Loading...
HomeMy WebLinkAboutOrdinance 10105 .. ~. ,~~ ORDINANCE NO. RN ORDINANCE ADOPTING THE 1985 UNIFORM FIRE CODE AND THE 1985 EDITION OF THE UNIFORM FIRE CODE STANDARDS WITH LOCAL AMENDMENTS BY AMENDING SECTIONS 13-1, 13-2, 13-3 AND 13-4 OF THE CODE OF THE CITY OF FORT WORTH (1986); PROVIDING THAT THTS ORDINANCE SHALL BE CUMULATIVE; PROVIDING PENALTIES FOR VIOLATIONS; PROVIDING FOR SEVERABILITY; PROVIDING A SAVINGS CLAUSE; PROVIDING FOR PUBLICATION IN PAMPHLET FORM; PROVIDING FOR PUBLICATION IN THE OFFICIAL NEWSPAPER; PROVIDING FOR ENGROSSMENT RND ENROLLMENT; AND PROVIDING AN EFFECTIVE DATE. BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF FORT WORTH, TEXAS: SECTION 1. Section 13-1 of the Code of the City of Fort Worth (1986) is amended to read as follows: Sec. 13-1. Code, Appendices and Standards - Adopted. (a) Code. The Fire Code of the City of Fort Worth is hereby revised and amended to conform to the 1985 edition of the Uniform Fire Code of the International Conference of Building Officials and the Western Fire Chief's Association, as amended hereby, and -the same as amended hereby is hereby adopted as the Fire Code of the City of Fort Worth from the effective date thereof. (b) Appendices. The following appendices to the 1985 edition of the Uniform Fire Code, as amended hereby, are specifically adopted as part of the Fire Code of the City of Fort Worth: Appendices I-A, I-C, II-A, II-B, II-C, IV-A, V-A, VI-A, VI-C, and Appendices I-}3, III-A, III-C, III-D, VII-A, VII-B are hereby created and adopted. (c) Standards. The 1985 edition of the Uniform Fire Code Standards of the International Conference of Building Officials and the Western Fire Chief's Association, as amended hereby, is adopted as a part of the Fire Code of the City of Fort Worth. Three copies of the 1985 edition of the Uniform Fire Code, in- cluding the Appendices thereto, marked Exhibit "A", and three copies of the 1985 Edition of the Uniform Fire Code Standards, marked Exhibit "B", are incorporated herein by reference and shall be filed in the office of the City Secretary for permanent record and inspec- tion. 4\ "r' 1. ~r Y' [~ ~S (d) Building Code Standards. Building Code Standard Numbers 38-1, 38-2, 38-3, 38-4 and 38-5 of the 1985 edition of the Uniform Building Code, as adopted and amended in Chapter 7 of this Code, are hereby incorporated by reference and made a part of the Fire Code of the City of Fort Worth for all purposes relating to fire safety, including enforcement of all provisions as set out in this Fire Code. These sections shall be filed in the office of the City Secretary for permanent record and inspection. SECTION 2. Section 13-2 of the Code of the City of Fort Worth (1986) is amended to read as follows: Sec. 13-2. Same -Amendments. (a) Generally. The 1985 edition of the Uniform Fire Code, in- cluding the Appendices thereto, and the 1985 edition of the Uniform Fire Code Standards are hereby amended and certain portions are added as set out in this section. (b) Fire Code. The 1985 edition of the Uniform Fire Code is amended by revising the following sections as follows: SECTION 2.102 Sec. 2.102. The Chief, with the approval of the administrator, is authorized to make and enforce such rules and regulations for the prevention and control of fires and fire hazards as may be necessary from time to time to carry out the intent of this code. Three certi- fied copies of such rules and regulations shall be filed with the City Secretary and shall be in effect thirty days following the last public notice, and additional copies of this Section 13-2 shall be kept in the office of the Fire Department for distribution to the public. SECTION 2.104 Sec. 2.104.(a) Designation and term of Chief of the Bureau of Fire Prevention. One officer of the Fire Department shall be desig- nated as the Deputy Chief of Fire Prevention, who shall be Chief of the Bureau of Fire Prevention. He shall hold office in accordance with the provisions of the Firemen's and Policemen's Civil Service Act. This officer may also be known as Fire Marshal. (b) Unchanged. -2- ~ ~ t, y~ SECTION 2.105 Section 2.105. Authority of fire personnel to enforce codes relating to fire safety. The Chief and members of the Fire Department shall have all powers to enforce the provisions of this code as are consistent with the laws of the State of Texas. Such personnel shall have concurrent jurisdiction to enforce provi sions of the Fort Worth Building Code which relate to fire safety. SECTION 2.201 Sec. 2.201.(a) The Fire Department shall inspect, as often as may be necessary, all buildings and premises, including such other hazards or appliances as the Chief may designate for the purpose of ascertaining and causing to be corrected any conditions which would reasonably tend to cause fire or contribute to its spread, or any violation of the purpose or provisions of this code and of any other law or standard affecting fire safety. (b) All buildings or structures which are structurally unsafe or not provided with adequate egress, or which constitute a fire hazard or are otherwise dangerous to human life, or which in rela- tion to existing use constitute a hazard to safety or health or pub- lic welfare, by reason of inadequate maintenance, dilapidation, obsolescence, fire hazard, disaster damage or abandonment as speci- fied in this code or any other effective ordinance, are, for the purpose of this section, unsafe buildings. All such unsafe buildings are hereby declared to be public nuisances and shall be abated by repair, rehabilitation, demolition or removal in accordance with the procedure specified in the code and ordinances of the City of Fort Worth, and other applicable laws of the State of Texas. SECTION 2.203 Section 2.203(b). Add the following to the list of recognized standards: UL 21 LP Gas Hose UL 51 Power Operated Pumps for Anhydrous Ammonia and LP Gas UL 125 Valves for Anhydrous Ammonia and LP Gas UL 132 Safety Relief Valves for Anhydrous Ammonia and LP Gas UL 144 Pressure Regulating Valves for LP Gas UL 565 Liquid-Level Gauges and Indicators for Anhydrous Ammonia and LP Gas UL 567 Pipe Connectors for Flammable and Combustible Liquid and LP Gas UL 569 Pigtails and Flexible Hose Connections for LP Gas UL 644 Container Assemblies for LP Gas UL 674 Electric Motors and Generators -3- a SECTION 2.204 Section 2.204.(a) Unchanged. (b) Unchanged. (c) The Chief or Fire Marshal may order the operation or use stopped, or the evacuation, of any premises, building or vehicle or portion thereof which has or is a fire hazard. (d) Unchanged. SECTION 2.205 Sec. 2.205.(a) Service of orders and notices; responsibility for violations. Any order or notice authorized or required by this code shall be given or served upon the owner, operator, occupant or other person responsible for the condition or violation either by verbal notification, personal service, or by delivering the same to and leaving it with some person of suitable age and discretion upon the premises, or, if no such person is found on the premises, by affixing a copy thereof in a conspicuous place on the door to the entrance of said premises and by mailing a copy thereof to such per- son by registered or certified mail. (b) The owner, occupant, or person in charge of any building or premises where any violation of this code or other ordinances of the City of Fort Worth relating to fire safety is found shall be prima facie responsible for such violations. SECTION 2.302 Sec. 2.302. The Construction and Fire Prevention Board of Appeals shall act on the fire code related matters commensurate with the provision of Ordinance Number 9282 of the City of Fort Worth. (Article II of Chapter 7 of this Code). SECTION 3.101 Section 3.101. Any person who violates, disobeys, omits, neglects, or refuses to comply with or who resists the enforcement of any of the provisions of this Code shall be guilty of a misde- meanor and fined not less than Five Dollars nor more than One Thousand Dollars for each offense. Each day that a violation or cir- cumstance not in compliance with the provision of this code is per- mitted to exist shall constitute a separate offense. SECTION 4.101 Sec. 4.101. (1) through (38) Unchanged. (39) Places of Assembly. To operate a place of assembly as de- ffined in Article 9 . -4- s4! ~~' 7 q, EXCEPTION: Churches and places of worship used solely for worship. (40) through (44) Unchanged. (45) Tire recapping and storage. To operate tire capping or re- building plants or to store tires more than 6 feet high or in a total area greater than 2,500 square feet. (46) and (47) Unchanged. (48) Special Hazard. To continue any special hazard as deter- mined by the Chief. SECTION 4.102 Sec. 4.102.(a) Unchanged. (b) A permit issued under this code shall continue until re- voked or for not more than one year following the date of issuance, except that those permits that specify a designated time period for expiratio n shall expire as designated on the permit. A permit shall not be transferable and any change in use, occupancy, operation or ownership shall require a new permit. (c) Unchanged. (d) A fee of twenty-five dollars ($25.00) shall be charged for permits required by Sec. 4.101 or permit renewal. SECTION 4.105 Sec. 4.105. Permits shall at all times be conspicuously posted on the premises designated therein and shall at all times be subject to inspection by an officer of the fire or police department or other authorized persons. SECTION 9.103 Delete the definition of aerosol (flammable) and add the fol- lowing: AEROSOL is a material which is dispensed from its container as a mist, spray or foam by propellant under pressure and classified according to the percentage by weight of flammable substances in the base product as follows: Level I. Maximum of 25 percent water miscible or nonmiscible flammable products (i.e., 75 to 100 percent nonflammable products) . Level II. Twenty-five to l0U percent water miscible flam- mable products, 25 to 55 percent nonmiscible flammable products (remaining 45 to 75 percent is nonflammable product). ~. ; Level III. Greater than 55 percent nonwater miscible flam- mable products. High piled storage of aerosols shall be considered greater than 6 feet. SECTION 9.108 Sec. 9.108. The following definition is added to those appear- ing in Sec. 9.108: FIRE MARSHAL is the Chief of the Bureau of Fire Prevention. SECTION 9.121 Sec. 9.121. The following definition is added to those appear- ing in Sec. 9.121: Class I is a standpipe system with a water supply consisting of a one-inch water fill connection at the top of the riser to maintain piping normally wet and a Fire Department connection which is equipped with 2-1 /2 inch outlets for use by Fire Department or trained personnel. SECTION 10.102 Sec. 10.102. Any person who obstructs the operations of the Fire Department in connection with extinguishing any fire, or other emergency, or disobeys any lawful command of the Chief or officer of the Fire Department who may be in charge at such a scene, or any part thereof, or any police officer assisting the Fire Department, shall be guilty of a misdemeanor. SECTION 10.207 Sec. 10.207.(a) General. Fire apparatus access roads, hereafter known as fire lanes, shall be provided in ac cordance with this sec- tion. Prior to the issuance of a building permit, fire lanes re- quired by this section shall be designated on a site plan and two (2) sets of said plan shall be submitted to the Chief for approval. No structure shall be allowed to progress beyond the foundation until required fire lanes are serviceable and approved. (b) Where Required. Fire lanes shall be required for every building hereafter constructed as follows: 1. Such that any portion of an exterior wall of the first story is within 150 feet of travel distance within a publicway. 2. Such that a Fire Department sprinkler or standpipe connection is within 50 feet from a dedicated street or fire lane. -6- 3. Such that a building which is four or more stories in height, is accessible by a dedicated street or fire lane that is not less than 15 feet nor more than 25 feet from the inside curb to the building face along at least one-half of the length of two sides of the building. (c) Permissible Modifications. 1. Clearances or widths required by this section may be increased when, in the opinion of the Chief, minimum clearances or widths are not adequate to provide fire apparatus access. 2. When a building is entirely protected by an approved automatic sprinkler system, the construction require- ments for fire lanes may be reduced or modified when, in the opinion of the Chief, a sufficient level of safety is provided. In no case shall any portion of an exterior wall of the first story be more than 300 feet from a dedicated street or fire lane. 3. When there are not more than two Group R, Division 3 or Group M occupancies, the requirements of this sec- tion may be modified, provided, in the opinion of the Chief, firefighting or rescue operations would not be impaired. (d) Surface. Fire lanes shall be designed and maintained to support a 12,500 pound wheel loading. The surface shall be designed to provide all weather driving capability. (e) Width. The minimum unobstructed width of a fire lane shall not be less than 20 feet except in unified residential construction where the minimum shall not be less than 26 feet. (f) Vertical Clearance. All fire lanes shall have an unob- structed vertical clearance of not less than 14 feet. (g) Turning Radius. The minimum inside turning radius shall be 25 feet, and the minimum outside turning radius shall be either 51 feet in unified residential construction or 45 feet otherwise. (h) Turnarounds. All dead-end fire lanes in excess of 100 feet in length shall be provided with a turnaround meeting the require- ments of Figure 10.207 (a). The cul-de-sac design shall be used unless the Chief permits the use of alternate designs. (i) Bridges. Where extending over a structure or open air- space, fire lanes shall be structurally designed in accordance with the H-20 loading requirements of the American Association of State Highways and Transportation officials. -7- (j) Grade. Grade incline of fire lanes shall not exceed 10°s. (k) Markings. Unless otherwise approved by the Chief, the owner, manager, or person in charge of any building to which fire access roadways have been approved, shall post and maintain curb markings consisting of continuous painted lines of red traffic paint four inches in width onto which the words "No Parking - Fire Lane" are stenciled with white paint in an approved manner at twenty-five (25) foot intervals and/or approved traffic signs which are posted and maintained in conspicuous places along such fire access road- ways. Such sign must be twelve (12) inches wide and eighteen (18) inches high stating "No Parking - Fire Lane" with a companion sign twelve (12) inches wide and six (6) inches high stating "Tow-Away Zone" and with a white background onto which red lettering, symbols, and border have been affixed. Signs shall be mounted at 6 feet and 6 inches above finished grade measured to the bottom of the "Tow-Away" sign. Drawings and samples of such signs may be obtained from the Bureau of Fire Prevention. Standards for mounting, including but not limited to the height above grade at which such signs are to be mounted, shall be adopted by the Chief and Director of Transporta- tion of the City of Fort Worth. (1) Obstructions. The required width of access roadways shall not be obstructed in any manner, including parking of vehicles. The Chief or Chief of Police or their duly authorized representative is authorized to cause fire access roadways to be maintained free of obstruction at all times by issuance of citations, removal and impoundment of a vehicle or obstruction in violation, by both a citation issuance and impoundment, or by orders to remove any ob- struction immediately. EXCEPTION: Except as prohibited by other ordinances and when approved by the Chief, gates may be in- stalled that restrict access to the fire lane pro- vided they are electrically operated and controlled by a key switch at the fire lane approached. The box shall be 12-15 feet in front of the gate, 4-1/2 - 5-1/2 feet above grade on the left hand side and accessible from within fire apparatus. (See Section 10.209.) (m) 'l'iming. Installation shall be timed in accordance with Section 10.3G1(d). -8- e~ ~1 1 :-.- <~ ~ ~ _._.-9 -- I ~ f ~ ~ Fi _Zf).1 ~ a ) ,. , SECTION 10.208 Sec. 10.208. Approved numbers or addresses shall be placed on all new and existing buildings as follows: (a) All occupancies except R-3 occupancies and apartment houses shall have six (6) inch numbers with a one (1) inch stroke. (b) R-3 occupancies and apartment houses with three (3) or less units shall have four (4) inch numbers with a one- half (1/2) inch stroke. (c) R-3 occupancies and apartment houses with 4 or more units shall have the building's full address and apartment num- hers as shown in Figure 10.208(a). The numbers and letters must be attached to a durable sign of contrasting color. The sign will then be attached to the building, which must be a contrasting color. EXCEPTION: Numbers alone may be acceptable if exist- ing signs are considered acceptable by the Chief. All numbers and letters shall be in a position as to be plainly visible and legible from the street or road front- ing the property. -10- 11',_I~IH 1i 1_ .Ili it ~ i ~I! tiff 91!' .` .... ~AATN~B ~IIoDIi~ ~IPIICJI?IO~i ~I~ 1) CUMBERS APED LE~CYERS !4(JS'f CONYR~SY OACKGROU&dD 2) ~CDCGROUND [BUSY COPIYRASY RUII,pIIdG. ~) INMBERS ALOA]E l~AY B~QT BE ACCEPTABLE; FULL SYREEY ADDRESS MUST RE INCLUDED E3iCEPT bJ@iER~ IT IS OBVIOUS TNAS 'f!(E R(JILDING IS OW A SPECIFIC STREET. ~) NUl~AERS IWD LEYTERS SMALL NOT BE AYTACHED mI1~ECTl,X Y'0 9UILDI[iG. YaiEY MUST ~E ON ~ SaG~. PtOSY RESYRICYIlIE 4.,. ~ARIA~'IOA1S 6201 - Zl (ODD) l4AYPl DRIVE BUILDIF~ 16 6201 I~YAI~I DRI61E APYS. 1°31 (ODD) DUII.DI~ l6 6201 6201 AP?'S. I°13 6201 APYS. 1°15 BUIi,DI~G b 4-7=-1= r r SECTION 10.209 Sec. 10.209. In any building which contains an elevator, any building or complex which contains a fire alarm system, or when access to or within a structure or an area is unduly difficult b ecause of secured openings, or where immediate access is necessary for lifesaving or firefighting purposes, the Chief shall require a key box to be installed in an accessible location approved by the Chief. The key box shall be a type approved by the Chief and shall contain keys to gain necessary access to any areas required by the Chief, keys to elevators, and keys to the fire alarm control panel and manual fire alarm actuating devices. When required by the Chief or Sec. 80.103(h), material safety data sheets shall be included in the key box. When installed for the primary purpose of providing access to the fire alarm system serving an apartment complex, the key box shall be placed at the exterior entrance of the property manager's office which shall be suitab ly marked as such. See Exception in Section 10.207(1). EXCEPTION: Where 24 hour guard or management service is provided, these requirements may be waived by the Chief. SECTION 10.301. INSTALLATION Sec. 10.301(a). Type Required. The Chief shall designate the type and number of fire appliances to be installed and maintained in and upon all buildings and premises in the jurisdiction other than private dwellings. This shall be done according to the relative severity of probable fire, including the rapidity with which it may spread. Such appliances shall be of a type suitable for the probable class of fire associated with such building or premises and shall have approval of the Chief. Portable fire extinguishers shall be in accordance with U.F.C. Standard No. 10-1. (b) Unchanged (c) Water Supply. An approved water supply capable of supplying required fire flow for fire protection shall be provided to all premises upon which buildings or portions of buildings are hereafter constructed. Prior to issuance of a building permit or commencement of construction of any required water supply components, two (2) plot plans indicating designated locations of fire hydrants, loca- tions and sizes of water mains, available water flow information, and information required by Sec. 10.207(a) shall be submitted to the Building Department of The City of Fort Worth for review by the Chief. The Chief will either approve or disapprove the designated water supply components and locations. One copy of an approved plan will be retained by the Chief. -12- Water supply may consist of water mains, elevated tanks, pres- sure tanks, or static water reservoirs equipped with approved fire pumps capable of supplying the required fire flow. In setting the requirements for fire flow, the Chief shall use Appendix III-D. All fire hydrants shall be accessible to the Fire Department apparatus by roadways meeting the requirements of Sec. 10.207. Fire hydrants shall be installed in accordance with the follow- ing criteria: (i). For all R-3 occupancies, excluding unified residential construction, fire hydrants must be installed such that all exterior points on a building fall within a 500 foot radius of a hydrant. No point of said building shall exceed an 800 foot hose lay distance using the route of access which Fire Department personnel would travel between the hydrant and the building. (ii). For all other land uses (except one and two family resi- dences), including unified residential construction, fire hydrants must be installed such that all exterior points on a building fall within a 300 foot radius of a hydrant. No point on any structure shall exceed 500 feet hose lay distance, using the route of access which Fire Department personnel would travel between the hydrant and the structure. (iii). A fire hydrant shall be installed no more than 150 feet from Fire Department connections for a standpipe system, 300 feet from Fire Department connections for a sprinkler system, and 150 feet from Fire Department connections for a combined system. (iv). All fire hydrants must be installed at least two feet, but not more than nine feet from the curb face of a paved street or edge of a designated approved fire access roadway. (v). All fire hydrants must be installed such that the center of the main outlet on the front of the hydrant is not less than 18 inches nor more than 48 inches above grade level. (vi). Only national standard three-way hydrants that open in the clockwise direction are approved. (vii). All hydrant threads must match those in use by the City of Fort Worth Fire Department. (viii). Where fire hydrants are installed on a metered water supply or are not owned by the City of Fort Worth, said hydrants shall be maintained in satisfactory operating condition and be kept free of obstructions. -13- y (ix). All fire hydrants hereafter installed shall be marked with an approved pavement marker. (x). All private fire hydrants shall be painted red and shall be properly maintained by the property owner. (d) Timing of Installation. When fire protection facilities, including fire access roadways and fire hydrants, are required to be installed for any structure or development, such facilities shall be installed, tested and approved prior to the time of which construc- tion has progressed beyond completion of the foundation of any structure. EXCEPTION: The steel framework on Type I and II buildings may be constructed prior to acceptance. (e) Approval and Testing. All fire alarm systems, fire hydrant systems, fire-extinguishing systems, (including automatic sprink- lers), wet and dry standpipes, basement inlet pipes, and other fire protection systems, pertinents thereto shall meet the approval of the fire department as to installation and location and shall be subject to such periodic tests as required by the Chief. Plans and specifications shall be submitted to the Fire Department for review and approval prior to construction. See Sec. 10.207(a), Sec. 10.301(c), and Appendix VII-B. SECTION 10.302. Maintenance Sec. 10.302.(a) Unchanged. (b) Unchanged. (c) Spare Sprinklers. A stock of spare sprinkler heads and a sprinkler wrench shall be maintained immediately adjacent to the sprinkler system control valve in accordance with the following schedule: i) less than 30U heads; not less than 6 spare heads ii) 30U-1000 not less than 12 spare heads iii) more than 1000 not less than 24 spare heads SECTION 10.305 Fire Protection in Recreational Vehicle and Mobile Home Parks, and Mobile Home Sales Lots Sec. 10.305(a). All new and existing mobile home and recrea- tional vehicle parks and mobile home sales lots shall be provided with protection and access roadways as required by the Chief. EXCEPTION: Recreational vehicle parks located in remote areas shall be provided with protection and access road- ways as required by the Chief. P Sec. 10.305(b). Mobile homes on sales lots shall be separated by at least 5 feet measured from eave to eave. SECTIOL~ 10.306 Sec. 10.306.(a) Fire Alarm systems shall comply with the re- quirements of Appendix III-C and Appendix VII-B. SECTIO~i 10.308 Sec. 10.308.(a) Where required. Automatic fire extinguishing systems shall be installed in the occupancies and locations set forth in this section. For special provisions on hazardous chemicals and magnesium and calcium carbide, see Section 10.301 and 45.208 and Articles 48, 49, and 80. For high-piled combustible stock, see Article 81. Regardless of the provisions of this section, all Group R, Division 1, Occupancies three stories or more in height, with inter- ior exiting systems, and all occupancies four stories or more in height, except open parking garages, shall be sprinklered throughout the building. (b) through (f) Unchanged. (g) Group I Occupancies. An automatic sprinkler system shall be installed in Group I occupancies. EXCEPTION: In jails, prisons and reformatories, the piping system may be dry, provided a manually operated valve is installed at a continuously monitored location. Opening of the valve will cause the piping system to be charged. Sprinkler heads in such systems shall be equipped with fusible elements or the system shall be designed as re- quired for deluge systems in U.B.C. Standard No. 38-1. SECTIOYVf 10.311 Sec. 10.311.(a) Unchanged. (b) Unchanged. (c) Location of Class I Standpipes. There shall be a Class I standpipe outlet connection at every floor level above the first story of every required stairway and on each side of the wall adja- cent to the exit opening of a horizontal exit. Outlets at stairways shall be located within the exit enclosure or, in the case of smoke- -15 - proof enclosures, within the vestibule or exterior balcony, giving access to the stairway. Risers and laterals of Class I standpipe systems not located within an enclosed stairway or smokeproof enclosure shall be pro- tected by a degree of fire resistance equal to that required for vertical enclosures in the building in which they are located. EXCEPTION: In buildings equipped with an approved auto- matic sprinkler system, risers and laterals which are not located with an enclosed stairway or smokeproof enclosure need not be enclosed with fire-resistive construction. There shall be a two-way outlet above the roof line on every standpipe when the roof has a slope of less than 4 inches in 12 inches. EXCEPTION: Standpipes located in stairways conforming to Section 3306(0) of the Building code may have the two-way outlet located at the topmost floor landing. In buildings where more than one standpipe is provided, the standpipes shall be interconnected at the bottom. (d) Unchanged. (e) Unchanged. -16- TABLE 10.311 TABS NO. 10.311 - SiAND~PIPE R~,2ili~~ NOL~SPRIN[4~ERED SPRINEQ~ERED BUILDING2 BUILDINGS 4 Standpipe Hose Standpipe Hose OCCUPANCY) Class R~uirement Class Requirement 1. Occupancies exceeding 150 ft. in height and mare than one III Yes III No story 2. Occupancies 4 stories or mare [I and II5] 6 I but less than 150 ft. in height, (or III) Yes (or III) No except Group R, Div. 3 3. Group A Occupancies with II Yes No Re- No occupant load exceeding 1000 quirement 4. Group A, Div. 2.1 Occupancies over 5000 square II Yes II Yes feet in area used for exhibition 5. Groups I, H, B, Div. 1, 2 or 3 Occupancies less than 4 stories II5 Yes No Re- No in height but greater than quirement 20,000 square feet per floor Klass II standpipes need not be provided in assembly areas used solely for v~rship. 2Except as otherwise specified in Item No. 4 of this table, Class II standpipes need not be provided in basements having an automatic fire-extinguishing syst~n throughout such basements. SCombined systems with their related water supplies may be used in sprinklered buildings. 4Portions of otherwise sprinklered buildings which are not protected by automatic sprinklers shall have Class II standpipes installed as required for the unsprink- lered portions. 5In open structures where Class II standpipes may be damaged by freezing, the build- ing official may authorize the use of Class I standpipes which are located as required for Class II standpipes. 6Hose is required for Class II standpipes only. For the purpose of this table, a story height shall be considered to be no rrore than 12 feet. -17- SECTION 10.402 Section 10.402 (a) through (c) Unchanged. (d). Ceiling Construction. In sprinklered buildings all ceiling tiles must be properly installed and maintained to prevent fire pen- etration and to meet required sprinkler head distances. ARTICLE 10 DIVISION V Division V, Sections 10.501 through 10.504, are added to Article 10, to read as follows: DIVISION V Emergency Plans and Fire Drills Section 10.501. High-Rise Buildings. (a) The operator of a premises which has floors used for human occupancy located more than 75 feet above the lowest level of fire department vehicle access shall draft an emergency plan to be located in the Fire Control Room to contain a diagram showing: 1) All means of egress from each floor. 2) Locations of doors which provide access to safe floor areas from the stairwell under emergency conditions. 3) The location of: i) fire command or central control station; ii) fire alarm systems, components and control panels; iii) fire extinguishing systems and valves thereto; iv) smoke control systems and controls thereof; v) fire department communications equipment, and vi) other information required by the Chief. (b) The plan shall include provisions for staff participation in fire emergencies to ensure safe evacuation of all occupants with special attention given to handicapped occupants. (c) Emergency diagrams may be required by the Chief to be posted in conspicuous locations detailing exit diagrams or other similar information or instructions. (d) Fire drills shall be conducted at regular intervals to ensure proper operation of the emergency plan in a fire emergency or at intervals required by the Fire Marshal. Section 10.502.(a) Hotels and Motels. Every hotel and motel having interior exits shall post and maintain on the room side of -18- every guest room door a sign depicting the layout of the floor on which the room is a part, the location of the room on that floor, the exits from that floor, the route to the nearest exit and fire extinguisher locations. (b) Fire drills and emergency plans shall be in accordance with Section 10.501.(b), (c) and (d). Section 10.503.(a) Educational Occupancies. The Fire Marshal may require a quartely fire drill at any educational institution. The operator of premises housing an educational institution shall: 1) Conduct one classroom fire drill each quarter; 2) Maintain a written report of each fire drill in the office of the operator of the premises; and 3) When required, provide the Fire Marshal with a copy of the written report of each fire drill. (b) The operator of premises housing an educational institution shall conduct fire drills in a manner requiring: 1) All students to immediately leave the structure upon hear- ing the fire drill signal; 2) A roll call by classes outside the structure; and 3) Doors to be closed as each area is evacuated. Section 10.504. Elevators. A sign shall be posted adjacent to every elevator call switch panel on every floor of a building containing elevators which states: "IN FIRE EMERGENCY, DO NOT USE ELEVATORS -- USE EXIT STAIRS" or graphically depicts this message in an approved manner. Such sign shall have a minimum dimension of three (3) inches. SECTION 11.101 Sec. 11.101. It shall be unlawful to burn or cause to be burned any combustibles including uncut grass, weeds, timber, rubbish, leaves, or other natural or synthetic materials on any street, alley, lot or premises. Such prohibited fires shall include bon fires and fires used for ceremonial purposes. EXCEPTIONS: 1. Burning may be conducted in an approved incinerator for purposes of cooking or heating in a device designated for such a purpose by the manufacturer. Incin- erators shall comply with Section 11.105. -19 - ,, 2. When approved by the Fire Marshal, burning within an approved trench burner may be permitted provided a standby firefighter is present if so desired by the Fire Marshal. A permit must be acquired as specified in Section 4.101, and approved safety measures must be employed. SECTION 11.117 Sec. 11.117 is added to Chapter 11, to read as follows: Barbecue Pits and Portable Cooking Grills Sec. 11.117 (a) Barbecue Pits (1) The operator of a premises where barbecue pits are used for cooking or heating of food shall provide and maintain the pit with construction of masonry or metal or separa- tion from the enclosed areas accessible to the public by one hour construction. EXCEPTION: One-hour construction shall not be required if the pit construction incorporates: i) automatic ventilation and air supply control; and ii) insulated construction adequate to restrict exterior pit surface temperature to 160°F; and iii) a design adequate to prevent the exposure of the fire box to grease drippings. (2) Where the barbecue pit is inside the building, an approved smoke tight, non-combustible ventilation hood shall be installed in accordance with the mechanical code. The hood shall be installed not more than 18 inches above the pit, extend not less than 12 inches beyond each side of the pit, and be connected to an approved exhaust pipe dis- charging at least 3 feet above the top of the structure. (3) The barbecue pit shall be protected by an approved extin- guishing system designed to meet the criteria of Sec. 10.314 of this code, and the mechanical code of having fixed water discharge openings inside the pit with manual controls located outside the pit enclosure. (4) The barbecue pit shall have nearby a metal container with a tight fitting metal cover for the storage of used grease. (5) No combustible storage shall be placed within 10 feet of the pit unless separated from the pit by a one-hour fire resistive partition. (6) Portable cooking grills shall not be operated within ten (10) feet of any combustible structure, including bal- conies. -2 0- SECTION 11.411 Sec. 11.411. Upon vacating owner and occupant thereof shall any and all noxious and hazardous been deposited, allowed to come thereon, and such premises shall tion. or abandoning any premises, the jointly be responsible for removing a material or waste matter which has to rest or permitted to accumulate be left in a clean and neat condi- When the Fire Department initiates removal of such materials describ ed in this section, the owner and occupant shall be liable for any and all expenses accrued for this service. SECTION 11.412 Sec. 11.412. Every person owning or in charge or control of any vacant building shall remove therefrom all accumulations of flam- mable or combustible waste or rubbish and shall securely lock, bar- ricade or otherwise secure all doors, windows and other openings thereof. When the Fire Department initiates removal, of waste or securing of openings described in this section, the owner and all persons in control of the building shall be liable for any and all expenses accrued for this service. ARTICLE 11, DIVISION V Division V, Section 11.501, is added to Article 11 to read as follows: DIVISION V Removal of Debris or Partially Burned Building After Fire Section 11.501(a). The owner or person having under his control or in his possession upon any premises any hay, straw, bales of wool, cotton, paper or other substances which have been rendered useless or unmerchantable by reason of any fire on such premises or any debris resulting from such fire must remove the same from such premises within forty-eight hours after notice to do so has been given by the Chief. (b) Whenever any building or other structure is partially burned, the owner thereof or the person in charge or control there- of, within ten days after notice from the Chief, shall remove from the premises all refuse, debris, charred and partially burned lumber and material. If such building or other structure is burned to such an extent that it is rendered incapable of being repaired, the owner of the property upon which same is located or the person in control thereof, within ten days after notice from the Chief shall remove from the premises all of the remaining portion of the building or structure. -21- SECTION 25.117 Section 25.117. Standby Firefighters. Whenever, in the opin- ion of the Chief, it is essential for public safety in any place of public assembly or any other place where people congregate due to the number of persons, or the nature of the performance, exhibition, display, contest or activity, the owner, agent or lessee shall employ one or more experienced firefighters, as required and approved by the chief, to be on duty at such place. Said fire- fighters shall be subject to the Chief's orders at all times when so employed and shall be in uniform and remain on duty during the times such places are open to the public, or when such activity is being conducted. Before each performance or the start of such activity, said firefighters shall inspect the required fire appliances pro- vided to see that they are in proper place and in good working order, and shall keep diligent watch for fire during the time such place is open to the public or such activity is being conducted and take prompt measures for extinguishment of fires that may occur. Firefighters shall not be required or permitted, while on duty, to perform any other duties than those herein specified. The Chief may also require the use of standby firefighters in accordance with the provisions of this section when automatic fire detection or protection systems are out of service. SECTION 28.105 Section 28.105. It shall be unlawful to store hay, straw, or other similar agricultural products adjacent to the buildings or combustible material unless a cleared horizontal distance not less than 50 feet is maintained between such storage and combustible material and buildings. All exposed surface area of such storage shall be covered by a tarp or similar cover which has been rendered flame retardant by an approved method or treatment. A permit shall not be required for such storage. Storage shall be limited to 100 tons each. Either an approved one-hour occupancy separating construction as specified in the Building Code or a clear space of 20 feet shall be maintained be- tween such stacks. SECTION 28.107 Section 28.107 is added to Article 28, to read as follows: Sec. 28.107. Any outdoor storage of combustible fibers shall be covered entirely by a tarp or similar cover rendered flame retardant by an approved method or treatment. ARTICLE 31 The title of Article 31 shall be amended to read as follows: -2 2- "TIRE-REBUILDING AND TIRE STORAGE" SECTION 31.101 Section 31.101. General. Tire-rebuilding plants and tire storage shall conform to all other applicable requirements of this code as well as to the following provisions. SECTION 31.102 Section 31.102. Permits. For permits to operate a tire- recapping, tire storage or rebuilding plant, see Section 4.101. SECTION 31.107 Section 31.107 shall be added to Article 31, to read as fol- lows: Section 31.107. Outdoor tire storage is prohibited. EXCEPTIONS: 1. Outdoor tire storage may be permitted when in conjunction with a tire rebuilding, tire recapping, or tire handling operation and less than 50 tires are stored within the boundary of any continuous properties owned by the same person or persons. 2. Outdoor tire storage may be permitted when in conjunction with a tire-rebuilding, tire-recapping, or tire handling opera- tion and 50 or more tires are stored within the boundary of any contiguous properties owned by the same person or persons if such tires are suitable for recapping or rebuilding and if: a) The property is zoned for industrial use, and b) The ground surface covering in the areas used for and adjacent to storage areas for 60 feet in any direction are hard surfaced and kept free of grass, weeds, debris, etc., and c) The perimeter of the storage area is enclosed by a fence not less than 6 feet in height to restrict access by unauthorized persons, and d) Tires are not stored within twenty feet of any structure or property line, and e) Storage configurations are piles not to exceed 625 square feet in area with a maximum dimension of 50 feet, a maxi- mum height of 10 feet and a minimum separation between piles of 20 feet; or in racks no more than 50 feet in length and 10 feet in width with a minimum aisle separa- tion between racks of 10 feet. -2 3 - 3. New or recapped tires displayed for purposes of sale. SECTION 31.108 Section 31.108 shall be added to Article 31, to read as follows: Sec. 31.108. Indoor tire storage six feet and over shall be considered high-piled combustible storage and protected in accor- dance with Article 81. SECTION 34.103 Section 34.103. The sto-rage of combustibles shall be in accor- dance with Article 28 of this code. No smoking or open flame shall be permitted in any area where combustible fibers or other com- bustible waste materials are stored or handled. NO SMOKING signs shall be provided in accordance with Article 13. Tire storage shall be in accordance with Article 31. SECTION 45.206 Sec. 45.206(a). All spraying areas shall be provided with mechanical ventilation adequate to prevent dangerous accumulation of vapors but not less than six (6) air changes per hour. Air changes shall be independent of the building ventilation system. (b) through (i) Unchanged. ARTICLE 78 FIREWORKS Section 78.101. Definition. For definition of FIREWORKS, see ~ Section 9.108. MANUFACTURING, SALE OR DISCHARGE OF FIREWORKS PROHIBITED; PUB- LIC DISPLAY PERMIT APPROVED AND ISSUANCE; NOT CITY LIABILITY. Section 78.102. It shall be unlawful for any person to possess, use, manufacture, sell, offer for sale, give away, transport, or discharge fireworks of any description; provided, however, that the Chief shall have the power to adopt reasonable rules and regulations for the granting of permits for supervised public displays of fire- works by artisans in pursuit of their trade. Every such use or display shall be handled by a competent ope- rator approved by the Chief, and shall be of such character and so located, discharged, or fired as in the opinion of the Chief after proper investigation so as not to be hazardous to property or endan- ger any person. No permit granted hereunder shall be transferable. The Chief shall not approve any application for permit for supervised public display of fireworks unless he finds that: -2 4- (a) The applicant has filed in the City 'Secretary's office a certificate showing the applicant has secured and agrees to keep in force during the term of the permit a policy providing for bodily injury and property damage insurance in the amounts as follows: Property Damage, Per Accident ..........................$100,000 Personal Injury or Death, Per Person ...................$250,000 Personal Injury or Death, Per Accident .................$500,000 Such insurance policy shall provide that it cannot be canceled or amended without at least thirty (30) days notice to the City Secretary; and (b) That the applicant has covenanted and agreed in writing to indemnify, hold harmless and defend at its own expense, the City of Fort Worth, its officers, agents and employees from and against any and all claims or suits for property damage and/or personal injury, including death, or whatsoever kind of character, whether real or asserted, arising out of or in connection with the execution, per- formance or attempted performance of fireworks at a public display whether or not caused, in whole or in part, by alleged negligence of officers, agents or employees of the City of Fort Worth; and the applicant hereby assumes all liability and responsibility for any and all claims or suits for property damage and/or personal injury, including death, or whatsoever kind of character, whether real or asserted, arising out of, or in connection with, the execution, per- formance, or attempted performance of fireworks at a public display, whether or not caused in whole or in part, by alleged negligence of officers, agents or employees of the City of Fort Worth. Applicant likewise covenants and agrees, and does hereby indemnify and hold harmless, the City of Fort Worth from and against any and all in- juries, damage or destruction of City property arising out of, or in connection with, directly or indirectly, all acts or omissions of applicant, his officers, agents, employees, contractors, subcontrac- tors or invitees, or caused by alleged negligence in whole or in part, of officers, agents or employees of the City; and (c) The application for the permit was made in writing at least fifteen (15) days prior to the date of display in accordance with Sec. 4.101 and, (d) The applicant has included in the application for permit the names of the organization sponsoring the display together with the names of persons actually in charge of the firing of the dis- play; and, (e) The applicant has included in the application for permit the date and time of day at which the display is to be held; and, (f) The applicant has included in the application for permit the exact location planned for the display; and, (g) The applicant has included in the application for the per- mit a description setting forth the age, experience, and physical -25- characteristics of the persons who are to do the actual discharging of the fireworks; and, (h) The applicant has included in application for permit the number and kinds of fireworks to be discharged; and, (i) The applicant has included in the application for permit the manner and place of storage of such fireworks prior to the dis- play; and, (j) The applicant has included in the application for the per- mit a diagram of the grounds on which the display is to be held showing the point at which the fireworks are to be discharged, the location of the buildings, highways and other lines of communica- tion, the lines behind the audience will be restrained, and the location of all nearby trees, telegraph or telephone lines or other overhead obstructions. Section 78.103. (a) Use and Handling. The Chief shall approve the application and issue the permit for the public display of fire- works if he finds that: the applicant has complied with the appli- cable provisions for this article; the discharge, failure to fire, faulty firing, or fall-out of any fireworks or other objects will not endanger any person, buildings, structures, forests, or brush; and the fireworks are to be fired more than 200 feet from the nearest permanent building, public highway, railroad, or other means of travel; and 50 feet from the nearest above ground telephone or telegraph line, tree or other overhead obstruction. In no case shall the Chief issue a permit for a display to be held within six hundred (600) feet of a school, theater, church, hospital, or similar insti- tution. (b) All fireworks that fire a projectile shall be so set up that the projectile will go into the air as nearly as possible in a vertical direction; provided, however, that where such fireworks are to be fired beside a lake or other large body of water, they may be directed in such a manner that the falling residue from the defla- gration will fall into said body of water. (c) Any fireworks that remain unfired after the display is con- cluded shall be immediately disposed of or removed in a manner safe for the particular type of fireworks. The debris from the discharged fireworks shall be properly disposed of by the operator before he leaves the premises. The operator, upon the conclusion of the dis- play, shall make a complete and thorough search for any unfired fireworks or pieces thereof which have failed to fire or function and shall dispose of them in a safe manner. The search shall be in- stituted at the earliest possible time following that conclusion of the display, but in no event later than the first period of daylight which follows. (d) No fireworks display shall be held during any windstorms in which the wind reaches a velocity of more than twenty (20) miles per hour. -2 6- (e) All fireworks articles and items at places of display shall be stored in a manner and in a place secure from fire, accidental discharge, and theft, and in a manner approved by the Chief. (f) The approval of any application and issuance of any permits by the Chief shall in no way be construed as an assumption of re- sponsibility or liability by the City for any damages or injuries to persons or property arising out of or incident to the discharge of fireworks at a public display. AIDING MINORS TO VIOLATE ARTICLE Section 78.104. No parent or guardian of a minor shall furnish money or a thing of value to a minor for the purchase of fireworks or encourage, act in conjunction with or in any manner instigate or aid a minor in the commission of possession, selling, offering for sale, giving away, using, transporting or manufacturing fireworks within the city. The commission of the offense by the minor on the property under the control or owned by the parent or guardian shall be prima facie proof that the relation or guardian was instigating or aiding the minor. Section 78.105. This article shall not apply to the possession or use of signaling devices for current daily consumption by rail- roads, vessels and others requiring them; or to the possession, sale or use of normal stocks of flashlight compositions by photographers or dealers in photographic supplies; or to the possession or use of flares or rockets for military or police purposes; or any auto flares; or paper caps containing not in excess of an average of twenty-five one hundredths (25/100ths) of a grain of explosive con- tent per cap, and toy pistols, toy canes, toy guns or other devices for use of such caps, the sale and use of which shall be permitted at all times. Model rockets that can be defined by the scope of NFPA 1122 shall be regulated by that code. TERRITORIAL APPLICABILITY Section 78.106. The provisions of this article shall be appli- cable within the corporate limits of the city and also within the area immediately adjacent and contiguous to the city limits and extending outside the city limits for a distance of five thousand feet unless such area is within the corporate limits of another municipality. Section 78.107. The Chief shall seize, take, remove or cause to be removed and destroyed at the expense of the owner, all stocks offered or exposed for sale, stored or held in violation of this article . SECTION 79.101 Section 79.101(a). The storage, use, dispensing and mixing of flammable and combustible liquids shall be in accordance with this -2 7- r article, except as otherwise provided in other laws or regulations. Installers of underground tanks should reference the guidelines of the "Information Bulletin - Storage and Handling of Flammable and Combustible Liquids" published by the Fire Prevention Bureau of the Fort Worth Fire Department. This article also applies specifically to all flammable and combustible liquids as defined in Section 79.102, except those that are solid at 100°F or above. When heated, sprayed or mixed, Class II or Class III liquids may assume the characteristics of lower flash point liquids. Under such conditions, the appropriate provisions of this article for the actual flash point shall apply. EXCEPTIONS: 1. The transportation of flammable and com- bustible liquids when in conformity with the Department of Transportation (DOT) regulations on file with and approved by the Department of Transportation. 2. Alcoholic beverages in retail sales or storage uses, provided the liquids are packaged in individual con- tainers not exceeding 4 liters. 3. Medicines, foodstuffs and cosmetics, containing not more than 50 percent by volume of water-miscible liquids and with the remainder of the solution not being flam- mable, in retail sales or storage uses when packaged in individual containers not exceeding 4 liters. 4. Storage and use of fuel-oil tanks and containers connected with oil-burning equipment. Such storage and use shall comply with Article 61 and the Mechanical Code. 5 Liquids without flash points that can be flammable under some conditions, such as certain halogenated hydro- carbons and mixtures containing halogenated hydrocarbons. 6. Mists, sprays or foams except flammable aerosols in containers as may be included under Division II. (b) through (c) Unchanged. SECTION 79.604 (a) Unchanged. (b) Tank openings other than vents for underground tanks. 1. General. All connections, fittings or other appurtenances shall be installed in accordance with Division VII, "Piping, Valves and Fittings." 2. Openings for manual gaging. Openings for manual gaging, if independent of the fill pipe, shall be provided with a liquid-tight cap or cover. Covers shall be kept closed when not gaging. If inside -2$- a building, each such opening shall be protected against liquid overflow and possible vapor release by means of a spring-loaded check valve or other approved device. 3. Fill pipe and discharge lines. Fill pipe and discharge lines shall enter tanks only through the top. Fill lines shall be sloped toward the tank. Underground tanks for Class I liquids having a capacity of more than 1,000 gallons shall be equipped with a tight fill device for connecting the fill hose to the tank. For Class I liquids other than crude oils and asphalts, the fill pipe shall be so designed and installed as to minimize the possibility of generating static electricity by terminating within 6 inches of the bottom of the tank. 4. Location of connections that are made or broken. Filling and emptying and vapor-recovery connections for Classes I, II and III-A liquids which are made and broken shall be located outside of build- ings at a location free from any source of ignition and not less than 5 feet away from any building opening. Such connections shall be closed and liquid tight when not in use and shall be properly identified. 5. Protection against vapor release. Tank openings provided for purposes of vapor recovery shall be protected against possible vapor release by means of a spring-loaded check valve or dry-break connec- tion, or other approved device, unless the opening is pipe-connected to a vapor-processing system. Openings designed for combined fill and vapor recovery shall also be protected against vapor release unless connection of the liquid delivery line to the fill pipe simultaneously connects the vapor-recovery line. All connections shal l be vapor t fight . OVERFILL PROTECTION SECTION 79.709 Section 79.709(a). All owners and operators shall ensure that releases due to spills or overfills do not occur. The owner and operator shall ensure that the volume available in the tank is greater than the volume of product to be transferred to the tank before the transfer is made and that a person is physically present at all times during transfer to observe the transfer. (b). All new storage systems, as well as all existing systems requiring external release detection, shall use one or more of the following spill or overfill prevention devices: (1) A sensor fo r measuring the level of product in the tank, equipped with an audible or visual alarm that is triggered when the tank is 95% full; (2) A device designed to cause flow into the tank to shut off automatically when the tank is 95% full; -29- (3) A spill catchment basin around the fill pipe large enough to contain the volume of the hose; (4) An equivalent device designed to prevent releases due to spills and overfills that is approved by the Chief. (c). All owners and operators of existing systems requiring overfill protection in 79.709(b), shall use one or more of the spill or overfill devices as specified in 79.709(b) for each tank when permitted for repairs, but no later than January 1, 1997. SECTION 79.902 Section 79.902.(a) Unchanged. (b) General Provisions. Class I liquids shall be stored in closed containers or in tanks located underground or in special enclosures as described in Section 79.902(c). Class II and Class III-A liquids shall be stored in containers or in tanks located underground or in special enclosures as described in section 79.902 (c) . A connection shall not be made between any above ground tank and any underground tank. The temporary use of portable or semi-portable tanks in conjuc- tion with the dispensing of Class I, II, or III-A liquids into the fuel tanks of motor vehicles or other motorized equipment shall only be permitted on construction sites. Such installations must have specific approval of the Fire Marshal. (c) Special Enclosures. Stationary tanks used for the fueling of motor vehicles shall not be installed in any manner other than underground. When installation of tanks in accordance with Division VI is impractical or because of property or building limitations, tanks for Class I, II or III-A liquids may be installed in buildings if enclosed as follows: Enclosure shall be liquid tight and vapor tight without backfill. Sides, top and bottom of the enclosure shall be reinforced concrete at least 6 inches thick, with openings for inspection through the top only. Tank connections shall be so piped or closed that neither vapors nor liquid can escape into the en- closed space. Means shall be provided whereby portable equipment may be employed to discharge to the outside any vapors which might accumulate should leakage occur. Tanks containing Class I, II or III-A liquids shall not exceed 6000 gallons individually or 18,000 gallons aggregately. (d) through (h) unchanged. SECTION 79.912 Section 79.912(a) General. This section shall apply to all vapor recovery and vapor-processing systems. -3 0- No person shall transfer, or allow the transfer of, gasoline from any delivery vessel into a storage tank with a nominal capacity greater than 1,000 gallons, unless displaced vapors are processed by a vapor recovery system. EXCEPTIONS: (1) Containers used exclusively for the fueling of implements of agriculture. (2) Storage tanks equipped with external floating roofs, internal floating roofs, or their equivalent. (3) Stationary containers of nominal capacity less than 2,000 gallons (7,571 liters) if installed before December 10, 1976. (4) Stationary storage tanks located at a facility which dispenses less than 120,000 gallons (454,249 liters) of gasoline per year. (b). Vapor-balance systems. 1. Dispensing devices. Dispensing devices incorporating provisions for vapor recovery shall be listed and labeled. Existing listed or labeled dispensing devices may be modified for vapor recovery, provided that the modifications made are "listed by report" by a nationally recognized testing labora- tory. The "listing by report" shall contain a description of the component parts used in the modification and recommended method of installation on specific dispensers. Such report shall be made available upon request to the Chief. Means shall be provided to shut down fuel dispensing in the event the vapor-retur n line becomes blocked. 2. Vapor-return line closeoff. An acceptable method shall be provided to close off the vapor-return line from dispensers when the product is not being dispensed. 3. Piping materials. All piping in a vapor-recovery system shall comply with Divisions V, VI and VII of this article. Nonmetal- lic piping, if used, shall be installed as per the manufacturer's installation instructions. 4. Piping installation. All existing or new vent piping shall comply with Divisions V, VI and VII. All vapor-return piping shall be so laid as to drain back to the tank. There shall be no sags or traps in the vapor-return piping in which liquid can become trapped. If necessary, due to grade, condensate tanks may be in- stalled in vapor-return piping. All condensate tanks shall be designed and installed so they may be emptied of liquids without opening. 5. Swing joints and shear section. Swing joints shall be pro- vided in all vapor-return piping at the tank and at the base of the riser, below the dispenser. -31- An approved shear section shall be properly installed, rigidly mounted and connected by a unio n in the vapor-return piping at the base of each dispensing device. "Properly installed" shall mean that the shear section is mounted flush with the top of the surface upon which the dispenser is mounted. 6. Testing. All vapor-return lines and vent piping shall be tested in accordance with Section 79.708. 7. Special provision for gasoline tanks. When a vapor balance system is used to comply with Section 79.912(a), the system shall meet the following conditions: (i) A vapor-tight return line is connected before gaso- line can be transferred into the storage container. (ii) No gasoline leaks exist anywhere in the liquid trans- fer system. (iii) The vapor return line's cross-sectional area is at least one-half of the product drop line's cross- sectional area. (iv) The only atmospheric fer into the storage container vent line no greater than 3/4 or a pressure-vacuum pressure of no less (3.4 kPa). emission during gasoline trans- container is through a storage equipped either with an orifice inch (1.9 cm) internal diameter relief valve set to open at a than 8 ounces per square inch (v) The delivery vessel is kept vapor-tight at all times (except when gauging) until the captured vapors are discharged to a loading facility with vapor recovery equipment. (vi) Gauge pressure in the tank-vehicle tank does not exceed l8 inches of water (4.5 kPa) or vacuum exceed 6 inches of water (1.5 kPa). (vii) Readings less than 100°s of the lower explosive limit (LEL, measured as propane) at 1 inch (2.5 cm) from potential leak sources when measured with a combus- tible gas detector. (c) through (d) Unchanged. SECTION 79.1204 Section 79.1204(a). Vehicle Maintenance. Tank vehicles shall not be operated unless they are in proper repair, devoid of accumu- lation of grease, oil or other flammables and free of leaks. Gaso- line tank vehicles delivering to tanks required to have a vapor recovery system shall be inspected for leaks within one year and -32- ~. shall display appropriate D.O.T. certification. See Section 79.912(a). (b) through (m) Unchanged. Section 80.112. Unauthorized Discharge Sec. 80.112(a). Accurate records shall be kept by the permittee of the unauthorized discharge of hazardous materials. (b). The Chief shall be immediately notified when an unautho- rized discharge becomes reportable under state, federal, or local regulations. (c). Provisions shall be made for controlling and mitigating unauthorized discharge. (d). Any person, firm or corporation responsible for any unau- thorized discharge shall institute and complete all actions neces- sary to remedy the effects of such unauthorized discharge, whether sudden or gradual, at no cost to the City of Fort Worth. When deemed necessary by the Chief, clean-up may be initiated by the Fire Department or by an authorized individual or firm, All costs associ- ated with such clean-up shall be borne by the owner, operator, or other person responsible for the unauthorized discharge. SECTION 81.105 Section 81.105. Fire Protection for buildings used for high- piled combustible storage shall be in accordance with Table No. 81.105 and the Building Code. Speculative buildings which are greater than 12,000 square feet which measure 15 feet or more from the floor to the bottom of the roof system shall be considered as containing Class IV Commodities for the purpose of determining fire protection. Storage of aerosols shall be as follows: Level I - Level I aerosols shall be treated as a Class III com- modity. Level II and III - Level II and III aerosols shall be treated as a Class V commodity and subjected to the sprinkler require- ments of Tables 81.108 and 81.109. Storage of Class II and III aerosols shall only be permitted in vaults with walls of masonry or concrete construction. Such vaults shall be maintained with self-closing doors which remain closed at all times except when goods are actually being transferred in or out of the vaults. No other storage shall be permitted within the vault except aerosols. -33- ' p. TAB1_E 81.108 TABLE 81.108. ARRANGEMENT AND PROTECTION OF PALLETIZED AND SOLID-PILE STORAGE ~ AEROSOL CONTAINERS Max. Height Duration Temperatur® Ho so Storage to Sprinklers Max. Pile Sprinkler Rating d Strewn Sprinkler _ d Hose Level Height Spacing Sprinkler Size Sprinkler Demand Demand Clearance Stream 18 ft 80-100 ft2 160°F (71°C) 15 heads at 50 psi 500 gpm 5 ft or less 11 (5.5 m) (7.4-9 m2) 0.64 in. 116.3 mm) (344 kPa) (1.9 m3/min) (1.5 m or less) 2 hr "large drop" 10 ft BO-100 ft2 160°F 171°C) 15 heads at 75 psi 500 gpm 10 ft or less III (3 m) (7.4-9 m2) 0.64 in. (16.3 mm) (517 kPa) (1.9 m3/min) (3 m or less) 2 hr "large drop" . TAA1 F R1 _ 1 AO TABLE 81.109. PROTECTION OF RACK STORAGE OF LEVEL II d III AEROSOL CONTAINERS Duration- Clearance Ceiling Hose Sprinklers Storage Ceiling Sprinkler In-Rack Sprinkler Sprinkler In-Rack Sprinkler Stream and Hose to Level Arrangement Arrangement* Demand Demand Demand Stream s Sprinklers it 286°F (141°C) 165°F (74°C> or 0.30 gpm/ft2 30 gpm (O.ttm3/min) 500 gpm 2 hr 15 ft rated heads 100 less sprinklers (12mm/min) discharge per head (1.9m3/ (4.6m). ft2 (9.3m2) max. 8 ft (2.4m) apart over 2500 minimum. Base on min) Need bar- spacing 1/2 in. max. One line at ft2 (230;n2) operation of hy- rier with (12.5mm) or each tier except drauiicaliy most re- sprinklers 17/32 in. (14mm) top. Locate in mote (1) 8 sprink- beneath if orifice longitudinal flue lers if one level. clearance spaces of double- (2) 6 sprinklers exceeds row racks. each of 2 levels if 15 ft only 2 levels. (3) (4.6m) 6 sprinklers on top 3 levels if 3 or more levels. III 286°F (141°C) 165°F (74°C) or 0.30 gpm/ft2 Same as Level II 500 gpm 2 hr 5 ft (1.5m) rated heads 17/32 less sprinklers (12mm/min) (1.9m3/ or less in. (14mm) ori- 8 ft (2.4 m) over 2500 min> face 100 ft2 apart max. In- ft2 (230m2) (9.3 m2) max. stall in long(- spacing tudinal flue 0.60 gpm/ft2 5 ft (1.5m) and on face. (24mm/min) to 15 ft Stagger face• over 1500 (4.6m). If sprinklers with ft2 (140m2) greater sprinklers on to 2500 ft2 than 15 ft opposite side (230 m2) (4.6m), of rack. need bar- ter with sprinklers beneath. *Prav idw annroved rack ctnranp cnrinkl~?rs with built-in water shields. Locate longitudinal flue in-rack sprinklers at least 2 3't (0.6m) from rack uprights. Provide at least 6 inches between sprinkler deflectors end top of storage In tier. -34-~.~ ~~ a .. SECTION 82.104 Section 82.104. All liquefied petroleum gas equipment, includ- ing such equipment installed at utility gas plants, shall be in- stalled in accordance with the provisions of UFC Standard No. 82-1 and UFC Standard No. 82-2 except as required by "Safety Rules, Liquefied Petroleum Gas Provision" of the Railroad Commission of Texas, Docket 1, which shall take precedence over all rules speci- fied in the Fire Code. SECTION 82.105 (a) through (c) Unchanged. Section 82.105(d). Liquid petroleum gas containers designed to hold 75 gallons or less shall not be filled in residential areas. II. THE FOLLOWING APPENDIX SECTIONS OF THE 1985 EDITION OF THE UNIFORM FIRE CODE (EXHIBIT "A") ARE HEREBY AMENDED, AND APPEN- DICES IB, III-A, III-C, III-D, VII-A AND VII-B ARE CREATED AND ADOPTED, TO READ AS FOLLOWS: AMEND APPENDIX I A TO RFAD AS FOLLOWS: APPENDIX I A LIFE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS OTHER THAN HIGH RISE 1. GENERAL (a) Unchanged. (b) Effective Date. Within 18 months after notice is given, either under Ordinance 9281, Ordinance 9280, Ordinance or this ordinance, plans for compliance shall be submitted and approved, and within 18 months thereafter the work shall be com- pleted or the building shall be vacated until made to conform. (c) Alternate Materials and Methods. Alternate materials and methods may be used, provided such materials or methods comply with the spirit and intent of this appendix. The Building Official may modify any of the provisions of this appendix in conformance with Section 106 of The 1985 Uniform Building Code. 2. EXITS (a) and (b) Unchanged. (c) Corridors. Corridors of Groups A, E, H, I and R, Division 1 Occupancies, serving as an exit for an occupant load of ~~ r 30 or more shall have walls and ceilings of not less than one-hour fire-resistive construction as required by this Code. Existing walls surfaced with wood lathe and plaster in good condition or 1/2 inch gypsum wallboard or openings with fixed wired glass set in steel frames are permitted for corridor walls and ceilings and occupancy separations when approved. Doors opening into such corridors shall be protected by 20-minute fire assemblies or solid wood doors not less than 1-3/4 inch thick. Where the existing frame will not accom- modate the 1-3/4 inch door, 1-3/8 inch thick solid bonded wood core door or equivalent insulated steel door shall be permitted. Doors shall be self-closing or automatic-closing by smoke detection. Transoms and openings other than doors from corridors to rooms shall comply with Section 3305(h) of the Building Code or shall be covered with a minimum of 3/4 inch plywood or 1/2 inch gypsum wallboard or equivalent material on the room side. EXCEPTIONS: (1) Existing corridor walls, ceilings and opening protection not in compliance with the above may be continued when such buildings are protected with an approved automatic sprinkler system throughout. Such sprinkler system may be supplied from the domestic water system if it is of adequate volume and pressure. (2) Where an approved fire alarm system is installed, which includes smoke detection in all common corridors serving an exit for an occupant load of 30 or more, wall openings 'may be non-protected except that doorway openings shall have self-closing doors. The fire alarm system shall be interfaced with the HVAC System to shut off any central HVAC unit in any area where a fire is detected and shall be installed in accordance with Appendix III-C of the Fire Code. (3) In a corridor of a Group B or E Occupancy, having been constructed with a six (6) foot wide corridor under Ordinance #6374, only the approved fire alarm system shall be required. Corridor protection required by this section will not be required. Remodeling of existing corridor wall must meet the requirements for new construction. (d) and (e) Unchanged. 3. ENCLOSURE OF STAIR~TAYS AND VERTICAL SHAFTS Interior vertical shafts, including but not limited to stair- ways, elevator hoistways, service and utility shafts, shall be enclosed by a minimum of one-hour fire-resistive construction. All openings into such shafts shall be protected with one-hour fire assemblies which shall be maintained self-closing or be automatic closing by smoke detection. All other openings shall be fire pro- tected in an approved manner. Existing fusible link-type automatic door closing devices may be permitted if the fusible link rating does not exceed 135°F. -36- iN EXCEPTIONS: (1) In other than Group I and Group R, Division 1 Occupancies, an enclosure will not be required for openings serving only one adjacent floor. (2) Stairways in other than Groups H, I and Group R, Division 1 Occupancies, need not be enclosed in a continuous vertical shaft if each story is separated from other stories by one-hour fire-resistive construction or approved wired glass set in steel frames. In addition, all exit corridors shall be sprink- lered and the openings between the corridor and occupant space shall have at least one sprinkler head above the openings on the tenant side. The sprinkler system shall be supplied from the domestic water supply if of adequate volume and pressure. (3 ) Vertical openings need not be protected if the building is protected by an approved automatic sprinkler system. 4. BASEMENT ACCESS OR SPRINKLER PROTECTION Unchanged. 5. STANDPIPES Unchanged. 6. SMOKE DETECTORS See Appendix III-C. 7. SEPARATION OF OCCUPANCIES Occupancy separations shall be provided as specified in Sec- tion 503 of the Building Code. When approved by the Building Official, existing wood lath and plaster in good condition or 1~2-inch gypsum wallboard may be acceptable where one-hour occupancy separations are required. CHAPTER I-B EXISTING HIGH-RISE BUILDINGS 1. Scope These provisions shall apply to existing high-rise buildings constructed prior to the adoption of this chapter and which house Group B, Division 2 offices or Group R, Division 1 Occupancies, each having floors used for human occupancy located more than 75 feet above the lowest level of fire department vehicle access. -37- EXCEPTION: Section 6(a) Item #14 applies to Group A, B, E, H, I and R-1 occupancies. 2. General Existing high-rise buildings as specified in the scope shall be modified to conform with not less than the minimum provisions specified in Table No. A-1-A and as further enumerated within this chapter. The provisions of this chapter shall not be construed to allow the elimination of fire protection systems or a reduction in the level of fire safety provided in buildings constructed in conformance with previously adopted codes. 3. Compliance Date After adoption of this chapter, the Building Official, upon finding non-compliance, shall duly notify the owners whose buildings are subject to the provisions of this chapter. Upon receipt of such notice, the owner shall, subject to the follow- ing time limits contained herein, take the necessary actions to comply with the provisions of this chapter. Plans and specifications for the necessary alterations shall be filed with the Building Official within 18 months after the date of owner notification. Work on the required alterations to the building shall commence within 30 months of the date of owner notification and such work shall be completed within five years from the date of owner notification. The Building Official shall grant necessary extensions of time where it can be shown that the specified time periods are not physically practical or pose an undue hardship. The granting of an extension of time for compliance shall be based upon the showing of good cause and subject to the filing of an accept- able systematic progressive plan of correction with the Building Official. 4. Authority of Building Official For the purpose of applying the provisions of this chapter, the Building Official shall have the authority to consider alterna- tive approaches and grant necessary deviations from this chap- ter as follows: A. Allow alternate materials or methods of compliance if such alternate materials or methods of compliance will provide levels of fire and life safety equal to or greater than these specifically set forth in this chapter. -38- B. Waive specific individual requirements of this chapter if it can be shown that such requirements are not physically possible or practical, that a practical alternative cannot be provided, and that said waiver will not create an unsafe condition or otherwise constitute a hazard to safety, health or public wel- fare. 5 . Appeal Appeals of the determination of the Building Official in apply- ing the provisions of this Code may be appealed to the Con- struction and Fire Prevention Board of Appeals. 6. Specific Provisions and Alternates (a). Specific Provisions. The following provisions shall apply when required by Table No. A-1-A. 1. Fire Department Communication System. When it is determined by test that portable fire department communications equipment is ineffective, a communications system acceptable to the Fire Department shall be installed within the existing high-rise building to permit emergency communication between fire suppression personnel. 2. Single-Station Smoke Detectors. Single-station smoke detectors conforming to UBC Standard 43-6 shall be installed within all dwelling units or guest rooms in accordance with their listing. Such detectors may be battery powered. 3. Manual Fire Alarm Systems. An approved manual fire alarm system connected to a central, proprietary or remote station service, or an approved manual fire alarm system which will provide an audible signal at a constantly attended location, shall be provided. 4. Occupant Voice Notification System. An approved occupant voice notification system shall be provided. Such system shall provide communication from a location acceptable to the Fire Department and shall permit voice notification to at least all normally occupied areas of the building. The occupant voice notification system may be combined with the Fire Department communication system and the public address system, provided the combined system has been approved and listed for such use. The sounding of a fire alarm system in any given area or floor shall not prohibit voice communication to other areas or floors. Combination systems shall be designed to permit voice notification -39- ,. system to override the fire alarm signal, but the fire alarm shall not terminate in less than three (3) minutes. 5. Vertical Shaft Enclosures. Openings through two or more floors except mezzanine floors, which contain a stairway, escalator or elevator, shall be provided with vertical shaft enclosure protection as specified herein. Such floor openings, when not enclosed by existing shaft enclosure construction, shall be protected by one-hour fire- resistive rated shaft enclosure construction. For floor openings which are enclosed by existing shaft enclosure construction having fire-resistive capabilities similar to wood lathe and plaster in good condition, 1/2-inch gypsum wallboard or 1/4-inch thick rated wire glass is accept- able. Wired glass set in a steel frame may be permitted in existing shaft enclosure walls, but shall be rendered inoperative and fixed in a closed position when required by the Building Official. Openings through two or more floors for other than stair- ways, elevators or escalators, such as openings provided for piping, ducts, gas vents, dumbwaiters and rubbish and linen chutes, shall be provided with vertical shaft en- closure as specified for stairways and elevators. EXCEPTION: Piping, ducts, gas vents, dumbwaiters and rubbish and linen chutes of copper or ferrous con- struction are permitted without a shaft enclosure, provided the floor openings are effectively fire- stopped at each floor level. 6. Shaft Enclosure Opening Protection. Openings other than those provided for elevator doors in new vertical shaft enclosures constructed of one-hour fire-resistive con- struction shall be equipped with approved 20-minute rated fire assemblies. Openings other than those provided for elevator doors in existing vertical shafts shall be equipped with approved 20-minute rated fire assemblies, 1-3/4 inch solid wood doors or the equivalent thereto. Doors shall be either self-closing or automatic closing. 7. Manual Shutoff of HVAC Systems. HVAC Systems shall be equipped with manual shutoff controls installed in a loca- tion approved by the Fire Department. 8. Automatic Elevator Recall System. Elevators shall be equipped with an approved automatic recall system as re- quired by Sec. 1808(h)2 of the Building Code. -40- ~+ 9. Unlocked Stairway Doors. Exit doors into exitway stairway enclosures shall be maintained unlocked from the stairway side on at least every fifth floor level. All unlocked doors shall bear a sign stating "ACCESS ON FLOOR THI5 LEVEL". Stairway doors may be locked, subject to the following conditions: A. Stairway doors which are to be locked from the~stair- way side shall have the capability of being unlocked simultaneously without unlatching upon a signal from the central control station. B. A telephone or other two-way communication system connected to an approved emergency service which operates continuously shall be provided at not less than every fifth floor in each required stairway. 10. Stair Shaft Ventilation. Stair shaft enclosures which ex- tend to the roof shall be provided with an approved manu- ally openable hatch to the exterior which has not less than 16 square feet in the area with a minimum dimension of two feet. EXCEPTION: (1) Stair shaft enclosures which comply with the requirements of stair pressurization. (2) Pressurized stair shaft enclosures. 11. Elevator Shaft Ventilation. Elevator shaft enclosures which extend to the roof shall be vented to the outside with vents whose area shall not be less than 3-1/2 percent of the area of the elevator shaft, with a minimum of 3 square feet per elevator. EXCEPTION: Where energy conservation or hoistway pressurization requires that vents be normally closed, automatic venting by activation of an elevator lobby detector or power failure may be acceptable. 12. Posting of Elevators. A permanent sign shall be installed in each elevator cab adjacent to the floor status indica- tor and at each elevator call station on each floor read- ing "IN FIRE EMERGENCY, DO NOT USE ELEVATOR -- USE EXIT STAIRS", or similar verbage approved by the Building Official. -41- EXCEPTION: Sign may be omitted at the main entrance floor level call station. 13. Exits. General. (a) Every floor from an existing high-rise building shall have access to two separate means of egress, one of which may be an existing exterior stairway not less than 30 inches in clear width. The stairway may be constructed with an 8-inch maximum rise and 9-inch minimum run, provided the greater riser height and largest tread do not exceed the smallest by more than 3/8 inches. The adequacy of fire escapes shall be demonstrated to the satisfaction of the Building Official. (b) Fire Escapes. Access to fire escapes may be any one of the following: (i) Through a room between the corridor and the fire escape if the door to the room is oper- able from the corridor side without the use of any key, special knowledge or effort. (ii) By a door to a fire escape operable from the interior without the use of any key, special knowledge or effort. (iii) By a window operable from the interior. Such window shall have a minimum dimension of 29 inches when open and the sill shall not be more than 30 inches above the floor and land- ing. (c) Protection of Exterior Openings. When a fire escape is accepted as one of the required means of egress, openings onto the fire escape landing and openings within 10 feet horizontally of the landing shall be protected in a manner acceptable to the Building Official. 14. Exit Corridor Construction and Openings Other Than Doors. Corridors of Groups A, B, E, H, I and R, Division 1 occu- pancies serving as an exit for an occupant load of 30 or more shall have walls and ceilings of not less than one- hour fire-resistive construction as required by the Building Code. Openings other than exit doors shall be protected as outlined in Item 15. Existing walls surfaced with wood lathe and plaster in good condition or 1/2-inch gypsum wallboard are permitted for corridor walls and ceilings and occupancy separations when approved. EXCEPTIONS: (1) Where an approved fire alarm system is installed, which includes smoke detection in all -42- common corridors serving as an exit for an occupant load of 30 or more, up to twenty-five percent (25°s) of the wall area of a room common to the corridor may be tempered glass installed in metal or solid wood frames. The fire alarm system shall be interfaced with the HVAC System to shut off any central HVAC unit in any area where a fire is detected. (2) Where a corridor of a Group B or E Occupancy, having been constructed with a six (6) foot wide corridor under Ordinance #6374, only the approved fire alarm system shall be required. Corridor protec- tion required by this section will not be required. Remodeling of existing corridor walls must meet the requirements for new construction. 15. Exit Corridor Openings. Openings in corridor walls and ceilings shall be protected by not less than 1-3/$ inch solid-bonded wood-core doors, 1/4-inch thick wired glass conforming to Section 4306(1) of the Building Code, by approved fire dampers conforming to UBC Standard No. 43-7, or by equivalent protection in lieu of any of these items. Transoms shall be fixed closed and covered with materials having a fire-resistive rating equal to 1/2-inch Type X gypsum wallboard or equivalent material installed on both sides of the opening. 16. Exit Corridor Door Closers. Exit doors into corridors shall be equipped with self-closing devices or shall be automatic closing by actuation of a smoke detector. 17. Exit Corridor Dead-ends. Corridors having a dead-end serv- ing an occupant load of more than 3U shall be arranged such that dead-end conditions do not exceed 35 feet. 18. Interior Finish. The interior finish to exit corridors, exit stairways and extensions thereof shall conform to the provisions of Chapter 42 of the Building Code. 19. Exit Stairway Illumination. Exit stairways shall be illu- minated at any time the building is occupied with lights having an intensity of not less than 1-foot candle from the floor level. Such lighting shall be equipped with an independent alternate source of supply such as an emer- gency battery pack. 20. Exit Corridor Illumination. Exit corridors shall be illu- minated at any time the building is occupied with lights having an intensity of not less than 1-foot candle at the -43- ~, ~. floor level. Such lighting shall be equipped with an inde- pendent alternate source of supply such as an emergency battery pack. 21. Exit Stairway Exit Signs. The location of exit stairways .shall be clearly indicated by illuminated exit signs. Such exit signs shall be equipped with an independent alternate source of supply such as a battery pack, or shall be an approved self-illuminating type. 22. Exitway Exit Signs. Illuminated exit signs shall be pro- vided in all exitways and located in such a manner as to clearly indicate the direction of egress. Such exit signs shall be equipped with an independent alternate source of supply such as a battery pack or shall be an approved self-illuminating type. 23. Emergency Planning. See Fire Code, Sec. 10.501. 24. Posting of Emergency Plans. See Fire Code, Sec. 10.501. 25. Fire Drill. See Fire Code, Sec. 10.501. (b) Sprinkler Alternatives. The following requirements of Table No. A-1-A are not required or may be modified as specified herein for existing high-rise buildings of Type I, II-FR, II-one-hour, III-one-hour, IV or V-one-hour construction covered by this chapter when an approved automatic sprinkler system is installed in accordance with the UBC Standard No. 38-1. Item 3. Manual Fire Alarm System shall not be re- quired. Item 4. Occupant notification system shall not be required; however, if the building is equipped with a public address system, it shall be available for use as an occupant voice notification system. Item 5. Vertical shaft enclosures may be of non- rated construction for required exit stair- way enclosures. Vertical shaft enclosures of openings in floors provided for eleva- tors, escalators and supplemental stairways shall not be required, provided such open- ings are protected by an approved curtain board and water curtain system. -4 4- 1 f .' Item 6. Protection of openings in vertical shaft enclosures may be non-rated but shall be not less than a 1-3/4 inch solid wood door or the equivalent thereto. Closing and latching hardware shall be provided. Item 8. An automatic elevator recall system shall not be required. Item 10. Stairshaft ventilation shall not be re- quired. Item 14. Exit corridor construction shall not be re- quired. Item 15. Exit door openings into exit corridors may be protected by assemblies other than those specified in Section 106(a), provided an effective smoke barrier is maintained. Closing and latching hardware shall be pro- vided. Protection of duct penetrations is not required. Item 17. The length of the existing corridor dead- ends shall not be limited. Item 18. Interior finish in exitways may be reduced by one classification but shall not be less than Class III. Installation of meters or backflow preventers for the connection to the water works system need not be pro- vided unless required by other regulations of the authority having jurisdiction. -45- rAar.~ so. s-I-s - occureNCi classlFICATION erD IISEI ~woP R DIVISIOA 1 cROOr a DIVISION 2 APARTMBIIT HOTHL OFFICB HEIGHT 7.O1fBS2 ITEM BEQIIIRSD 1 2 3 1 2 3 1 2 3 1 Fire department communication system or radios See Section 6(a)1 R R R R R R R R R 2. Single-station smoke detectors See Section 6(a)2 R R R R R R NR NR NR 3 Manual fire warning system See Section 6(a)3 R R R R R R R R R 4 Occupant voice notification system See Section 6(a)4 NR R R NR R R NR NR NR 5 Vertical shaft enclosure walls of one-hour fine resistance See Section 6(a)5 R A R R R R R R R 6 Protection of openings in vertical shaft enclosures by 20-minute- rated assemblies See Section 6(a)b R R R R R R R R R 7 Manual shutoff of HVAC systems See Section 6(a~l R R R R R R R R R 8 Automatic elevator recall system See Section 6(a)8 R H R R R R R R R 9 Unlocked stairway doors every fifth floor See Section 6(a)9 R R R R R R NR R R 10 Stair shaft ventilation See Section 6(a)10 R R R R R R R R R 11 Elevator shaft ventilation See Section b(a)ll R R R R R R R R R 12 Posting of elevators as not intended for exiting purposes See Section 6(a)12 R R R R R R R R R 13 Minimum of two exits from each floor, of vlrich one may be afire escape See Section 6(a)13 R R R R R R R R R 14 Exit corridor wall construction See Section 6(a)14 R R R R R R R R R 15 Protected exit corridor openings with 20-minute-rated assemblies or 1-3/4-inch solid wood door See Section 6(a)15 R R R R R R NR NR NR 16 Exit corridor doors equipped with self-closing devices See Section 6(a)16 R R R R R R NR NR NR 17 Exit corridor dead ends limited to 35 feet maximum See Section 6(a)17 R R R R R R NR NR NR 18 Interior finish controlled in exit corridors, exit stairways and extensions thereof See Section 6(a)18. R R R R R R R R R 19 Exit stairway illumination. See Section 6(a)19 R R R R R ~R R R R 20 Exit corridor illumination See Section 6(a)20 R R R R R R NR NR NR 21 Exit stairway exit signs See Section 6(a)21 R R R R R R R R R 22 Exit way exit signs See Section 6(a)22 R R R R R R R R R 23 Emergency planning See Section 6(a)23 R R R R R R R R R 24 Posting of emergency instructions See Section 6(a)24. R R R R R R R R R 25 Fire drills See Section 6(x)25 NR NR NR NR NR NR NR NR NR lR indicates provisions are required NR indicates provisions are not required 2Neight tones are established based on a building having a floor as measured to the top of the floor surface used for human occupancy located within the ranges of heights above the lowest level of fire department vehicle access in accordance with the following Height Zone No 1 More than 75 feet but not in excess of 149 feet Neighs Zone No 2 More than 149 feet but not in excess of 399 feet Neight Zone No 3 More than 399 feet -46-~' -~_ .~ APPENDIX III-A TESTING FIRE-EXTINGUISHING SYSTEMS, STANDPIPES AND COMBINATION SYSTEMS TEST PROCEDURES FOR FIRE-EXTINGUISHING SYSTEMS 1. TESTING (a) Intervals. Tests of systems or devices herein regulated shall be conducted at least every two years or when inspection by the Chief indicates that there is reason to believe that the system or device would fail to operate properly in an emergency. Fire extinguishing systems which have been tested shall be tagged by the Chief. This tag shall not be removed. (b) Testing Personnel. The test established by this regula- tion shall be conducted by a person approved and qualified by the Chief to perform the full testing procedure for the particular system or device being tested or tests shall be conducted by the Fire Department personnel. (c) Witness. The Chief shall be notified at least one working day in advance of the performance of any full testing procedure for the particular system or device being tested when tests are conducted by persons other than Fire Department personnel. (d) Notification of Inoperable Systems. At the conclusion of each test, the Chief shall be notified of any fire- protection equipment that was determined to be inoperable when tests are conducted by persons other than Fire Department personnel. (e) Certification of Operable Systems. When the fire- protection equipment is operable, the owner or his agent shall certify its condition to the Chief in writing, when tests are conducted by other than Fire Department person- nel. (f) Plugs and Caps. All Fire Department inlets and outlets must be equipped with approved plugs or caps. (g) Fees. When Fire Department personnel conduct the tests described in Section 3 of this Appendix, a charge of $150 shall be made to the owner who is responsible for remit- ting same to the City of Fort Worth. -47- 2. TEST PROCEDURES FOR AUTOMATIC SPRIL~KLER SYSTEMS (a) Notification. The concerned agency shall be notified be- fore supervised systems are tested. (b ) Backflow. F3ackflow inlet connections from the check valve to the inlet by disassembling the check valve or blocking the check valve open so the water will backflow out of the fire department connections. (c) Control Valves. All control valves shall be closed and re- opened to assure their ability to operate. (d) Alarm test. For wet systems only, open the inspector's test valve to test the alarm bell response. When fully opened, the response shall occur within five minutes. When canducting such a test on a dry pipe, preaction or deluge system, use the alarm test line. (e) Gauge test. An approved test gauge shall be connected at the test gauge opening to test the reliability of the existing gauges. (f) Flow test. Observe pressure with main drain valve closed. Open main drain valve wide open and observe pressure. Close main drain valve and observe how quickly pressure is restored to determine if there are closed valves or obstructions in water supply lines. (g) Trip test. Dry-pipe, Preaction and Deluge Systems shall be trip tested annually in accordance with NFPA 13A, "Inspection Testing and Maintenance of Sprinkler Systems," 1981 . 3. TEST PROCEDURE FOR STANDPIPE SYSTEMS. Tests performed on Class I and III systems shall be conducted according to the Standard Operating Procedures of the Fire Department. Appendix III-C FIRE ALARM SYSTEMS 1. SCOPE This appendix governs the requirements for the installation, use and maintenance of fire alarm systems in all occupancies as specified herein. 2. PURPOSE The purpose of this appendix is to provide a reasonable degree of safety through early warning of a fire emergency and is -48- predicated on the potential hazards of life and property evi- dent in each type of occupancy. 3. ORDER OF PRECEDENCE Where a more restrictive provision of this appendix varies from a general provision, the more restrictive provision shall govern. , 4. DEFINITIONS (a) ALARM-ACTUATING DEVICE is any manually or automatically operated equipment which, when activated, initiates an alarm through an alarm-indicating device. (b) ALARM-INDICATING DEVICE is any equipment that produces an approved alarm signal. (c) ALARM SIGNAL is an audible or visual signal, or both, indicating the existence of an emergency fire condition. Audible devices may be bells, horns, chimes, speakers or similar devices. Voice alarms and their messages shall be approved by the Chief. Visual devices may be continuous or pulsating lights, flags or other visual indicators, as approved by the Chief. (d) ALARM SYSTEM is a combination of approved compatible devices with the necessary electrical interconnection and energy to produce an alarm signal in the event of fire or system activation. (e) ANNUNCIATOR is any equipment which indicates the zone or area of a building from which an alarm has been initiated, the location of an alarm-actuating device or the opera- tional condition of alarm circuits of the system. (f) APPROVED means approval by the Fire Chief as a result of investigation or tests conducted by him or by reason of accepted principles or tests by national authorities, technical or scientific organizations. (g ) BREEZEWAY is an accessway which is provided in apartments which contain stairs and landings that constitute a pri- marily vertical access to apartments. (h) CODED SIGNAL is an alarm signal or voice alarm which con- sists of not less than three complete repetitions of the transmission. (i) COMMON CORRIDOR is any interior corridor serving more than one tenant space. -49- (j) CONTROL UNIT is a unit comprising the controls, relays, switches and associated circuits necessary to (1) dis- tribute power to a fire alarm system, (2) receive signals from alarm-actuating devices and transmit them to alarm- indicating devices and accessory equipment, and (3) elec- trically supervise the system circuitry. The control unit may be contained in one or more cabinets in adjacent or remote locations as approved by the Chief. (k ) ELECTRICALLY SUPERVISED FIRE ALAR~Y SYSTEI~ii is a system designed to transmit a trouble signal to an approved location for any condition that prevents the required operation of a fire alarm system or failure of its main power source. (1) OCCUPANCY CLASSIFICATION See Sec. 9.117. (m) PULL STATION is a manual alarm actuating device. (n) TROUBLE SIGNAL is a distinct audible and visual signal which indicates an abnormal condition of the system being monitored. (o) ZONE is a building or a defined area of a building as approved by the Fire Chief for purposes of identifying locations. 5. DESIGN REQUIREMENTS (a) General. Fire Alarm Systems required by this appendix shall only be installed by contractors possessing an installation certificate for installation of fire protec- tion equipment according to Appendix VII-B of this Code. All information required by this section will be prepared by qualified engineers, specialists, laboratory or fire- safety specialty organizations acceptable to the Chief and to the owner. Correspondence required by this appendix shall be directed to Fort Worth Fire Prevention Bureau, Fire Alarm Section, 1000 Throckmorton Street, Fort Worth, TX 76102. (b) Submittals. The Chief shall be consulted in every case to determine compliance with fire alarm requirements. Prior to the installation of any fire alarm system required by this Appendix, the installing fire alarm contractors shall submit to the Chief two (2 ) sets of drawings and specifi- cations required by this subsection for review. The Chief shall designate those corrections necessary for acceptance of the proposed installation design and return one copy. -50- The following information shall be included with all sub- mittals: (1) General Information: a. Company name, state fire alarm contractor's number, and City of Fort Worth permit number. b. Alarm superintendent name and state license number. c. Signature of alarm superintendent, certifying that plans are in compliance with this ordi- nance. d. Property name and address. (2) Site and floor plans diagraming the layout of build- ings, exiting systems, and alarm equipment loca- tions. Drawings shall be scaled or dimensioned. (3) Equipment data sheets on all system components and devices; (4) Supervision: a. Monitoring provisions b. Trouble signal initiating circumstances; (5) Power Supply and Circuitry: a. Type of primary power. b. Type of stand-by/emergency power c. Schematic riser diagram, including alarm receiv- ing circuits, alarm sending circuits, control circuits, etc. d. Design provisions for fire alarm zones. (6) Operational Sequences: Describe the operational sequence of all intercon- nected systems from alarm initiation until reset. (7) Additional Provisions for High-Rise: Details on all provisions required herein for high- rise fire alarms. Any deviation from an approved plan must be reviewed and approved by the Chief. (c) Equipment. Fire Alarm equipment, devices and systems shall be approved for their intended purpose. -51- (d) Acceptance Tests. Upon completion of a system, a satisfac- tory test of the entire installation shall be made in the presence of the Chief. (e) Installation Certification. Upon completion of the instal- lation, the Contractor shall provide the Chief with one copy of a Texas State Fire Marshal's Fire Alarm Installa- tion Certificate, certifying that the system has been installed in accordance with the approved plans and speci- fications . (f) Operating Instructions. Written operating instructions are to be provided at the control unit. 6. MANUAL ALARM-ACTUATING DEVICES, EXTERIOR AND INTERIOR (a) Manual alarm-actuating devices shall be an approved double-action type for exterior use when installed in an exterior location. (b) A maximum travel distance between two devices shall not exceed 200 feet, in both interior and exterior locations. (c) Devices shall be securely mounted with the bottom of the device not less than 3-1/2 feet nor more than 5 feet above the floor level, in both interior and exterior locations. 7. REQUIRED INSTALLATIONS IN NEW BUILDINGS Fire Alarm Systems shall be installed in accordance with this section. A. Assembly Occupancies (1) Group A, Division 1, 2 and 2.1 occupancies having an occupant load of at least 300, but less than 500, other than night clubs and churches, when used pri- marily for worship. Shall be provided with an approved manually operated fire alarm system. Actuation of any alarm actuating device shall initiate a continuous or pulsating alarm signal throughout the building and identify on an annunciator the zone from which the alarm signal initiated. The system shall be electrically super- vised and installed in accordance with the provisions of the Uniform Fire Code Standard number 10-2. (a) Manual alarm actuating devices shall be approved double action type installed adjacent to each -52- r exit from each floor level, and shall be in accordance with Section 6 of this Appendix. (b) If sprinkler or other fire protection systems are provided within the building, such systems shall be connected to the fire alarm system. (c) Alarm indicating devices shall be installed such that they are sufficiently audible to be recog- nized throughout the building as a fire alarm signal. (d) Control units and annunciator panels shall be located in a common corridor adjacent to a main entrance. Outside that entrance a red strobe light which flashes when the alarm is sounding shall be placed above the door. The annunciator shall not be concealed. (e) Zoning shall be arranged such that not less than one zone per floor level is provided. (f) If the system is not centrally supervised by an approved monitoring agency, a sign which states "Local Alarm Only, Call Fort Worth Fire Department, 9-1-1" and contains the address of the property protected by the alarm shall be located above each pull station. The sign shall have a minimum dimension of 4 inches. (2) Group A, any nightclub or bar use with an occupant load of at least 20U, but less than 500: Shall be protected with an approved manually operated fire alarm system. Actuation of any alarm actuating device shall initiate a continuous or pulsating alarm on all alarm indicating devices in the building until manually reset. The system shall be electrically supervised and installed in accordance with the pro- visions of the Uniform Fire Code Standard number 10-2. (a) Manual alarm actuating devices shall be an approved double action type installed behind every service bar and adjacent to every exit from non-public areas, and in accordance with Section 6 of this Appendix. -53- (b) If sprinkler or other fire protection systems are provided within the building, such systems shall be connected to the fire alarm system. (c) Alarm indicating devices shall consist of horn/ strobe units located in the immediate vicinity above each pull station or such that they are audible and visible throughout. (d) Control units shall be located in the area behind the disc jockey's booth, when present, or when approved, in the office. If a trouble signal from the control unit would not be readily evident because of the unit location, a yellow flashing light shall be prominently dis- played outside the area where the control unit is located as a remote trouble signal. A sign shall be adjacent to the light stating, "Fire Alarm Trouble - Call Maintenance." The sign shall have a minimum dimension of 4 inches. (e) Zoning shall be arranged such that not less than one zone per floor level is provided. (f) If the system is not centrally supervised by an approved monitoring agency, a sign which states "Local Alarm Only, Call Fort Worth Fire Department, 9-1-1" and contains the address of the property protected by the alarm shall be located above each pull station. The sign shall have a minimum dimension of 4 inches. (g) The fire alarm shall be interfaced with the entertainment sound system such that when the alarm sounds, the entertainment/music system shall be rendered silent. (3) Group A, Division 1, 2 and 2.1 occupancies having an occupant load of 500 or more, other than churches, when used primarily for worship. Shall be protected with an approved manually operated fire alarm system. Actuation of any alarm actuating device shall initiate a continuous or pulsating alarm in an approved constantly attended location until manually reset and indicate the zone in which the alarm initiated. The system shall be electrically supervised and installed in accordance with the pro- visions of the Uniform Fire Code Standard number 10-2. -54- r EXCEPTION: Occupancies other than night clubs and bars shall install a fire alarm system as required by Sec. 7(A)(2) if the Chief determines it to be more appropriate for the building use. (a) Manual alarm actuating devices shall be in- stalled in a breakglass enclosure adjacent to every public exit and approved double-action device shall be installed adjacent to every exit in non-public areas. Manual devices shall be installed in accordance with Section 6 of this Appendix. (b) If sprinkler or other fire protection systems are provided within the building, such systems shall be connected to the fire alarm system. (c) Alarm indicating devices shall consist of a public address system which is sufficiently audible to be clearly understood throughout the building. The public address system shall be equipped with an approved emergency power supply or battery. The microphone and controls for this system shall be located at the approved con- stantly attended location, immediately adjacent to the control unit. (d) Control units shall be located at the approved constantly attended location in the immediate vicinity of an accessible telephone. The annun- ciator shall not be concealed. (e) Zoning shall be arranged such that not more than 10,000 square feet of floor area is served by a single zone, unless such large area is contained within a single room in which case the room shall serve as a zone. Additionally, not less than one zone per floor level will be permitted. (f) If the system is not centrally supervised by an approved monitoring agency, a sign shall be located above each pull station which states, "Local Alarm Only, Call Fort Worth Fire Department, 9-1-1" and contains the address of the property protected. The sign shall have a minimum dimension of 4 inches. (g) When required by the Chief, a fire department key box shall be provided, containing all fire alarm control keys. -55- y (h) The fire alarm shall be interfaced with the entertainment sound system .such that the enter- tainment/music system shall be capable of being manually rendered silent by controls which are located in the approved constantly attended location, immediately adjacent to the public address system. (i) Operation of this type system shall be as fol- lows: A manual pull-station is actuated and sounds a signal in the constantly attended location; the responsible party in the charge of this location shall attempt to verify the existence of an emergency either by radio contact with other personnel or by visual inspection from the con- stantly attended location; if no emergency is evident, other personnel shall inspect the area where the alarm was initiated and report back. At any time an emergency is detected, the responsible party shall 1) notify the Fire Department, 2) disable the sound system, 3) has been an emergency reported in the building. DO NOT PANIC. Please move calmly to the nearest exit." This message shall be repeated and then additional instructions given as necessary. (j) Instructions for operating the constantly attended station and action to be taken in a fire emergency shall be posted at the constantly attended station. (k) If an approved constantly attended location can- not be provided, a flashing strobe light shall be located above each pull station, all of which will flash in the event of a pull station actua- tion. This signal shall be used to notify the responsible party in charge to report to the control equipment and initiate the aforemen- tioned procedures. B. Business Occupancies: - See High-Rise Occupancies When Appl icab le C. Educational Occupancies: (1) Group E, Division 1 and 3 occupancies shall be pro- vided with an approved fire alarm system as specified in this section. Actuation of any alarm actuating -56- t'ki device shall initiate a continuous or pulsating alarm on all alarm indicating devices in the building until manually reset. The system shall be electrical- ly supervised and installed in accordance with the Uniform Fire Code Standard number 10-2. (a) Manual alarm actuation devices shall be in- stalled adjacent to every exit and in the main office. In Division 1 occupancies devices shall be installed in break-glass enclosures. Heat or smoke detectors shall be installed in mechani- cal, electrical, and storage rooms as deemed appropriate by the Chief. EXCEPTION: In Division 1 occupancies, cor- ridor smoke detectors may be installed in lieu of the manual devices at exit loca- tions. (b) In Division 3 occupancies, system smoke detec- tors shall be installed in all occupiable areas. (c) If sprinkler or other fire protection systems are provided within the building, such systems shall be connected to the fire alarm system. (d) Alarm indicating devices shall be installed such that they are sufficiently audible to be recog- nizable throughout the building as a fire alarm signal. (e) Control units and annunciator panels shall be located in the main office. The annunciator shall not be concealed. (f) Zoning shall be arranged such that not more than 10,000 square feet of floor area is served by a single zone unless such a larger area is con- tained in a single room in which case the room shall serve as a zone. Additionally, not less than one zone per floor level shall be per- mitted. (g) If the system is not centrally supervised by an approved monitoring agency, a sign shall be located above each pull station which states, "Local Alarm Only, Call Fort Worth Fire Department, 9-1-1,'° and contains the address of the property by the alarm. The sign shall have a minimum dimension of 4 inches. -57- D. High-Rise Occu ancies: (Also see Section 1807 of The Building Code Sec. 7(D)(1). Any new high-rise occupancy required to comply with Section 1807 of the Building Code shall be provided with an approved fire alarm system as specified in this section. Actuation of any automatic or manual device shall initiate an alarm signal of the alarm floor, the floor above, and the floor below and identify on an annunciator the zone from which the alarm signal origi- nated. (a) Manual alarm actuating devices shall be in- stalled adjacent to each exit from each floor level, and at nurses' stations, guards' sta- tions, telephone operators' switchboards and similar areas. Manual devices shall be in accor- dance with Section 6 of this appendix. (b) System smoke detectors shall be located as fol- lows: (i) In every mechanical, electrical, trans- former, telephone, elevator, or similar equipment room. (ii) In every elevator lobby. (iii) In the main return and exhaust air plenum of each air-conditioning system and in a serviceable area downstream of the last duct inlet. (iv) At each connection to a vertical duct or riser serving two or more stories from a return-air duct or plenum of an air- conditioning system. In Group R, Division 1 occupancies, an approved smoke detector may be used in each return air riser carrying not more than 5000 CFM and serving not more than 10 air inlet openings. (v) In Group I and Group R, Division 1 occu- pancies, system smoke detectors shall be located in all common corridors at a dis- tance of not more than 30 feet between detectors or 15 feet from any wall. Single station detectors shall be installed to -58- protect all sleeping areas and patient rooms as prescribed in Section 1210 of the Building Code for apartment or hotel guest rooms. EXCEPTION: When approved by the Chief, single station smoke detectors may be omitted in Group I Occupancies. (c) Water flow detectors for sprinklers and stand- pipe systems shall be provided for each riser floor tap and shall cause an alarm upon detec- tion of water flow for more than 15 seconds. All control valves in the sprinkler and standpipe systems except for Fire Department hose connec- tion valves shall be electrically supervised to initiate a trouble signal at the central control station upon tampering. The fire-pump system shall also be supervised for "power available" and "pump running" conditions by trouble signal on distinct circuits. (d) Alarm indicating devices shall consist of an alarm and communications system which is con- nected such that damage to any terminal unit or speaker will not render more than one zone of the system inoperative. The voice alarm and public address system may be combined. Communi- cation systems shall be as follows: (i) Voice Alarm - The operation of any alarm initiating device including pull stations, detectors, etc. shall cause operation of the alarm system which will give two repe- titions of a whooping tone followed by an approved voice message directing occupants' evacuation. This message shall be repeated until manually reset. The system shall be supervised to cause the activation of an audible trouble signal in the central con- trol station upon interruption or failure of the audiopath including amplifiers, speaker wiring, switches, and electrical contacts, and shall detect open circuits, shorts, and grounds which might impair the function of this system. The system shall be designed to be heard clearly by all occupants within the build- -59- 6 ~ ing or designated portion thereof and as is required for the public address system. (ii) Public Address System - A public address communications system designed to be clear- ly heard by all occupants of the building shall operate from the central control station. It shall be established for a selective or general basis to the following terminal areas: ° Elevators Rooms and tenant spaces over ° Elevator Lobbies 1000 square feet ° Corridors Dwelling units or guest rooms in R-1 ° Exit Stairways occupancies (iii) Fire Department Communications System - A telephone communications system for the exclusive use of fire department personnel shall be installed to operate between the central control stations and every eleva- tor, elevator lobby, and entry to every enclosed stairway in a selective manner. Fire phones may either be placed in a break-glass/key operated enclosure at each of the above locations or not less than five portable telephone handsets shall be located in the central control station. (e) (i) Control units and annunciators shall be located in the fire control room. (ii) Control units shall either be supervised by an approved monitoring agency or by person- nel at an approved constantly attended location. If a 24-hour desk is provided for monitor- ing, a single sign shall be placed at the telephone operators' switchboard or the constantly attended location stating, "WHEN FIRE ALARM SOUNDS, CALL FORT WORTH FIRE DEPARTMENT, 9-1-1" and containing the address of the building protected by the alarm may be permitted. The sign shall have a minimum dimension of 4 inches. (f) Zones shall be arranged such that not less than one zone per floor level is provided and which -60- ~. ,: will give a distinct signal for water flow de- tection. (g) Control circuits to be operated upon alarm activation shall include but not be limited to the following: (i) Automatic elevator recall (ii) Air handling systems shall be shut-off or placed in 100 percent exhaust mode on the fire floor, the floor above and the floor below. (iii) Stairwell pressurization (iv) Remote door unlocking (v) Smoke or fire doors which are automatic closing (h) When required by the chief, a Fire Department key box shall be provided, containing all fire alarm control keys. E. Institutional Occupancies (1) Group I occupancies shall be provided with an approved fire alarm system as specified in this sec- tion. The system shall be electrically supervised and installed in accordance with the Uniform Fire Code Standard number 10-2, or NFPA Standard number 72B-1979, 72C-1982, or 72D-1979. EXCEPTION: High-rise buildings shall comply with the high-rise provisions of this Appendix. (a) In Division 1 and 2 occupancies, actuation of any automatic or manual device shall initiate a zone-coded alarm throughout the building and identify on an annunciator the zone from which the alarm signal originated. (b) In Division 3 occupancies, actuation of any automatic or manual device shall initiate a zone-coded alarm signal to selected areas of the building and identify on an annunciator the zone from which the alarm signal originated. (c) Manual alarm actuating devices shall be in- stalled adjacent to each exit from each floor level, and at nurses stations, guard stations and telephone operators' switchboards, and shall be in accordance with Section 6. -61- 4 ,~ (d) System smoke detectors shall be installed in all common corridors. Single station smoke detectors shall be installed in all sleeping rooms in the manner prescribed by Section 1210 of the Building Code for hotel guest rooms. (e) Audible alarm indicating devices shall be pro- vided in all non-patient areas. A visible alarm may be used in lieu of audible devices in patient-occupied areas. (f) (i) Control units and annunciators shall be located at a constantly attended location or in a common corridor adjacent to a main entrance. The annunciator shall not be con- cealed. (ii) Control units shall either be supervised by an approved monitoring agency or by person- nel at an approved constantly attended location. If a 24-hour desk is provided for monitor- ing, a signal sign shall be placed at the telephone operators' switchboard or the constantly attended location stating, "WHEN FIRE ALARM SOUNDS, CALL FORT WORTH FIRE DEPARTMENT, 9-1-1" and containing the address of the building protected by the alarm may be permitted. The sign shall have a minimum dimension of 4 inches. (g) Zones shall be arranged such that not more than 10, 000 square feet is in a single zone and not less than one zone per floor is provided. A dis- tinct signal for water flow detection shall also be provided. (h) When required by the chief, a Fire Department key box shall be provided, containing all fire alarm control keys. F. Residential Occupancies (1) Group R, Division 1 occupancies and dormitories three or more stories in height or containing more than 15 dwelling units in an apartment house or dormitory or containing 20 or more guest rooms in hotels shall be provided with an approved fire alarm system as de- scribed in this section. Actuation of any automatic -62 - or manual device shall initiate a continuous or pul- sating alarm on all alarm-indicating devices in the building until manually reset and identifies, in the manner prescribed by this section, the zone from which the alarm signal originated. EXCEPTION 1): A Fire Alarm system need not be installed in apartment houses not over two stories in height with one-hour fire resistive construction throughout, including one-hour occupancy separations between each dwelling unit and all other spaces within the building and each individual dwelling unit has an exit directly to a public way, exit court or yard, exterior stairway or exterior exit balcony. EXCEPTION 2): A fire alarm system need not b e installed in one and two story apartment houses containing less than fifteen (15) dwelling units between area separation walls . EXCEPTION 3: A separate fire alarm system need not be installed in buildings which are protected throughout by an approved fire sprinkler system conforming to the Building Code and U.B.C. Standard No. 38-5 and having an approved local alarm. EXCEPTION 4): High-rise buildings shall comply with the high-rise provisions of this Appendix. (a). Detection devices. (i) Group R, Division 1 occupancies (with interior corridors.) The alarm system for Group R, Division 1 occupancies having common interior exit corridors or lobbies serving as a required exit shall consist of not less than an approved and listed system-type smoke detector installed within such corridors or lobbies in accordance with the UFC Standard 10-2 and listed spacing limitations. When activated, such detectors shall initiate an alarm which is audible throughout the building. When a front desk is provided and manned 24 hours -63- per day, smoke detectors may be omitted from one immediate area of the desk when approved by the Chief. (ii) Common areas within Group R, Division 1 occupancies. Approved and listed system-type automatic rate-of-rise heat detectors shall be installed in accordance with listed spacing limitations within common areas such as recreational rooms, laundry rooms, offices, kitchens, restaurants, storage rooms, closets, exitways, and furnace rooms of buildings containing Group R, Division 1 occupancies. The detectors shall be installed on the ceiling or wall of such rooms in accordance with the manufacturer's installation instructions and, when activated, shall initiate an alarm which is audible throughout the building. (iii) Group R, Division 1 occupancies. Approved and listed system-type automatic rate-of- rise heat detectors shall be installed in the main living area of each unit. The detectors shall be installed on the ceiling of such rooms in accordance with the manu- facturer's installation instructions and, when activated, shall initiate an alarm which is audible throughout the building. (b ). Alarm indicating devices shall be located in each sleeping room and in other locations to be suf- ficiently audible throughout the building. (c). Control units and annunciators, when required, shall be located at a main building entrance or at a 24 hour desk, if provided. When such units are in- stalled outside, a weather-tight enclosure shall be required. If the annunciator is not located at a 24 hour desk, a red strobe light shall be placed above the entrance providing the most immediate access to the annunciator, except for outside annunciators, which shall have the strobe light directly above the annunciator. Annunciators shall not be concealed. If no annunciator is required, the control unit may be concealed; provided that if a trouble signal is not readily evident because of the unit location, a yellow flashing light shall be prominently displayed -64- outside the area where the control unit is located as a remote trouble signal. A sign shall be adjacent to the light stating, "FIRE ALARM TROUBLE - CALL MAINTE- NANCE". The sign shall have a minimum dimension of 4 inches. (d). Zones shall be as follows: (i) Apartments - with breezeway style (see Figure 7-1): A single zone (non- annunciating) control unit shall be used for each building. A red strobe light shall be located on the face of the building, at the eaves, adjacent to each vertical set of pull stations . The light (s ) may be powered by an auxiliary set of contacts on pull stations and detectors. Only the light adjacent to that area where a firefighter must enter the building to find the initi- ating device will flash during the alarm. (ii) Hotels, Motels, or Apartments non- breezeway) - A multiple zone control unit with annunciator is required and shall be zoned not less than one zone per floor per building. (e). If the system is not centrally supervised by an approved monitoring agency or 24 hour desk, a sign shall be located above each pull station which states: "LOCAL ALARM ONLY, CALL FORT WORTH FIRE DEPARTMENT, 9-1-1", and shall contain the address of the property protected. The sign shall have a minimum dimension of 4 inches. If a 24 hour desk is provided for monitoring, a single sign may be placed at the telephone operators' switchboard or the constantly attended location in lieu of the above requirement stating, "WHEN FIRE ALARM SOUNDS, CALL FORT WORTH FIRE DEPARTMENT, 9-1-1", and containing the address of the building protected by the alarm may be permitted in lieu of the above requirements. The sign shall have a minimum dimension of 4 inches. (f). A Fire Department key box outside wall adjacent to the approved location. This box alarm control keys. shall be located on an leasing office in an shall contain all fire -6 5- (2) Grou R, Division 3 Occu ancies which are used by more than six 6 persons, three (3) of which are under 18 years of age, not related by blood or marriage, shall be provided with system smoke detec- tors protecting each sleeping area which connect to an approved automatic fire alarm system capable of alerting all occupants. (3) Group R Occupancies shall be provided with single station, hard-wired smoke detectors to protect each sleeping area as required by Section 1210 of the Building Code. (4) See Section 11 for requirements for fire alarms in existing buildings. 8. POWER SUPPLY AND WIRING (a) All required fire alarm systems shall have an approved secondary power supply which shall be capable of operating the entire system for not less than 24 hours under non- alarm conditions, and 15 minutes under alarm conditions. Upon interruption of the normal power, the system shall be automatically transferred to the secondary source of power, and full power shall be obtained within 60 seconds of transfer. Except as otherwise specified, the secondary source of power may be one of the following: (i) Generators; (ii) Storage batteries; (iii) Separate electrical (iv) Separate substations service from the normal sevice; of the same electrical service. When generators are provided they shall be served by a fuel supply sufficient to operate the system as required by this section. (b) Wiring shall be listed for Fire Alarm System use by an approved testing agency. All wiring installed on exterior locations shall be in rigid conduit. Exposed wiring in- stalled inside within the 7-1 /2 feet of floor level shall be in rigid conduit or wire-mold. 9. PRECEDENCE When a fire alarm system is approved for use in combination with a public address or other means of communication, the fire -66- alarm system shall take precedence over such other communica- tion system upon activation of the fire alarm system. 10. SPECIAL PROVISIONS (a) The requirements for fire alarm systems under Section 7 may be reduced upon inspection of plans, in other than high-rise, Group I, and Group E Occupancies if the build- ing is protected by an approved sprinkler system with shut-off valves and water flow devices supervised in an approved manner. (b) All fire alarm systems shall be installed in such a manner that the failure of any single alarm-actuating or alarm- indicating device will not interfer with the normal opera- tion of any other such device. 11. REQUIRED INSTALLATIONS IN EXISTING BUILDING (a) Effective on the adoption date of this Code, the provi- sions of this Appendix applicable to new occupancies shall also apply to the following existing occupancies: (1) All Group R occupancies other than those covered by Section 7F(2), except that required single station smoke detectors may be battery operated as set forth in Section 1210 of the Building Code even though such detectors were not required at the time of the con- struction; (2) Night clubs having an occupant load of over 200; (3) Restaurants with dancing having an occupant load of over 300. (b) Effective as specified in the Building Code Appendix Chapter 1, Division II, high-rise occupancies shall be provided with a fire alarm system. High-rise fire alarm systems installed in existing buildings shall be automatic or manually operated system. Actuation of any automatic or manual device shall initiate an alarm signal on the alarming floor, the floor above, and the floor below and shall identify on an annunciator the zone from which the alarm signal originated. (1) Manual alarm actuating devices shall be installed adjacent to each exit from each floor level, and at guards' stations and building operators' switchboards and shall be in accordance with Section 6 of this Appendix. -67- ' ,, ,. (2) System smoke detectors shall be located as follows: (i) In every elevator lobby; (ii) In Group B, Division 2 Occupancies, system smoke detectors shall be located in all common corri- dors when the corridor does not have the re- quired fire resistive rating called for by the Building Code, Appendix Chapter I, Division II. Detectors shall be located at a distance of not more than 30 feet between detectors or 15 feet from any wall. (iii) In Group R, Division 1 Occupancies, system smoke detectors shall be located in all common corri- dors at a distance of not more than 30 feet between detectors or 15 feet from any wall. Single station detectors shall be installed to protect all sleeping areas as prescribed in Section 1210 of the Building Code. Battery powered detectors may be installed when hard- wired detectors were not required at the time of construction. (3) Sprinkler system water-flow detectors, when provided shall cause an alarm upon detection of water flow for more than 15 seconds. (4) Alarm indicating devices shall be installed such that they are sufficiently audible to be recognizable in an alarming zone as a fire alarm signal. In buildings classified as Group B, Division 2 or buildings classified as Group R, Division 1, in Height Zone 1 of Building Code, Appendix Chapter 1, Division II, bells or horns are permitted. In Group R, Division 1 Occupancies, higher than Height Zone 1, an occupant voice notification system shall be provided in accor- dance with Section 7 D(1)(d)(i) of this Appendix• (5) (i) Control units and annunicators shall be located in the fire control room, and a duplicate annun- ciator shall be located either at a constantly attended location or in a common corridor adja- cent to a main entrance. The duplicate annuncia- tor shall not be concealed. (ii) Control units shall either be supervised by an approved monitoring agency or by personnel at an approved constantly attended location. -68- If a 24-hour desk is provided for monitoring, a single sign shall be placed at the telephone operators' switchboard or the constantly attended location stating, "WHEN FIRE ALARM SOUNDS, CALL FORT WORTH FIRE DEPARTMENT, 9-1-1," and containing the address of the building pro- tected by the alarm. The sign shall have a mini- mum dimension of 4 inches. (6) Zones shall be arranged such that not less than one zone per floor level is provided and which will give a distinct signal for water flow detection. (7) Control circuits to be operated upon alarm activation shall include but not be limited to the following: (i) Automatic elevator recall (ii) When corridor smoke detection is provided in accordance with Section 11 (b)2(ii) of this Appendix air handling systems shall be shut-off or placed in l0U per cent exhaust mode on the fire floor. (iii) Stairwell pressurization when provided. (iv) Remote door unlatching when provided• (v) Smoke or fire doors which are automatic closing when provided. (8) When required by the Chief, a fire department key box shall be provided, containing all fire alarm control keys. (c) All existing one and two family dwellings which are sold or altered, repaired, renovated or improved in any manner requiring a building permit shall be provided with smoke detectors as required in Section 1210 of the Building Code. The owner of any dwelling which is sold or repaired in violation of this subsection shall be guilty of a mis- deameanor. (d) Mobile homes which are sold, rented, remodeled or relo- cated within or into the City of Fort Worth shall have a smoke detector provided in accordance with the provisions of Sec. 1210 of the Building Code. (e) Rented or leased residential occupancies. (1) For purposes of this subsection, the term dwelling unit shall include the following: -69- (i) All one family, two family and multi-family dwellings, including mobile homes; (ii) All one family, two family and multi-family dwellings where one or more rooms are rented for use as permanent residence under a single lease. (2) All dwelling units which are currently rented, leased or sub-leased or are hereafter rented, leased, or subleased shall be provided with smoke detectors which meet the requirements of Section 1210 of the Building Code, except that such detectors may be battery operated in accordance with Section 11(a)1 of this Appendix. Those occupancies which are leased for the first time or to new lessee after the adoption date of this Code shall have smoke detectors in- stalled prior to occupancy by the leasee. The smoke detector purchase and installation shall be the sole responsibility of the landlord. (3) Duty to inspect and repair. (i) Upon commencement of a tenant's possession of a dwelling unit containing a smoke detector, the landlord shall have a duty to test the smoke detector to verify that it is in good working order. Upon installation of a smoke detector by a landlord after commencement of the tenant's possession of a dwelling unit, the landlord shall have a duty to test the smoke detector at the time to verify that it is in good working order. (ii) During the term of the rental agreement or any renewal or extension thereof, the landlord shall have a duty to inspect and repair a smoke detec- tor only if the tenant has given notice to the landlord of malfunction or has made a request to the landlord for inspection or repair. The notice to the landlord need not be in writing unless written notices required in the Rental Agreement. The landlord shall comply with the tenant's request for inspection and repair with- in a reasonable time, considering the avail- ability of material, labor and utilities. (iii) A landlord shall not have a duty to repair a smoke detector if the damage or malfunction is caused by the tenant or the tenant's family, guest or invitees during the term of the rental -70- agreement or any renewal or extension period of the rental agreement. Provided, however, a land- lord shall have a duty to repair or replace a smoke detector covered by this subsection if the tenant pays in advance for the reasonable cost of the repair or replacement, including labor, materials, taxes, and overhead. (iv) A landlord shall have satisfied the duty to in- spect or repair a damaged or malfunctioning smoke detector if, after a test of the smoke detector, the test indicates that the smoke de- tector is in good working order. (v) After commencement of possession by the tenant of a dwelling unit, the landlord shall have no duty to provide replacement batteries for a battery operated smoke detector which was in good working order according to a test of the smoke detector at the time of commencement of possession by the tenant. (4) A person commits an offense if as landlord of a dwel- ling unit that person: (i) Fails to install a smoke detector in compliance with this section; or (ii) fails to test or repair a smoke detector in com- pliance with this section. 12. MAINTENANCE OF SYSTEMS All fire alarm systems shall be maintained in an operative con- dition at all times and shall be replaced or repaired when defective. Such systems shall be extended, altered or augmented as necessary to maintain and continue protection whenever any building so equipped is altered, remodeled or added to. All additions, repairs, alterations and servicing shall be in accordance with this Appendix. An approved log shall be kept on the premises to indicate when this system was checked and/or serviced, and a tag issued by the Fire Department indicating test dates shall be placed in the control unit. This tag shall not be removed. 13. TAMPERING WITH FIRE ALARM SYSTEM Any person who willfully and maliciously tampers with, molests, injures, or breaks any fire protection equipment, fire protec- tion installation, fire alarm apparatus, wire, or sounds any -71- false alarm of fire, by means of any fire alarm system or signal or by any other means or methods, is guilty of a misde- meanor. APPENDIX III-D FIRE-FLOW REQUIREMENTS FOR BUILDINGS 1. SCOPE This appendix is the procedure for determining fire-flow requirements for all buildings or portions of buildings hereafter constructed. This appendix is not intended to apply to structures other than build- ings. The fire-flow requirement is the quantity of water in gallons per minute needed to control an anticipated fire in a building or group of build- ings. The Chief shall establish the minimum residual pressure and the flow duration to be used when deter- mining fire flow. 2. DEFINITIONS FIRE AREA is the total floor area in square feet for all floor levels within the exterior walls, or under the horizontal projection of the roof of a building. Area separation walls, as specified in the Building Code, may be considered as dividing a building into separate fire areas for the purposes of determining fire flow. 3. MODIFICATIONS Fire-flow requirements may be modified downward by the Chief for isolated buildings or group of buildings in rural areas where the development of full fire-flow requirements is impractical. Fire flow may be modified upward by the Chief where conditions indicate an unusual susceptibility to group fires or conflagrations. An upward modifica- tion shall not be more than twice that required for the building under consideration. 4. FIRE-FLOW REQUIREMENTS FOR BUILDINGS The minimum fire-flow requirements for one- and two-family dwellings shall be 75U gallons per minute for fire areas under 2,500 square feet and 1,000 gallons per minute for fire areas greater than or equal to 2,500 square feet. -72- EXCEPTION: Fire flow may be reduced 50 percent when the building is provided with an approved automatic sprinkler system. The fire flow for buildings other than one- and two-family dwellings shall be not less than that specified in Table No. 3°D-1 and as modified by Table 3-D-2 . EXCEPTION: The required fire flow may be re- duced up to 75 percent when the building is provided with an approved automatic sprinkler system, but in no case less than 1,500 gallons per minute. In Types I and II-F.R. construction, only the three largest successive floor areas shall be used. -73- ' .~ TABI~; NO. 3-D-1 FIRE-FLOW GUIDE FOR BUILDINGS O'THER THAN ONE- AND TWO-FAMILY L)WELLINGS FIRE OONSTRUCTION TYPE FLOW (Gallons Per I I I ONE-~3R. IV H. T. I I N Minute) II-F. R. III ONE HR. V-0NE-HR. III-N V-N TOTAL FIR E AREA IN SQL F~RE FEET 1,500 22,700 12,700 8,200 5,900 3,600 1,750 30,200 17,000 10,900 7,900 4,800 2,000 38,700 21,800 12,900 9,800 6,200 2,250 48,300 24,200 17,400 12,600 7,700 2,500 59,000 33,200 21,300 15,400 9,400 2,750 70,900 39,700 25,500 18,400 11,300 3,000 83,700 47,100 30,100 21,800 13,400 3,250 97,700 54,900 35,200 25,900 15,600 3,500 112,700 63,400 40,600 29,300 18,000 3,750 128,700 72,400 46,400 33,500 20,600 4,000 145,900 82,100 52,500 37,900 23,300 4,250 164,200 92,400 59,100 42,700 26,300 4,500 183,400 103,100 66,000 47,700 29,300 4,750 203,700 114,600 73,300 53,000 32,600 5,000 225,200 126,700 81,100 58,600 36,000 5,250 'L47,7U0 139,400 89,200 65,400 39,600 5,500 271,200 152,600 97,700 70,600 43,400 5,750 295,900 166,500 106,500 77,000 47,400 6,000 UNLIMITID UNLIMITID 115,800 $3,700 51,500 6,250 125,500 90,600 55,700 6,500 135,500 97,900 60,200 6,750 145,$00 106,800 64,800 7,000 156,700 113,200 69,600 7,250 167,900 121,300 74,600 7,500 179,400 129,600 79,800 7,750 191,400 138,300 85,100 8,000 UNLIMITID UNLIMITID UNLIMITID TABLE NO. 3-D-2 FIRE FLOW I~ATLTIPLICATION FACTOR (GPM * FACTOR) OCCUPANCY TYPE MULTIPLICATION FACTOR B-2, H-1, H-2, H-3, H-4, H-5, H-6, I-l, I-2, I-3 1.00 A-1, A-2, A-2.1, B-1, B-3, R-1 0.87 A-3, A-4, B-4 0.75 E-1, E-2, E-3, M 0.50 -74- DIVISION VII INSPECTION APPENDIX VII A SCHEDULE AND PROCEDURES OF FIRE INSPECTION CERTIFICATES AND FEES. 1. (A) Certificate of Inspection for Buildings Less Than Four Stories in Height. The occupant of every commercial establishment (defined as all buildings, facilities and structures except residential dwelling units) shall be required to have a valid certificate of inspection. A Certificate of Inspection shall be valid until a subse- quent inspection takes place or until revoked; provided, however, that possession of a Certificate of Inspection shall not exempt a commercial establishment from reinspec- tion or citation for violations occurring during the period of time between inspections. A Certificate of Inspection shall not be transferable, and any change in use, occupancy, or operation shall require a new Certifi- cate of Inspection. (B) Certificate of Inspection for Buildings of Four or More Stories in Height. The owner, building manager, or prop- erty manager representative of any building four (4) or more stories high shall be required to have a valid cer- tificate of inspection for the entire building, structure, or facility. A Certificate of Inspection shall be for the entire building, structure, or facility and shall be valid until a subsequent inspection takes place or until revoked; provided, however, that possession of a Certifi- cate of Inspection shall not exempt a building from rein- spection or citation for violations occurring during the period of time between inspections. A Certificate of Inspection shall not be transferable, and any change in use or occupancy of the major portion of the building or its operation shall require a new Certificate of Inspec- tion. Such inspection shall be performed by duly authorized members of the Fort Worth Fire Department. If no hazardous conditions or violations of the fire code are detected at the time of the inspection, the occupant of the inspected business or the owner or building manager of a building as provided above shall be issued a Certificate of Inspec- tion. If at the time of inspection, a building is found to be not in compliance with this Code, a Certificate of Inspec- tion will not be issued. After notification of the viola- -75- tions which were detected, the owner, manager, or occupant shall b e required to remedy the conditions of violation, and a citation may be issued. The occupant, owner or manager shall be notified of a time at which reinspecton will occur. The date of reinspection shall not be more than 30 days from the time of the original inspection. 2. Conditions of Certificates of Inspection. The issuance or granting of a Certificate of Inspection shall not be deemed or construed to be a permit for, or an approval of any violation of any of the provisions of this Code. No certificate presum- ing to give authority to violate or cancel the provisions of this Code shall be valid, except insofar as the work or use which it authorizes is lawful. 3. Inspection Fee. A fire inspection fee will be charged not more than once per year for a fire inspection of any occupancy or building except private residences. Any permits required by the Fire Code may require a separate inspection, and the fee for such permits shall be in addition to the Certificate of Inspection fee, provided, however, that this Section shall not prohibit inspections from occurring more often than once per year. 4. Retention of Certificate of Inspection. Certificates of Inspec- tion shall at all times be kept on the premises designated therein and shall at all times be posted in a conspicuous loca- tion and be subject to inspection by an officer of the fire or police department or other authorized persons. 5. Revocation of Certificates of Inspection. Any Certificate of Inspection issued under this code may be suspended or revoked when it is determined after a hearing by the Chief that: (a) It is used by a person other than the person to whom the certificate was issued; or (b) It is used for a location other than that for which it was issued; or (c) Any of the conditions or limitations set forth in the Certificate have been violated; or (d) The possessor of the Certificate fails, refuses, or neglects to comply with any order or notice served upon him under the provisions of this code within the time period provided therein; or -76- (e) There has been any false statement or misrepresentation as to a material fact in the plans, specifications or docu- mentation on which the certificate was based. 6. Whenever a change in use or occupancy of a building occurs, the existing Certificate of Inspection shall be automatically revoked and a new Certificate of Inspection shall be required. (a) The following two elements shall be used in determining the inspection fee to be charged: I. Number of Square Feet in Building II.. Number of Stories in Building (b) The inspection fee shall be developed according to the following formula: (Total floor area fee) + (multiple story charge) I. Charge per square foot of floor space of the busi- ness, structure or facility inspected: Number of Square Feet Base Fee Less than 5,000 $20.00 5,001 10,000 $25.00 10,001 25,000 $30.00 25,001 50,000 $45.00 50,001 75,000 $70.00 75,001 100,000 $95.00 Greater than 100,000 square feet shall be charged the base rate of $95 plus $15.00 for each additional 50,000 square feet of floor area, or portion thereof. II. Multiple Story Charge: an additional charge of $5.00 per floor shall be charged for inspection of multiple story buildings four stories or more in height. III. Shopping Malls shall be assessed an inspection fee based on total floor area of the public areas within the structure plus the per story charge. The individ- ual tenant spaces will be assessed on the basis of the square footage of the individual space. 7. Special Fees. A special fee shall be charged for those items listed below, according to the following schedule. (a) Permits required by the Fire Code (see Chapter 4) -77- (b) Official fire reports $ 5.00 (c) Knox lock rentals $ 10.00 (d) Knox lock deposits $ 40.00 8. Failure to Pay Inspection or Special Fees. Any person, busi- ness, owner or manager that fails to pay the required fees resulting from a fire inspection, report, registration, rental or deposit within a forty-five (45) day period from the state- ment date shall be guilty of a misdemeanor and may be issued a citation as prescribed by the Fire Code. Each day that the charges are delinquent shall constitute a separate offense. 9. Optional Billing. Any owner or manager of a building of less than four stories and that is occupied by multiple tenants may elect to have all Certificates of Inspection required within his building billed directly to the owner or manager of the building. The owner or manager must make a written request to the Fire Marshal that they are to be billed directly and that the owner or manager will take responsibility for the charges. Charges shall be the same as if each tenant was billed sepa- rately. APPENDIX VII - B INSTALLATION OF FIRE PROTECTION SYSTEMS 1. Definitions FIRE PROTECTION SYSTEM for the purpose of this Appendix shall include the following: Fire Alarm System: A system of electrical and/or mechanical devices connected to a central control panel which are designed for the purpose of signaling the presence of a fire when auto- matically or manually actuated. Each control panel and all com- ponents on the system side of the control panel shall be considered to be a separate system. Fire Sprinkler System: A system of underground and/or above- ground piping which conveys water with or without other agents to dispersal openings or devices to extinguish, control or contain fire and to provide protection from exposure to fire or the products of combustion. Each required alarm valve or flow detecting device and all components on the system side of the alarm valve or flow detecting device shall be considered to be a separate system. -7t3- Fire Standpipe System: A wet or dry system of piping, valves, outlets and related equipment designed to provide water at specified pressures and installed exclusively for the fighting of fires. When serving sprinklers, a standpipe shall be con- sidered as a sprinkler system component. Special Agent System: A system of electrical and/or mechanical devices which are designed to extinguish a fire by discharging a chemical agent other than water. Such systems shall include but not be limited to halon and carbon dioxide systems. Each control panel and all components on the system side of the con- trol panel shall be considered to be a separate system. Systems required by the Mechanical Code shall be in accordance with that Code and need not comply with this Appendix. Atrium Smoke Control System: A system of electrical or mechani- cal devices which are designed for the purpose of removing smoke from atriums as required by Section 1715 of the Building Code. FIRE PROTECTION SYSTEM CONTRACTOR shall be any contractor who installs fire protection system(s) and shall be licensed in accordance with the following provisions and shall have filed copies of such licenses with the Bureau of Fire Prevention: Fire Alarm System: Texas state licenses for sale, service and installation of fire alarm systems; and fire alarm superinten- dent. Fire Sprinkler System: Texas state licenses for sales, service and installation of fire sprinkler systems; and responsible managing employee. Fire Standpipe System: Same as sprinkler if sprinklers are served from the same piping; otherwise, license for plumbing in City of Fort Worth or licensed fire sprinkler contractor. Special Agent System: Texas state licenses for sales, service and installation of fire extinguishing systems, fire extin- guisher technician; sales, service and installation of fire alarm systems; and fire alarm superintendent. Other Systems: No requirements. Installation Certificate is an authorization by the Fire Prevention Bureau for a Fire Protection Equipment Contractor to install or tenant finish a Fire Protection System. -79- Installations shall include the initial placement of or reloca- tion of any components of a Fire Protection System into areas which are not protected. 2. Maintain shall include servicing or replacement with similar devices of existing components of a Fire Protection System in the same location. Tenant Finish shall include the relocation of existing devices or addition of new devices which are necessary to maintain an existing level of protection in an area. Addition of devices into previously unprotected areas shall be considered as installation. Installation Certificate Required. It shall be unlawful for any person, firm or corporation to perform installation or tenant finish of any Fire Protection System without first having obtained an installation certifi- cate from the Bureau of Fire Prevention. Installation certifi- cates shall only be issued to Fire Protection System Contrac- tors. Installation certificates shall not be required for maintenance. EXCEPTIONS: 1) Installation certificates shall not be re- quired for installation of tenant finish of fire protection when: a) not more than ten (1G) sprinkler heads are installed or relocated, or; b) not more than five (5) alarm initiat- ing devices are installed or relo- cated, or c) special agent systems are self- contained and do not require auxiliary controls or piping to operate. 2) Installation certificates for systems other than fire sprinkler systems may be issued to persons other than fire protection system contractors when approved by the Chief . The installers shal l be required to possess valid licenses from the State Fire Marshal to demonstrate their competence to install a fire protection system. _80_ 3. Conditions of Installation Certificates. A. An installation certificate shall constitute permission to install or tenant finish a Fire Protection System in accordance with approved plans and specifications except that such permission shall not be construed as authority to violate, cancel or set aside any of the provisions of this Code. B. An installation certificate issued under this Appendix shall continue until revoked or until the installation or tenant finish of the fire protection system is completed and approved. An installation certificate issued for initial installation shall not be transferable to tenant finish work in the same area. Additionally, installation certificates shall not be transferable to any other loca- tion or fire protection system contractor. C. The Chief is authorized to withhold issuance of an instal- lation certificate to an authorized installer or contrac- tor if: 1) the installer or contractor has failed to make reasonable progress on work for which an installation certificate previously has been issued; 2) a fire protection system contractor has failed, after notice, to correct any defective condition resulting from improper installation; or 3) a fire protection system contractor has failed to pay all prior fees assessed in accordance with this Appendix. 4. 5. Application for Installation Certificate. Application for a fire protection system installation certifi- cate shall be made to the Bureau of Fire Prevention. The appli- cant shall be required to present the name and street address of the job site and the information necessary for fee calcula- tion. At the time of application, plans need not be submitted to acquire an installation certificate. Inspection and Testing Fees. A. Upon application for an installation certificate, the applicant shall be required to pay all inspection fees associated with the installation or tenant finish work as specified in this section or agree to have such fees posted in the prearranged billing account with the Bureau -81- of Fire Prevention to be billed monthly. Account balances shall be required to be paid within 21 days of the billing date. Fire alarm systems with more than five (5) automatic detection devices, fire sprinkler systems and special agent systems: $40.00 for each system on the first story, plus $20.00 for each story in excess of one $25.00 for tenant finish work Fire alarm systems with five (5) or less automatic detec- tion devices: 50% of figure above. Fire Standpipe Systems: $150.00 for installation or bi- annual testing. Fire Pump: $150.OU for installation or testing. Atrium smoke control systems: $250.OU B. Fees specified in subparagraph A, above, will be doubled if a contractor starts installation or tenant finish work without a valid installation certificate. C. An additional test fee of $50.00 shall be charged to the fire protection system contractor for failure to correct system deficiencies for which the fire protection system contractor is responsible which have been cited on a Construction Plans Evaluation Report (FD 890) or a Fire Protection System Test Report (FD 880) by the subsequent resubmittal or inspection date listed thereon. 6. Plan Review, Inspection and Approval. A. Plans. All fire protection systems requiring an installation certificate shall be installed in accordance with approved plans. Any variances from approved plans shall require approval by the Chief. Not less than two (2) sets of plans and specifications shall be submitted; however, not more than one set of approved drawings shall be returned. Sub- mittals for fire alarm systems shall be in accordance with Appendix III-C, Section 5. Submittals for sprinkler systems shall be in accordance with Uniform Building Code Standard 38-1, Section 1-9.2, as amended. -82- EXCEPTION: Plans shall not be required for fire sprinkler system installation and tenant finish work of less than 20 heads. B. C. Inspections. It shall be the responsibility of the contractor instal- ling fire protection systems to notify the Bureau of Fire Prevention not less than 48 hours prior to required inspections. All systems shall be checked by the contrac- tor prior to requesting an inspection. Systems are re- quired to be inspected as follows: Fire Alarm Systems Final Inspection upon completion of installation or tenant finish work: All end-of-line supervision resistors must be exposed prior to inspection. Fire Sprinkler System Inspection of Underground Piping: All joints are required to b e exposed. Rough-in Inspection: Prior to concealment of piping, all above-ground pipe shall be inspected. Piping inspections shall not be requested for less than the entire work area of any one floor. Final Ins ection upon completion of installation or tenant finish work when work is completed and a certificate of occupancy is to be requested for any area): All system components including tamper and flow monitoring are re- quired to be completed. Special Agent Systems Final Inspection upon completion of installation: All end-of-line supervision resistors to be exposed prior to inspection, full operational testing of all components and a smoke test will be performed. Approval. Upon correction of all deficiencies noted in the construc- tion plans evaluations and system test reports and submit- tal of required State Fire Marshal's Certification certificates to the Bureau of Fire Prevention, a system test report shall be issued indicating approval of the system. In buildings where fire protection systems are required, such approval shall be required prior to the issuance of certificate of occupancy. -83- 7. Retention of Installation Certificates. Installation certificates shall at all times be conspicuously posted on premises designated therein and at all times be sub- ject to inspection by an officer of the Fire Department. 8. Installation Certificates for the Same Location. Whenever more than one type fire protection system is to be installed at the same location, each type of system shall require a separate installation certificate. Where a develop- ment involves multiple buildings, each free-standing structure shall require a separate installation certificate. 9. Revocation of Installation Certificates. Any installation certificate for work on a fire protection sys- tem issued under this Code may be suspended or revoked when it is determined by the Chief that: (a) It is used by a company other than the company to whom it was issued. (b) It is used for a location other than that for which is was issued. (c) The installation certificate holder fails, refuses or neglects to comply with any order or notice duly served upon him under the provisions of this Code within the time provided therein.. (d) There has been any false statement or misrepresentation as to a material fact in the application or plans on which the permit or application was based. (e) Any of the provisions set forth in this Appendix have been violated. III. THE 1985 EDITION OF THE UNIFORM FIRE CODE STANDARDS (EXHIBIT "B") IS HERESY AMENDED BY REVISING THE FOLLOWING SECTIONS AS FOLLOWS: Uniform Fire Code Standard 10-1 Selection, Installation, Inspection, Maintenance and Testing of Portable Fire Extinguishers See Sections 10.301(a); 10.303(b); 24.113(b), (c), (d); 30.104(b); 30.105(b); 45.209(b); 45.307(a); 79.205(a); and 79.807(c), Uniform Fire Code. -84- This standard, with certain exceptions, is based upon the National Fire Protection Association Standard for Portable Fire Extin- guishers, NFPA 10-1984. Part I of this standard contains the exceptions to NFPA 10-1984. PART I AMENDMENTS Section 10.101. The National Fire Protection Association Standard for Portable Fire Extinguishers, NFPA 10-1984, applies to the selection, installation, inspection, maintenance, and testing of portable fire extinguishers except as follows: (1) through (4) unchanged. (5) Sec. 3-2.2 is changed by amending the second sentence to read as follows: 3-2.2. One-half of the extinguishers required by Table No. 3-2.1 may be omitted when the building is equipped with a Class I or III standpipe system that complies with the Uniform Fire Code. (6) Unchanged. (7) Sec. 5-4.2.1 is changed to read as follows: 5-4.2.1. The equipment for testing cylinders and cartridges shall be an approved water jacket type. (8) Sec. 5-5.1.1 is changed by amending the second sentence to read as follows: 5-5.1.1. Procedure for internal examination and hydraulic testing shall be in accordance with approved standards. (9) Sec. 5-5.1.2 is deleted. (10) Chapter 6 is deleted. Part II is deleted. U.F.C. Standard No. 10-3 Add a new standard 10-3 as follows: -85- Uniform Fire Code Standard No. 10-3 Standard on Automatic Fire Detectors Section 10.301 ADOPTION OF NFPA STANDARD Sec. 10.301. Except for the limitations, deletions, modifica- tions or amendments set forth in Sec. 10.302 of this standard, the installation of automatic fire detectors required by the Uniform Fire Code shall be in accordance with the "Standard on Automatic Fire Detectors, NFPA 72E-19$4", published by the National Fire Protection Association, copyright 1935, Batterymarch Park, Quincy, Massachusetts 02269, as if set out at length herein. Section 10.302 AMENDMENTS Sec. 10.302. The National Fire Protection Association standard adopted by Sec. 10.301 applies to the installation of automatic fire detectors except as follows: (1) Sec. 1-2.2 is amended by deleting the word "NFPA". (2) Sec. 1-2.3 is deleted. (3) Sec. 2-1 is amended by revising the definition of "Autho- rity Having Jurisdiction" to read as follows: "Authority Having Jurisdiction" is the Building Official. Sec. 2-1. The definition of "Approved" and "Listed" shall be as set forth in the Uniform Building Code. Sec. 2-1 is amended by deleting the words "Should" and "Standard" and by adding the definition for "Acceptance", "Building Official" and " Fire Chief" to read as follows: .. "Acceptance" is acceptance by the Authority Having Juris- diction. "Building Official" is the officer or other designated authority charged with the administration and enforcement of the standard ar his duly authorized representative. "Fire Chief" is the Chief of the Fire Department or his duly authorized representative. (4) Sec. 2-6.4 is amended by deleting the word "NFPA". -86- (5) Sec. 3-1.2 is amended by (6) Sec. 4-5.1.6 is amended for Rack Storage of Mater (7) Sec. 5-1.2 is amended by (8) Sec. 7-1.1 is amended by (9) Sec. 9-1.1 is deleted. (10) Chapter 10 is deleted. U.F.C. Standard No. 81-1 deleting the by changing ials" to "UFC deleting the deleting the word "NFPA". '°NFPA 231C Standard Standard No. 81-2". word "NFPA". word "NFPA". Update standard by adopting NFPA 231-1985 with amendments as fol- lows: Uniform Fire Code Standard No. 81-1 High-Piled General Storage of Combustibles in Buildings See Sections 81.101, 81.104, 81.106, 81.108 and $1.110, Uniform Fire Code. This standard, with certain exceptions, is based upon the National Fire Protection Association Standards for General Storage, NFPA 231-1985. Part I of this standard contains the exceptions to NFPA 231-1985. PART I - GENERAL STORAGE AMEND~9ENTS Sec. 81.101. The National Fire Protection Association Standard for General Storage, NFPA 231-1985, applies to the classification of commodities and the installation of fire protection equipment used in conjunction with high-piled storage, except as follows: (1) Sec. 1-1 is amended to read as follows: 1-1 Scope. This part applies to storage of materials rep- resenting the broad range of combustibles, 30 feet or less in height, including the storage of Groups B and C plas- tics in all configurations and free-flowing Group A plas- tics. This part also applies to storage of Group A plastics, except free-flowing, up to 25 feet in height. _g~_ Storage piled higher than the above stated heights are not within the scope of this part and require special consid- eration. This part does not apply to: 1. Storage of commodities which, with their packaging and storage aids, would be classified as noncombustible. 2. Unpackaged bulk materials such as grain, coal or simi- lar commodities. 3. Commodities covered by other standards except where specifically mentioned herein. 4. Commodities presenting special fire hazards not covered by specific standards, e.g., roll paper, wax-coated car- tons, etc. 5. Storage on racks. U.F.C. Standard ATo. 81-1 (2) Sec. 1-'l is amended by revising the definition of com- modity to read as follows: Commodity. Combinations of products, packaging mater- ial and container. Commodities shall be classified as fol- lows: Class I commodity is a commodity which is essentially noncombustible products on combustible pallets, in ordi- nary corrugated cartons, with or without single-thickness dividers, or in ordinary paper wrappings with or without pallets. Class II commodity is Class I products in slatted wooden crates, solid wooden boxes, multiple thickness paperboard cartons or equivalent combustible packaging material with or without pallets. Class III commodity is a commodity of wood, paper, natural fiber cloth, or Group C plastics or products thereof, with or without pallets. Products may contain a limited amount of Group A or B plastics. (Metal bicycles with plastic handles, pedals, seats and tires are an example of a commodity with a limited amount of plastics.) -88- Class IV commodity is Class I, II or III products containing an appreciable amount of Group A plastics in ordinary corrugated cartons and Class I, II and III prod- ucts in corrugated cartans with Group A plastic packaging, with or without pallets. Group B plastics and free-flowing Group A plastics are also included in this class. Sec. 1-2 is further amended by deleting the definition for "Should". (3) Sec. 2-1.1 is amended to read as follows: 2-1.1. Commodity classification shall be as set forth in Uniform Fire Code Article 81 and this part. (4) Secs. 2-1.2 through 2-1.4, inclusive, are deleted. (5) Chapter 3 is deleted. (6) Sec. 4-4.1.1 is deleted. (7) Sec. 4-4.2.1 is deleted. (8) Sec. 5-1 is amended by substituting the phrase "U.B.C. Standard No. 38-1" for the phrase "Installation of Sprink- ler Systems, NFPA 13" wherever it appears. (9) Sec. 5-1.2 is amended by adding a sentence as follows: 5-1.2. Sprinkler system design density shall not be less than 0.15 GPM/Ft2 [0.10(L/S)/M2] for any commodity class or group. When the sole water supply consists of a munici- pal waterworks connection, the municipal water supply must exceed the calculated hydraulic pressure demand by 5 PSI at the calculated flow demand. (10) Sec. 5-1.3 is amended by substituting the phrase "U.F.C. Standard No. 81-2" for the phrase "Rack Storage of Mater- ials, NFPA 231C". (11) Sec. 5-2.1 is amended by substituting the phrase "U.F.C. Standard No. 79-1" for the phrase "High Expansion Foam Systems, NFPA 11A". (12) Sec. 5-3.1 is amended by adding an exception to read as fo 1 lows -89- EXCEPTION: In buildings served by a single automatic sprinkler system, the hose stations may be supplied from the ceiling sprinkler piping downstream of the sprinkler control valve. (13) Sec. 5-4 is changed to read as follows: 5-4. The water for protection of the building and premises shall be in accordance with Uniform Fire Code Section 10.301. (14) Sec. 5-5 is deleted. (15) Sec. 5-6 is amended by deleting all text following the first sentence. (16) Sec. 6-2.2 is amended to read as follows: 6-2.2. Where storage height is less than 30 feet high but more than 15 feet in solid piles and 12 feet high for palletized or bin storage, ceiling densities indicated in the design curves, based on 20-foot nominal storage height, shall be modified in accordance with Figure 6-2.2. (17) Sec. 7-l, including Figure 7-l.l referenced therein, is amended by substituting the phrase "U.B.C. Standard No. 38-1" for the term "NFPA 13" wherever it appears. (18) Note 1 of Figure 7-l.l is changed to read as follows: 1. Sprinklers rated at 286°F shall be used. (19) Sec. 7-1.2 is amended by deleting reference to "Appendix Bye (20) Secs. 8-1 through 8-7, inclusive, are deleted. (21) Appendix C is deleted. PART II is deleted. U.F.C. Standard No. 81-2 Update standard by adopting NFPA 231C-1986 with amendments as fol- lows: Uniform Fire Code Standard No. 81-2 High-Piled Rack Storage of Combustibles in Buildings See Section 79.203(a), Table No. 79.200-D-3, Sections 81.101, 81.106, 81.108 and 81.110, Uniform Fire Code -90- This standard, with certain exceptions, is based upon the National Fire Protection Association Standards for Rack Storage of Materials, NFPA 231C-1986. Part I of this standard contains the exceptions to NFPA 231C-1986. PART I - RACK STORAGE OF MATERIALS AMENDMENTS Sec. 81.201. The National Fire Protection Association Standard for Rack Storage of Materials, NFPA 231C-1986, applies to the clas- sification of commodities and the installation of fire protection equipment used in conjunction with the rack storage of materials, except as follows: (1) Sec. 1-1 is amended to read as follows: 1-1 Scope. This part applies to storage of materials rep- resenting the broad range of combustibles stored over 12 feet in height on racks. For storage heights of 12 feet or less, see U.B.C. Standard No. 38-1. Storage on plastic pallets or plastic shelves is outside the scope of this part. Storage of high-hazard materials such as tires, plastic and flammable liquids, except for those flammable liquids stored in a liquid storage room complying with Uniform Fire Code Section 79.203, is outside the scope of this standard. Bin storage and shelf storage are outside the scope of this part. (2) Sec. 1-2 is amended by revising the definition of "Autho- rity Having Jurisdiction" to read as follows: "Authority having Jurisdiction" is the official respon- sible for the administration and enforcement of this standard. The definitions of APPROVED, LABELED and LISTED shall be as set forth in the Uniform Fire Code. Sec. 1-2 is further amended by deleting the definition for "Should". -91- (3) Sec. 2-1.1 is amended to read as follows: 2-l.l Commodity classification shall be as set forth in Uniform Fire Code Article 81 and Standard 81-1. (4) Secs. 2-1.2 through 2-1.4, inclusive, are deleted. (5) Secs. 3-1 through 3-3, inclusive, are deleted. (6) Secs. 4-1 through 4-7, inclusive, are deleted. (7) Sec. 5-1 is amended by adding Sec. 5-1.3 to read as fol- lows: 5-1.3. When the sole water supply consists of a municipal waterworks connection, the municipal water supply must exceed the calculated hydraulic pressure demand by 5 P5I at the calculated flow demand. (8) Sec. 5-2.1 is amended by substituting the phrase "U.B.C. Standard No. 38-1" for the phrase "Installation of Sprink- lers, NFPA 13." (9) Sec. 5-8 is amended by adding an exception to read as fol- lows: EXCEPTION: In buildings served by a single automatic sprinkler system, the hose stations may be supplied from the ceiling sprinkler piping downstream of the sprinkler control valve. (lU) Sec. 5-11.1 is amended by substituting the phrase "U.F.C. Standard No. 79-1" for the phrase "High Expansion Foam Systems, NFPA 11A". (11) Sec. 6-1 is amended by substituting the phrase "U.B.C. Standard No. 38-1" for the term "NFPA 13". (12) Sec. 7-1 is amended by substituting the phrase "U.B.C. Standard No. 38-1" for the term "NFPA 13". (13) Sec. 10-1 is deleted. (14) Secs. 11-1 through 11-6, inclusive, are deleted. (15) Appendix C is deleted. PART II is deleted. -92 - SECTION 3801 Section 3801.(a) General. All fire extinguishing systems re- quired in this code shall be installed in accordance with the requirements of this chapter. Persons installing any fire protection equipment under this section shall first be required to obtain a certificate of installa- tion from the Bureau of Fire Prevention as set forth in the Fire Code. Prior to installation of any system required by this section, plans and other documents pertaining to said installation shall be submitted to the Bureau of Fire Prevention for review in accordance with Appendix VII-B of the Fire Code. Fire hose threads used in connection with fire-extinguishing systems shall be National Standard hose thread or as approved by the fire department. Pumps required by this chapter shall be installed in accordance with Standard 38-3. (b) through (c) Unchanged. Section 3801.(d) Standards. Fire-extinguishing systems shall comply with U.B.C. Standards Nos. 38-1 and 38-2. EXCEPTIONS: 1. Automatic fire-extinguishing systems not covered by U.B.C. Standard No. 38-1 or 38-2 shall be approved and in- stalled in accordance with the Fire Code. 2. Automatic sprinkler systems may be connected to the domestic water-supply main when approved by the building official, pro- vided the domestic water supply is of adequate pressure, capa- city and sizing for the combined domestic and sprinkler requirements. In such case, the sprinkler system connection shall be made between the public water main or meter and the building shutoff valve, and there shall not be intervening valves or connections. The fire department connection may be omitted when approved by the fire department. 3. Where sprinklers are installed in electrical rooms they shall be separated from the building's main sprinkler system by a preaction valve. This valve shall be connected to fire detec- tion device(s) in the electrical room. Sprinkler piping shall remain dry until the fire detection device activates and opens the preaction valve. Sprinkler head(s) shall be of a type to remain closed until sufficient heat is present to open them. Detection device shall have a minimum temperature rating of -y3- 165°F. The sprinkler shall have a minimum temperature rating of 212°F. Sprinkler heads in electrical rooms shall be protected with a listed guard over the head. SECTION 3802 Section 3802.(a) Where extinguishing system shall be locations as set forth in this hazardous chemicals, magnesium, rack storage in warehouse or spe fire code. Required. An automatic fire- installed in the occupancies and section. For special provisions on calcium carbide, or high-piled or culative warehouse property, see the Regardless of the provisions of 3802(b) through (f), all Group R, Division 1 occupancies with interior corridors and three stories or more in height and all occupancies four stories or more in height shall be sprinklered throughout the building. (b) through (c) Unchanged. Section 3802.(d) Group B, Division 2 Occupancies. An automatic sprinkler system shall be installed in retail sales rooms classed as Group B, Division 2 Occupancies where the floor area exceeds 12,000 square feet on any floor or 24,000 square feet on ali floors. The area of mezzanines shall be included in determining the areas where sprinklers are required. Speculative buildings over 12,000 square feet which measure 15 feet or more from the floor to the bottom of the roof system shall be protected as Class IV commodities according to Article 81 of the Fire Code. (e) through (g) Unchanged. SECTION 3805 Section 3805. (a) and (b) Unchanged. (c) Location of Class I Standpipes. There shall be a Class I standpipe outlet connection at every floor level above the first story of every required stairway and on each side of the wall adjacent to the exit opening of a horizontal exit. Outlets at stair- ways shall be located within the exit enclosure or in the case of smokeproof enclosures, within the vestibule or exterior balcony, giving access to the stairway. Risers and laterals of Class I standpipe systems not located within an enclosed stairway or smokeproof enclosure shall be pro- tected by a degree of fire resistance equal to that required for vertical enclosures in the building in which they are located. -94- ii EXCEPTION: In the buildings equipped with an approved automatic sprinkler system, risers and laterals which are not located within an enclosed stairway or smokeproof enclosure need not be enclosed within fire-resistive con- struction. There shall be a two-way outlet above the roofline on every standpipe when the roof has a slope of less than 4 inches in 12 inches. EXCEPTION: Standpipes located in stairways conforming to Section 3306(0) may have the two-way outlet located at the topmost floor landing. In buildings where more than one standpipe is provided, the standpipes shall be interconnected at the bottom. U.B.C. STANDARD NO. 38-1 Amend U.B.C. Standard 38-1 to read as follows: Uniform Building Code Standard No. 38-1 Installation of Sprinkler Systems See Sections 911(c), 1807(c), 3801 (d ), 3802(8) and Appendix Sections 125(a), 125(b), 713(a) and 1108(b), Uniform Building Code; and Sections 10.307(d); 10.308(8), Exception 2; 79.201(e), Item No. 3(i) and (ii); 70.2U1(e), Item No. 4(i); 79.203(a); 79.204(b); 79.301(d) and 79.506(c), Uniform Fire Code. SECTION 38.101 ADOPTION OF NFPA STANDARD Section 38.101. Except for the limitations, deletions, modifi- cations or amendments set forth in Section 3$.102 of this standard, the installation of sprinkler systems required by the Uniform Building Code shall be in accordance with the Standard for the Installation of Sprinkler Systems, NFPA 13-1983 published by the National Fire Protection Association, copyright 1983, Batterymarch Park, Quincy, Massachusetts 02269, as if set out at length herein. SECTION 38.102 AMENDMENTS Section 38.102. The National Fire Protection Association stan- dard adopted by Section 38.101 applies to the selection, installa- tion, inspection, maintenance and testing of sprinkler systems, except as follows: -95- l.. SECTION 1-1 is amended by deleting the note. 2. SECTION 1-2 is deleted. 3. SECTION 1-3 is amended by revising the definition of "Authority Having Jurisdiction" to read as follows: The "authority having jurisdiction" is the building official. The definitions of "Approved" and "Listed" shall be as set forth in the Uniform Building Code. Section 1-3 is further amended by deleting the definitions of the words "Should" and "Standard" by deleting the note following the definition of "Sprinkler System", and by adding definitions for "Acceptance", "Building Official" and '°Fire Chief" to read as fol- lows: "Acceptance" is acceptance by the authority having jurisdic- tion. "Building Official" is the officer or other designated autho- rity charged with the administration and enforcement of this standard, or his duly authorized representative. "Fire Chief" is the Chief of the Fire Department or his duly authorized representative. 4. SECTION 1-4 is deleted. 5. SECTION 1-7 is amended to read as follows: 1-7 Classification of Occupancies: 1-7.1. For the purpose of determining the level of protection to be provided by required sprinkler system installation, the build- ing official shall classify the use of each building or portion thereof as a Light Hazard; an Ordinary Hazard, Group 1, 2 or 3 Occupancy; or an Extra Hazard, Group 1 or 2 Occupancy, as defined in this section. Any use not specifically mentioned or about which there is any doubt shall be included in the classification which it most nearly resembles based on the life and fire hazard. For high-piled stock, see the Uniform Fire Code. 1-7.2 Light Hazard Occupancies: 1-7.2. Light Hazard Occupancies are users where the quantity or combustibility, or both, of contents is low and fires of low rates of heat release are expected. -96- a ~ Light Hazard Occupancies include uses such as: Churches Clubs Eaves and overhangs, if combustible construction with no com- bustibles beneath Educational Hospitals Institutional Libraries, except large stack rooms Museums Nursing or convalescent homes Office, including data processing Residential Restaurant seating areas Theaters and auditoriums excluding stages and prosceniums Unused attics 1-7.3 Ordinary Hazard Occupancies: 1-7.3. Ordinary Hazard Group 1 Occupancies are uses where com- bustibility is low, quantities of combustibles are moderate, stock piles of combustibles do not exceed B feet and fires with moderate rates of heat release are expected. Ordinary Hazard Group 1 Occupancies include uses such as: Automobile parking garages Bakeries Beverage manufacturing Canneries Dairy products manufacturing and processing Electronics plants Glass and glass products manufacturing Laundries Restaurant service areas 1-7.3.2. Ordinary Hazard Group 2 Occupancies are uses where the quantity and combustibility of contents are moderate, stock piles do not exceed 12 feet in height and fires with moderate rates of heat release are expected. Ordinary Hazard Group 2 Occupancies include uses such as: Cereal mills Chemical plants -- ordinary Cold storage warehouses Confectionary products Distilleries Leather goods manufacturing _g~_ Libraries -- large stack room areas Machine shops Metal works Mercantiles Printing and publishing Textile manufacturing Tobacco products manufacturing Wood product assembly 1-7.3.3. Ordinary Hazard Group 3 Occupancies are uses where the quantity or combustibility of contents, or both, is high and fires of high rates of heat release are expected. (Ordinary Hazard Group 3 Occupancies shall be hydraulically designed.) Ordinary Hazard Group 3 Occupancies include uses such as: Exhibition halls Feed mills Paper and pulp mill's Paper processing plants Piers and wharves Repair garages Tire manufacturing Warehouses (having moderate to tent, such as paper, household age, whiskey, etc., except for storage. See the Fire Code.) Wood machining 1-7.4. Extra Hazard Occupancies: higher combustibility of con- furniture, paint, general stor- warehouses used for high-piled 1-7.4. Extra Hazard Group 1 Occupancies are uses where the quantity and combustibility of contents is very high and dust, lint or other materials other than flammable or combustible liquids are present and rapidly developing fires with high rates of heat release are expected. (Extra Hazard Group 1 Occupancies shall be hydrau- lically designed.) Extra Hazard Group 1 Occupancies include uses such as: Combustible hydraulic fluid use areas such as die casting and metal extruding Plywood and particle board manufacturing Printing (using inks with below 100°F flashpoints) Rubber reclaiming, compounding, drying, milling, vulcanizing Saw mills Textile picking, opening, blending, garnetting, carding, com- bining of cotton, synthetics, wood shoddy, or burlap Upholstering with plastic foams -98- r t 1-?.4.2. Extra Hazard Group 2 Occupancies are uses with moder- ate to substantial quantities of flammable or combustible liquids or where shielding of combustibles is extensive. (Extra Hazard Group 2 Occupancies shall be hydraulically designed.) Extra Hazard Group 2 Occupancies include uses such as: Asphalt saturating Flammable liquid spraying Flow coating Mobile home or modular building assemblies (where finished en- closure is present and has combustible interiors) Open oil quenching Solvent cleaning Varnish and paint dripping 6. SECTION 1-9.2 is amended as follows: Add to SECTION 1-9.2(a): and current mailing addresses Add to SECTION 1-9.2(u): and antifreeze system: include NFPA calculations Add to SECTION 1-9.2(z): with rod sizes, trapeze bar dimen- sions and locations of hangers on piping indicated Change SECTION 1-9.2(gg): "contractor" to "sprinkler contrac- tor" 7. SECTION 1-10 is amended by changing "Authority Having Jurisdic- tion" to "Fire Chief". 8. SECTION 1-11.2.2 is amended to read as follows: 1-11.2.2. Leakage Prohibited. The sprinkler system including inside piping, underground mains, lead-in piping and common supply piping charges with water shall not display visible leakage during or after testing. 9. SECTION 1-12 is revised by substituting the City of Fort Worth Contractors Materials and Text Certificates. 10. SECTION 2-2.1.1 and 2-2.1.1(a) are amended to read as follows: 2-2.1.1. Occupancy classifications shall be as set forth in Section 1-7. See Item No. 5 of these amendments. (a) Table 2-2.1(A) shall be used in determining the minimum water supply requirements for pipe schedule sprinkler systems in Light Hazard Occupancies or in Ordinary Hazard Group 1 and Group 2 Occupancies. In Ordinary Hazard -99- R Group 3 Occupancies, Extra Hazard Occupancies and in high-rise buildings, the sprinkler system shall be hydrau- lically designed. 11. SECTION 2-2.1.2.2 is amended by adding the following: "If such pressure is adequate for operation of the hose stream." 13. SECTION 2-2.1 is amended by adding Section 2-2.1.13 to read as follows: 2-2.1.13. For uses which have the potential for fast-spreading fires due to the presence of lint, combustible residue, combustible hydraulic fluids under high pressure with ignition sources nearby and similar factors, the minimum area of operation shall encompass the entire area likely to be involved in such a fire. -10U- 14. TABLE 2-2.1(A) is amended to read as follows: Table 2-2.1(A). Water Supply Requirements for Pipe Schedule Sprinkler Systems. OCCUPANCY MINIMUM RESIDUAL MINIMUM FLOW AT BASE DURATION IN CLASSIFICATION PRESSURE OF RISER GPM MINUTES (PSI) (SEE NOTE 2) (SEE NOTE 1) Light Hazard 15 500 (See Note 3) 30 Ordinary Hazard 15 70U 60 (Group 1 ) Ordinary Hazard 15 850 60 (Group 2 ) Ordinary Hazard Hydraulic design (Group 3) required Warehouses Hydraulic design required. For high- piled stock storage, see Uniform Fire Code Standard No. 81-1. High-Rise Bldgs Hydraulic design required. Extra Hazard Hydraulic design required. NOTES: 1. The pressure required at the base of the sprinkler riser is the residual pressure required at the elevation of the highest sprinkler plus the pressure required to reach this elevation. 2. When the greater flow or higher pressures are required by UBC Standard No. 38-2, the more restrictive requirement shall apply unless the building is sprinklered throughout whereby only the sprinkler demand need `be met when compliance with UBC Section 1807 is not required. 3. The requirements may be reduced to 250 gpm in buildings of noncombustible con- struction. -101- 15. SECTION 2-2.1.2.5 is amended to read as follows: 2-2.1.2.5. The water supply shall not be less than the duration set forth in Tables 2-2.1(A) and 2-2.1(B) nor less than set forth in Uniform Building Code Section 1807(c). 16. SECTION 2-2.1.2.11 is deleted. 17. SECTION 2-3.1.1 is amended by adding paragraph two as follows: When the sole water supply consists of a municipal waterworks connection, the municipal water supply shall exceed the calculated hydraulic pressure demand from Section 2-2.1.2 by 5 psi at the cal- culated flow demand. Flow tests shall be conducted within 12 months of the date of beginning sprinkler installations and may be required to be taken at peak hours of water demand when deemed necessary by the Fire Chief. 18. SECTION 2-7.3 is amended by adding Section 2-7.3.7 as follows: 2-7.3.7. Fire Department connections shall be located on a wall or in a yard adjacent to a fire lane or public roadway within 300 feet of a fire hydrant unless otherwise approved by the Fire Chief. Connections shall be placed between 18 and 48 inches above grade in a location acceptable to the Fire Chief. 19. SECTION 2-7.6.1 is amended to read as follows: 2-7.6.1. Hose couplings shall be in accordance with the re- quirements of the Uniform Building Code. 20. SECTION 3-l.l.l is amended by adding the exception as follows: EXCEPTION: Other material approved for specific use in residen- tial Automatic Sprinkler Systems may be approved for use in non-residential systems when approved by both the Building Official and Fire Chief and when such applications are in light hazard occupancies and piping is protected in an approved manner. Such systems must employ fast response sprinkler heads listed by Underwriters Laboratories or equivalent. 21. SECTION 3-3.1 is amended by changing the last paragraph to read as follows: See Uniform Fire Code Standard No. 81-1 for definitions of solid-piled, palletized or rack storage. 22. SECTION 3-8.1 is amended to read as follows: 3-8.1. For sprinklers in storage racks, see Uniform Fire Code Standard No. 81-2. -102- 23. SECTION 3-8.7 is amended by changing Item (c) to read as fol- lows: (c) When a sprinkler system contains a 2-1/2 inch outlet, the supply shall be in accordance with UBC Standard No. 38-2. SECTION 3-8.7 is further amended by substituting the phrase "UBC Standard No. 38-2" for the phrase "NFPA 14" in Item (d). 24. SECTION 3-15.1.11 is amended by substituting the phrase "Uniform Fire Code Standard No. 81-2" for the phrase "NFPA 2310". 25. SECTION 3-16.2.9 is amended by adding the following sentences: Residential sprinklers shall be used in any room which contains a sleeping area and is arranged for use by four or less occupants. Rooms which contain sleeping areas such as apartments or hotel/ motel, or dormitories for more than four people such as resting areas in day care centers and schools, or in institutional occu- pancies shall be protected by fast response commercial sprinklers bearing an Underwriters Laboratories listing or equivalent. 26. SECTION 3-16.6.2 is amended by changing the second sentence of the second exception to read as follows: For situations involving high-piled or rack storage, refer to Uniform Fire Code Standard No. 81-2. 27. SECTION 3-17.4.1 is amended by adding a second paragraph as follows: Alarm devices, such as water motor gongs, installed outside of buildings shall be installed as close as practicable to the Fire Department connections. Adjacent to the alarm shall be a sign which states "When alarm sounds, call Fort Worth Fire Department, 9-1-1", and which contains the address of the property. The minimum sign dimension shall be 9 inches. 28. SECTION 3-17.6.1 is amended to read as follows: 3-17.6.1. Electrically operated alarm attachments forming part of a central station, proprietary, remote or local station signaling system required by Section 3-17.8 of these amendments shall be in- stalled in accordance with approved nationally recognized standards. 29. SECTION 3-17.6.2 is amended to read as follows: 3-17.6.2. Electrically operated alarm attachments forming part of a local sprinkler waterflow alarm system may be of open-circuit type and shall comply with Uniform Fire Code Standard No. 10-2. -103- 30. SECTION 3-17 is amended by adding a new Section 3-17.8 to read as follows: 3-17.8. Alarm Supervision. When serving more than 100 sprink- lers, automatic sprinkler systems shall be supervised by an approved central, proprietary or remote station service or a local alarm which will give an audible signal at a constantly attended location. 31. SECTION 4-1.1 is amended by adding a new Section 4-1.1.6 to read as follows: 4-1.1.6. The authority having jurisdiction shall be consulted in every case as to location and spacing of sprinklers for protec- tion of building and contents and for .life safety. 32. SECTION 4-1.2 is amended by redesignating the existing Section 4-1.2 as Section 4-1.2.1 and adding a new Section 4-1.2.2 to read as followse 4-1.2.2. PerBnissible Sprinkler Omissions. Sprinklers may be omitted in rooms or areas as provided in Section 3804 of the Uniform Building Code. 33. SECTION 4-1.3.5 is amended to read as follows: 4-1.3.5. Standard Mill Construction refers to Type IV heavy timber buildings in the Uniform Building Code. 34. SECTION 4-1.3.8 is amended to read as follows: 4-1.3.8. High-piled Storage. See Uniform Fire Code. 35. SECTION 4-2.2.2 is amended by substituting the phrase "Uniform Fire Code Standard Nos. 81-1 and 81-2" for the phrase "NFPA 231 and 231C" in the exception. 36. SECTION 4-2.5 is amended by substituting the phrase "Uniform Fire Code Standard No. 81-2" for the phrase "NFPA 231C, Rack Storage of Materials". 37. SECTION 4-4.8.2.3 is amended to read as follows: 4-4.8.2.3. When floor openings are unenclosed, the floor open- ings involved shall be protected by draft curtains in combination with closely spaced sprinklers. See Uniform Building Code Section 1706(a). Exception 1, the floor openings provided for escalators. -104- 7' r 38. SECTION 4-4.8.2.4 is amended to read as follows: 4-4.8.2.4. Stairs enclosed in shafts of combustible or non- combustible construction shall have sprinklers provided at each floor landing and beneath the first landing above the lowest level. 39. SECTION 4-4.9 is amended to read as follows: 4-4.9. Building service chutes shall be protected in accordance with Uniform Building Code Section 3802 (b ), Item No. 2. 40. SECTION 4-4.16.1 is amended by adding a new sentence to read as follows: See Uniform Building Code Section 5208(b). 41. SECTION 4-1.17.3 is amended by deleting the note. 42. SECTION 4-4.18.1 is amended by changing the sentence "(See NFPA 96, Standard for Vapor Removal from Cooking Equipment.)" to "(See Uniform Mechanical Code.)" 43. SECTION 4-4.19 is amended by substituting the phrase "see Uniform Fire Code Standard No. 81-2" for the phrase "see NFPA 231C, Standard on Rack Storage of Materials" in the first sen- tence. 44. SECTION 8-1 is amended by changing the first sentence to read as follows: This chapter deals with automatic sprinkler systems designed for life safety and fire protection in high-rise buildings which are used predominantly for Light Hazard Occupancies. It is intended to cover totally sprinklered buildings only, and shall not apply to partially sprinklered buildings. 45. SECTION 8-2 is amended to read as follows: 8.2. Definition. High-Rise Building is a building having floors used for human occupancy located more than 75 feet above the lowest level of Fire Department vehicular access. 46. SECTION 8-5.4 is amended to read as follows: 8-5.4. Alarm and supervisory systems in connection with the sprinkler system shall be installed in accordance with the national- ly recognized standards. 47. Appendix Chapter D is amended by deleting SECTIONS D-1-1 and D-2. -105- L).B.C. STANDARD NO. 38-2 SECTION 38.202 Delete definition of "dry standpipe system" and substitute the fol- lowing: DRY STANDPIPE SYSTEM (Class 1) is a standpipe system with a water supply consisting of a one-inch water fill connection at the top of the riser to maintain piping normally wet and a Fire Department con- nection which is equipped with 2-1/2 inch outlets for use by the Fire Department or trained personnel. EXCEPTION: Dry standpipes are permitted without the water fill connection when they are located in areas subject to freezing. SECTION 38.207(d) Add Exception 2 to paragraph (d) as follows: EXCEPTION 2: In buildings other than high-rise which are fully equipped with an approved automatic fire sprinkler system which are not equipped with occupant use hose cabinets, only the sprinkler system demand need be provided, if the fire hose demand can be satisfied by Fire Department apparatus. SECTION 38.208 Add the following paragraph: Fire Department connections shall be located on a wall or in a yard adjacent to the fire lane or public roadway within 150 feet of a fire hydrant unless otherwise approved by the Fire Department. Connections shall be placed between 18 and 48 inches above grade in a location acceptable to the Fire Chief. SECTION 38.210 Delete and substitute the following: Section 38.210. Outlet pressures shall not be permitted to exceed 150 pounds per square inch. Where greater pressures may exist, an approved automatic pressure regulating device shall be installed to restrict pressures to not greater than 150 pounds per square inch. The pressures regulating device shall not be externally adjustable for varied pressures. -106- U.B.C. STANDARD NO. 38-3 Add a new Standard 38-3 as follows: Uniform Building Code Standard No. 38-3 Installation of Centrifugal Fire Pumps See Section 3801(a), Uniform Building Code; and Section 10.306(a), Uniform Fire Code. SECTION .38.301 ADOPTION OF NFPA STANDARD Section 38.301. Except for the limitations, deletions, modifi- cations or amendments set forth in Section 38.302 of this Standard, the installation of stationary centrifugal fire pumps for use in fire protection systems required by the Uniform Building Code shall be in accordance with the "Standard for the Installation of Centrifugal Fire Pumps, NFPA 20-1983", published by the National Fire Protection Association, copyright 1983, Batterymarch Park, 4uincy, Massachusetts 02269, as is set out at length herein. SECTION 38.302 Ae+lENDMENTS Section 38.302. The National Fire Protection Association Standard adopted by Section 38.301 applies to the selection, instal- lation, inspection, maintenance, and testing of centrifugal fire pumps except as follows: 1. Section 1-2.1 is deleted. 2. Section 1-7.3 is amended by "NFPA 70, National Electrical Worth Electrical Code". 3. Section 1-7.8 is amended by: changing all references of Code" to "the City of Fort (a) Revising the definition of "Authority Having Juris- diction" to read as follows: "Authority Having Jurisdiction" is the Building Official. (b) Deleting the definitions "Should" and "Standard" and by adding definitions for "Acceptance", "Building Official" and "Fire Chief" to read as follows: -1U7- "Acceptance" is acceptance by the Authority Having Jurisdiction. "Building Official" is the officer or other desig- nated authority charged with the administration and enforcement of the standard or his duly authorized representative. "Fire Chief" is the Chief of the Fire Department or his duly authorized representative. (c) The definition of "Approved" and "Listed" shall be as set forth in the Uniform Building Code. 4. Section 2-8.3 is amended by changing "NFPA 13" to "UBC Standard 38-1". 5. Section 2-9.1 is amended by changing "NFPA 24, Standard for Private Fire Service Mains and Their Appurtenances" to "Nationally Recognized Standards". 6. Section 2-9.6 is amended by changing " Private Fire Service Mains and Their "Nationally Recognized Standards". 7. Section 2-10.2 is amended by changing Standard 38-1" and by changing "NFPA Private Fire Service Mains and Their "Nationally Recognized Standards". NFPA, Standard for Appurtenances" to "NFPA 13" to "UBC 24, Standard for Appurtenances" to 8. Section 2-13.3.2 is amended by revising the text to read as follows: "Hose valve(s) shall have threads as specified in the Uniform Building Code". 9. Section 5-1.2 is amended by changing "NFPA 13" to "UBC Standard 38-1" and "NFPA 14, Standard for the Installation of Standpipe and Hose Systems, Chapter 5 and Chapter 6" to "UBC Standard 38-2". 10. Section 6-1 is amended by changing "NFPA 70, National Electrical Code" to "the City of Fort Worth Electrical Code". 11. Section 6-4.1 is amended by changing "NFPA 70, National Electrical Code" to "the City of Fort Worth Electrical Code" . -108- a:, 12. Section 6-5.3.2 is amended by changing "NFPA 70" to "City of Fort Worth Electrical Code". 13. Section 7-3.6 is amended by changing "NFPA 70, National Electrical Code" to "the City of Fort Worth Electrical Code". 14. Section 7-4.1 is amended by changing all references of "NFPA 7U, National Electrical Code" to "the City of Fort Worth Electrical Code". 15. Section 7-4.2 is amended by changing all references of "NFPA 70, National Electrical Code" to "the City of Fort Worth Electrical Code". 16. Section 8-5.3 is amended by changing "NFPA 37, Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines" to "the City of Fort Worth Mechanical Code". 17. Section 11-1.1 is amended by changing "NFPA" to "UBC". 18. Section 11-1.2 is amended by changing "NFPA 13" to "UBC Standard 38-1". 19. Section 11-2.2 is amended by changing "Authority Having Jurisdiction" to "Fire Chief". 20. Appendix C-1-1 is deleted. U.B.C. STANDARD NO. 38-4 Add a new standard 38-4 as follows: Uniform Building Code Standard No. 38-4 Installation of Halon 1301 Fire Extinguishing Systems Section 38.401 ADOPTION OF NFPA STANDARD Sec. 38.401. Except for the limitations, deletions, modifica- tions or amendments set forth in Sec. 38.402 of this standard, the installation of Halon 1301 fire extinguishing systems required by the Uniform Building Code shall be in accordance with the "Standard on Halon 1301 Fire Extinguishing Systems, NFPA 12A-1985", published by the National Fire Protection Association, copyright 19$5, Batterymarch Park, Quincy, Massachusetts 02269, as if set out at length herein. -109- y r-' j Section 38.402 AMENDMENTS Sec. 38.402. The National Fire Protection Association Standard adopted by Sec.. 38.401 applies to the installation of Halon 1301 systems except as follows: (1) Sec. 1-1 is amended by changing "NFPA 10, Standard for Portable Extinguishers" to "U.F.C. Standard No. 10-1". (2) Sec. 1-4 is amended by revising the definition of "Autho- rity Having Jurisdiction" to read as follows: "Authority Having Jurisdiction" is the Building Official. Sec. 1-4. The definition of "Approved" and "Listed" shall be as set forth in the Uniform Building Code. Sec. 1-4 is amended by deleting the words "Should" and "Stan- dard" and by adding the definition for "Acceptance", "Building Official" and "Fire Chief" to read as follows: "Acceptance° is acceptance by the Authority Having Jurisdic- tion. "Building Official" is the officer or other designated autho- rity charged with the administration and enforcement of the standard or his duly authorized representative. "Fire Chief° is the Chief of the Fire Department or his duly authorized representative. (3) Sec. 1-8.1 is amended by changing " tection Signaling Systems Standards "Fire Code Appendix III-C". (4) Sec. 1-8.2.2 is amended by changing for Automatic Fire Detectors" to lU-3". (5) Sec. 2-2.3 is added as follows: Appropriate NFPA Pro- (See Chapter 4)" to "NFPA 72E - Standard "Fire Code Standard 2--2.3. Soak Time. The minimum concentration of Halon specified herein to protect an area shall be maintained for a period of not less than 10 minutes throughout the protected area at a level of one foot below the ceiling or one foot above the highest level of pos- Bible storage, whichever is higher. (6) Sec. 4-1.1 is deleted. -110- 't f U.B.C. STANDARD NO. 38-5 Add a new standard 38-5 as follows: Uniform Building Code Standard No. 38-5 Installation of Residential Sprinkler Systems See Sections 508, 1705(b}(2), 3305(8), and Appendix, Chapter 1, Section III(c), Uniform Building Code; and Appendix III-C, Section 7(F)(1) and Appendix I-A, Uniform Fire Code. Section 38.501 ADOPTION OF NFPA STANDARD Sec. 38.501. Except for the limitations, deletions, mod- ifications or amendments set forth in Section 38.302 of this standard, the installation of residential sprinkler systems required by the Uniform Building Code shall be in accordance with the "Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings, NFPA 13D-1984", published by the National Fire Protection Association, copyright 1984, Batterymarch Park, Quincy, Massachusetts 02269, as if set out at length herein. Section 38.502 AMENDMENTS Sec. 38.502. The National Fire Protection Association Standard adopted by Section 38.501 applies to the installation of residential sprinkler systems except as follows: (1) Sec. 1-1 is amended as follows: Sec. 1-1. Scope. This standard deals with the design and installation of automatic sprinkler systems in resi- dential occupancies as permitted by the Uniform Building Code and the Uniform Fire Code. (2) Sec. 1-2 is amended by deleting the second paragraph. (3) Sec. 1-3 is amended as follows: Sec. 1-3 is amended by revising the definition of "Authority Having Jurisdiction" to read as follows: "Authority Having Jurisdiction" is the Building Official. Sec. 1-3 is amended by revising the definition of dwelling to read as follows: -111- Dwelling. Any building which contains "dwelling units" intended to be used, rented, leased, let or hired out to be occupied, or which are occupied for habitation purposes. Sec. 1-3 is amended by deleting the definitions "Dry System", "Should" and "Standard" and by adding definitions for "Acceptance", "Building Official" and "Fire Chief" to read as follows: Acceptance. Acceptable to the authority having jurisdic- tion. Building Official. The officer or other designated autho- rity charged with the administration and enforcement of the standard or his duly authorized representative. Fire Chief. The Chief of the Fire Department or his duly authorized kepresentative. Sec. 1-3. The definition of "Approved" and "Listed" shall be as set forth in the Uniform Building Code. (4) Sec. 1-5.1.4 is amended by changing "NFPA 13, Standard for the Installation of Sprinkler Systems" to "U.B.C. Standard 38-1". (5) Sec. 2-2(c) is amended as follows: 2-2(c). A pressure tank installed in accordance with U.B.C. Standard 38-1 and other nationally recognized stan- dards. (6) Sec. 2-3 is deleted. (7) Sec. 3-1.3 is deleted. (8) Sec. 3-2.1 is amended by deleting the words "... on dry systems and ..." (9) Sec. 3-5.1 is amended by deleting the exception. (10) Sec. 3-6 is amended by deleting the exception. (11) Sec. 4-3.2 is deleted. (12) Sec. 4-4 is amended by changing "NFPA 13, Standard for the Installation of Sprinkler Systems" to "U.B.C. Standard No. 38-1". -112- (13) Sec. 4-6 is amended by: (a) Deleting Exception #1. (b) Deleting Exception #2. (c) Deleting Exception #5. (d) Changing "Exception #3" to "Exception #1". (e) Changing "Exception #4" to "Exception #2". (14) Chapter 5 is deleted. SECTION 3. Section 13-3 of the Code of the City of Fort Worth (1986) is amended to read as follows: Sec. 13-3. Effect of conflict with other ordinances. This ordinance shall be cumulative of all provisions of ordinances and of the Code of the City of Fort Worth (1986), as amended, except where the provisions of this ordinance are in direct conflict with the provisions of such ordinances and such Code, in which event conflicting provisions of such ordinances and such Code are hereby repealed. Former Chapter 13 of the Code, as amended, is expressly superseded by the terms of this Chapter. SECTION 4. Section 13-4 of the Code of the City of Fort worth (1986) is amended to read as follows: Sec. 13.4. It shall be unlawful for any person to erect, construct, enlarge, alter, repair, move, improve, convert, demolish, equip, use, occupy or maintain any building or structure in the City or cause the same to be done con- trary to or in violation of any of the provisions of this Code. Any person, firm or corporation who violates, dis- ob eys, omits, neglects or refuses to comply with or who resists the enforcement of any of the provisions of this Code shall be fined not more than One Thousand Dollars ($1,000.00) for each offense. Each day that a violation is permitted to exist shall constitute a separate offense. SECTION 5. It is hereby declared to be the intention of the City Council that the sections, paragraphs, sentences, clauses and phrases of -113- this ordinance are severable, and, if any phrase, clause, sentence, paragraph or section of this ordinance shall be declared unconsti- tutional by the valid judgment or decree of any court of competent jurisdiction, such unconstitutionality shall not affect any of the remaining phrases, clauses, sentences, paragraphs and sections of this ordinance, since the same would have been enacted by the City Council without the incorporation in this ordinance of any such unconstitutional phrase, clause, sentence, paragraph or section. SECTION 6. All rights and remedies of the City of Fort Worth, Texas, are expressly saved as to any and all violations of the provisions of Chapter 13 of the Code of the City of Fort Worth, as amended, or any other ordinance affecting construction and fire safety, which have accrued at the time of the effective date of this ordinance; and, as to such accrued violations and all pending litigation, both civil and criminal, whether pending in court or not, under such ordi- nances, same shall not be affected by this ordinance but may be prosecuted until final disposition by the courts. SECTION ?. This ordinance constitutes a digest and revision of the Fire Code of the City of Fort Worth, as provided in Section 2, Chapter XXV, and Section 9, Chapter XXVII, of the Charter of the City of Fort Worth. The City Secretary of the City of Fort Worth, Texas is hereby authorized to publish this ordinance in pamphlet form for general distribution among the public, and the operative -114- 7' ~u _ _~ ~, ~. u ~. x, a.~. -4~Y 3 provisions of this ordinance, as so published, shall be admissible in evidence in all courts without further proof than the production thereof, as provided in Chapter XXV, Section 3, of the Charter of the City of Fort Worth, Texas. SECTION 8. The City Secretary of the City of Fort Worth is hereby directed to engross and enroll this ordinance by copying the caption, penalty clause and effective date in the minutes of the City Council and by filing the ordinance in the ordinance records of the City. SECTION 9. The City Secretary of the City of Fort Worth, Texas, is hereby directed to publish the caption, penalty clause and effective date of this ordinance for two (2) days in the official newspaper of the City of Fort Worth, Texas, as authorized by Section 52.013, Texas Local Government Code. SECTION 10. This ordinance shall be in full force and effect thirty (30) days after its passage and publication, and it is so ordained. APPROVED AS TO FORM AND LEGALITY: ity Attorney Date: ~/- 2 D ~~~ ADOPTED: EFFECTIVE: -115- .. ;, _n ___ .~ AccouN ~ IfdGl .z xRA~1Sf'1)RIAT.{,UN~pS1ULIC_.41. g ~yrn~ //®l, iliYI~~L1V ~®~l/W~~~tV ~®~~tVWU IV~~'li1V~L~~~ y1AIP.R ADN~INISTRATiufd ~ ~VOILyJ( a F.~RE ADMiNI.S LRD?tfiEd:L REFERENCE SUBJECT AdOptlOri Of the 1985 UnlfOrm I PAGE 04/21/88 NUMBER G- 755 3 Fire Code and City Amendment 1 oft It is recommended that the attached proposed ordinance be presented to the City Council for adoption of the 1985 Uniform Fire Code and City Amend- ments. This draft proposed ordinance has been reviewed by the construction and Fire Prevention Board of Appeals and presented to the citizens and parties in interest at two public hearings. Comments of citizens and parties in interest were considered by the construction and Fire Prevention Board. The proposed ordinance adopts changes that will benefit the citizens of Fort Worth. Among those changes are: 1. Requirement that makes property owners and management monetarily liable for Fire Department initiation of waste removal and securing of vacant buildings. 2. Requirement that makes companies monetarily liable for Fire Department initiated clean-up of unauthorized discharges of hazardous materials. 3. Relaxed sprinklering requirements of open parking garages, which are not considered a significant hazard. 4. Option that allows builders to install a defined residential sprinkler system in lieu of a building fire alarm system in apartment buildings (smoke detectors in individual units still required). 5. Clarification of flammable aerosol hazards and requirement for appro- priate fire protection based on fire test research. 6. Authority for the Fire Marshal to seize, remove, and destroy illegal fireworks. The Code is also amended to align with State of Texas and Federal Regula- tions concerning• 1. Requirement for installation and use of gasoline vapor recovery sys- tems. 2. Requirement for gasoline tank vehicles to have Department of Transpor- tation certification for vapor recovery systems. 3. Requirement for reporting of unauthorized hazardous material dis- charges. ~~~~~~~~ ~~TY CQU~N SUBMITTED FOR Inc CITY MANAGER'S DISPOSITION BY COUNCIL. PROCESSED BY OFFICEBY Bob Terrell ~ APPROVED ,~~~ ~~ f ORIGINATING C OTHER (DESCRIBE) DEPARTMENT HEAD R S C a s s a d a CI SECR TARP FOR ADDITIONAL INFORMATION R S C a s s a d a 6 85 8 y Adopted Ordinance No. /~_~ .98TE CONTACT ~Y ,~1~, fi~ ...~wMS~ ~4tY ~oaretarY of thel a;~ht of Fort W.~. T