HomeMy WebLinkAboutOrdinance 9669ORDINANCE NO. ~~C ~
AN ORDINANCE AMENDING ORDINANCE NO. 8907, AS AMENDED, THE
FORT WORTH MECHANICAL CODE, BY ADDING REQUIREMENTS FROb'I
THE 1985 EDITION OF THE UNIFORM MECHANICAL CODE REGARDING
NEW PRODUCTS AND METHODS OF INSTALLATION FOR HIGH ENERGY
EFFICIENCY EQUIPMENT AND SMOKE PROTECTIONS; MAKING THIS
ORDINANCE CUMULATIVE OF PRIOR ORDINANCES AND REPEALING THE
PARTS OF ALL PRIOR ORDINANCES IN CONFLICT HEREWITH; PRO-
VIDING A SEVERABILITY CLAUSE; PROVIDING A PENALTY; PROVID-
ING FOR PUBLICATION IN PAMPHLET FORM; PROVIDING FOR
ENGROSSMENT AND ENROLLMENT; PROVIDING FOR PUBLICATION IN
THE OFFICIAL NEWSPAPER; AND NAMING AN EFFECTIVE DATE.
BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF FORT WORTH,
TEXAS:
SECTION 1.
Sectior.~ 204 of Ordinance No. 8907, as amended, is hereby
amended by revising Paragraphs (a)(1) and (a)(2) thereof to read as
follows:
"BUSINESS REGISTRATION AND MECHANICAL LICENSE
Sec. 204(a)(1) Business Registration. Permits shall be issued
only to a business which has a valid registration with the City of
Fort Worth to make an installation of equipment regulated by this
code. Each business, including self-employment, shall have in its
employ a licensed individual where licenses are required by this
code or an official of the business listed with that business
registration who will be designated for issuance of permits. Each
registered business listed shall notify the City of Fort Worth of
any change .i.n licensee or designated official. Permits shall not be
issued where a business registration or license has been suspended
or revoked.
Where a Business Registration requires a license for the
installation of heating and air conditioning and this license is one
issued by tYie State of Texas, the licensee shall maintain a continu-
ing valid list of people, their home addresses and phone numbers,
that are under his supervision, which are covered by his liability
insurance. The list shall be filed with the Chief Mechanical
Inspector who then will issue an identification card for each
employee. T]ze identification card shall show the employees name and
the name of the supervising licensee. The employee shall have the
identification card on his person anytime he does work supervised by
a State of Texas licensed air conditioning contractor.
Each registered business shall notify the City of Fort Worth of
any change in licensee, designated official, or listed employee.
(2) License Required. Only a person who possesses a valid Fort
Worth Mechanical Air Conditioning Contractors License or a valid
State of Texas Air Conditioning Contractors License will be issued
permits for the installation of all forms of heating, cooling,
heating and cooling duct systems and other heat-producing appli-
ances regulated by this code. Such licensed contractors may extend
to and connect thereto any gas piping that may be required for the
operation of: such equipment. All electrical connections are regu-
lated by the Fort Worth Electrical Code. Only a person who possesses
a Fort Worth Mechanical Air Conditioning Contractors License will be
issued permits for the installation of refrigeration systems which
are not connected to environmental air conditioning.
A Maintenance Journeyman Electrician License shall be required
for all persons who perform electrical service, repair or main-
tenance on equipment regulated by the Mechanical Code when an
electrical permit is not required.
EXCEPTION: Those persons who possess a valid State of
Texas Air Conditioning Contractors license registered with
the City of Fort Worth and the employees under their
supervision who have been listed on the same Business
Registration shall not be required to obtain a Fort Worth
M ainten.ance Journeyman Electrician license to service and
maintain the internal part of the system as manufactured
and listed.
Plumbing Contractors registered with the City of Fort Worth
with a valid State of Texas Plumbing license may install gas fired
appliances which are not considered "air conditioning contracting"
by the State Air Conditioning Licensing Law. All L. P. gas piping
installations shall conform to the applicable Texas Railroad
Commission regulations.
SECTION 2.
Section. 405 of Ordinance No. 8907, as amended, is hereby
amended by adding the following definition of "Condensing Appliance"
thereto:
CONDENSING APPLIANCE is an appliance which condenses part
of the water vapor generated by the burning of hydrogen in
fuels.
SECTION 3.
Chapter 5 of Ordinance No. 8907, as amended, is hereby amended
by revising Tables 5-A and 5-B to read as contained in the 1985
Edition of the Uniform Mechanical Code, on file in the office of the
Department ~f Development, a copy of said revised Tables 5-A and 5-B
being reproduced and attached to this Ordinance as Exhibit "A" and
Exhibit "B" respectively.
-2-
SECTION 4.
Section 703 of Ordinance No. 8907, as amended, is hereby
amended to read as follows:
"Sec. 703. A furnace room shall have an opening or
door and passageway thereto not less than 2 feet in width
and large enough to permit removal of the largest furnace
in such room. The furnace shall be installed so as to
permit removal without disturbing piping, conduits, appur-
tenant valves and junction boxes.
EXCEPTIONS: 1. When the furnace room is large enough
to permit dismantling the furnace within the room,
the access opening and passageway need be large
enough only to permit removal of the largest piece of
furnace. This exception shall not be construed to
waive the requirements of a minimum door and passage-
way of 2 feet.
2. Access to warm-air furnaces installed in
under-floor spaces shall comply with Section 709.
3. Access to warm-air furnaces installed in an
attic or furred space shall comply with Section 708.
4. Access to warm-air furnaces installed on a
roof or on an outside wall structure shall comply
with Section 710.
5. In existing residential construction, an
existing furnace room may be used for a replacement
furnace, providing the door is not smaller than
eighteen (18) inches in width.
An unobstructed working space not less than 30 inches
in depth and the height of the furnace, but not less than
30 inches, shall be provided along the entire front or
firebox side of every warm-air furnace when the door of
the furnace enclosure is open.
Heating system air filters, fuel control valves, vent
collars, air-handling units and externally maintained
controls shall be accessible for maintenance, repair and
replacement. Access space shall be as specified for cool-
ing equipment in Section 1202."
SECTION 5.
Section 704 of Ordinance No. 8907, as amended, is hereby
amended to read as follows:
-3-
"Sec. 704. Warm-air furnaces shall not be installed:
1. In a closet or alcove less than 12 inches wider
than the furnace or furnaces installed therein with a
minimum clear working space less than 3 inches along the
sides, back and top of the furnace.
EXCEPTION: Replacement forced-air furnaces or air
conditioning cooling coils may be installed in an
existing closet or alcove with lesser width when
approved by the Building Official and provided that
such width is in compliance with conditions of list-
ing.
2. In a hazardous location.
3. In a surgical operating room or medical treatment
room.
4. Under a stairway.
5. In a Group A, B, E, or I Occupancy, unless sepa-
rated from the rest of the building by not less than One-
hour Fire-resistive Occupancy Separation.
EXCEPTION: Boilers or central heating plants where
the largest piece of fuel equipment does not exceed
400, 000 BTU/h input.
6. In any Group
such occupancy by not
Occupancy Separation.
pancies, there shall
except for necessary c
H Occupancy unless separated from
less than a Two-hour Fire-resistive
In Group H, Division 1 and 2 Occu-
be no opening in such separations
Ducts and piping.
In Group H, Division 4 Occupancies, devices which
generate a spark or glow capable of igniting gasoline
vapors shall not be installed or used within 18 inches of
the floor.
7. In Group R, Division 1 Occupancies, unless sepa-
rated from such occupancy by not less than a One-hour
Fire-resistive Occupancy Separation.
EXCEPTION: A separation shall not be required for
such equipment serving only one dwelling unit.
8. In a room used or designed to be used as a bed-
room, bathroom, closet or in any enclosed space with
access only through such room or space.
- 4-
EXCEPTION: Direct vent furnaces, enclosed furnaces
and electric heating furnaces. Access to furnaces
located in an attic or under-floor crawl space may be
through a closet.
9. Outside of a building unless listed for exterior
installation or enclosed in a weatherproof housing comply-
ing with Section 710.
10. With clearance along the combustion-chamber open-
ing side of less than 6 inches or working space along the
entire front or firebox side less than specified in
Section 703."
SECTION 6.
Section 901 of Ordinance No. 8907, as amended, is hereby
amended to read as follows:
"Sec. 901. Every appliance designated to be vented shall
be connected to a venting system as specified in Section 902
and such system shall comply with the provisions of this chap-
ter, except as provided in this section.
Venting systems shall consist of approved chimneys, Type B
vents, Type BW vents, Type L vents, plastic pipe recommended by
the manufacturer of listed condensing appliances for use with
specified models, or a venting assembly which is an integral
part of a listed appliance.
Venting systems shall be so designed and constructed as to
develop a positive flow adequate to convey all combustion
products to the outside atmosphere.
Venting systems may be designed in accordance with ac-
cepted engineering methods when such design method has been
approved by the building official.
A venting system which is an integral part of the vented
appliance and plastic pipe recommended by the manufacturer in
installation instructions as suitable for use with listed
condensing appliances shall be installed in accordance with the
appliance listing, manufacturer's installation instructions and
applicable requirements of this code.
Gas venting systems serving appliances equipped with draft
hoods and appliances listed for use with Type B vents may be
designed in accordance with tables in Appendix C, Chapter 9,
when such design method has been approved by the building
official. "
SECTION 7.
Section 902 of Ordinance No. 8907,
amended to read as follows:
Type of Venting Systems Required
as amended, is hereby
"Sec. 902. (a) General. The type of venting system re-
quired to serve various classifications of appliances shall be
as set forth in Tables No. 9-A and No. 9-B.
(b) Limitations. Type B vents shall not be used for vent-
ing the following:
1. Appliances which may be converted readily to
the use of solid or liquid fuels;
2. Combination gas-oil-burning appliances;
3. Appliances listed for use with chimneys only
(c) Vent Connector. Connectors used for gas appliances
having draft hoods and for listed conversion-burner-equipped
appliances having draft hoods may be constructed of materials
having resistance to corrosion and heat not less than that
specified in Section 915(c) or they may be of Type B or Type L
vent material.
(d) Solid Fuel. Solid-fuel-burning appliances shall not
be connected to a venting system which serves gas or oil-
burning appliances.
(e) Plastic Venting Systems for Use with Listed Condensing
Appliances. Condensing appliances which cool flue gases nearly
to the dewpoint within the appliance resulting in low vent gas
temperatures may use plastic venting materials and vent config-
urations unsuitable for noncondensing appliances. Listed con-
densing appliances shall be considered properly vented when
installed in accordance with the terms of listing and manufac-
turer's installation instructions."
SECTION 8.
Chapter 9 of Ordinance No. 8907, as amended, is hereby amended
by revising Table 9-B to read as follows:
-6-
TABLE NO. 9-B - VENT SELECTION CHART
Column 1
Type B, Gas
Round or Oval Column II
Type BW Gas Column III
Type L Column IV
Plastic Pipe
All listed gas 1. Gas-burning 1. Oil-burning 1. Condensing
appliances with wall heaters appliances appliances
draft hoods such listed for listed for listed for
as: use with use with Type use with a
1. Central Furnaces Type BW L vents specific
2. Floor Furnaces vents 2. Gas appli- plastic
3. Heating boilers ances as pipe rec-
4. Ranges & Ovens shown in ommended &
5. Recessed wall first column identified
furnaces ( above in the mfg.
wall section) installation
6. Room & Unit instructions
heaters
7. Water heaters
SECTION 9.
Section 1002 of Ordinance No. 8907, as amended, is hereby
amended by revising Paragraph (a) thereof to read as follows:
"Sec. 1002. (a) GENERAL. Circulating-air and condi-
tioned-air supply for heating, cooling or evaporative cooling
systems shall be conducted through duct systems constructed of
metal as set forth in Tables Nos. 10-A, 10-B, and 10-C; metal
ducts complying with U.M.C. Standard No. 10-2 with prior
approval; or factory-made air ducts complying with U.M.C.
Standard No. 10-1. Ducts, plenums and fittings may be con-
structed of concrete, clay, ceramics, or tested and listed
ducts for underground installation when installed in the ground
or in a concrete slab, provided the joints are tightly sealed.
Concealed building spaces or independent construction
within buildings may be used as ducts or plenums.
When gypsum products are exposed in ducts or plenums, the
air temperature shall be restricted to a range from 50° F. to
125° F. and moisture content shall be controlled so that the
material is not adversely affected. Gypsum products shall not
be exposed in ducts serving evaporative coolers.
Venting systems shall not extend into or through ducts or
plenums.
Materials exposed within ducts or plenums shall have a
flame-spread index of not more than 24 and a smoke-developed
rating of not more than 50.
-7-
EXCEPTIONS: 1. Circulating-air ducts, plenums or
concealed spaces which serve a dwelling unit may be
of combustible construction.
2. Air filters serving a dwelling unit.
3. Air filters listed by an approved testing
agency as complying with reference standards included
in Appendix C.
4. Air filters used as water evaporation medium
in an evaporative cooler.
5. Charcoal filters when protected with an
approved fire suppression system.
6. Polyethylene tubing having a U. L. 94V2 list-
ing and where the total weight does not exceed 1
pound per 1,000 square feet and the density does not
exceed 5 pounds in any one 16-foot radius may be used
in the concealed spaces forming air plenums when
there is a product of combustion detector located
where the return air enters the equipment to stop all
air circulating in this space. Polyethylene tubing
enclosed in a rated metal pipe or raceway with all
seams and ends sealed with a sealant having a flame-
spread of 25 and a smoke-development of 50 shall not
be added into the weight per 1,000 square feet or the
density of any 16-foot radius.
Wiring in plenums shall comply with the Electrical Code,
Article 725. "
SECTION 10.
Section 1009 of Ordinance No. 8907, as amended is hereby
amended to read as follows:
"Sec. 1009 (a) Automatic Shutoff. When Required. Each
building or space with interconnecting openings having a single
system or multiple systems providing heating or cooling with a
combined circulated air in excess of 2000 cubic feet per minute
(based on 400 CFM per nominal ton) in Group A, Group B,
Division 2; Group E; Group I, and Group R, Division 1 Occupan-
cies shall be equipped with an automatic shutoff. Automatic
shutoffs shall shut down the air-moving equipment when smoke is
detected in a circulating airstream or as an alternate when
smoke is detected in rooms served by the system. Whenever such
system serves more than one occupancy, such devices shall be
provided.
-8-
EXCEPTIONS: 1. Such detectors need not be installed
when rooms have direct exit to the exterior of the
building.
2. Such detectors need not be installed in
systems specifically designed for smoke control.
3. Areas used for egress having a separate cir-
culating air system with a capacity less than 2000
CFM shall have automatic shut down except where this
system is specifically designed for smoke control.
(b) Smoke Detection. Smoke detection required by
Subsection (a) above shall be by a smoke detector installed in
the main circulating-air duct ahead of any fresh-air inlet or
installed in each room or space served by the return-air duct.
Activation of any detector shall cause the air-moving equipment
to automatically shut down.
SECTION 11.
Section 1507 of Ordinance No. 8907, as amended, is hereby
amended to read as follows:
"Sec. 1507. Required machinery rooms shall be of at least one-
hour fire-resistive construction provided with doors complying with
the Uniform Building Code, Section 3305(h) and having no other
openings that will permit the passage of escaping refrigerant to
other parts of the building.
There shall be no direct opening between a machinery room con-
taining a Group 2 refrigerant and a room or space in which there is
an open flame, spark-producing device or heating surface hotter than
800° F. A machinery room containing Group 2 refrigerants shall have
at least two means of egress located at least one-fifth the perime-
ter of the room apart. Exit doors shall be not less than 3 feet by 6
feet 8 inches.
Machinery rooms containing Group 1 refrigerants shall have at
least one exit door not less than 3 feet by 6 feet 8 inches.
A machinery room door shall open in the direction of egress.
feet.
A machinery room shall have an area of not less than 50 square
An unobstructed working space not less than 2 feet 6 inches in
width and not less than 7 feet in height shall be provided around
two adjacent sides of all moving machinery in a machinery room."
-9-
SECTION 12.
Section 1508 of Ordinance No. 8907, as amended, is hereby
amended to read as follows:
"Sec. 1508. Machinery rooms shall be provided with means of
ventilation to the outside of the building. Such ventilation shall
be either of the following:
1. A separate and individual exhaust system of ventilation
serving no other area and having the capacity to provide a complete
change of air in such room at least once every five minutes and dis-
charge to the outside of the building at a location not less than 20
feet from any exterior door, window or ventilation air inlet in any
building. Provisions shall be made for the supply of air to replace
that being exhausted. Each exhaust ventilation system shall be con-
trolled by a readily accessible emergency ventilation switch located
within 2 feet of the switch specified in Section 1509, and the
switch shall be labeled to comply with Section 1519.
2. M echanical ventilation or gravity ventilation openings to
the outside of the building shall be sized in accordance with Table
No. 15 based on accumulated horsepower in the rooms with refrigera-
tion units.
Gravity openings shall be so installed that approximately one-
half of the required area is located within 12 inches of the ceiling
and one-half of the required area is located within 12 inches of the
floor of the room. Every portion of the lower opening shall be hori-
zontal or slope downward from the opening in the machinery room to
the exterior of the building at or above the adjacent ground level.
-10-
SECTION 13.
Section 2003 of Ordinance No. 8907, as amended, is hereby
amended by revising Paragraph (k) thereof to ,read as follows:
"(k) Performance Test. Upon completion and before final
approval of the installation of a ventilation system serving commer-
cial food heat-processing equipment, a performance test may be
required to verify the rate of airflow and proper operation as
specified in this chapter. The permitee shall furnish the necessary
test equipment and devices required to perform the tests.°'
SECTION 14.
Section 2600 of Ordinance No. 8907, as amended, is hereby
amended to read as follows:
"Sec. 2600. ( a) Cross References. See U. B. C. Standard No. 43-7
and Chapter 43 of the Building Code for the construction and instal-
lation of duct openings in walls and ceilings. U.B.C. Standard
No. 43-7 is reprinted in Appendix "A". Fire dampers shall not be
located in a combustion-air duct or opening; see Uniform Mechanical
Code Section 602(b). Conditioned supply- and circulating-air ducts
or plenums may pass through the wall, floor or ceiling separating a
Group R, Division 3, from a Group M Occupancy without a fire damper,
provided all such ducts and plenums within the Group M Occupancy are
constructed of steel having a thickness of not less than 0.019 inch
(No. 26 galvanized sheet gage) and have no openings into the Group M
Occupancy; see Building Code Section 503.
(b) Access Openings. Suitable openings with tightly fitted
covers shall be provided to make fire dampers accessible for inspec-
tion and shall be large enough to permit maintenance and resetting
of the damper. When a fire damper is installed in an air duct, a
tight-fitting hinged or sliding access door shall be provided on the
duct and the door shall comply with all of the following require-
ments.
1. The door shall be constructed of metal which is equal to
or greater in thickness than the duct and of the same
material.
2. Each access door shall have a label with letters not less
than 1/2-inch in height reading "FIRE DAMPER."
3. No external duct insulation shall conceal a fire damper
access door unless there is a label attached to the
insulation indicating the exact location of the door.
(c) Freedom from Interference. Fire dampers shall be installed
in a manner to ensure positive closing. Interior insulation and
-12-
acoustical linings shall be placed so as not to interfere with posi-
tive closing of the fire damper.
(d ) Temperature Classification of Fusible Links. Fusible links
shall be classified in accordance with U.M.C. Standard No. 10-4.
Fusible link-actuated fire dampers shall be equipped with listed
fusible links having 165° F. temperature classification and listed
to sustain the design load.
EXCEPTIONS: 1. Fire dampers serving duct openings in a
warm-air furnace room or enclosure may be equipped with
links having a high-temperature classification.
2. Fusible links with a temperature rating classification
higher than ordinary may be used in locations approved by
the building official.
SECTION 15.
This ordinance shall be cumulative of all provisions of
ordinances and of the Code of the City of Fort Worth, Texas (196 4),
as amended, except where the provisions of this ordinance are in
direct conflict with the provisions of such ordinances and such
Code, in which event conflicting provisions of such ordinances and
such Code are hereby repealed.
SECTION 16.
It is hereby declared to be the intention of the City Council
that the sections, paragraphs, sentences, clauses and phrases of
this ordinance are severable, and if any phrase, clause, sentence,
paragraph or section of this ordinance shall be declared unconstitu-
tional by the valid judgment or decree of any court of competent
jurisdiction, such unconstitutionality shall not affect any of the
remaining phrases, clauses, sentences, paragraphs and sections of
this ordinance, since the same would have been enacted by the City
-13-
Council without the incorporation in this ordinance of any such
unconstitutional phrase, clause, sentence, paragraph or section.
SECTION 17.
Any person, firm or corporation who violates, disobeys, omits,
neglects or refuses to comply with or who resists the enforcement of
any of the provisions of this ordinance involving fire safety or
public health and sanitation shall be fined not more than One
Thousand Dollars ($1,000) for each offense and shall be fined not
more than Two Hundred Dollars ($200.00) for all other violations of
this ordinance. Each day that a violation is permitted to exist
shall constitute a separate offense.
SECTION 18.
All rights and remedies of the City of Fort Worth, Texas, are
expressly saved as to any and all violations of the provisions of
Ordinance No. 8907 or any other ordinances affecting heating, venti-
lation, air conditioning or refrigeration which have accrued at the
time of the effective date of this ordinance; and, as to such
accrued violations and all pending litigation, both civil and
criminal, whether pending in court or not, under such ordinances,
same shall not be affected by this ordinance but may be prosecuted
until final disposition by the courts.
SECTION 19.
The C ity Secretary of the C ity of Fort Worth, Texas , is hereby
authorized to publish this ordinance in pamphlet form for general
distribution among the public, and the operative provisions of this
ordinance as so published shall be admissible in evidence in all
-14-
courts without further proof than the production thereof, as pro-
vided in Chapter XXV, Section 3, of the Charter of the City of Fort
Worth, Texas.
SECTION 20.
The City Secretary of the City of Fort Worth is hereby directed
to engross and enroll this ordinance by copying the caption and
Sections 17, 21 and 22 in the minutes of the City Council and by
filing the ordinance in the ordinance records of the City.
SECTION 21.
The City Secretary of the City of Fort Worth, Texas, is hereby
directed to publish the caption and Sections 17, 21 and 22 of this
ordinance for two (2) days in the official newspaper of the City of
Fort Worth, Texas, as authorized by Art. 1176b-1, Revised Civil
Statutes of Texas.
SECTION 22.
This ordinance shall be in full force and effect from and
after its passage and publication as required by law, and it is so
ordained.
APPROVED AS TO FORM AND LEGALITY:
City Attorney
Date: b --Z-`~ -$ ~
ADOPTED:
EFFECTIVE:
-15-
Chapter 15 of Ordinance No. 8907, as amended, is hereby amended
by adding Table 15, which table shall read as follows:
TABLE NO. 15
MINIMUM AIR DUCT NET AREAS AND OPENINGS
MECHANICAL
DISCHARGE
HORSEPOWERI OF AIR, cfm
MECHANICAL
EXHAUST
DUCT AREA
(SQUARE FEET)
AREA OF GRAVITY
OPENINGS TO
THE OUTSIDE OF
THE BUILDING
(SQUARE FEET)
6 150 1/4 4
16 250 1/3 6
33 400 1/2 10
50 550 2/3 12-1/2
66 680 2/3 14
83 800 1 15
100 900 1 17
133 1,100 1-1/4 20
166 1,275 1-1/4 22
200 1,450 1-1/2 24
233 1,630 1-1/2 26
266 1,800 2 28
300 1,950 2 30
333 2, 050 2 31
416 2,250 2-1/4 33
500 2,500 2-1/4 37
583 2,700 2-1/4 38
667 2,900 2-1/4 40
833 3,300 2-1/2 43
1,OOD 3,700 3 48
1,333 4,600 3-3/4 55
1,667 5,500 4-1/2 62
2,000 6,300 5 68
2,333 7,200 5-1/2 74
2,667 8,000 5-3/4 80
3,000 8,700 6-1/4 85
3,333 9,500 6-1/2 90
_ 4,000 10,900 7 100
4,667 12,200 7-1/2 109
5,333 13,300 7-3/4 118
6,000 14,300 8 125
6,667 15,200 8-1/4 130
8,333 17,000 8-3/4 140
10,000 18,200 9 145
11,667 19,400 9-1/4 150
13,333 20,500 9-1/2 155
15,000 21,500 9-3/4 160
for greater
1Table assumes 3 pounds of refrigerant per horsepower. Systems uti-
lizing a different charge weight shall be corrected accordingly.
-11-
~~~~-=
MASTER FILE+L ~ ~it~ ®f ' 1~®9°t ~®~°t~, ~~.~~~
At; CaUNTING•2 ,~ ~j
TRANSPORTATfONIP_UBLIG,yy- ®R~~~~®~ ~~~ ~®- " ~~~~ ~®~~~~~~~~~®~
N 4TER ADMIR
UEYELUPMEN
DATE • ~ NUMBER CE suB~E~~CHANICAL CODE AMENDMENT PAGE
'6'/24/86 **G-6712 REQUEST , at 1 _
RECOMMENDATION
It is recommended that the City Council amend the Mechanical Code of the City of
Fort Worth as provided below.
DISCUSSION
The Mechanical Code of the City of Fort Worth (Ordinance No. 8907, as amended)
regulates the installation of heating, ventilation, air conditioning, and refri-
yeration (HVACR) systems.
The Mechanical Code is modeled from the Uniform Mechanical Code published by the
International Conference of Building Officials (ICBO). Ordinance No. 8907
adopted the 1982 edition of the Uniform Mechanical Code with certain local amend-
ments. The U.M.C. is updated every three years, and the Mechanical Board with
the City staff reviews each new edition.
The 1985 edition of the U.M.C. has been reviewed to determine what changes should
be incorporated into the Fort Worth Mechanical Code. For the most part, the
changes are editorial but some changes involve new materials and products being
anufactured as high energy efficient equipment. To keep the Fort Worth Code up
o date with the new products, some of the 1985 U.M.C. changes are necessary.
City staff recommends that these changes be incorporated into the Mechanical Code
by amending Ordinance No. 8907 rather than adopting the 1985 U.M.C.
The Mechanical Board of Appeals has reviewed these changes and recommends that
hey be adopted.
AI•kcq
APPROVED BY
c~TY cou~c~~
,~E1N ~4 i~
~~~~
city secretary of tYae
Ci.y of pout Worth, Taxa~I
SUBMITTED FOR IHG /~ ~`
CITY MANAGER'S
a
~~ DISPOSITION BY COUNCIL.
APPR
VED PROCESSED BY
OFFICE BY ~ ~ ;
/ ^
O
ORIGINATING v [ OTHER (DESCRIBE)
DEPARTMENT HEAD: Joe Bi 1 a1"di CITY SECRETARY
FOR ADDITIONAL INFORMATIQN Hansen 8033
K ~~Qp~e~ QrdIt1811C6 ~0^ ~~,
DATE
CONTACT