-2g-
The contractor or person given permission to use any
portion of the street shall provide a stacking lane for
vehicles waiting to load and unload behind the portion of
the street for which permission of use has been granted
All gates and doors in barricades shall swing in toward the
construction site All pedestrian walkways installed in the
street shall include a walking platform
(b), (c), and (d) unchanged.
SECTION 4506
Sec 4506 (a) unchanged.
(b) Construction.
but may have combustible
collapsible, retractable
face of the supporting b
folded, the design shall
any required exit
Awnings shall have noncombustible frames
coverings Every awning shall be
or capable or being folded against the
wilding When collapsed, retracted, or
be such that the awning does not block
EXCEPTION 1 Fixed awnings with a maximum projection of
three (3) feet from the exterior wall of a building may be
erected when such awnings slope downward toward the street
The remaining requirements of this section shall still apply
to fixed awnings
2 A fixed awning not more than ten (10) feet in
length may be erected over a doorway to a building when
exceeding a 3-foot projection and as permitted for marquees
(c) and td) unchanged
SECTION 4601
Sec 4601 (a) General No person, firm, or corporation
shall ~~se or occupy a public street, alley, or sidewalk without
first complying with the requirements of this chapter
No person, firm, or corporation shall perform any work or
store any material in or adjacent to any public street, alley, or
sidewalk that is not in compliance with the provisions of
Chapters 44 and 45 of this Code
(b) Temporary encroachments may be used to permit the
temporary use of public property for other purposes besides
construction The Encroachment Committee in these cases shall
formulate a policy covering such use Each policy shall be
approved by the City Council
z
_29_
SECTION 4602
Temporary Encroachments.
Sec 4602. (a) General. No person- firm- or corporation
shall permanently occupy any public space or work or store
materials in any public space or perform any work in any public
space that requires a permit under this Code without first
obtaining a duly executed Temporary Consent Agreement with the
City of Fort Worth
(b) Temporary Consent Agreement. The applicant shall
furnish a duly executed agreement with the City upon forms
furnished by the City The forms for such agreement shall be
approved from time to time by the City Attorndy and City
Council Approved forms shall be kept and made available in the
offices of the Building Official and City Secretary.
(c) Liability Insurance. The Temporary Consent Agreement
shall be accompanied by proof that the applicant has secured and
paid for a policy of public liability insurance covering all
public risks related to the proposed use and occupancy of public
property as described in the Agreement and permits The amount
of insurance coverage shall be at least the maximum amounts of
liability which can be imposed upon the City under State Law
Each such insurance policy shall provide that it cannot be
canceled or amended without at least ten (10) days advance
written notice to the City
(d) Plans. Each Temporary Consent Agreement shall be
accompanied by a plan showing the location and amount of public
property to be occupied; the location of all railings, fences,
canopies and construction offices, sheds and other appurtenances;
and the nature and location of all warning devices necessary to
protect pedestrian and vehicular traffic It shall be unlawful
for vehicles to park or stand outside the barricade limits
SECTION 4603
Temporary Occupancy.
Sec 4603 (a) Time. For temporary occupancy, the applicant
shall state the estimated length of time the area is to be
occupied
(b) Inspection Fee. In all fire zones, the applicant shall
deposit with Building Official a sum equal to the amount of the
inspection fee for the space calculated on the estimated time in
the following manner
1 If the time does not exceed three (3) days, the fee will
be $30 00 per day up to and including the third day;
t
-30-
2 If the time exceeds three (3) days, the fee per day will
be six-tenths of one cent ($ 006 per square foot of
sidewalk space and one and two-tenths of one cent
($.012) per square foot of street space used
(c) Inspection Fee Refund. If the length of time is
underestimated, the deposit will be retained and an additional
inspection fee shall be required, calculated as set out in
Section 4603(b) If the length of time is overestimated, the
Building Official shall, upon request, calculate the inspection
fee based on the actual number of days and return any overages to
the applicant
(d) Approval. The Building Official is hereby authorized
to execute the Encroachment Agreement on behalf of the City for
temporary use or occupancy of public property The Building
Official shall approve and execute such agreement when the
applicant has complied with all the provisions of this Code
SECTION 4604
r
Special Temporary Occupancy Restrictions.
Sec 4604 (a) The special provisions of this section
shall apply to temporary use or public property
(b) Storage and Use Material or equipment may be placed
or stored on public property subject to the following conditions
1 The Building Official and the Director of Transportation
and Public Works shall determine the area of street, alley,
or public sidewalk which may be used during construction
period for work space and for storage of materials and
equipment Such area shall be based upon the actual need of
the builder, with due consideration being given to public
inconvenience Not more than two (2)-lanes of a four (4)-
lane street nor one (1)-lane of a two (2)-lane street nor
one (1)-lane of a one way street may be blocked and no
material or equipment shall be stored or placed within
8-feet, b-inches of the center line of any railway track
EXCEPTIONS 1 The City Council may approve additional
lanes to be blocked, provided an application and other
agreements and drawings have first been filed with the
Building Official
2 Entire street widths may be approved for closure by
the Director of Transportation and Public Works,
provided the length of time does not exceed one 8-hour
day For this purpose, no encroachment is required
-30a-
2 Alleys adjoining a
been issued may be used
materials and equipment
unobstructed roadway of
maintained through such
such roadway is require
trucks, or for access t
on the alley
building site for which a permit has
for work space and for storage
provided that a clear and
not less than 10-feet in width is
alley along the building site, if
d for use by fire trucks, garbage
o public utilities or other buildings
-31-
3 Any portion of a public sidewalk in front of a building
site for which a permit has been issued may be used for work
space and for storage of materials and equipment, except on
the walkway required to be maintained for public use.
SECTION 4605
Special Working Restrictions.
Sec 46'05 (a) Earth and Rubbish. Earth or other waste
material taken from buildings shall not be stored either upon
sidewalks or streets, but shall be removed therefrom each day
upon accumulation. When dry rubbish is being handled, same shall
be wetted so as to prevent dust and blowing debris.
(b) Demolition. No wrecked or waste materials shall be
placed upon any floor of any building during the course of
demolition so as to cause the overloading of such floor Such
materials shall be lowered to the ground immediately upon
displacement. No material shall be thrown from a building to a
sidewalk or pavement but shall be conveyed to the ground by
properly constructed chutes
Blasting, pulling or throwing of masonry walls shall not be
permitted, except in emergencies, and then such work shall be
permitted under a special blasting permit, issued by the Fire
Marshal with the approval of the Building Official.
SECTION 4606
Dangerous Demolition.
Sec 4606 The Building Official may order the cessation of
the wrecking or demolition of any building or structure within
the City when the same is being accomplished in a reckless or
careless manner or in such a manner so as to endanger life and
property When such work has been ordered stopped by the
Building Official, same shall not be resumed until said official
is satisfied that adequate precautions have been or will be taken
far protection for life and property To continue such work
without the expressed approval of the Building Official shall
constitute a violation of this Ordinance, and each day that such
work continues shall constitute a separate offense
SECTION 4607
Permanent Occupancy.
Sec 4607 (a) No part of any building or structure, or
any appendage thereto, that is not in compliance with the
provisions of this chapter shall project into public property
c
-32-
EXCEPTIONS: 1 The projections in Chapter 45 of this Code
are permitted unless specifically restricted in this
chapter
2 Gratings over openings in public property which have
openings not exceeding 7/16 inch and are designed to
withstand loads in excess of 150 pounds psf may permanently
occupy public property
tb) Permanent Encroachments. All permanent encroachments
into public property not otherwise provided for by the provisions
of this chapter shall require City Council approval.
(c) Signs. Advertising sign projecting into public
property are to be considered a permanent occupancy of public
property All advertising signs shall conform to the City of
Fort Worth Sign Code
EXCEPTIONS 1 An identification sign displayed as part of
a marquee shall be considered a part of the marquee,
provided the sign contains no off-premise advertising, is
displayed to identify or locate the building or place of
business and the height of the message does not exceed three
t3) feet
2 Signs that are covered by existing consent agreements
shall have those consent agreements become null and void
when a sign is altered in size, removed, and requires
structural repair
td) Application schedule for permanent consent agreements.
TABLE 46-A - FEE SCHEDULE
APPROVED BY APPLICATION FEE
1 Building Official when in compliance $ 50 00
with Chapter 45 and the Sign Code
2 City Manager when beyond the property $100 00
line and no closer than 18 inches of
the curb except as provided in 1 above
3. City Council when within 18 inches of the $200 00
curb and over and under the roadway
SPECIAL PROVISIONS The Building Official is hereby authorized
to execute Consent Agreements on behalf of the City covering
signs that do not project more than two t2) feet over public
property when all requirements of this Code and of the Sign Code
have been satisfied
~ S-
...
-33-
SECTION 4608
Permanent Occupancy Special Requirements. ~
Sec 4608. (a) Procedure. The applicant shall forward to
the City Secretary three (3) copies of the duly executed Consent
Agreement, Certification of Insurance, and plans.
(b) Fees. The applicant shall pay to the Building Official
the application and inspection fees as shown in Table 46-A.
fc) Approval. When all requirements of this chapter have
been satisfied, the City Secretary shall forward the application
to the City Council for its consideration
td) When City Council approval is required, the Building
Official shall issue a building permit after such approval
SECTION 4711
Sec 4711 (a) through (d) unchanged.
(e) All interior gypsum wall board must be taped and
bedded
EXCEPTION: Taping and bedding shall not be required when
paneling, battens, or other materials are applied over the
joints
II THE APPENDIX OF THE 1988 EDITION OF THE UNIFORM BUILDING
CODE (EXHIBIT "A") IS HEREBY AMENDED BY REVISING THE FOLLOWING
CHAPTERS AS FOLLOWS
APPENDIX CHAPTER 1
Amend Appendix Chapter 1, Division 1, to read as follows
Chapter 1
LIFE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS
GENERAL
Section 110 (a) unchanged.
(b) Effective Date. Within eighteen (18) months after
notice is given, either under Ordinance 9280, 9281, 10105, 10115,
or this ordinance, plans for compliance shall be submitted and
approved, and within eighteen (18) months thereafter the work
shall be completed or the building shall be vacated until made to
conform
-34-
(c) Alternate Materials and Methods. Alternate materials
and methods may be used, provided such materials or methods
comply with the spirit and intent of this appendix
The Building Official may modify any of the provisions of
this appendix in conformance with Section 106 of this Code
SECTION 111
Sec 111 (a) and (b) unchanged.
(c) Corridors. Corridors of Groups A, E, H, I, and R,
Division 1 Occupancies, serving as an exit for an occupant load
of 30 or more shall have walls and ceilings of not less than
one-hour fire-resistive construction as required by this Code
Existing walls surfaced with wood lathe and plaster in good
condition of 1/2 inch gypsum wallboard or openings with fixed
wired glass set in steel frames are permitted for corridor walls
and ceilings and occupancy separations when approved Doors
opening into such corridors shall be protected by 20-minute fire
assemblies or solid wood doors not less than 1 3/4-inch thick
Where the existing frame will not accommodate the 1 3/4-inch
door, 1 3/8-inch thick solid bonded wood core door or equivalent
insulated steel door shall be permitted Doors shall be
self-closing or automatic-closing by smoke detection' Transoms
and openings other than doors from corridors to rooms shall
comply with Section 3305(h) of this Code or shall be covered with
a minimum of 3/4-inch plywood or 1/2-inch gypsum wallboard or
equivalent material on the room side
EXCEPTIONS (1) Existing corridor walls, ceilings, and
opening protection not in compliance with the above may be
continued when such buildings are protected with an approved
automatic sprinkler system throughout Each sprinkler
system may be supplied from the domestic water system if it
is of adequate volume and pressure
(2) Where an approved fire alarm system is installed,
which includes smoke detection in all common corridors
serving an exit for an occupant load of 30 or more, wall
openings may be non-protected except that doorway openings
shall have self-closing doors The fire alarm system shall
be interfaced with the HVAC System to shut off any central
HVAC unit in any area where a fire is detected and shall be
installed in accordance with Appendix III-C of the Fire
Code
(3) In a corridor of a Group B or E Occupancy, having
been constructed with a six (6) foot wide corridor under
Ordinance #6374, only the approved fire alarm system shall
be required Corridor protection required by this section
will not be required Remodeling of existing corridor wall
must meet requirements for new construction
e
2
-35-
(d) and (e) unchanged.
SECTION 112
Sec 112 Interior vertical .shafts, including but not
limited to stairways, elevator hoistways, service and utility
shafts, shall be enclosed by a minimum of one-hour fire-resistive
construction. All openings into such shafts shall be protected
with one-hour fire assemblies which shall be maintained
self-closing or be automatic closing by smoke detection. All
other openings shall be fire protected in an approved manner.
Existing fusible link-type automatic door closing devices may be
permitted if the fusible link rating does not exceed 135 degrees
F
EXCEPTIONS (1) In other than Group I and Group R,
Division 1 Occupancies, an enclosure will not be required
for openings serving only one adjacent floor.
(2) Stairways in other than Groups H, I, and Group R,
Division 1 Occupancies, need not be enclosed in a continuous
vertical shaft if each story is separated from other stories
by one-hour fire-resistive construction or approved wired
glass set in steel frames In addition, all exit corridors
shall be sprinklered and the openings between the corridor
and occupant space shall have at least one sprinkler head
above the openings on the tenant side The sprinkler system
may be supplied from the domestic water supply if there is
adequate volume and pressure
(3) Vertical openings need not be protected if the
building is protected by an approved automatic sprinkler
system
APPENDIX CHAPTER 1
Amend Appendix Chapter 1, Division 2 to read as follows:
SECTION 120
Sec 120 These provisions apply to all existing high-rise
buildings except Group I, Division 3 constructed prior to the
adoption of this chapter
SECTION 122
Compliance Data
Sec 122 Is unchanged except paragraph two which reads:
Plans and specifications for the necessary alterations
shall be filed with the Building Official within eighteen
(18) months after the date of owner notification Work on
;,_
-36-
the required alterations to the building shall commence
within thirty (30) months of the date of owner notification
and such work shall be completed within five (5) years from
the date of owner notification.
SECTION 124
Appeal
Sec 124 Appeals of determination of the Building Official
in applying the provisions of this Code may be appealed to the
Construction and Fire Prevention Board of Appeals
SECTION 125
Specific Provisions and Alternates
Sec 125 (a) Specific Provisions. Remains the same
except
Delete paragraphs 1 and 2
Add to Paragraph 10: This paragraph shall apply to all
existing Group I, High Rise Occupancies
Add to Paragraph 16
EXCEPTION 1 Where an approved fire alarm system is
installed, which includes smoke detection in all common
corridors serving as an exit for an occupant load of
thirty (30) or more, up to twenty-five percent (25$) of
the wall area of the room common to the corridor may be
tempered glass installed in metal or solid wood
frames The fire alarm system shall be interfaced with
HVAC System to shut off any central HVAC in any area
where a fire is detected
2 Where a corridor of a Group B or E Occupancy,
which has been constructed with a six- (6) foot wide
corridor under ordinance #6374, only the approved fire
alarm system shall be required Corridor protection
required by this section will not be required
Remodeling of existing corridor walls must meet the
requirements for new construction
19 Exit Corridor Dead-Ends The length of dead end
corridors serving an occupant load of more than thirty (30)
shall not exceed thirty-five (35) feet
25 Emergency Planning. See Fire Code, Section 10 501
26. Posting Emergency Plans. See Fire Code, Section
10 502
~-,
-37-
27 Fire Drills. See Fire Code, Section 10.503
(b) Sprinkler Alternatives. Delete items 19 and 20
Item 18 Interior finish in exitways may be reduced by one
classification but shall not be less than Class III.
Installation of meters or backflow preventers for the
connection to the water works system need not be provided
unless required by other regulations of the authority having
jurisdiction
Table A-1-A Change column titled Group B, Division 2, to
read, "All Other Occupancies "
APPENDIX CHAPTER 51
SECTION 5110
Sec 5110 Delete (a) and (c) and add the following to (b)
The Certificate of Inspection shall be conspicuously
displayed and posted in each elevator car or in close proximity
of each dumbwaiter, escalator, or moving walk
(e) Fees. Fees shall be as follows
Annual Business Registration
Annual Inspector's Registration
Certificate of Inspection for each elevator,
escalator, moving walk or commercial
dumbwaiter
(Each escalator or moving walk unit
powered by one motor shall be considered
a separate escalator or moving walk )
SECTION 5113
- $100
- 25
- 20
Sec 5113 (a) Change the word, "periodic" in the first
sentence to read "annual "
Add (f) Inspections shall be performed by certified and
registered inspection organizations and certified and registered
inspectors in accordance with criteria of set forth by the City
of Fort Worth Construction and Fire Prevention Board of Appeals
Add (g) Registration. Each inspection business
organization shall be annually registered with the City of Fort
Worth The business registration shall be authorization for such
business organization to perform inspections and submit
inspection reports All inspectors shall be annually registered
with the City of Fort Worth Only inspection reports submitted by
-38-
registered inspectors who are employed by registered inspection
business organizations shall be acceptable when applying for a
Certificate of Inspection
Add (h) Registration Revocation. The Building Official,
for due cause, may revoke registration of any organization or
inspector Appeals of such revocation may be made to the City of
Fort Worth Construction and Fire Prevention Board of Appeals.
APPENDIX CHAPTER 56
Adopt a New Appendix Chapter 56 as follows:
Chapter 56
PIERS AND BOATHOUSES
Sec 5601 Permit and Applications. No person shall erect,
construct, enlarge, alter, or move any boathouse, pier, or
combination to any body of water within the corporate limits of
Fort Worth under the jurisdiction and control of the City of Fort
Worth No person shall cause any of said acts to be done without
first having made application and obtaining a permit for such
structure
Sec 5602 Approval of Applications and Permits. Each
application for a permit, together with plans for a boathouse,
pier, or any combination thereof shall be approved by the
Building Official or his authorized agent Where such structures
are constructed on Lake Worth or any body of water subject to the
jurisdiction of the Park and Recreation Department of the City of
Fort Worth, the additional approval of such department shall be
obtained
Sec 5603 Use. Boathouses shall be classified as a Group
M Occupancy and shall not be used for Group A through Group R
Occupancies, except where permitted by the Zoning Ordinance,
together with the approval of the Park and Recreation Department
for those properties and uses in or adjacent to Lake Worth or any
body of water subject to the jurisdiction of the Park and
Recreation Department of the City of Fort Worth
Sec 5604 Design, Design Loads All pier and pier
platforms shall be designed to withstand the live and dead loads
specified in Chapter 23 of this Code The minimum live load for
the pier platform shall be 40 psf Piles shall conform to
Chapter 29 of this Code
Sec 5605 Length and Width Requirements. The minimum
width of any pier shall be four (4) feet The maximum length of
any pier shall not exceed 100 feet
~~' A
-39-
Sec 5606 Construction. Piers shall meet or exceed the
minimum requirements for construction as follows:
(a) 1 Wood Piles: Wood piles shall be a minimum of six (6)
inches in diameter. Such piles shall be driven to a
minimum depth of twenty-four (24) inches below the top
layer of silt Such piles shall be driven in pairs,
one on either side of the platform, and braced as
required by Paragraph (e) of this section. Such piles
shall not be spaced apart more than ten (10) feet
center to center
2 Metal Piles: Metal piles shall be a minimum of three
(3) inches inside diameter pipe capable of being driven
to a minimum depth of twenty-four (24) inches below the
top layer of slit. Such piles shall be driven in
pairs, one on either side of the platform, and braced
as required by Paragraph (e) of this section Such
piles shall not be spaced apart more than then (10)
feet center to center
3 Alternate Method: Sets of structural columns of the
same size forming a box crib may be used Such crib
shall be braced as required in Paragraph (e) of this
section and anchored as required in paragraph (g) of
this section
(b) Beams. Beams shall be defined as those members which
connect to piers or support the stringers All beams when
of wood shall be a minimum nominal 2-inch material
(c) Stringers. Stringers shall be defined as those members
usually supporting the decking All stringers when of wood
shall be of a minimum 2-inch material Pipe stringers
shall be a nominal 2-1/2-inch I D and spaced not more than
eighteen (18) inches O C
(d) Decking. 1 Wooden platform decking shall be of a minimum
nominal 2-inch material
2 Other materials, to include lightweight concrete or
metal decking may be used when approved by the Building
Official Such decking shall meet the load requirements of
Section 5605
(e) Bracing. 1 All wooden bracing shall be of a minimum
nominal 2-inch material
2 Bracing shall be accomplished by one or more of the
following methods
a Cross or "X" bracing Cross or "X" bracing may be
used on each set of pier and box cribs
Fy.
-40-
b Beams may be used as bracing, provided the
connections give sufficient support to resist
horizontal forces equivalent to that of cross or
"X" bracing
c Knee bracing Knee bracing shall be used on each
pier attached to and paralleling the platform
deck Pipe knee bracing shall be a nominal 2-1/2-
inch I D
(f) Flotation Units. All flotation units shall adequately
support the dead and live loads of all beams, stringers,
and platforms Data shall be submitted to the Building
Official showing that the buoyancy of such units will
support the loads imposed Where standard 55-gallon
barrels are used, the allowable buoyancy support of the
dead and live loads shall be 300 pounds per barrel
(g) Anchorage 1 Anchorage of the platform deck to beam and
piles shall be accompanied by one or more of the following
methods
a By attaching the beams to the piers and box cribs
by lag bolts
b By caps Wood caps shall be a minimum nominal
4-inch material and anchored by bolts and welded
2 Flotation and box crib structures Such structures
shall be anchored with solid units that will provide
the following anchorage -
a Piers less than fifty (50) feet in length An
anchor on each corner that will support one-
fourth of the total dead load plus one-eighth
the total live load
b Piers fifty (50) feet or more in length Anchors
at the midpoint of the piers
c All piers shall be anchored to the shore line
d All anchors shall be of masonry, concrete, or steel
and shall be securely fastened to the .pier by wire
rope, cable, chain, or other approved methods
(h) Required Water Proofing i All wood below one (1) foot
above spillway elevation on lakes or below one (1) foot
above the 50-year flood elevations on other bodies or water
shall be treated lumber Such treatment shall be six (6)
pounds of creosote or pentachlorophenol or other approved
water proofing material per cubic foot Such treatment
materials shall comply with the latest Federal
Specifications TT-W-571
-41-
2 All metal, including bolts, lag bolts, and fasteners,
shall be galvanized or painted with paints of similar
materials approved for immersion in water
Sec 5607 Construction of boathouses shall meet or exceed
the requirements for framing and coverage as specified in other
parts of this Code Where concentrated Toads are applied to
joists or rafters, the concentrated load, when producing moments
greater than the minimum uniform live load, shall be used for
design purposes
Sec 5608 Alternate Methods. Alternate methods of
construction may be used, provided that such methods meet the
intent of this chapter and such alternate methods are designed
and plans sealed by an architect or engineer licensed to practice
in the State of Texas Such design shall be approved by the
Building Official
Sec 5609 The requirements of this chapter are considered
minimum requirements for safety purposes Any such structures
that do not meet these requirements shall be considered hazardous
and shall be abated, as provided by Section 203 of this Code If
the Tarrant County water Control and Improvement District Number
One regulations are more restrictive than the City of Fort Worth
regulations, the Tarrant County Water Control and Improvement
District Number One regulations apply
APPENDIX CHAPTER 70
Revise Appendix Chapter 70 as follows
Chapter 70
EXCAVATION AND GRADING
Sec 7001 Purpose The purpose of this chapter is to
safeguard life, limb, property, and the publi~~ welfare by
_egulatinq grading on private property
Sec 7002 Whenever the Building Official determines that
any existing excavation or embankment or fill on private property
has become a hazard to life and limb, or endangers property, or
adversely affects the safety, use or stability of a public way or
drainage channel, the owner of the property upon which the
excavation of fill is located, or other person or agent in
control of said property, upon receipt of notice in writing from
the Building Official, shall within the period specified therein
repair or eliminate such excavation or embankment so as to
eliminate the hazard and be in conformance with the requirements
of the Code
-42-
Sec 7003 (a) General Unless otherwise recommended in
the approved soil engineering report, fills shall conform to the
provisions of this section
(b) Fill Location Fill slopes shall not be constructed on
natural slopes steeper than two to one
(c) Compaction All fills shall be compacted to a minimum of
ninety (90) percent of maximum density as determined by
U B C Standard No 70-1 Field density shall be determined
in accordance with U B C Standard No 70-2 or equivalent as
approved by the Building Official
(d) Slope. The slope of fill surface shall be not steeper than
is safe for the intended use Fill slopes shall be no
steeper than two horizontal to one vertical
Sec 7004 through 7015 Deleted.
U.B.C. STANDARD NO. 38-1
Amend U.B.C. Standard 38-1 to read as follows.
Uniform Building Code Standard No. 38-1
Installation of Sprinkler Systems
See Sections 911(c), 1807(c), 3801(d), 3802(8) and Appendix Sections
125(aj, 125(b), 713(a) and 1108(b), Uniform Building Code, and
Sections 10.307(d), 10.308(8), Exception 2, 79.201(e), Item No. 3(i)
and (ii), 70.201(e), Item No. 4(i), 79.203(a), 79.204(b), 79.301(d)
and 79.506(c?, Uniform Fire Code.
SECTION 38.101
ADOPTION OF NFPA STANDARD
Section 38.101. Except for the limitations, deletions,
modifications or amendments set forth in Section 38.102 of this
standard, the installation of sprinkler systems required by the
Uniform Building Code shall be in accordance with the Standard for the
installation of Sprinkler Systems, NFPA 13-1987 published by the
National Fire Protection Association, copyright 1987, Batterymarch
Park, ~uinc~r, 'Massachusetts 02269, as if set out at length herein.
SECTION 38.102
AMENDMENTS
Section 38.102. The National Fire Protection Association standard
adopted b~- Section 38.101 applies to the selection, installation,
inspection, maintenance and testing of sprinkler systems, except as
follows
1 SECTION 1-1 is amended by deleting the note.
2. SECTION 1-2 is deleted
3. SECTION 1-3 is amended by revising the definition of "Authority
Having Jurisdiction" to read as follows
The "Authority Having Jurisdiction" is the building official
The definitions of "Approved" and
in the Uniform Building Code
Section 1-3 is further amended by
words "Should" and "Standard" by
definition of "Sprinkler S~rstem",
".,_cceptance", "Building Official''
follows
"Listed" shall be as set forth
deleting the definitions of the
ieleting the note following the
and by adding definitions for
and "Fire Chief" to read as
"Acceptance" is acceptance by the authority having ,jurisdiction.
43
"Building Official" is the officer or other designated authority
charged with the administration and enforcement of this
standard, or his duly authorized representative.
"Fire Chief" is the Chief of the Fire Department or his duly
authorized representative.
4. SECTION 1-4 is deleted.
5. SECTION 1-7 is amended to read as follows'
1-7 Classification of Occupancies:
1-7.1. For the purpose of determining the level of protection
to be provided by required sprinkler system installation, the
building official shall classify the use of each building or
portion thereof as a Light Hazard, an Ordinary Hazard, Group 1, 2
or 3 Occupancy, or an Extra Hazard, Group 1 or 2 Occupancy, as
defined in this section.
any use not specifically mentioned or about which there is any
doubt shall be included in the classification which it most nearly
resembles based on the life and fire hazard. For high-piled stock,
see the Uniform Fire Code
1-7 2 Light Hazard Occupancies.
1-7.2. Light Hazard Occupancies are users where the quantity or
combustibility, or both, of contents is low and fires of low rates of
heat release are expected.
Light Hazard Occupancies include uses such as
Churches
Clubs
Eaves and overhangs, if combustible
combustibles beneath
Educational
Hospitals
Institutional
Libraries, e~:cept large stack rooms
Musel_tms
Nursing or convalescent homes
Office, including data processing
Residential
Restaurant seating areas
Theaters and auditoriums excluding
Unused attics
1-7 3 Ordinary Hazard Occupancies.
construction with no
stages and proscenium
1-7.3.1 Ordinar~r Hazard Group 1 Occupancies are uses where
combustibility is loco, quantities of combustibles are moderate, stock
piles of combustibles do not exceed 8 feet and fires with moderate
rates of heat release are expected.
44
Ordinary Hazard Group 1 Occupancies include uses such as
Automobile parking garages
Bakeries
Beverage manufacturing
Canneries
Dairy products manufacturing and processing
Electronics plants
Glass and glass products manufacturing
Laundries
Restaurant service areas
1-7.3.2. Ordinary Hazard Group 2 Occupancies are uses where the
quantity and combustibility of contents are moderate, stock piles do
not exceed 12 feet in height and fires with moderate rates of heat
release are expected.
Ordinary Hazard Group 2 Occupancies include uses such as
Cereal mills
Chemical plants -- ordinary
Cold storage warehouses
Confectionery products
Distilleries
Leather goods manufacturing
Libraries -- large stack room areas
Machine shops
Metal works
Mercantile
Printing and publishing
Textile manufacturing
Tobacco products manufacturing
Wood product assembly
1-7.3.3. Ordinary Hazard Group 3 Occupancies are uses c,~here the
~~uantity or combustibilitS~ of contents, or both, is high and fires of
high rates of heat release are expected {Ordinar~~ Hazard Group 3
Occupancies shall be hydraulically' designed.)
Ordinary Hazard Group 3 Occupancies ~.nclude i.ises such as
Exhibition halls
Feed mills
Paper and pulp mills
Paper processing plants
Piers and wham es
Repair garages
Tire manufacturing
Warehouses (having moderate to higher combustibility of content,
such as paper, household furniture, paint, general storage,
whiskey, etc except for warehouses used for high-piled
storage. See the Fire Code.}
Wood machining
45
~.
1-?.4. Extra Hazard Occupancies•
1-7.4.1 Extra Hazard Group 1 Occupancies are uses where the
quantity and combustibility of contents is very high and dust, lint or
other materials other than flammable or combustible liquids are
present and rapidly developing fires with high rates of heat release
are expected. (Extra Hazard Group 1 Occupancies shall be hydraulically
designed.)
Extra Hazard Group 1 Occupancies include uses such as
Combustible hydraulic fluid use areas such as die casting and
metal extruding
Plywood and particle board manufacturing
Printing (using inks with below 100°F flash points)
Rubber reclaiming, compounding, drying, milling, vulcanizing
Saw mills
Textile picking, opening, blending, garnetting, carding,
combining of cotton, synthetics, wood shoddy, or burlap
Upholstering with plastic foams
1-7.4.2. Extra Hazard Group 2 Occupancies are uses with moderate
to substantial quantities of flammable or combustible liquids or where
shielding' of combustibles is e~tensi~e (Extra Hazard Group 2
Occupancies shall be hydraulically designed.)
Extra Hazard Group 2 Occupancies include uses such as
Asphalt saturating
Flammable liquid spraying
Flow coating
Mobile home or modular building assemblies (where finished
enclosure is present and has combustible interiors)
Open oil quenching
Solvent cleaning
Garnish and paint dripping
6 SECTION 1-9 2 is amended as follows
Add to SECTION 1-9 2(a) and current mailing addresses
Add to SECTION 1-9.2(u) and antifreeze s~-stem include NFPA
calculations
Add to SECTION 1-9.2(z) with rod sizes, trapeze bar
dimensions and locations of hangers
on piping indicated
Change SECTION 1-9 2(gg) "contractor" to "sprinkler
contractor"
7. SECTION 1-10 is amended by ;.hanging "authority Having
Jurisdiction" to "Fire Chief"
46
8. SECTION 1-11.2.2 is amended to read as follows
1-11.2.2. Leakage Prohibited. The sprinkler system including
inside piping, underground mains, lead-in piping and common supply
piping charges with water shall not display visible leakage during
or after testing.
9. SECTION 1-12 is revised by substituting the City of Fort Worth
Contractors Materials and Test Certificates.
10. SECTION 2-2.1..1 and 2-2.1.1(a) are amended to read as follows
2-2.1.1. Occupancy classifications shall be as set forth in
Section 1-7. See Item No. ~ of these amendments.
(a} Table ^-2.1(A) shall be used in .determining the minimum
water supply requirements for pipe schedule sprinkler systems
in Light Hazard Occupancies or in Ordinary Hazard Group 1 and
Group 2 Occupancies In Ordinary Hazard Group 3 Occupancies,
Extra Hazard Occupancies and in high-rise buildings, the
sprinkler system shall be hydraulically designed.
(b) Unchanged.
11. SECTION 2-2.1.2.3 is amended to read as follows
2-2.1.2.3. When inside hose stations are planned or are
required by other standards, a water allowance of 50 gpm (189 L/min)
for a one hose station installation [100 gpm (378 L/min) for a two or
more station installation] shall be added to the sprinkler requirement
at the point of connection to the s~~stem at the residual pressure
required by the sprinkler system design if such pressure is adequate
for the operation of the hose stream.
12 SECTION 2-2.1 is amended by addin Section 2-2.1 4 to read as
follows
2-2.1.4. For all speci.ilative offices a minimum of 300 fpm
flok is required at an adequate residual pressure. The residual
pressure shall be sufficient to cover anticipated pipe friction losses
and sprinltiler flow pressures with the spacing limits used in Chapter 4
13. SECTION 2-2.1 is amended by adding Section 2-2.1.1<1 to read as
follows
2-2.1.14. For uses cahich have the potential for fast-spreading
fires due to the presence of lint, combustible residue,
combustible hydraulic fluids ~.tnder high pressure with ignition
sources nearb~r and similar factors, the minimum area of operation
shall encompass the entire area liltely to be involved in such a fire.
47
14. TABLE 2-2.1(A) is amended to read as follows'
Table 2-2.1(A). Water Supply Requirements for Pipe Schedule
Sprinkler Systems.
OCCUPANCY MINIMUM RESIDUAL MINIMUM FLOW AT BASE DURATION IN
CLASSIFICATION PRESSURE OF RISER GPM MINUTES
(PSI} {SEE NOTE 2}
(SEE NOTE 1)
Light Hazard 15 500 (See Note 3} 30
Ordinary Hazard 15 700 60
(Group 1)
Ordinary Hazard 15 850 60
(Group 2)
Ordinary Hazard Hydraulic design required
(Group 3)
Warehouses Hydraulic design required. For high piled stock
storage, see Uniform Fire Code Standards
No. 81-1 and 81-2.
High-Rise Bldgs. Hydraulic design required.
Extra Hazard Hydraulic design required.
NOTES 1. The pressure required at the base of the
sprinkler riser is the residual pressure
required at the elevation of the highest
sprinkler plus the pressure required to
reach this elevation.
2 When the treater flow or higher pressures
are required by UBC Standard No. 38-2, the
more restrictive requirement shall apply
unless the building is sprinklered
throughout whereby only the sprinkler
demand need be met when compliance with
tJBC Section 1807 is not required.
3. The requirements may be reduced to 25U gpm
in buildings of noncombustible construction.
15 SECTION 2-2.1.2.6 is amended to read as follows
2-2.1.2.5.. The water supply shall not be less than the
duration set forth in Tables 2-2.1(A) and 2-2.1(B) nor less than
set forth in Uniform Building Code Section 180~(c).
7.6 SECTION 2-2.1.2.12 is deleted.
48
~a
17. SECTION 2-3.1.1 is amended by adding paragraph two as follows.
2-3.1.1 When the sole water supply consists of a municipal
water works connection, the municipal water supply must exceed the
calculated hydraulic pressure demand from Section 2-2.1.2 by 5 psi at
the calculated flow demand. Flow tests must be conducted within 12
months of the date of beginning sprinkler installations and may be
required to be taken at peak hours of water demand when deemed
necessary by the Fire Chief.
18. SECTION 2-7.3 is amended by adding Section 2-7.3.7 as follows
2-7.3.7. Fire Department connections shall be located on a
wall or in a yard adjacent to a fire lane or public roadway within
300 feet of a fire hydrant unless otherwise approved by the Fire
Chief. Connections shall be placed between 18 and 48 inches above
grade in a location acceptable to the Fire Chief
19 SECTION 2-7.6.1 is amended to read as follows
2-7.6.1. Hose couplings shall be in accordance with the
requirements of the Lniform Building Code
20. SECTION 3-3.1 is amended to read as follows
3-3.1 The malimum floor area on any one floor to be protected
by sprinklers supplied by any one sprinkler system riser or combined
system riser shall be as follows
Light Hazard - 52,000 sq.ft. (4831 m2?
Ordinary Hazard - 52,000 sq.ft (4831 m2)
E~:tra Hazard - 25,000 sq.ft (2323 mz)
Storage - High-piled storage (as defined in =~-1 3 9) and storage
covered by Uniform Fire Code Standards - 40,000 sq ft (3716 m2)
EYCeption When single systems protect both high-piled storage
covered by other Uniform Fire Code Standards and ordinary hazard
areas, the storage area coverage shall not emceed 40,000 sq ft and
the total area coverage shall not eYCeed 52,000 sq ft
21. SECTION 3-8.1 is amended to read as follows
3-8.1. For sprinklers in storage racks, see Uniform Fire Code
Standard Rio. 81-2.
22. SECTION 3-8.7 is amended by changing Item (c) to read as follows
ic) When a sprinkler system contains a 2-1/2 inch outlet,
the supply shall be in accordance with tiBC Standard 'Vo 38-~
SECTION 3-8.7 is further amended by substituting the phrase "UBC
Standard X10 38-2" for the phrase "NFPA 14" in Item (d)
49
23. SECTION 3-11.4.1 is amended by adding the following sentence
Drainage shall be to an approved location.
24. SECTION 3-15.1.12 is amended by substituting the phrase "Uniform
Fire Code Standard No. 81-2" for the phrase "NFPA 231C".
25. SECTION 3-16.2.9 is amended by adding the following sentences
Residential sprinklers shall be used in any room which
contains a sleeping area and is arranged for use by four or less
occupants. Rooms which contain sleeping areas such as apartments or
hotel/motel, or dormitories for more than four people such as resting
areas in day care centers and schools, or in institutional occupancies
shall be protected by fast response commercial sprinklers bearing an
Underwriters Laboratories listing or equivalent.
26 SECTION 3-16.6.2 is amended by changing the fourth exception to
read as follows
For situations involving high-piled or rack storage, refer to
Uniform Fire Code Standard Nos. 81-1 and 81-2.
2'r SECTION 3-17.4.1 is amended by adding a second paragraph as
follows
Alarm devices, such as water motor gongs, installed outside of
buildings shall be installed as close as practicable to the Fire
Department connections Adjacent to the alarm shall be a sign which
states "When alarm sounds, call Fort t+'orth Fire Department, 9-1-1",
and which contains the address of the property The minimum sign
dimension shall be 9 inches.
Z8 SECTION 3-17.7.1 is amended to read as follows
3-17.7.1. Electrically operated alarm attachments forming
part of a central station, proprietary, remote or local station
signaling system required bar Section 3-17 9 of these ,amendments shall
be installed in accordance +.-ith approved nationally recognized
standards.
29. SECTION 3-17 7.2 is amended to read as follows
3-17.7.2. Electrically operated alarm attachments forming
part of a local sprinkler caater flow alarm system may be of open-
circuit t~rpe and shall comply with Uniform Fire Code Standard No 10-2.
30. SECTION 3-17 is amended by adding a new Section 3-17 9 to read as
follows
3-17.9. Alarm Supervision. when serving more than 100
sprinklers, automatic sprinkler s~-stems shall be supervised b~- an
approved central, proprietary- or remote station service cr a local
alarm which will give an audible signal at a constantly attended
location
50
,.
31. SECTION 4-1.1 is amended by adding a new Section 4-1.1.4 to read
as follows
4-1.1.4. The Fire Chief shall be consulted in every case
as to location and spacing of sprinklers for protection of building
and contents and for life safety.
32. SECTION 4-1.2 is amended by redesignating the existing Section
4-1.2 as Section 4-1.2.1 and adding a new Section 4-1.2.2 to read as
follows.
4-1.2.2. Permissible Sprinkler Omissions. Sprinklers may be
omitted in rooms or areas as provided in Section 3804 of the Uniform
Building Code.
33. SECTION 4-1.3.5 is amended to read as follows
4-1.3.5. Standard Mill Construction refers to Type IV heavy
timber buildings in the Uniform Building Code.
34. SECTION 4-1.3.7 is amended to read as follows
4-1.3.7. Wood Joist Construction. The term caood joist
construction refers to wood members or rectangular cross section,
which may vary from 2 to 4 inches (51 to 102 mm) nominal c~ridth and up
to 14 inches (356 mm) nominal depth, spaced up to 3 feet (0.9 m) on
centers, and spanning up to 40 feet (12 m) between supports,
supporting a floor or roof deck. Wood members less than 4 inches (102
mm) nominal thickness spaced more than 3 feet (0 9 m) on centers are
also considered as wood joist. construction.
35 SECTION 4-1.3 is amended by adding Section 4-1 3 10 as follows
4-1.3.10. Wood Truss Construction. The term wood truss
construction refers to parallel chord beams with caood webbing
supporting a roof or floor declt. Trusses with steel webbing similar
to bar foist construction having wood chords shall be considered as
combustible bar joist construction.
36 SECTION 4-1.3.9 is amended to read as follows
4-1.3.9. High-piled Storage. See Uniform Fire Code
3r SECTION 4-2.2.4 is amended by substituting the phrase "Uniform
Fire Code Standard No. 81-2" for the phrase "other NFPA
standards", the phrase "Uniform Fire Code Standards Nos 81-1 and
81-2 for the phrase "NFPA 231, Standard for Indoor General
Storage, and NFPA 231C, Standard for Rack Storage of Materials" in
Exception 1, and deleting Exception 2
38 SECTION 4-2.2.5 is deleted
39 SECTION 4-2.5.1. is amended by substituting the phrase "Uniform
sire Code Standard No. 81-2" for the phrase "NFPA 231C, Rack
Storage of Materials".
51
40. SECTION 4-4.4 is amended by adding Section 4-4.4.5 as follows
4-4.4.5. Wood Trusses In Concealed Spaces. When wood trusses
are present in concealed spaces, sprinklers shall be placed at a
maximum protection area of 100 sq.ft. per head. Heads shall be placed
not closer than 6 feet nor farther than 10 feet from adjacent heads
and shall be staggered. Heads shall not be placed closer than 6
inches from the truss members and shall be installed in the reverse
position. (pendant sprinklers in the upright position and upright
sprinklers in the pendant position.) The systems shall be
hydraulically calculated.
Deflectors height shall be centered in the trusses, but no more
than 12 inches.
Hangers shall be as follows
A. Drive or lag screws shall not. be Lased to attach hangers to
any chord of any truss.
B. A horizontal beam should be placed between at least two web
members and the hanger shall be attached to that horizontal
beam in an appro`ed manner. When this method is used, the
beam shall be attached to the web member with through bolts.
Only one drill hole not to eYCeed 1j4 inch diameter shall be
used in each web member.
C. Other hanging systems may be used when in compliance with
Section 3-15.
41 SECTION 4-4.8.2.3 is amended to read as follows
4-4,8.2.3. When floor openings are unenclosed, the floor
openings invol`ed shall be protected by draft curtains in combination
with closer spaced sprinklers. See Uniform Building Code Section
1~06(a), E~;ception 2, the floor openings provided for escalators.
42. SECTION 4-4.8.2.4 is amended to read as follows
4-4.8.2.4. Stairs enclosed in shafts of combustible ar non-
combustible construction shall have sprinklers provided at each floor
landing and beneath the first landing above the lowest level.
43 SECTION 4-4.9 is amended to read as follows
4-4.9. Building service chutes shall be protected in
accordance with Uniform Building Code Section 3802(b), Item No. 2.
~4 SECTION 4-4.16.1 is amended by adding a nec~ sentence to read as
follows
See Uniform Building Code Section 5208(b).
45 SECTION 4-1.17.3 is amended by deleting the note
52
46. SECTION 4-4.18.1 is amended by changing the sentence "(See NFPA
96, Standard for Vapor Removal from Cooking Equipment.)" to "(See
Uniform Mechanical Code.)"
4'7. SECTION 4-4.19 is amended by substituting the phrase "see
Uniform Fire Code Standard No. 81-2" for the phrase "see NFPA 231C,
Standard on Rack Storage of Materials" in the first sentence..
48. Appendix Chapter D is amended by deleting SECTIONS D-1.1 and D-2.
U.B.C. STANDARD NO. 38-2
SECTION 38.202
Delete definition of "dry standpipe system" and substitute the following
DRY STANDPIPE SYSTEM (Class 1) is a standpipe system with a water
supply consisting of a one-inch caater fill connection at the top of
the riser to maintain piping normally wet and a Fire Department
connection which is equipped faith 2-1/2 inch outlets for use by the
Fire Department or trained personnel
EXCEPTION Dry standpipes are permitted caithout the water fill
connection when they are located in areas subject to
freezing.
SECTION 38.207(d)
Add Exception 2 to paragraph (d) as follows
EXCEPTION 2 In buildings other than high-rise which are fully
equipped with an approved automatic fire sprinl~ler
system which are not equipped with occupant use
hose cabinets, only the sprinkler system demand
need be provided, if the fire hose demand can be
satisfied by Fire Department apparatus.
SECTION 38.208
add the following paragraph
Fire Department connections shall be located on a wall or in a yard
adjacent to the fire lane or public roadway within 150 feet of a fire
hydrant unless otherwise approved by the Fire Department. Connections
shall be placed betcaeen 18 and 48 inches above grade in a location
acceptable to the Fire Chief
SECTION 38.210
Delete and substitute the following
Section 38 210. Outlet pressures shall not be permitted to
eZCeed 150 pounds per square inch. Where greater pressures may exist,
53
an approved automatic pressure regulating device shall be installed to
restrict pressures to not greater than 150 pounds per square inch.
The pressures regulating device shall not be externally adjustable for
varied pressures.
U.B.C. STANDARD NO. 38-3
Add a new Standard 38-3 as follows
Uniform Building Code Standard No. 38-3
Installation of Centrifugal Fire Pumps
See Section 3801(a), Uniform Building Code, and Section 10.306(a),
Uniform Fire Code.
SECTION 38.301
ADOPTION OF NFPA STANDARD
Section 38.301 Except for the limitations, deletions,
modifications or amendments set forth in Section 38 302 of this
Standard, the installation of stationary centrifugal fire pumps for
use in fire protection systems required by the Uniform Building Code
shall be in accordance with the "Standard for the Installation of
Centrifugal Fire Pumps, NFPA 20-1987", published by the National Fire
Protection Association,. copyright 1987, Batterymarch Park, Quincy,
Massachusetts 02269, as is set out at length herein.
SECTION 38.302
AMENDMENTS
Section 38 302. The National Fire Protection association
Standard adopted by Section 38.301 applies to the selection,
installation, inspection, maintenance, and testing of centrifugal fire
pumps e;,cept as follows
1. Section 1-2.1 is deleted
2. Section 1-7.3 is amended by changing all references of "ti'FPA 70,
National Electrical (,ode" to "the City of Fort t9orth Electrical Code"
3. Section 1-7.8 is amended by
(a) Revising the definition of "Authority Having
Jurisdiction" to read as follows
"Authority Having Jurisdiction" is the Building Official
(b) Deleting the definitions "S1-iould" and "Standard" and by
adding definitions for "Acceptance", "Building Official"
and "Fire Chief" to .read as follows
"Acceptance" is acceptance by the Authority Having
Jurisdiction.
54
~,
"Building Official" is the officer or other designated
authority charged with the administration and
enforcement of the standard or his duly authorized
representative.
"Fire Chief" is the Chief of the Fire Department or his
duly authorized representative.
(c) The definition of "Approved" and "Listed" shall be as
set forth in the Uniform Building Code.
4 Section 2-8.3 is amended by changing "NFPA 13" to "UBC Standard
38-1"
5. Section 2-9.1 is amended by changing "NFPA 24, Standard for
Private Fire Service Mains and Their Appurtenances" to "Nationally
Recognized Standards".
6. Section 2-9.6 is amended by changing "NFPA, Standard for Private
Fire Service Mains and Their Appurtenances" to "Nationally
Recognized Standards".
7 Section 2-10.2 is amended by changing "NFPA 13" to "UBC Standard
38-1" and by changing "NFPA 24, Standard for Private Fire Service
Mains and Their Appurtenances" to "Nationally Recognized Standards"
8 Section 2-13.3.2 is amended by revising the teat to read as
follows
"Hose valve(s) shall have threads as specified in the
Uniform Building Code"
9 Section 5-1.2 is amended by changing "'NFPA 13" to "UBC Standard
38-1" and "'NFPA 1-1, Standard for the Installation of Standpipe and
Hose Systems, Chapter 5 and Chapter 6" to "UBC Standard 38-2".
10 Section 6-1 is amended by changing "\'FPA 70, National Electrical
Code" to "the City of Fort Worth Electrical Code"
11 Section 6-4.1 is amended by changing "NFPA 70, National Electrical
Code" to "the City of Fort t9orth Electrical Code"
12 Section 6-5.3.2 is amended by changing "NFPA 70" to "Cit3- of Fort
Worth Electrical Code".
13. Section 7-3.6 is amended by changing "NFPA 'i0, National Electrical
Code" to "the City of Fort Worth Electrical Code"
1-1. Section 7-4 is amended by changing all references of "NFPA '~0,
National Electrical Code" to "the City of Fort tvorth Electrical Code".
15. Section 8-5.3 is amended by changing "NFPA 37, Standard for the
Installation and Use of Stationary Combustion Engines and Gas
Turbines" to ''the Cite of Fort Worth tfechanical Code"
55
,.
A '~
16. Section 11-2.2 is amended by changing "Authority Having
Jurisdiction" to "Fire Chief".
U.B.C. STANDARD NO. 38-4
Add a new standard 38-4 as follows
Uniform Building Code Standard No. 38-4
Installation of Halon 1301 Fire Extinguishing Systems
Section 38.401
ADOPTION OF NFPA STANDARD
Sec. 38.401. Except for the limitations, deletions,
modifications or amendments set forth in Sec. 38 402 of this standard,
the installation of Halon 1301 fire extinguishing systems required by
the Uniform Building Code shall be in accordance with the "Standard on
Halon 1301 Fire Extinguishing Systems, VFPA 12A-1987", published by
the National Fire Protection Association, copyright 1987, Batterymarch
Parlt, Quincy, Massachusetts 02269, as if set otit at length herein.
Section 38.402
AMENDMENTS
Sec. 38.402. The National Fire Protection association Standard
adopted by See. 38 401 applies to the installation of Halon 1301
systems except as follows
1. Sec. 1-1 is amended by changing "'~'FPA 10, Standard for Portable
E,.tinguishers" to "t.F.C. Standard No. 10-1"
Sec. 1-4 is amended by revising the definition of "authori.ty Haying
Jurisdiction" to read as follows
"Authority Having Jurisdiction" is the Building Official
Sec. 1-4. The definition of "Approved" and "Listed" shall be as
set forth in the Uniform Building Code.
Sec. 1-4 is amended b~~ deleting the words "Should" and "Standard"
and by adding the definition for "Acceptance", "Building Official"
and "Fire Chief" to read as follows
"Acceptance" is acceptance by the Authority Haying
Jurisdiction
"Building Official" is the officer or other designated
authority- charged with the administration and enforcement of
the standard or his duly authorized representative.
"Fire Chief" is the Chief of the Fire Department or his duly
authorized representative.
56
:F ~
ts~yw
''_..
ry
3. Sec. 1-8.1 is amended by changing "Appropriate NFPA Protection
Signaling Systems Standards (See Chapter 4)" to "Fire Code
Article 14".
~#. Sec. 1-8.2.2 is amended by changing "NFPA 72E - Standard for
Automatic Fire Detectors" to "Fire Code Standard 14-2".
5. Sec. 2-2.3 is added as follows
2-2.3. Soak Time. The minimum concentration of Halon
specified herein to protect an area shall be maintained for a
period of not less than 10 minutes throughout the protected
area at a level of one foot below the ceiling or one foot above
the highest level of possible storage, whichever is higher.
6. Sec. 4-1.1 is deleted.
U.B.C. STANDARD NO. 38-5
Add a new standard 38-5 as follows
Uniform Building Code Standard No. 38-5
Installation of Residential Sprinkler Systems
See Sections 508, 1705(b)(2), 3305(g}, and Appendit, Chapter 1,
Section III(c), Uniform Building Code, grid Article 14, Section
14.107(F)(1) Uniform Fire Code.
Section 38.501
ADOPTION OF NFPA STANDARD
Sec. 38.501. Except for the limitations, deletions,
modifications or, amendments set forth in Section 38.302 of this
standard, the installation of residential sprinkler systems, for
R-1 occupancies, one and two story and three stories without
interior e~siting systems, required by the Uniform Building Code
shall be in accordance with the "Standard for the Installation of
Sprinkler Systems in Residential Occupancies Up To Four Stories
in Height, NFPA 13R-1989", published by the National Fire Protec-
tion Association, copyright 1989, Batterymarch Parh, (~uincy,
Massachusetts 02269, as if set out at length herein.
Section 38.502
AMENDMENTS
Sec. 38.502. The National Fire Protection Association Standard
adopted by Section 38.501 applies to the installation of residential
sprinkler systems e~:cept as follows
1. Sec 1-1 is amended as follows
57
f
Sec. 1-1. Scope. This standard deals with the design and
installation of automatic sprinkler systems in residential
occupancies as permitted by the Uniform Building Code and the
Uniform Fire Code.
2. Sec. 1-3 is amended as follows
Sec. 1-3 is amended by revising the definition of "Authority
Having Jurisdiction" to read as follows
"Authority Having Jurisdiction" is the Building Official.
Sec. 1-3 is amended by adding the definition of dwelling to
read as follows
Dwelling. Any building which contains "dwelling units"
intended to be used, rented, leased, let or hired out `to be
occupied, or which are occupied for habitation purposes.
Sec. 1-3 is amended b~- deleting the definitions
"Residential Occupancies", "Should" and "Standard" and by
adding definitions for "Acceptance", "Building Official"
and "Fire Chief" to read as follows
Acceptance. Acceptable t.o the authority- hay°ing
jurisdiction.
Building Official. The officer or other designated
authoritti~ charged with the administration and enforcement of
the standard or his duly authorized representative
Fire Chief. The Chief of the Fire Department or his dul~°
authorized Representative.
Sec. 1-3. The definition of "Approved" and "Listed" shall be as
set forth in the Uniform Building Code
3 Sec. 1-6.2.1 is amended b~- changing "NFPA 13, Standard for the
Installation of Sprinkler Systems" to "U B.C. Standard 38-1"
=~. Sec. 2-1.2.1 is amended as follows
2-1.2.1 Plaris shall be submitted as required by .~ppendi~
~'II-B of the Uniform Fire Code
5 Sec 2-1.3.1 is amended as follows
2-1.3.1 The installer shall perform all required acceptance
tests, complete the City of Fort tdorth Contractor's Material
and Test Certificates, and forward the certificate(s) to
the Fire Chief, prior to asking for final approval of the
installation
6. Sec. 2-1.3.2 is deleted.
58
~, f,
r'~
7. Sec. 2-1.4.2 is amended by changing "NFPA 13" to "UBC Std.
38-1".
8. Sec. 2-3.2(c) is amended by changing "NFPA 13" to "UBC Std.
38-1".
9. Sec. 2-3.2(d) is amended by changing "NFPA 20" to "UBC Std.
38-3".
10. Sec. 2-3.3.2 is amended by changing "NFPA 13" to "UBC Std.
38-1".
11. Sec. 2-4.5.1 is amended by deleting exception #2.
12. Sec. 2-5.2 is amended by changing "NFPA 13" to "UBC Std. 38-1" ~
e
S-
13. Sec. 2-5.3 is amended by changing "NFPA 13" to "UBC Std. 38-1".
14. Sec. 2-6 is amended by deleting exception #2.
l~ Chapter 3 is deleted.
59
~; ~ p
t ~~
~, ,.
SECTION 3
Section 7-48 of the Code of the City of Fort Worth (1986) is
amended to read as follows:
Sec. 7-48 Effect of conflict with other ordinances.
This article shall be cumulative of all provisions of
ordinances and of the Code of the City of Fort Worth, Texas
(1986), as amended, except where the provisions of these
ordinances and such Code, in which event conflicting provisions
of such ordinances and such Code are hereby repealed
SECTION 4.
Section 7-49 of the Code of the City of Fort Worth (1986) is
amended to read as follows:
Sec 7-49 Compliance required; penalty.
It ,s hall be unlawful for any person to erect, construct,
enlarge, alter, repair, move, improve, remove, convert, demolish,
equip, use, occupy, or maintain any building or structure in the
City or cause the same to be done contrary to or in violation of
any of the provisions of this Code Any person, firm, or
corporation who violates, disobeys, omits, neglects, or refuses
to comply with or who resists enforcement of any of the
provisions of this code with respect to fire safety shall be
fined not more than Two Thousand Dollars ($2,000 00) for each
offense, and with respect to all other provisions of this Code
shall be fined not more than Two Hundred Dollars ($200 00) for
each offense Each day that a violation is permitted to exist
shall constitute a separate offense
SECTION 5
It is hereby declared to be the intention of the City
Council that the sections, paragraphs, sentences, clauses, and
phrases of this ordinance are severable, and, if any phrase,
clause, sentence, paragraph, or section of this ordinance shall
be declared unconstitutional by the valid judgment or decree of
any court of competent jurisdiction, such unconstitutionality
shall not affect any of the remaining phrases, clauses,
sentences, paragraphs, and sections of this ordinance, since this
same would have been enacted by the City Council without the
incorporation in this ordinance, since the same would have been
enacted by the City Council without the incorporation in this
ordinance of such unconstitutional phrase, clause, sentence,
paragraph, or section
~., ,. ~.~
:~.
SECTION 6
All rights and remedies of the City of Fort Worth, Texas are
expressly saved as to any and all violations of the Ordinance No.
10115, as amended, or any other ordinances affecting construction
and fire safety, which have accrued at the time of the effective
date of this ordinance; and, as to such accrued violations and
all pending litigation, both civil and criminal, whether pending
in court of not, under such ordinances, same shall not be
affected by this ordinance but may be prosecuted until final
disposition by the courts.
Building permits heretofore issued under existing ordinances
shall be valid for the time being for which they are issued under
the existing Building Code, but, upon expiration thereof, the
same shall be void
SECTION 7
This ordinance constitutes a digest and revision of the
Building Code of the City of Fort Worth, as provided in Section
2, Chapter XXV, and Section 9, Chapter XXVII, of the Charter of
the City of Fort Worth The City Secretary of the City of Fort
Worth, Texas, is hereby authorized to publish this ordinance in
pamphlet form for general distribution among the public, and the
operative provisions of this ordinance, as so published, shall be
admissible in evidence in all courts without further proof than
the production thereof, as provided in Chapter XXV, Section 3, of
the Charter of the City of Fort Worth, Texas
SECTION 8
The City Secretary of the City of Fort Worth, Texas, is
hereby directed to engross and enroll this ordinance by copying
the caption, penalty clause, and effective date in the minutes of
the City Council and by filing the ordinance in the ordinance
records of the City
SECTION 9
The City Secretary of the City of Fort Worth, is hereby
directed to publish the caption, penalty clause, and effective
date of this ordinance for two (2) days in the official newspaper
of the City of Fort Worth, Texas, as authorized by Section
52 013, Texas Local Government Code
~ .,.
's
a
SECTION 10
This ordinance shall be in full force and effect thirty (30)
days after its passage and publication- and it is so ordained.
APPROVED AS TO FORM AND-~I.EGALITY:
%~ ~
City Attorney
~; - ; ~ ~., - ~l
Date
ADOPTED : ~~>
EFFECTIVE:
r ~ ~ ~.
MASTER f~lE t J
~~ ACCRUNTINfi•2 ; ~ '
YGANSPORTAt10N~f WLIC M/ORK~•~ ~ `~~~~~ Of JL UY ~ ~®Y G~~ ~~~wS
`L N/1TER ApRa1NISTRAt10N ~J\\/1/ ~~) p®~Y ~t~W~~ ~./~ ~LN/U 1{/~L/ (L~ ~/®~~~~ fL~~~ U/®~
V'l1 IyJ
e~
F~~N,3Wd0'13
~ArE REFERENCE sue~ECr:APPROVE THE ADOPTION AND AMENDMENT PAGE
NuMeER TO THE 1988 UNI60RM BUILDING CODE 2
F~~RE AUMINIS R,T6~20~89 G-8086
1 of
RECOMMENDATION:
~. ,,
It is recommended that the attached proposed ordinance be presented to City
Council for adoption of the 1988 Uniform Building Code and City amendments.
This draft proposed ordinance has been reviewed by the Construction and Fire
Prevention Board of Appeals and presented to the citizens and parties in
interest' at two public hearings. Comments~of citizens and parties in
interest were considered by the Construction and Fire Prevention Board of
Appeals.
The proposed ordinance format changes and text changes will benefit the
citizens of Fort Worth. Among these changes are.
1) This proposed ordinance amendment will be printed in a single pamphlet
with the proposed Fire Code. This will ensure users of the Codes have
all the information in both codes to properly design a project. In the
past, the lack of having both codes has caused designs that do not
comply with minimum requirements of the Building and Fire Codes,
2) Registration of contractors performi ng remodeling of one- and two-family
residential buildings has been added to help citizens in obtaining
reliable contractors to perform contracting of alterations, additions,
or repair Work.
The Homebuilders Association is in favor of the program and during the
~hear~ng process has helped in the development of this portion of the
proposed ordinance. A Mr. Parker, President of the Senior Association,
is also in favor of the proposed ordinance,
3) Temporary Occupancy restrictions for use of public property have been
rewritten to provide more timely response to contractor needs while
still ensurin;gfminimum impact on traffic movement,
4) Registration of businesses and inspectors performing elevator,
dumbwaiter, or moving walks inspections has been added to increase the
emphasis on annual inspection requirements for such equipment and better
protect the citizens using the equipment, ~"~-
5) Posting of ce~rti ficati on of i nspecti on for each el evator, escala-tor,
dumbwaiter, or moving walk has been added to help ensure required annual
inspections of such equipment has been performed and better protect the
citizen`s using the equipment.
NOTE: Items 2, 4, and 5 above can only be accomplished by adding staff
to the Development Department to perform the administrative
functions of registrations and certifications. Two (2) clerk
positions have been requested in the 1989-90 budget request. If
these two positions are not approved, then the portions of the
...rr. t r. {~.~:~1. +i'i I. t *J it :Y h~ ly '1 4
°~
r ~7
I
~"` 4
DATE NUMBER CE sUB~ECT APPROVE THE~ADOPTION AND^AMENDME TS PAGE -
6/20/89 G-8086 TO THE 1988 UNIFORM BUILDING CODE 2 ~or,_,2
proposed draft regarding registration of contractors performing
remodeling work on one- and two-family residential buildings, the
registration of businesses, and inspectors performing required
inspections on escalators, elevators, dumbwaiters, and moving
walks and the issuing of certificates for posting regarding
elevators, escalators, dumbwaiters, and moving walks cannot be
achieved. Revenue from the registration fees and certificate
fees will cover the cost of filling these two (2) positions.
The Construction and Fire Prevention Board recommends the employment of one
of these staff persons at this time. The registration of remodeling
contractors on one- and two-family dwellings will exceed three hundred. This
number will bring in approximately $30,000 in revenues. The first year's
cost will be approximately $14,000 including salaries, desks, chairs, and
other office equipment. The second year's cost will be $28,000 and no
additional costs can be seen after that. The program will pay for itself.
The Board also has stated that if the additional personnel are not employed,
then the program should not be implemented.
APPRO~IED BY
CITY COUNCIL
~ 1J N 20 1989
K~ ~~ax~~
c3rP saax~.ca~r of w.
City of Fort VJostb~, Te>Kq~
SUBMITTED FOR THE
CITY MANAGER'S
OFFICE BY David Ivory
DISPOSITION BY COUNCIL:
^ APPROVED
PROCESSED BY
ORIGINATING. [~ OTHER (DESCRIBE)
DEPARTMENT HEAD: Le$ter Paige CITY SECRETARY
CONTACT TIONAL INFODRM LeWi S 81 T6 Adopt Or finance -Yo'
DATE
~ !,
~,,.. .
,;,.