CONTRACTOR'S BONDING CO. SPECIFICATIONS
4029
CONSTRUCTION'S COPY CONTRACT DOCUMENTS
CLIENT DEPARTMENT FOR
VILLAGE CREEK DRAINAGE BASIN
CONTRACT LXIX (69) - CONTRACT 1
D.O.E. No. 4157, File No. 15308
Sanitary Sewer Main M-257R & M-503R, Sanitary Sewer
Laterals L-6313, L-6319, L-6322 & Sun Valley Drive, &
8" Water Line °
SEWER PROJECT No. PS58-070580176170
WATER PROJECT No. PW53-060530177980
IN
THE CITY OF FORT WORTH,TEXAS 2005 �,
MIKE MONCRIEF CHARLES BOSWELL
MAYOR CITY MANAGER
ROBERT D.GOODE,P.E.
DIRECTOR OF TRANSPORTATION
AND PUBLIC WORKS DEPARTMENT
S.FRANK CRUMB,P.E.
ACTING DIRECTOR OF WATER DEPARTMENT
A.DOUGLAS RADEMAKER,P.E. 4vaur
% h�
DIRECTOR OF ENGINEERING DEPARTMENT *��
Prepared by: A LUNSWI
•.e................q...�
84992
TranSystems Corporation Consultants
500 West Seventh St.,Suite 600 �`s ' °°" �� •
Fort Worth,Texas 76102Clff
05
WWW
X , .
DirectoryHome I Council Agenda I M&C I Employee
Print M&C
COUNCIL ACTION: Approved on 9/20/2005
DATE: 9/20/2005 REFERENCE NO.: C-21010 LOG NAME: 30DRAINAGE 69
CODE: C TYPE: NON-CONSENT PUBLIC HEARING: NO
SUBJECT: Authorize Execution of Contract with William J. Schultz, Inc., d/b/a Circle "C" Construction
Company, for Village Creek Drainage Basin Contract LXIX (69) - Contract 1
RECOMMENDATION:
It is recommended that the City Council authorize the City Manager to execute a contract with William J.
Schultz, Inc., d/b/a Circle "C" Construction Company in the amount of$2,958,285.00 for construction of
Village Creek Drainage Basin Contract LXIX (69)- Contract 1.
DISCUSSION:
On January 20, 2004, (M&C C-19937) the City Council authorized the City Manager to execute an
engineering agreement with TransSystems Corporation Consultants for Sanitary Sewer Rehabilitation
Contract LXIX (69) Village Creek Drainage Basin. This project will provide additional capacity to the present
and future growth in the rapidly developing Village Creek Drainage Basin.
Under this contract, Sanitary Sewer Main 257 between Vista Farley and Kay Street, Sanitary Sewer Main
503 on Kay Drive, Sanitary Sewer Lateral 6313, 6319 and 6322 will also be replaced. This project includes
approximately 3303 linear feet of 54-inch sanitary sewer, 2277 linear feet of 8-inch sanitary sewer, 29
manholes, two junction boxes and nine gate valves will be installed. This contract also includes new 2457
linear feet of 8-inch water line on Kay Drive between Sun Valley Drive and David Strickland Road.
After the proposed improvements are complete, the impacted streets will be repaired with permanent
asphalt pavement and concrete pavement as shown on the plans.
This project was advertised on May 26 and June 2, 2005. On June 30, 2005, the following bids were
received:
Bidder Amount
William J. Schultz, Inc. d/b/a $2,958,285.00
Circle "C" Construction Company
S. J. Louis Construction of Texas, Ltd. $2,971,691.53
Oscar Renda Contracting, Inc. $3,012,769.00
Jackson Construction, Ltd. $3,442,142.00
Conaster Construction TX, L.P. $3,454,096.00
North Texas Contracting $3,516,457.00
Time of Contract is 120 Calendar Days.
William J. Schultz, Inc. d/b/a Circle "C" Construction Company is in compliance with the City's M/WBE
Ordinance by committing to 21% M/WBE participation. The City's goal on this project is 21%.
This project is located in COUNCIL DISTRICT 5, Mapsco 93 C, L&Q, 80 LM &N, 78Z and 79 x & Z.
Funding in the amount of$207,079 is included for associated water and sewer construction survey and
inspection requirements (sewer$197,855; water$9,224) and contingency funding requirement is $88,748
(sewer$84,795; water$3,953).
FISCAL INFORMATION/CERTIFICATION:
The Finance Director certifies that funds will be available in the current capital budgets, as appropriated, of
the Sewer and Water Commercial Paper Fund.
TO Fund/Account/Centers FROM Fund/Account/Centers
PS46. 541200 070460140350 $2,826_501.00
501.00
PW77 541200 060770157380 $131,784.00
Submitted for City Mananees_Office by: Marc Ott (8476)
Originating Department Head: A. Douglas Rademaker (6157)
Additional Information Contact: A. Douglas Rademaker (6157)
ATTACHMENTS
CITY OF FORT WORTH
DEPARTMENT OF ENGINEERING
ADDENDUM NO. 1
TO THE PLANS, SPECIFICATIONS AND CONTRACT DOCUMENTS FOR
SANITARY SEWER MAIN REHABILITATION
(Village Creek Drainage Basin Contract LXIX(69)—Contract 1)
D.O.E. NO. 4157
SEWER PROJECT NO. PS58-070580176170
WATER PROJECT NO.PW53-060530177980
BID RECEIPT DATE: 1:30 PM,June 30,2005
ISSUED: June 28,2005
This Addendum No. 1 forms a part of the Contract Documents referenced above and modifies the
s Original Contract Documents and Plans. Acknowledge receipt of this Addendum in the space
provided below, in the revised proposal (page B1-21R) and acknowledge receipt on the outer
envelope of your bid. Failure to acknowledge receipt of this Addendum could subject the bidder to
disqualification.
The Plans, Specification and Contract Documents for SANITARY SEWER MAIN
REHABILITATION, are hereby revised by Addendum No. 1 as follows:
l 1. Delete Part B -Proposal in its entirety and replace with the attached Part B—Proposal
2. Delete Part DA—Additional Special Conditions in its entirety and replace with the attached
Part DA—Additional Special Conditions. (Revised DA items have highlighted titles)
3. The following is provided for sheets 33 through 35 as clarifications:
- Typical Sanitary Sewer Manhole(5' diameter)
The Typical Sanitary Sewer Manhole shall include the pipe placed through the structure as
shown in sheet 33. A 36" opening shall be formed on top of the pipe and centered under the
riser. A neoprene waterstop shall be keyed between the base and riser section.
For fiberglass mortar pipe sewers installations, a fiberglass tee base shall be used as shown
on sheet 33. The riser material shall be fiberglass, or reinforced concrete coated with DA-
121 (T-Lock) or DA-128 (Raven Lining System). The entire structure shall have a corrosion
resistant surface.
For lined reinforced concrete pipe installations, the lined pipe shall be placed though the
manhole, requiring a straight joint or fitting depending on the change of alignment. A 36"
opening shall be formed or cut then coated a corrosive protection material approved by the
Engineer. The riser shall be placed on the concrete base as shown on sheet 33. The riser
Addendum No.I 1 of 2
G:1FVWW05%Sp=\Addmd=\W1 Addend Ube
material shall be fiberglass or reinforced concrete coated with DA-121 (T-Lock) or DA-128
(Raven Lining System). The entire structure shall have a corrosion resistant surface.
- Standard 5' Diameter Manhole
The Standard 5' Diameter Manhole shall be constructed as shown in Figure 103 with a
coatings as describe in DA-121 (T-Lock) or DA-128 (Raven Lining System). These
manholes are located at M-257R Station 19+52 and 95+19.
- Structure 1 and Structure 2
Structure 1 on sheet 34 and Structure 2 on sheet 35 shall have a coating as described in DA-
121 (T-Lock) or DA-128 (Raven Lining System).
r -Standard 4' Manholes
Standard 4' Manholes shall be coated as specified in the plans.
4. The embedment and backfill standard for this project is the attached Figure A.
All other provisions of the addendums, plans, specifications and contract documents for the project
` which are not expressly amended herein shall remain in full force and effect.
Failure to return a signed copy of the addendum with the proposal shall be grounds for rendering the
bid non-responsive. A signed copy of this'addendum shall be placed into the proposal at the time of
bid submittal.
RECEIPT ACKNOWLEDGED: A.Douglas Rademaker,E4,Director
��la
_ By: _
4- Trice,P.E/, Assistant Director
Addendum No.1 2 of 2
G:1FW¢TO¢5914P=Addeadb®�EBI Added Ldx
PART DA - ADDITIONAL SPECIAL CONDITIONS
DA-1 AWARD OF CONTRACT FOR PROJECTS WITH MULTIPLE UNITS..............5
DA-2 PIPELINE REHABILITATION CURED-IN-PLACE PIPE (OMITTED)............... 5
DA-3 PIPE ENLARGEMENT SYSTEM (OMITTED).........................................................5
DA4 FOLD AND FORM PIPE(OMITTED) ........................................................................ 5
DA-5 SLIPLINING(OMITTED).............................................................................................5
DA-6 PIPE INSTALLED BY OTHER THAN OPEN CUT..................................................5
DA-7 TYPE OF CASING PIPE................................................................................................8
DA-8 SERVICE LINE POINT REPAIR/CLEANOUT REPAIR.......... ............................9
DA 9 PROTECTIVE MANHOLE COATING FOR:CORROSION PROTECTION:
(CIMITTEI )..................... ............................................................................................................. 12
DA-10 MANHOLE REHABILITATION(OMITTED) ........................................................ 12
DA-11 SURFACE PREPARATION FOR MANHOLE REHABILITATION(OMITTED)
12
IDA'12 INTERIOR MANHOLE COATING,-MICROSILICATE MORTAR SYSTEM''
(OMITTED . . ....,....... 12
DA 13 INTERIOR 1VIANHOLE COATING QUADEX S 'STEM MITT
(OED) ,.. ...,.. 12
])A 14 INTERIOR MANHOLE C(DATING .SPRAT WALL SYSTEM(ONUTTETD) .., 12
P*,15 IN. MANHOLE COATING 'MAVEN LINING SYSTEM(OMITTED . 12
DA 17 INTERIOR MANHOLE CQATINO-STRONG-SEAM, SYSTEM(OMITTI)).,.. 12
DA-18 RIGID FIBERGLASS MANHOLE LINERS(OMITTED) ................. 12
DA-19 FVC LINED CONCRETE WALL RECONSTRUCTION (OMITTED)................ 12
DA-20 PRESSURE GROUTING (OMITTED)...................................................................... 1.2
DA-21 VACUUM TESTING OF REHABILITATED MANHOLES................................... 12
DA-22 FIBERGLASS MANHOLES (OMITTED)................................................................. 15
DA-23 LOCATION AND EXPOSURE OF MANHOLES AND WATER VALVES .,.....,, 15
DA-24 REPLACEMENT OF CONCRETE CURB AND GUTTER......... .......................... 16
DA-25 REPLACEMENT OF 6" CONCRETE DRIVEWAYS............................................. 16
DA-26 REPLACEMENT OF H.M.A.C.PAVEMENT AND BASE..................................... 16
DA-27 GRADED CRUSHED STONES................................................................................... 17
DA-28 WEDGE MILLING 2" TO 0" DEPTH 5.0'WIDE (OMITTED)............................. 17
DA-29 BUTT JOINTS-MILLED (OMITTED)............................................................. ...... 17
DA-30 2" H.M.A.C.SURFACE COURSE (TYPE "D" MIX).............................................. 17
DA-31 REPLACEMENT OF 7" CONCRETE VALLEY GUTTER(OMITTED)....,....,,, 18
DA-32 NEW 7" CONCRETE VALLEY GUTTER(OMITTED)........................................ 18
DA-33 NEW 4" STANDARD WHEELCHAIR RAMP(OMITTED).................................. 18
DA-34 8" PAVEMENT PULVERIZATION(OMITTED).................................................... 18
DA-35 REINFORCED CONCRETE PAVEMENT OR BASE (UTILITY CUT)
(OMITTED) ................................................................................................................................... 18
DA-36 RAISED PAVEMENT MARKERS (OMITTED)...................................................... 18
DA-37 POTENTIALLY PETROLEUM CONTAMINATED MATERIAL HANDLING
(OMITTED)................................................................................................................................... 18
DA-38 LOADING,TRANSPORTATION,AND DISPOSAL OF CONTAMINATED SOIL
(OMITTED) ............................................... .......... ....................................................................... 18
DA-39 ROCK RIPRAP- GROUT-FILTER FABRIC (OMITTED).................................. 18
s DA-40 CONCRETE RIPRAP................................................................................................... 18
11/02/04 Revised ASC-1 R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
DA-41 CONCRETE CYLINDER PIPE AND FITTINGS (OMITTED).............................. 19
DA-42 CONCRETE PIPE FITTINGS AND SPECIALS (OMITTED) ............................... 19
DA-43 UNCLASSIFIED STREET EXCAVATION .............................................................. 19
DA-44 6"PERFORATED PIPE SUBDRAIN (OMITTED).................................................. 19
DA-45 REPLACEMENT OF 4" CONCRETE SIDEWALKS (OMITTED)....................... 19
DA46 RECOMMENDED SEQUENCE OF CONSTRUCTION......................................... 19
DA47 PAVEMENT REPAIR IN PARKING AREA(OMITTED)......................................20
DA-48 EASEMENTS AND PERMITS....................................................................................20
DA-49 HIGHWAY REQUIREMENTS (OMITTED)............................................................20
DA-50 CONCRETE ENCASEMENT .....................................................................................20
DA-51 CONNECTION TO EXISTING STRUCTURES.......................................................20
DA-52 TURBO METER WITH VAULT AND BYPASS INSTALLATION (OMITTED)21
DA-53 OPEN FIRE LINE INSTALLATIONS (OMITTED)................................................21
DA-54 WATER SAMPLE STATION (OMITTED)...............................................................21
DA-55 CURB ON CONCRETE PAVEMENT (OMITTED).................................................21
DA-56 SHOP DRAWINGS.......................................................................................................21
DA-57 COST BREAKDOWN ..................................................................................................22
DA-58 STANDARD STREET SPECIFICATIONS H.M.A.C.OVERLAY.........................22
DA-59 H.M.A.C.MORE THAN 9 INCHES DEEP(OMITTED).........................................22
DA-60 ASPHALT DRIVEWAY REPAIR...............................................................................22
DA-61 TOP SOIL........................................................................................................................22
DA-62 WATER METER AND METER BOX RELOCATION AND ADJUSTMENT.....22
DA-63 BID QUANTITIES........................................................................................................22
DA-64 WORK IN HIGHWAY RIGHT OF WAY (OMITTED)...........................................23
DA-65 CRUSHED LIMESTONE (FLEX-BASE) .................................................................23
DA-66 OPTION TO RENEW(OMITTED)............................................................................23
DA-67 NON-EXCLUSIVE CONTRACT (OMITTED).........................................................23
DA-68 CONCRETE VALLEY GUTTER(OMITTED)........................................................23
DA-69 TRAFFIC BUTTONS (OMITTED).............................................................................23
DA-70 PAVEMENT STRIPING (OMITTED).......................................................................23
DA-71 H.M.A.C.TESTING PROCEDURES .........................................................................23
DA-72 SPECIFICATION REFERENCES..............................................................................24
DA-73 RELOCATION OF SPRINKLER SYSTEM BACK-FLOW
PREVENTER/CONTROL VALVE AND BOX(OMITTED)..................................................24
DA-74 RESILIENT-SEATED GATE VALVES.....................................................................24
DA-75 EMERGENCY SITUATION,JOB MOVE-IN...........................................................24
DA-76 1 Y2"&2"COPPER SERVICES (OMITTED)...........................................................24
DA-77 SCOPE OF WORK(UTIL. CUT) (OMITTED).........................................................24
DA-78 CONTRACTOR'S RESPONSIBILTY (UTIL.CUT) (OMITTED).........................24
DA-79 CONTRACT TIME (UTIL.CUT) (OMITTED)........................................................24
DA-80 REQUIRED CREW PERSONNEL & EQUIPMENT (UTIL. CUT) (OMITTED) 24
DA-81 TIME ALLOWED FOR UTILITY CUTS (UTIL. CUT)(OMITTED)...................24
DA-82 LIQUIDATED DAMAGES (UTIL. CUT) (OMITTED)...........................................24
DA-83 PAVING REPAIR EDGES (UTIL. CUT)(OMITTED)............................................25
DA-84 TRENCH BACKFILL(UTIL. CUT) (OMITTED)....................................................25
11/02/04 Revised ASC-2R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
DA-85 CLEAN-UP(UTIL. CUT) (OMITTED)......................................................................25
DA-86 PROPERTY ACCESS(UTIL. CUT) (OMITTED)....................................................25
DA-87 SUBMISSION OF BIDS (UTIL. CUT)(OMITTED) ................................................25
DA-88 STANDARD BASE REPAIR FOR UNIT I(UTIL. CUT) (OMITTED)..................25
DA-89 CONCRETE BASE REPAIR FOR UNIT II& UNIT III(UTIL.CUT)(OMITTED)
25
DA-90 2"TO 9"H.M.A.C.PAVEMENT(UTIL.CUT) (OMITTED).................................25
DA-91 ADJUST WATER VALVE BOXES,MANHOLES,AND VAULTS(UTIL. CUT)
(OMITTED)...................................................................................................................................25
DA-92 MAINTENANCE BOND (UTIL.CUT) (OMITTED).................. 25
.............................
DA-93 BRICK PAVEMENT (UTIL. CUT) (OMITTED)...................................................... 25
DA-94 LIME STABILIZED SUBGRADE (UTIL. CUT)(OMITTED)...............................25
DA-95 CEMENT STABILIZED SUBGRADE (UTIL.CUT) (OMIITED).........................25
DA-96 REPAIR OF STORM DRAIN\STRUCTURES (UTIL. CUT) (OMITTED)..........25
DA-97 "QUICK-SET" CONCRETE (UTIL. CUT)(OMITTED)...........-.......................-25
DA-98 UTILITY ADJUSTMENT(UTIL.CUT)(OMITTED)............................................. 25
DA-99 STANDARD CONCRETE SIDEWALK AND WHEELCHAIR RAMPS (UTIL.
CUT)(OMITTED). .......................................... ............................................................................25
DA-100 LIMITS OF CONCRETE PAVEMENT REPAIR(UTIL. CUT)(OMITTED)..25
DA-101 CONCRETE CURB AND GUTTER(UTIL. CUT)(OMITTED)........................25
DA-102 PAYMENT(UTIL. CUT) (OMUTTED).................................................................25
DA-103 DEHOLES (MISC.EXT.)(OMITTED)..................................................................25
DA-104 CONSTRUCTION LIMITATIONS (MISC.EXT,)(OMMITTED)....................25
DA-105 PRESSURE CLEANING AND TESTING(MISC.EXT,) (OMITTED).............25
DA-106 BID QUANTITIES (MISC.EXT.)(OMITTED)....................................................25
DA-107 LIFE OF CONTRACT(MISC.EXT.) (OMITTED).............................................25
DA-108 FLOWABLE FILL(MISC.EXT.) (OMITTED)....................................................26
DA-109 BRICK PAVEMENT REPAIR(MISC.REPL.) (OMITTED) .............................26
DA-110 DETERMINATION AND INITIATION OF WORK(MISC.REPL,)
(OMITTED)...................................................................................................................................26
DA-111 WORK ORDER COMPLETION TIME (MISC.REPL.)(OMITTED)..............26
DA-112 MOVE IN CHARGES (MISC.REPL.)(OMITTED)............................................26
DA-113 PROJECT SIGNS (MISC.REPL,) (OMITTED)...................................................26
DA-114 LIQUIDATED DAMAGES (MISC,REPL.)(OMITTED) ...................................26
DA-115 TRENCH SAFETY SYSTEM DESIGN (MISC. REPL.) (OMITTED)...............26
DA-116 FIELD OFFICE (OMITTED)..................................................................................26
DA-117 TRAFFIC CONTROL PLAN (OMITTED)............................................................26
DA-118 COORDINATION OF WORK WITH.CONTRACTOR FOR OTHER UNITS
(OMITTED)...................................................................................................................................26
DA 11 S
FIB LASS SE ?4�ER.FIPE r'GRA IT` ............................................................26
DA-120 HINGED MANHOLE...............................................................................................29
DA 121 T-L ................... ................... 30
DA 122 PASSIVE ODOR CONTROL FOR VENTING PIPE..................... 36
......................
DA-123 STOP LOGS...............................................................................................................39
I?�`I24 REINFORCED CONCRETE PIPE......................................................... ................43
11/02/04 Revised ASC-3R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
DA-125 MYERS PROPERTY RESTORATION .................................................................44
DA-126 FILTER FABRIC.......................................................................................................44
DA-127 FLOWABLE FILL. .. .45
......... ............ ....................... ............. ............................ .......
DA-128 NEW,STRUCTURE INTERIOR MANHOLE COATING `;:RAVEN INNING
SYSTEM 45
11/02/04 Revised ASC-4R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
DA-1 AWARD OF CONTRACT FOR PROJECTS WITH MULTIPLE UNITS
The City reserves the right to abandon without obligation to the contractor, any part of the project,
or the entire project, at any time before the contractor begins any construction work authorized by
the City. Award, if made, shall be to the lowest responsible bidder.
The following shall apply for contract documents with multiple units of work. Each unit represents
a separate project, each with an individual M/WBE specification and proposal section. The
proposal sections are arranged to allow prospective bidders to submit bids on one unit, some of
the units, or all of the units. Award of contract(s), if made, shall be to the lowest responsible
bidder for each individual unit. If a contractor is the low bidder on two units or more, a single set
of contract documents consisting of all applicable units will be created and one single award of
contract shall be made. The Contractor shall comply with the City's M/WBE Ordinance for the
applicable unit or combination of units and shall submit monthly MIWBE reports for the applicable
unit or combination of units.
Construction time on all units will run concurrently. For situations involving approved contracts
with multiple units, the total allowable construction completion time period for all the units shall be
the same as the unit with the longest construction time period.
DA-2 PIPELINE REHABILITATION CURED-IN-PLACE PIPE (OMITTED)
DA-3 PIPE ENLARGEMENT SYSTEM (OMITTED)
DA-4 FOLD AND FORM PIPE (OMITTED)
DA-5 SLIPLINING (OMITTED)
DA-6 PIPE INSTALLED BY OTHER THAN OPEN CUT
C. GENERAL:
1. Furnish materials and necessary accessories, with strengths, thickness, coatings,
and fittings indicated, specified and/or necessary to complete the work.
2. All excavation shalt provide an open area conforming to the outside diameter of
the casing and/or carrier conduit. The excavation shall be to an alignment and
grade which will allow the carrier conduit to be installed to proper line and grade as
shown on the Plans and as established in the Specifications.
3. Work shall be performed in accordance with the requirements of the City of Fort
Worth Water Department, the Texas Department of Transportation, or railroad
company, as applicable.
d. MATERIALS:
1. Casing Pipe: Casing pipe shall be steel conforming to ANSI B36.10 and the
following:
a. Field Strength: 35,000 psi minimum.
11/02/04 Revised ASC-5R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
b. Wall thickness: 0.312 in, minimum (0.5 for railroad crossings).
C. Diameter: As shown on the drawings (minimum size requirements).
d. Joints: Continuous circumferential weld in accordance with AWS D1.1.
2. Carrier Pipe in Casing: Carrier pipe shall be as shown on drawings and as
specified in the General Contract Documents.
3. Sewer Pipe without Casing Pipe: Shall be minimum Class 51 ductile iron pipe, or
as designated on the plans.
4. Grout: Grout shall be Portland Cement grout of min. 2000 psi compressive
strength at 28 days. Proportioned not less than 1 cu. ft, of cement to 3 cu. ft. of
fine sand with sufficient water added to provide a free flowing thick slurry.
e. EXECUTION
1. Where sewer pipe is required to be installed under railroad embankments or under
highways, streets or other facilities in other than open cut, construction shall be
performed in such a manner so as to not interfere with the operation of the
railroad, street, highway, or other facility, and so as not to weaken or damage any
embankment or structure. During construction operations, barricades and lights to
safeguard traffic and pedestrians shall be furnished and maintained, until such
time as the backfill has been completed and then shall be removed from the site.
2. Pits and Trenches:
a. If the grade of the pipe at the end is below the ground surface, suitable pits
or trenches shall be excavated for the purpose of conducting the jacking or
tunneling operations and for placing end joints of the pipe. Wherever end
trenches are cut in the sides of the embankment or beyond it, such work
shall be sheeted securely and braced in a manner to prevent earth from
caving in.
b. The location of the pit shall meet the approval of the Engineer.
C. The pits of trenches excavated to facilitate these operations shall be
backfilled immediately after the casing and carrier pipe installation has
been completed.
3. Boring and Jacking Steel Casing Pipe: Steel casing pipe shall be installed by
boring hole with the earth auger and simultaneously jacking pipe into place.
a. The boring shall proceed from a pit provided for the boring equipment and
t workmen. The holes are to be bored mechanically. The boring shall be
done using a pilot hole. By this method an approximate 2-inch hole shall
be bored the entire length of the crossing and shall be checked for line and
grade on the opposite end of the bore from the work pit. This pilot hole
shall serve as the centerline of the larger diameter hole to be bored. Other
11/02/04 Revised ASC-6R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
methods of maintaining line and grade on the casing may be approved if
acceptable to the Engineer. Excavated material shall be placed near the
top of the working pit and disposed of as required. The use of water or
other fluids in connection with the boring operation will be permitted only to
the extent required to lubricate cuttings. Jetting or sluicing will not be
permitted.
b. In unconsolidated soil formations, a gel-forming colloidal drilling fluid
consisting of at least 10 percent of high grade carefully processed
bentonite may be used to consolidate cuttings of the bit, seal the walls of
the hole, and furnish lubrication for subsequent removal of cuttings and
installation of the pipe immediately thereafter.
C. Allowable variation from the line and grade shall be as specified under
paragraph A.2. All voids between bore and outside of casing shall be
pressure grouted.
4. Installation of Carrier Pipe in Casing:
a. Sanitary sewer pipe located within the encasement pipe shall be supported
by "skids" or "bands" to prevent the pipe and bells from snagging on the
inside of the casing, and to keep the installed line from resting on the bells.
b. All skids shall be treated with a wood preservative. Skids should extend for
the full length of the pipe with the exception of the bell area and spigot area
necessary for assembly unless otherwise specified.
C. The Contractor shall prevent over-belting the pipe while installing it through
the casing. A method of restricting the movement between the assembled
bell and spigot where applicable shall be provided.
d. Af all bored, jacked, or tunneled installations, the annular space between
the carrier pipe and casing shall be filled with grout. Care must be taken
that not too much water is forced into the casing so as not to float the pipe.
The backfill material will not be required unless specified on the plans and
specified by the Engineer.
e. Closure of the casing after the pipe has been installed shall be plugged at
the ends of the casing as shown on the drawings or as required by the
Engineer.
5. Boring and Jacking Ductile Iron Pipe without Casing Pipe:
_. a. As indicated on drawings and as required and directed by the Engineer
sewer shall be constructed of bore and jacked ductile iron pipe.
b. When a casing pipe is not designated on the drawings, the contractor shall
provide a casing pipe if necessary to achieve line and grade. Casing pipe
shall be provided at no additional cost and shall be subsidiary to the cost
bid for installation By Other than Open Cut.
11/02104 Revised ASC-7R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
C. Bore and jack in accordance with paragraph C.3. above.
d. Short length of sewer consisting of a single pipe section may be installed
by jacking without a bore hole if permitted by the Engineer and in soft soil
layer. All voids outside of installed pipe shall be pressure grouted.
6. Tunneling: Where the characteristics of the soil, the size of the proposed pipe, or
the use of monolithic sewer would make the use of tunneling more satisfactory
than jacking or boring, or when shown on the plans, a tunneling method may be
used, with the approval of the Engineer or railroad/highway officials.
a. When tunneling is permitted, the lining of the tunnel shall be of sufficient
Strength of support the overburden. The Contractor shall submit the
proposed liner method to the Engineer for approval. The tunnel liner
design shall bear the seal of a licensed professional engineer in the State
t of Texas. Approval by the Engineer shall not relieve the Contractor of the
responsibility for the adequacy of the liner method.
b. The space between the tunnel liner and the limits of excavation shall be
pressure grouted or mud jacked.
C. Access holes for placing concrete shall be space at maximum intervals of
10 feet.
f. MEASUREMENT AND PAYMENT: Installation of pipe by other than open cut will be
measured by the linear foot of pipe, complete in place. Such measurement will be made
between the ends of the pipe along the central axis as installed. The work performed and
materials furnished as prescribed by this item will be paid for at the Contract Unit Price bid
per linear foot for Pipe Installed by Other Than Open Cut of the type, size, and class of
pipe specified as shown on plans. The furnishing of all materials, pipe, liner materials
required for installation, for all preparation, hauling and installing of same, and for all
labor, tools, equipment and incidentals necessary to complete the work, including
excavation, backfilling and disposal of surplus material shall be included in the Contract
Unit Price as shown in the Bid Proposal. Payment shall not include pavement
replacement, which if required, shall be paid separately.
DA-7 TYPE OF CASING PIPE
1. WATER:
The casing pipe for open cut and bored or tunneled section shall be AWWA C-200
Fabricated Electrically Welded Steel Water Pipe, and shall conform to the provisions of
E1-15, E1-5 and E1-9 in Material Specifications of General Contract Documents and
Specifications for Water Department Projects. The steel casing pipe shall be supplied as
follows:
A. For the inside and outside of casing pipe, coal-tar protective coating in accordance with
the requirements of Sec. 2.2 and related sections in AWWA C-203.
B. Touch-up after field welds shall provide coating equal to those specified above.
11/02104 Revised ASC-8R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
C. Minimum thickness for casing pipe used shall be 0.375 inch.
Casing Spacers (centering style)such as manufactured by Cascade Waterworks Manufacturing
Company, Advanced Products and Systems, Inc., or an approved equal shall be used on all non-
concrete pipes when installed in casing. Installation shall be as recommended by the
manufacturer.
2. SEWER:
Boring used on this project shall be in accordance with the material standard E1-15 and
Construction standard E2-15 as per Fig. 110 of the General Contract Documents.
3. PAYMENT:
Payment for all materials, labor, equipment, excavation, concrete grout, backfill, and
incidental work shall be included in the unit price bid per foot.
DA-8 SERVICE LINE POINT REPAIR! CLEANOUT REPAIR
A. GENERAL: The work covered by this item consists of furnishing all labor, material,
equipment, supervision, etc. necessary to construct a point repair on the portion of a
service line located within a utility easement, street right-of-way or on private property.
Point repairs on private property shall only be addressed after the Contractor has received
written permission from the property owner to do the work. A blank Right-of-Entry
Agreement form to be completed by the Contractor and the individual property owners is
included at the end of this section. The Contractor shall keep a record copy of all Right-
of-Entry forms obtained and have it on hand at all times during construction.
The street addresses and approximate location of service line repairs are shown in
Table_ and the Field Survey Forms in Attachment . It shall be the Contractors
responsibility to accurately field locate the exact point of repair.
B. MATERIALS:
The pipe replacement material shall be gasketed joint, gravity PVC sewer pipe (ASTM D-
3034, SDR 26) and have a minimum cell classification of 12454 A or B as defined in
ASTM D-1784. Installation shall be in strict compliance with the manufacturer,
recommendations and the Uni-Bell Plastic Pipe Association. The method of jointing the
ends of the replaced pipe with the existing pipe shall be water tight.
C. EXECUTION:
1. After the location of the point repair is determined, the Contractor shall excavate
and remove the damaged pipe and replace with new pipe. The minimum length of
pipe replaced shall be three (3) feet. All work shall be performed by a licensed
lup mber. Determine whether additional lengths of line beyond "minimum length"
criteria need replacement. Report need for additional replacement to City and
obtain approval before proceeding.
11/02/04 Revised ASC-9R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
2. The Contractor shall excavate, shape the bottom of the trench and place the
required pipe bedding so that the grade of the replaced pipe matches the existing
service line grade.
3. Numerous service line point repairs along with lateral line point repairs and
obstruction removals are located in areas which in many instances will require the
removal of existing landscaping, structures, sidewalks, driveways, etc. Items
removed or disturbed shall replaced or restored to original conditions or better.
4. Removal of Debris: Excess excavated material and debris are to be removed from
the work site daily. Cost of hauling excess excavation and debris is to be included
in the price bid for"Service Line Point Repair.
5. Roof and Yard Drains: At the locations indicated in Table of the Attachments.
The Contractor shall disconnect roof'and,yard drains from the sanitary sewer
service line. For yard drains, the Contractor shall excavate and remove the drain
from the yard and plug the line at the property line. For roof drains, the Contractor
shall remove the downspout from the drain line and plug the line to prevent inflow.
In addition, the Contractor shall install an elbow fitting at the bottom of the
downspout to direct runoff, away from the building, and a concrete splash pad to
prevent erosion.
6. Disconnected Service Lines: At the locations indicated in Table of
Attachments to the Special Contract Documents, the Contractor shall remove
the service line no longer in use by excavating at the property line and plugging
the service line.
7. Abandonment of Point Repair: If a pipe is exposed and found in good condition,
not requiring a point repair, notify City Engineer who will record abandonment of
point repair.
Backfill the excavation, replace pavement or sidewalk and repair and seed or sod
unpaved areas.
8. Cleanout Repair: The Contractor shall make appropriate repairs to cleanouts as
indicated in Table _and as shown on the PLANS. All cleanout repair work shall
be performed by a licensed plumber.
a. General
- This special condition describes the repair of sanitary sewer cleanouts
located on private property as designated on the III Elimination Repair
plans. Repair of the cleanouts shall consist of replacing defective cleanout
caps or installing new caps where none exist, such that inflow is eliminated.
There will be no repairs made to the existing cleanouts that require
excavation, other than what is required to expose the top of the cleanout so
that the new caps can be installed.
b. Materials
11/02/04 Revised ASC-1 OR Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
Replacement cleanout caps shall be Dal-Caps as manufactured by Dallas
Specialty & Mfg. Company, or equal. The rubber caps are held down by
stainless steel clamps.
c. Excavation
1) The Contractor shall submit shop drawings on all materials and
equipment to be installed.
2) The Contractor is responsible for obtaining right of entry from the
property owners prior to performing any work. Property owners
should be notified 48 hours in advance of any work on their property.
3) The Contractor shall restore any disturbed surface to its original or
better condition at no separate pay.
D. MEASUREMENT AND PAYMENT:
1. Payment for service line point repair shall be on a unit price basis for each repair
performed on all sizes of service fines for the respective depths. The minimum
length of service line point repair shall be three (3) feet. No separate pay if the
work is done within the limits of a service line reconnect as defined in Special
Condition, D-28, "Sanitary Sewer Services".
- 2. Measurements for extra length repair is on a linear foot basis for repairs in excess
of the minimum 3 foot replacement length.
_ 3. All pipe fittings, adapters, concrete collars, bedding, and removal and
replacements of grass sodding required shall be considered incidental to service
line point repair.
3. If no pay item is included for any work required to properly complete a service line
point repair as specified, the cost to perform said work, including any required
removal and replacement of materials, shall be considered incidental to the service
line point repair.
5. Depth of Bury is to be measured from Natural Ground Level to the Flow Line of the
Sanitary Sewer Service Line at the Point of Replacement. The minimum trench
width shall be 3'-0".
6. All excavation, backfill, removal and replacement of grass sodding and
landscaping, plugs, fittings, and splash pads shall be considered incidental to
removal of yard drains, disconnecting roof drains and plugging disconnected
service lines.
7. No separate payment will be made for the Contractor to obtain written permission
to enter private property.
8. Payment will be made for Abandonment of Point Repairs at the Contract Unit Price
for Excavation and Backfill Abandoned Point Repairs.
11/02/04 Revised ASC-11 R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
9. Payment shall be made at the Contract Unit Price for each sanitary sewer cleanout
successfully repaired. Payment shall be full compensation for all materials,
equipment, and labor required to perform the work.
DA 9 PROTECTIVE MANHOLE COATING FOR CORROSION PROTECTION:(OMITTED)
DA-10 MANHOLE REHABILITATION (OMITTED)
t, DA-11 SURFACE PREPARATION FOR MANHOLE REHABILITATION (OMITTED)
DA '2 INTERIOR MANHOLE COATING -MICROSILICATE MORTAR SYSTEM (OMITTED)
DA 1,3INTERIOR'MANHOLE COAT10 QUADEX SYSTEM(OMITTED)
DAALNTERIOR..MANHO, E COATING SPRAY WALL SYSTEM (OMITTED)
DA 95 INTERIOR MANHOLE COATING RAVEN'LINING SYSTEM (OMITTED)
DA 16''�NTERIOR�''MANHOLE,�"COATIN!G PERMACAST r5,:,,YS�EM��V17H k EI�OXY_ LINER
(OMITTMTf��'
"" DA 17 fNTERIOR MANHOLE COATING STRONG;SEAL SYSTEM(OMITTED)
DA-18 RIGID FIBERGLASS MANHOLE LINERS (OMITTED)
DA-19 PVC LINED CONCRETE WALL RECONSTRUCTION (OMITTED)
DA-20 PRESSURE GROUTING (OMITTED)
DA-21 VACUUM TESTING OF REHABILITATED MANHOLES
A. GENERAL
Scope. This section describes manhole testing to effectively confirm the watertight integrity of
existing manholes following structural ,infiltration and inflow related repairs and that the appearance
of the work is acceptable.
Description:
Infiltration may be observed in manhole defects at manhole walls, pipe seals or bench/trough areas.
Infiltration related repairs are intended to eliminate leakage of groundwater into manholes,
Inflow may be observed in manhole defects at manhole frames, covers,frame seals, grade
adjustments, grade adjustment seals, corbels, or walls. Inflow related repairs are intended to
eliminate sources of surface water entry that become active during rainfall events.
Structural repairs may be required when making 1/1 related manhole repairs, Structural repairs may
include defects in any manhole components but not displaying 1/1.
Testing, Observations and Guarantee Periods:
11/02/04 Revised ASC-12R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
The testing required shall be performed by the Contractor at locations designated by the Engineer
and documented to the satisfaction of the Engineer.
Any new or rehabilitated manholes that are observed to be leaking by the Engineer during periods
of high groundwater or during inflow conditions shall be subject to additional repairs, The Contractor
shall be responsible for all additional repairs required on these unsatisfactory manholes during the
guarantee period.
All manhole rehabilitation work shall be warranted to be free of defects and of good workmanship
for a minimum of three(3)years from the date of final acceptance of the project Any manhole
repairs completed by the Contractor which fail during the warranty period shall be repaired to the
satisfaction of the City at no additional cost to the City.
B. MATERIALS- Not specified.
C. EXECUTION
Infiltration Testing_
All interior coated manholes and all partial replacement manholes shall be observed (tested)by the
Contractor in the presence of the Engineer for sources of infiltration. Observations will be made
during high groundwater conditions,wherever possible.
Manholes shall be tested after installation with all connections(e)isting and/or proposed)in place.
Drop-connections and gas sealing connections shall be installed prior to testing. The lines entering
the manhole shall be temporarily plugged with the plugs braced to prevent them from being drawn
into the manhole. The plugs shall be installed in the lines beyond drop-connections, gas sealing
connections, etc. The test head shall be placed inside the frame at the top of the manhole(so that
the manhole frame seal is tested)and inflated in accordance with the manufacturer's
recommendations. A vacuum of 10 inches of mercury shall be drawn, and the vacuum pump will be
turned off. With the valve closed, the level of vacuum shall be read after the required test time. If
the drop in the level is less than 1-inch of mercury(final vacuum greater than 9-inches of mercury),
the manhole will have passed the vacuum test. After a successful test, the temporary plugs will be
removed. The required test time is determined from Table 1.
Table 1
MINIMUM TIME REQUIRED FOR A VACUUM DROP
OF 1" H9 (10"H9 -9"Hs)(SEC)
DEPTH OF M.H. 48-Inch Dia. 60-Inch Dia. 72-Inch Dia,
(FT.) Manhole Manhole Manhole
8 20 sec. 26 sec. 33 sec.
10 25 sec. 33 sec. 41 sec.
12 30 sec. 39 sec. 49 sec.
14 35 sec. 45 sec. 57 sec,
16 40 sec. 52 sec. 67 sec.
18 45 sec. 59 sec. 73 sec.
** T=5 sec. T=6.5 sec. T=8 sec.
11/02/04 Revised ASC-13R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
**For all Manholes over 18 feet in depth, add "T"seconds as shown for each respective diameter
for each two feet of additional depth of manhole to the time shown for that 18 foot depth. [Example:
A 30 (thirty)foot deep,48 (forty-eight)inch Manhole Total Test Time would be 75.0 seconds.
45.0+6(5.0)-75.0 seconds] (Values listed above are extrapolated from ASTM C924-85).
Manhole vacuum levels observed to drop greater than 1-inch of mercury(Final vacuum less than 9-
inches of mercury)will have failed the test and will require additional rehabilitation. The Contractor
shall make the necessary repairs to the already completed rehabilitation work at no additional
compensation. If the failure of the vacuum test is determined to be due to preexisting conditions not
on the manhole rehabilitation schedule for that manhole, this additional work may be authorized by
the Owner's Representative. After completion of the additional rehabilitation the manhole shall then
be re-tested as described above until a successful test is made. Only one payment for manhole
vacuum testing will be made on each manhole.
Vacuum testing is required on all manholes having interior rehabilitation.
Inflow Testing:
All partially rehabilitated manholes shall be dyed water tested unless the manhole has successfully
passed the vacuum test. Manholes shall be dyed water tested in the presence of the Engineer.
The dye test shall consist of applying a concentrated dye solution around the manhole frame. Dyed
water shall be applied for at least ten minutes.
Manholes observed to be actively leaking greater than one drip per five seconds will have failed the
test and will not be acceptable. Manholes failing the test will require additional rehabilitation by the
Contractor at no additional compensation.
Other Testing:
One (1) rehabilitated manhole will be randomly selected for further testing. A laboratory selected by
the City will take core samples of wall sections of manholes with wall coatings. Testing of the core
samples will be done to evaluate material thickness, compressive strength,flexural strength and
slant shear bond strength. The following are the minimum required strengths for cementitious and
non-cementitious wall coatings:
Compressive Strength. Compressive strength shall conform to ASTM C 495 and C 109 and shall
meet or exceed a minimum 28-day break of 4,000 psi.
Flexural Strength.Flexural strength shall conform to ASTM C 348 and shall meet or exceed a
minimum 28-daybreak of 1,200 psi.
Slant Shear Bond Strength. Slant shear bond strength shall conform to ASTM 882 modified and
shall meet or exceed a minimum 28-day break of 2,400 psi.
If the manhole tested fails to pass any of these requirements,another manhole shall be selected and
tested. If the second manhole fails,the City may,at its option,stop work until the Contractor can
provide assurance that testing requirements can be met.
Guarantee:
11/02/04 Revised ASC-14R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
Contractor shall warrant that the workmanship and materials are free from defects and that the
manholes are sealed from inflow and infiltration for a period of three (3)years from the date of final
acceptance of the project.
D. MEASUREMENT AND PAYMENT
Payment for manhole vacuum testing shall be made at the Contract Unit Price bid for each Manhole
Vacuum Test actually performed and passed and the appearance of the completed manhole is
visually acceptable. Payment shall be full compensation for all labor and materials necessary to
complete each test. No payment will be made for additional vacuum tests or any dyed water
testing.
Payment for manhole core testing, including all labor and materials necessary to complete each
test, shall be made at the Contract Unit Price bid for each Manhole Core Test actually performed
and passed.
DA-22 FIBERGLASS MANHOLES (OMITTED)
DA-23 LOCATION AND EXPOSURE OF MANHOLES AND WATER VALVES
The contractor shall be responsible for locating and marking all previously exposed manholes
and water valves in each street of this contract before the resurfacing process commences for a
particular street.
The contractor shall attempt to include the Construction Engineer (if he is available) in the
observation and marking activity. In any event a street shall be completely marked a minimum of
two (2) working days before resurfacing begins on any street. Marking the curbs with paint is a
recommended procedure.
It shall be the contractors responsibility to notify the utility companies that he has commenced
work on the project. As the resurfacing is completed (within same day) the contractor shall locate
the covered manholes and valves and expose them for later adjustment. Upon completion of a
street the contractor shall notify the utilities of this completion and indicate the start of the next
one in order for the utilities to adjust facilities accordingly. The following are utility contact
persons:
Company Telephone Number Contact Person
Southwestern Bell Telephone 338-6275 "Hot Line"
Texas Utilities 336-9411 Mr. Roy Kruger
Ext. 2121
Lone Star 336-8381 Mr. Jim Bennett
Ext. 6982
City of Fort Worth, 8718100 Mr. Jim Bob Wakefield
Street Light and Signal
Of course, under the terms of this contract, the contractor shall complete adjustment of the storm
drain and Water Department facilities, one traffic lane at a time within five (5) working days after
completing the laying of proposed H.M.A.C. overlay adjacent to said facilities.
11/02/04 Revised ASC-15R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
Any deviation from the above procedure and allotted working days may result in the shut down of
the resurfacing operation by the Construction Engineer.
The contractor shall be responsible for all materials, equipment and labor to perform a most
accurate job and all costs to the contractor shall be figured subsidiary to this contract.
DA-24 REPLACEMENT OF CONCRETE CURB AND GUTTER
These provisions require the contractor to remove all failed existing curb and gutter, as
designated by the Construction Engineer, and replace with standard concrete curb and gutter,
laydown curb and gutter, or in like kind, as governed by the standard City Specifications, Item No.
104 "Removing Old Concrete% Item No. 502 "Concrete Curb and Gutter", and Drawing Nos. S-S2
through S-S4. Pay limits for laydown curb and gutter are shown in Drawing No. S-S5 of the
Standard Specifications. Contractor shall saw cut the curb and gutter and pavement prior to
E removal. Included, and figured subsidiary to this unit price,will be the required sawcut excavation,
as per specification item No. 106 "Unclassified Street Excavation", into the street to aid in the
construction of the curb and gutter. The pay limit will be 9" out from the gutter lip, with same day
haul-off of the removed material to a suitable dump site. The street void shall be filled with
H.M.A.C. "Type D" mix as per specification. No. 300 "Asphalts, Oils and Emulsions", Item No. 304
"Prime Coat" and Item No. 312 "Hot Mix Asphaltic Concrete" and compacted to standard City
densities and top soil as per specification item No. 116 "Top Soil", if needed, shall be added and
leveled to grade behind the curb. Existing improvements within the parkway such as water
meters, sprinkler system, etc. damaged during construction shall be replaced with same or better
at no cost to the City.
Backfill for curb and gutter shall be completed within fourteen (14) calendar days from the day of
demolition to date of completion. If the contractor fails to complete the work within fourteen (14)
calendar days, a $100 dollar liquidated damage will be assessed per block per day.
The unit price bid per linear foot shall be full compensation for all materials, labor, equipment and
incidentals necessary to complete the work.
DA-25 REPLACEMENT OF 6" CONCRETE DRIVEWAYS
This item shall include the removal and replacement of existing concrete driveways, due to
deterioration or in situations where curb and gutter is replaced to adjust grades to eliminate
ponding water with same day haul-off of the removed material to a suitable dump site. For
specifications governing this item see Item No. 104 "Removing Old Concrete", Item No. 504"
Concrete Sidewalk and Driveways". Pay limits for concrete driveway are as shown in Drawing No.
S-S5 of the Standard Specifications.
The unit price bid per square yard shall be full compensation for all labor, material, equipment,
supplies, and incidentals necessary to complete the work.
DA-26 REPLACEMENT OF H.M.A.C. PAVEMENT AND BASE
The contractor shall remove all existing deformed H.M.A.C. pavement and/or bad base material
that shows surface deterioration and/or complete failure. The Engineer will identify these areas
upon which time the contractor will begin work. The failed area shall be saw cut, or other similar
means, out of the existing pavement in square or rectangular fashion. The side faces shall be cut
vertically and all failed and loose material excavated. As a part of the excavation process, all
11/02/04 Revised ASC-16R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
unsatisfactory base material shall be removed, if required, to a depth sufficient to obtain stable
sub-base. The total depth of excavation could range from a couple of inches to include the
surface-base-some sub-base removal for which the Engineer will select the necessary depth. The
remaining good material shall be leveled and uniformly made ready to accept the fill material. All
excavated material shall be hauled off site, the same day as excavated, to a suitable dump site.
After satisfactory completion of removal as outlined above, the contractor shall place the
permanent pavement: patch, with "Type D" surface mix. This item will always be used even if no
base improvements are required. The proposed H.M.A.C. repair shall match the existing
pavement section or the depth of the failed material, whichever is greater. However, the patch
thickness shall be a minimum of 2 inches. Generally the existing H.M.A.C. pavement thickness
will not exceed 5". Before the patch layers are applied, any loose material, mud and/or water shall
be removed. A liquid asphalt tack coat shall be applied to all exposed surfaces. Placement of the
surface mix lifts shall not exceed 3 inches with vibrator compactions to follow each lift.
_ Compactions of the mix shall be to standard densities of the City of Fort Worth, made in
preparation to accept the recycling process.
All applicable provisions of Standard Specification Item Nos. 300"Asphalts, Oils, and Emulsions",
304 "Prime Coat", and 312 "Hot-Mix Asphaltic Concrete" shall govern work.
The unit price bid per cubic yard shall be full compensation for all materials, labor, equipment and
incidentals necessary to complete the work.
DA-27 GRADED CRUSHED STONES
This item shall be used to repair the failed base material in areas exceed 8" deep as directed by
the Engineer. The material shall be graded crushed stones.
For specifications governing this item see Item No. 208"Flexible Base".
The unit price bid per cubic yard shall be full compensation for all materials, labor, equipment and
incidentals necessary to complete the work.
DA-28 WEDGE MILLING 2" TO 0" DEPTH 5.0'WIDE (OMITTED)
DA-29 BUTT JOINTS— MILLED (OMITTED)
DA-30 2" H.M.A.C. SURFACE COURSE (TYPE "D" MIX)
All applicable provisions of Standard Specifications, Item Nos. 312 "Hot-Mix Asphaltic Concrete",
300 "Asphalts, Oils and Emulsions", 304 "Prime Coat", and 313 "Central Plant Recycling-Asphalt
Concrete"shall apply to the construction methods for this portion of the project.
Standard Specification 312.5 (1) shall be revised as follows: The prime coat, tack coat, or the
asphaltic mixture shall not be placed unless the air temperature is fifty (50) degrees Fahrenheit
and rising, the temperature being taken in the shade and away from artificial heat. Asphaltic
material shall also not be placed when the wind conditions are unsuitable in the opinion of the
Engineer.
11/02/04 Revised ASC-17R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
The contractor shall furnish batch design of the proposed hot mix asphaltic concrete for City
approval 48 hours prior to placing the H.M.A.C. overlay. The City will provide laboratory control as
necessary.
The unit price bid per square yard of H.M.A.C. complete and in place, shall be full compensation
for all labor, materials, equipment, tools, and incidentals necessary to complete the work.
DA-31 REPLACEMENT OF 7" CONCRETE VALLEY GUTTER (OMITTED)
DA-32 NEW 7" CONCRETE VALLEY GUTTER(OMITTED)
DA-33 NEW 4" STANDARD WHEELCHAIR RAMP (OMITTED)
DA-34 8" PAVEMENT PULVERIZATION (OMITTED)
DA-35 REINFORCED CONCRETE PAVEMENT OR BASE (UTILITY CUT) (OMITTED)
DA-36 RAISED PAVEMENT MARKERS (OMITTED)
DA-37 POTENTIALLY PETROLEUM CONTAMINATED MATERIAL HANDLING (OMITTED)
DA-38 LOADING, TRANSPORTATION, AND DISPOSAL OF CONTAMINATED SOIL
(OMITTED)
DA-39 ROCK RIPRAP - GROUT - FILTER FABRIC (OMITTED)
DA-40 CONCRETE RIPRAP
1 GENERAL: The following shall govern the furnishing and placing of concrete riprap as shown
on the plans or as directed by the Engineer.
2 MATERIALS: Concrete for riprap shall be placed in accordance with the details and to the
dimensions shown on the plans or as established by the Engineer. Unless otherwise shown on
the plans, concrete riprap shall be reinforced using wire or bar reinforcement.
The concrete shall be 3000 PSI at 28 days, Class A.
Wire reinforcement shall be six (6) by six(6) inch No. 6 plain electric welded reinforcing fabric or
its equal. A minimum lap of six (6) inches shall be used at all splices. At the edge of the riprap,
the wire fabric shall not be less than one (1) inch, no more than three (3) inches from the edge of
the concrete and shall have no wire projecting beyond the last member parallel to the edge of the
concrete.
Reinforcement shall be supported properly throughout the placement to maintain its position
equidistance from the top and bottom surface of the slab.
If the slopes and bottom of the trench for toe walls are dry and not consolidated properly, the
Engineer may require the entire area to be sprinkled, or sprinkled and consolidated before the
concrete is placed. All surfaces shall be moist when concrete is placed.
11102104 Revised ASC-18R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
After the concrete has been placed, compacted, and shaped to conform to the dimensions shown
on the plans, and after it has set sufficiently to avoid slumping, the surface shall be finished with a
wooden float to secure a reasonably smooth surface..
3. PAYMENT; Payment for concrete riprap in place shall be made at the unit price bid in the
Proposal multiplied by the quantity of material used. Bid price will be full compensation for
placing all materials, and for all labor, tools, equipment, and incidentals necessary to complete
the work.
Payment for all necessary excavation below natural ground, and bottom or slope of the excavated
channel will be included in the bid price.
DA-41 CONCRETE CYLINDER PIPE AND FITTINGS (OMITTED)
DA-42 CONCRETE PIPE FITTINGS AND SPECIALS (OMITTED)
DA-43 UNCLASSIFIED STREET EXCAVATION
This item will be used if additional excavation is needed that is not covered by "8" PAVEMENT
PULVERIZATION". Additional Excavation is the removal of the excessive crown and base to
bring the new base to proper grade and City standard specifications for street reconstruction. All
applicable provisions of Item No. 106 "Unclassified Street Excavation" shall apply, work shall be
paid per cubic yard.
DA-44 6" PERFORATED PIPE SUBDRAIN (OMITTED)
DA-45 REPLACEMENT OF 4" CONCRETE SIDEWALKS (OMITTED)
DA-46 RECOMMENDED SEQUENCE OF CONSTRUCTION
The Contractor shall coordinate operations with the Waterfront at Enchanted.Bay Development
and other utilities,maintain the sewer system's capacity, and sequence the relocation of existing
lines as stated in the plan. Below is the recommended schedule. It is arrange in two parts that are
independent of one another.
North of Sun Valley Drive
1. North of David Strickland Rd.,construct proposed M-257R from Sta. 97+17 to 97+28
and Structure 1.
2. Relocate the existing 6"water line located along the east side of Kay Dr, to the
proposed Water Line"A"location on the west side of the street,
- 3. Construct the proposed 10" Sun Valley lateral. Then after the proposed lift station is
completed by others,construct and the connect the proposed laterals along Dvaid
Strickland Rd.,Festa Farely Rd. and Laster Rd,to the Sun Valley lateral.
4. Construct proposed M-503R from Sun Valley Rd.to the northern end of the project
and connect service to Block 7 Lot 16.
11/02/04 Revised ASC-19R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
5. Existing M-257B is to be put out of service. Sewer capacity is maintained by the
construction ofM-257R and M-503R. Connect remaining lateral to the proposed
sewer.
_ South of Kaltenburn Rd
1. Coordinate the relocation of existing gas line at Water line"B"Sta. 8+55.
2. Relocate existing 8"water line to the proposed location of Water Line"B."
3. Construct proposed M-257R and Structure 2.
4. Abandon existing M-309 that is parallel to proposed M-257R.
5. Construct proposed service line for Block 12 Lot 1 along Kaltenburn Rd, to existing
M-503.
6. Abandon existing M-257C and coordinate abandonment of existing M-257B,by
others.
DA-47 PAVEMENT REPAIR IN PARKING AREA(OMITTED)
DA-48 EASEMENTS AND PERMITS
Easements and permits, both temporary and permanent, have been secured for this project at
this time and made a part thereto. Any easements and/or permits, both temporary and
permanent, that have not been obtained by the time of publication shall be secured before
construction starts. No work is to be done in areas requiring easements and/or permits until the
necessary easements are obtained. The Contractor's attention is directed to the easement
description and permit requirements, as contained herein, along with any special conditions that
may have been imposed on these easements and permits.
Where the pipeline crosses privately owned property, the easements and construction areas are
shown on the plans. The easements shall be cleaned up after use and restored to their original
conditions or better, In the event additional work room or access is required by the
Contractor, it shall be the Contractor's responsibility to obtain written permission from the
property owners involved for the use of additional property required. No additional payment
will be allowed for this item.
DA-49 HIGHWAY REQUIREMENTS (OMITTED)
DA-50 CONCRETE ENCASEMENT
Concrete encasement shall be Class E (1500 psi) concrete and for sewer line encasements shall
conform to Fig. 113; for water line encasements it shall conform to Fig. 20 of the General
Contract Documents. Requirements for such encasement are specified in Sections E1-20 and
E2-20 of the General Contract Documents.
Payment for work such as forming, placing, and finishing including all labor, tools, equipment and
material necessary to complete the work shall be included in the linear foot price bid for Concrete
Encasement.
DA-51 CONNECTION TO EXISTING STRUCTURES
11/02/04 Revised ASC-20R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
All connections between proposed and existing facilities, shall consist of a watertight seal.
Concrete used in the connection shall be Class A (3000 psi)concrete and meet the requirements
of Section E1-20 and E2-20 of the General Contract Documents. Prior to concrete placement, a
gasket, RAM-Nek or approved equal shall be installed around penetrating pipe.
Payment for such work as connecting to existing facilities including all labor, tools, equipment,
and material necessary to complete the work shall be included in the linear foot price of the
appropriate pipe BID ITEM.
DA-52 TURBO METER WITH VAULT AND BYPASS INSTALLATION (OMITTED)
DA-53 OPEN FIRE LINE INSTALLATIONS (OMITTED)
DA-54 WATER SAMPLE STATION (OMITTED)
DA-55 CURB ON CONCRETE PAVEMENT (OMITTED)
DA-56 SHOP DRAWINGS
1. Submit seven (7) copies of shop drawings, layouts, manufacturer's data and material
schedules as may be required by the Engineer for his review. Submittals may be checked by and
stamped with the approval of the Contractor and identified as the Engineer may require. Such
review by the Engineer shall include checking for general conformance with the design concept of
the project and general compliance with information given in the General Contract Documents.
Indicated actions by the Engineer, which may result from his review, shall not constitute
concurrence with any deviation from the plans and specifications unless such deviations are
specifically identified by the method described below, and further shall not relieve the Contractor
of responsibility for errors or omissions in the submitted data. Processed shop drawing
submittals are not change orders. The purpose of submittals by the Contractor is to demonstrate
that the Contractor understands the design concept, and that he demonstrates his understanding
by indicating which equipment and materials he intends to famish and install, and by detailing the
fabrication and installation methods he intends to use. if deviations, discrepancies or conflicts
between submittals and the design drawings and/or specifications are discovered, either prior to
or after submittals are processed, the design drawings and specifications shall govern. The
Contractor shall be responsible for dimensions which are to be confirmed and correlated at the
job site, fabrication processes and techniques of constriction, coordination of his work with that of
other trades and satisfactory performance his work. The Contractor shall check and verify all
measurements and review submittals prior to being submitted, and sign or initial a statement
included with the submittal, which signifies compliance with plans and specifications and
dimensions suitable for the application. Any deviation from the specified criteria shall be
expressly stated in writing in the submittal. Three (3) copies of the approved submittals shall be
retained by the Contractor until completion of the project and presented to the City in bound form..
2. Shop drawings shall be submitted for the following items prior to installation:
List the required submittals here
Additional shop drawing requirements are described in some of the material specifications.
3. Address for Submittals-The submittals shall be addressed to the Project Manager:
11/02104 Revised ASC-21 R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
Gopal Sahu, P.E.
City of Fort Worth
1000 Throckmorton
Fort Worth, TX 76102
DA-57 COST BREAKDOWN
In order to establish a basis upon which partial payments to the Contractor may be authorized,
.e immediately after execution of the contract the Contractor shall furnish a detailed cost breakdown
of his contract price arranged and itemized to meet the approval of the Engineer.
DA-58 STANDARD STREET SPECIFICATIONS H.M.A.C. OVERLAY
All work involving paving and/or drainage shall conform to the two following published
specifications, except as modified herein:
STANDARD SPECIFICATIONS FOR STREET AND STORM DRAIN CONSTRUCTION — CITY
OF FORT WORTH
STANDARD SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION NORTH CENTRAL
TEXAS
DA-59 H.M.A.C. MORE THAN 9 INCHES DEEP (OMITTED)
DA-60 ASPHALT DRIVEWAY REPAIR
At locations where H.M.A.C. driveways are encountered, such driveways shall be completely
replaced for the full extent of utility cut with H.M.A.C. equal to or better than the existing driveway.
DA-61 TOPSOIL
Where directed by the Engineer, top soil shall be applied in accordance with the City of Fort
Worth Transportation and Public Works Department's Standard Specifications for Street and
Storm Drain Construction, Item 116, except as follows: All labor, equipment, tools and incidentals
shall be included in the square yard bid price for the top soil.
DA-62 WATER METER AND METER BOX RELOCATION AND ADJUSTMENT
This item shall include raising or lowering an existing meter box to the parkway grade specified
No payment will be made for adjusting existing boxes which are within 0.001 feet of specified
parkway grade. The unit price bid shall be full and sufficient payment for all labor, equipment and
materials used in the adjustment of the meter box.
DA-63 BID QUANTITIES
Bid quantities of the various items in the proposal are for comparison only and may not reflect the
actual quantities. There is no limit to which a bid item can be increased or decreased.
Contractor shall not be entitled to renegotiation of unit prices regardless of the final measured
quantities. To the extent that C4-4.3 conflicts with this provision, this provision controls. No claim
} will be considered for lost or anticipated profits based upon differences in estimated quantities
versus actual quantities.
11/02/04 Revised ASC-22R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
In particular, the Contractor shall be aware that it is the City's intention that the quantities in Unit I
be used on an "emergency" basis only.
Total quantities given in the bid proposal may not reflect actual quantities; however, they are
given for the purpose of bidding and awarding the contract. A contract in the amount of$200,000
(see Options to Renew) shall be awarded with final payment based on actual measured
quantities and the unit price bid in this proposal. Moreover, there is to be not limit on the variation
between the estimated quantities shown and actual quantities performed.
It is understood and agreed that the scope of work contemplated in this contract is that which is
designated by the City bit will in not case exceed $200,000 (see Options to Renew) including all
change orders.
DA-64 WORK IN HIGHWAY RIGHT OF WAY (OMITTED)
DA-65 CRUSHED LIMESTONE (FLEX-BASE)
Crushed limestone required for use as a flexible base material shall conform to Specification Item
No. 208 of the Standard Specifications for Street and Storm Drain Construction for the City of
Fort Worth Transportation and Public Works Department.
DA-66 OPTION TO RENEW (OMITTED)
DA-67 NON-EXCLUSIVE CONTRACT (OMITTED)
DA-68 CONCRETE VALLEY GUTTER(OMITTED)
DA-69 TRAFFIC BUTTONS (OMITTED)
DA-70 PAVEMENT STRIPING (OMITTED)
DA-71 H.M.A.C. TESTING PROCEDURES
The contractor is required to submit a Mix Design for both Type "B" and "D" asphalt that will be
used for each project. This should be submitted at the Pre-Construction Conference. This
design shall not be more than two (2) years old. Upon submittal of the design mix a Marshal
(Proctor) will be calculated, if one has not been previously calculated, for the use during density
testing. For type "B" asphalt a maximum of 20% rap may be used.. No Rap may be used in type
"D"
Upon approval of an asphalt: mix design and the calculation of the Marshal (proctor) the
contractor is approved for placement of the asphalt. The contractor shall contact the City
Laboratory, through the inspector, at least 24 hours in advance of the asphalt placement to
schedule a technician to assist in the monitoring of the number of passes by a roller to establish a
rolling pattern that will provide the required densities. The required Density for Type "B" and for
Type "D"asphalt will be 91% of the calculated Marshal (proctor). A Troxler Thin Layer Gauge will
be used for all asphalt testing.
11/02/04 Revised ASC-23R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
After a rolling pattern is established, densities should be taken at locations not more than 300
feet apart. The above requirement applies to both Type "B" and "D" asphalt. Densities on type
"B" must be done before Type"D" asphalt is applied.
Cores to determine thickness of Type "B" asphalt must be taken before Type "D" asphalt is
applied. Upon completion of the application of Type"D"asphalt additional cores must be taken to
determine the applied thickness.
DA-72 SPECIFICATION REFERENCES
When reference is made in these specifications to a particular ASTM, AWWA, ANSI or other
specification, it shall be understood that the latest revision of such specification, prior to the date
of these general specifications or revisions thereof, shall apply.
DA-73 RELOCATION OF SPRINKLER SYSTEM BACK-FLOW PREVENTER/CONTROL
VALVE AND BOX (OMITTED)
DA-74 RESILIENT-SEATED GATE VALVES
Any resilient-seated gate valves supplied for this contract shall conform to Material Standard
E1-26, STANDARD SPECIFICATIONS FOR RESILIENT-SEATED GATE VALVES, with the
exception of size requirements in sections E-26.1. All resilient-seated gate valves shall be
mechanical joints and be approved on the City of Fort Worth Standard Product List.
DA-75 EMERGENCY SITUATION, JOB MOVE-IN
The Owner or Engineer shall determine when an emergency situation shall exist. When water
emergency work is required, the Contractor shall mobilize to the said location within twenty-four
(24) hours after given notification from the Inspector and/or Project Manager. The Contractor
shall make all necessary arrangements for bypass pumping, setting up barricades, notifying
citizens, etc., while waiting for other utilities to be located as directed by the Engineer. The
Contractor shall work continuously until the emergency work order has been completed at a time
agreed to by the Project Manager, Inspector, and Contractor. After the emergency work order
has been completed, there will be no additional "Job Move-In" charges paid to remobilize back to
the previous project location site.
DA-76 1 %11 &2" COPPER SERVICES (OMITTED)
DA-77 SCOPE OF WORK (UTIL. CUT) (OMITTED)
DA-78 CONTRACTOR'S RESPONSIBILTY(UTIL. CUT) (OMITTED)
DA-79 CONTRACT TIME (UTIL. CUT) (OMITTED)
DA-80 REQUIRED CREW PERSONNEL & EQUIPMENT (UTIL. CUT) (OMITTED)
DA-81 TIME ALLOWED FOR UTILITY CUTS (UTIL. CUT) (OMITTED)
DA-82 LIQUIDATED DAMAGES (UTIL. CUT) (OMITTED)
11/02/04 Revised ASC-24R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
DA-83 PAVING REPAIR EDGES (UTIL. CUT) (OMITTED)
DA-84 TRENCH BACKFILL (UTIL. CUT) (OMITTED)
DA-85 CLEAN-UP (UTIL. CUT) (OMITTED)
DA-86 PROPERTY ACCESS (UTIL. CUT) (OMITTED)
DA-87 SUBMISSION OF BIDS (UTIL. CUT) (OMITTED)
DA-88 STANDARD BASE REPAIR FOR UNIT I (UTIL. CUT) (OMITTED)
DA-89 CONCRETE BASE REPAIR FOR UNIT II& UNIT III (UTIL. CUT) (OMITTED)
DA-90 2" TO 9" H.M.A.C. PAVEMENT (UTIL. CUT) (OMITTED)
DA-91 ADJUST WATER VALVE BOXES, MANHOLES, AND VAULTS (UTIL. CUT) (OMITTED)
DA-92 MAINTENANCE BOND (UTIL. CUT) (OMITTED)
DA-93 BRICK PAVEMENT (UTIL. CUT) (OMITTED)
DA-94 LIME STABILIZED SUBGRADE (UTIL. CUT) (OMITTED)
DA-95 CEMENT STABILIZED SUBGRADE (UTIL. CUT) (OMITTED)
DA-96 REPAIR OF STORM DRAINI STRUCTURES (UTIL. CUT) (OMITTED)
DA-97 "QUICK-SET" CONCRETE (UTIL. CUT) (OMITTED)
DA-98 UTILITY ADJUSTMENT (UTIL. CUT) (OMITTED)
DA-99 STANDARD CONCRETE SIDEWALK AND WHEELCHAIR RAMPS (UTIL. CUT)
(OMITTED)
DA-100 LIMITS OF CONCRETE PAVEMENT REPAIR (UTIL. CUT) (OMITTED)
DA-101 CONCRETE CURB AND GUTTER(UTIL. CUT) (OMITTED)
DA-102 PAYMENT (UTIL. CUT) (OMIITTED)
DA-103 DEHOLES (MISC. EXT.) (OMITTED)
DA-104 CONSTRUCTION LIMITATIONS (MISC. EXT.) (OMMITTED)
DA-105 PRESSURE CLEANING AND TESTING (MISC. EXT.) (OMITTED)
DA-106 BID QUANTITIES (MISC. EXT.) (OMITTED)
DA-107 LIFE OF CONTRACT (MISC. EXT.) (OMITTED)
11/02104 Revised ASC-25R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
DA-108 FLOWABLE FILL (MISC. EXT.) (OMITTED)
DA-109 BRICK PAVEMENT REPAIR (MISC. REPL.) (OMITTED)
DA-110 DETERMINATION AND INITIATION OF WORK (MISC. REPL.) (OMITTED)
DA-111 WORK ORDER COMPLETION TIME (MISC. REPL.) (OMITTED)
DA-112 MOVE IN CHARGES (MISC. REPL.) (OMITTED)
DA-113 PROJECT SIGNS (MISC. REPL.) (OMITTED)
DA-114 LIQUIDATED DAMAGES (MISC. REPL.) (OMITTED)
DA-115 TRENCH SAFETY SYSTEM DESIGN (MISC. REPL.) (OMITTED)
DA-116 FIELD OFFICE (OMITTED)
DA-117 TRAFFIC CONTROL PLAN (OMITTED)
DA-118 COORDINATION OF WORK WITH CONTRACTOR FOR OTHER UNITS
(OMITTED)
DA-119 FIBERGLASS SEWER PIPE GRAVITY
A. GENERAL
1. Section Includes
a) Fiberglass Reinforced Polymer Mortar Pipe.
1. References
a) ASTM D3262 - Standard Specification for "Fiberglass" (Glass-Fiber-Reinforced
Thermosetting-Resin)Sewer Pipe.
b) ASTM D4161 - Standard Specification for "Fiberglass" (Glass-Fiber-Reinforced
Thermosetting-Resin) Pipe Joints Using Flexible Elastomeric Seals.
c) ASTM D2412 - Standard Test Method for Determination of External Loading
Characteristics of Plastic Pipe by Parallel-Plate Loading.
3. Specifications
The specifications contained herein govern, unless otherwise agreed upon between purchaser
and supplier.
4. Submittals
11/02/04 Revised ASC-26R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
Contractor shall submit load and pipe calculations confirming selected pipe behavior. Load
calculations shall include, but not limited to, buckling resistance, pipe deflection, pipe wall strain
cracking and wall crushing load. All design calculations shall be sealed by a Registered
Professional Engineer of the State of Texas.
Product data submittals to include the following are as a minimum:
Details of the proposed pipe.
Details of proposed manholes.
Properties, strengths, etc. of the pipe.
Joint detail drawing, including maximum interior Joint gap opening, in the deflected
position and in the straight alignment.
Instructions on storage, handling, transportation, and pipe installation.
Standard catalog sheets.
Gasket type and composition showing ability to withstand the chemicals and conditions
within sanitary sewers.
Pipe laying schedule.
Connections to all proposed structures including water stop.
B, PRODUCTS
5. Materials
a} Resin Systems: The manufacturer shall use only polyester resin systems with a
proven history of performance in this particular application. The historical data shall
have been acquired from a composite material of similar construction and composition
as the proposed product.
bj Glass Reinforcements: The reinforcing glass fibers used to manufacture the
components shall be of highest quality commercial grade E-glass filaments with binder
and sizing compatible with impregnating resins.
c) Silica Sand: Sand shall be minimum 98% silica with a maximum moisture content of
0.2%.
d) Additives: Resin additives, such as curing agents, pigments, dyes fillers, thixotropic
agents, etc.,when used, shall not detrimentally affect the performance of the product.
e} Elastomeric Gaskets: Gaskets shall be supplied by approved gasket manufacturers
and be suitable for the service intended.
1. Manufacture and Construction
a) Pipes: Manufacture pipe to result in a dense, non-porous, corrosion-resistant,
consistent composite structure.
bj Joints: Unless otherwise specified, the pipe shall be field connected with fiberglass
sleeve couplings that utilize elastomeric sealing gaskets made of EPDM rubber
compound as the sole means to maintain joint watertightness. The joints must meet
the performance requirements of ASTM D4161. Joints at tie-ins, when needed may
utilize fiberglass, gasket-sealed closure couplings.
11/02/04 Revised ASC-27R Addendum 1
MW
PART DA - ADDITIONAL SPECIAL CONDITIONS
c) Fittings: Flanges, elbows, reducers, tees, wyes, laterals and other fittings shall be
capable of withstanding all operating conditions when installed. They may be contact
molded or manufactured from mitered sections of pipe joined by glass-fiber-reinforced
overlays. Properly protected standard ductile iron, fusion-bonded epoxy coated steel
and stainless steel fittings may also be used.
3. Dimensions
a) Diameters: The actual outside diameter (18" to 48") of the pipes shall be in
accordance with ASTM D3262. For other diameters, OD's shall be per manufacturers
literature.
b) Lengths: Pipe shall be supplied in nominal lengths of 20 feet. Actual laying length
shall be nominal +1, -4 inches. At least 90% of the total footage of each size and
class of pipe, excluding special order lengths, shall be furnished in nominal length
sections.
c) Wall Thickness: The minimum wall thickness shall be the stated design thickness.
d) End Squareness: Pipe ends shall be square to the pipe axis with a maximum
tolerance of 1f8".
s 4. Testing
a) Pipes: Pipes shall be manufactured and tested in accordance with ASTM D3262.
b) Joints: Coupling Joints shall meet the requirements of ASTM D4161.
Stiffness: Minimum pipe stiffness when tested in accordance with ASTM D2412 should in
no case have the stiffness be less than the following:
Soil Cover< 15' >= SN46
Soil Cover> 15'and all levee crossings.and river crossings >= SN72
5. Customer Inspection
a) The owner or other designated representative shall be entitled to inspect pipes or
witness the pipe manufacturing.
b) Manufacturers Notification to Customer: Should the Owner request to see specific
pipes during any phase of the manufacturing process, the manufacture must provide
the Owner with adequate advance notice of when and where the production of those
pipes will take place.
5. Packaging, Handling, Shipping
a) Packaging, handling, and shipping shall be done in accordance with the
manufacturer's instructions.
C. EXECUTION
11/02/04 Revised ASC-28R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
1. Installation
a) Burial: The bedding and burial of pipe and fittings shall be in accordance with the
project plans and specifications and the manufacturers requirements (Section 13 A of
the product brochure).
b) Pipe Handling: Use textile slings, other suitable materials or a forklift. Use of chains
or cables is not recommended.
c) Jointing:
1) Clean ends of pipe and coupling components.
2) Apply joint lubricant to pipe ends and elastomeric seals of coupling. Use only
lubricants approved by the pipe manufacturer.
3) Use suitable equipment and end protection to push or pull the pipes together.
4) Do not exceed forces recommended by the manufacturer for coupling pipe.
5) Join pipes in straight alignment then deflect to required angle. Do not allow the
deflection angle to exceed the deflection permitted by the manufacturer.
d) Field Testing
1) Contractor shall not use the Fort Worth Water Department Material Specification
E2-9.7c Exfittration Test Pneumatic Method: Air Test. The Contractor shall test
according to the current edition of NCTCOG - Standard Specification for Public
Works, 6.72f Low Pressure Air Test— 3) Test Methods. The Time Pressure Drop
Method will be used for this project
2) Infiltration / Exfiltration Test: Maximum allowable leakage shall be per local
specification requirements,
3) Deflection: Maximum allowable long-term deflection is 5% of the initial diameter.
DA-120 HINGED MANHOLE
"PAMREX", or similar approved Manhole Cover and Frame. Covers and frames shall be
manufactured from ductile iron. Covers shall be hinged, and incorporate a 90 degree blocking
system to prevent accidental closure when in the open position. Covers shall be one man
operable using standard tools and shall be capable of withstanding a test load of 80,000 lbs.
Frames shall incorporate a continuous seating ring, have a 32" clear opening, frame depth shall
not exceed 5", the flange shall incorporate bedding slots and bolt holes. All components shall be
black coated.
11/02104 Revised ASC-29R Addendum 1
Aw
PART DA - ADDITIONAL SPECIAL CONDITIONS
The manhole frame shall be installed with the hinge end aligned with the flow of traffic to allow
traffic to close frame when gas pressure partially lifts lid.
The contractor shall also provide the manufactures recommend locking mechanism. The
locations shall be approved by the engineer.
DA-121 T-LOCK SHEET LINER
A. General
This specification covers the supply and installation of a flexible sheet liner with locking
extensions in reinforced concrete pipe and auxiliary structures to effectively protect the exposed
concrete surfaces from corrosion. To accomplish this, the liner must be continuous and free of
pinholes both across the joints and in the liner itself. All work for and in connection with the
installation of the lining in concrete pipe, and the field sealing and welding of joints, shall be done
in strict conformity with all applicable specifications, instructions and recommendations of the
lining manufacturer. The manufacturer of the lining shall furnish an affidavit attesting to the
successful use of its material as a lining for sewer pipes for a minimum period of 40 years in
sewage conditions recognized as corrosive or otherwise detrimental to concrete.
B. MATERIAL
a) Liner shall be Amer-Plate T-Lock as manufactured by Ameron Protective Linings
Division, Brea, California or approved equal.
= 1. Composition
a) The material used in the liner, welding strips, and other accessory items, shall be a
combination of poly vinyl chloride resin, pigments and plasticizers, specially
compounded to remain flexible. Poly vinyl chloride resin shall constitute not less than
99 percent, by weight, of the resin used in the formulation. Copolymer resins will not
be permitted. Linear Low Density Polyethylene (LLDPE) may also be specified..
2. Physical Properties
a) All plastic liner plate sheets, welding strips and other accessory items, shall have the
following physical properties when tested at 77"F±5° (250C±3°).
Property Initial (Par.2.4)
Tensile Strength 2200 psi min.
(15 Mpa min.) 2100 psi min.
(14.5 Mpa min.)
Elongation at break 200% min. 200% min.
Shore durometer, Type D
(with respect to initial test result) 1-sec, 50-60
10-sec. 35-50 ±5
±5
Weight change 1.5%
b) Tensile specimens shall be prepared and tested in accordance with ASTM D412 using
Die B. Weight change specimens shall be 1-inch (25-mm) by 3-inch (75-mm)samples.
11/02/04 Revised ASC-30R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
Specimens for testing of initial physical properties may be taken from liner plate sheet
and welding strip at any time prior to final acceptance of the work.
c) Liner plate locking extensions embedded in concrete shall withstand a test pull of at
least 100 pounds per linear inch (1800 kg/cm), applied perpendicularly to the concrete
surface for a period of one minute, without rupture of the locking extensions or
withdrawal from embedment. This test shall be made at a temperature of 700- 80°F
(21° - 270C) inclusive.
d) All plastic liner plate sheets, including locking extensions, all joint, corner and welding
strips shall be free of cracks, cleavages or other defects adversely affecting the
protective characteristics of the material. The engineer may authorize the repair of
such defects by approved methods.
e) The lining shall have good impact resistance, shall be flexible and shall have an
elongation sufficient to bridge up to 1/4" (6mm)settling cracks, which may occur in the
pipe or in the joint after installation without damage to the lining.
- f) The lining shall be repairable at any time during the life of the pipe or structure.
2. Chemical resistance*
After conditioning to constant weight at 110°F (43"C), tensile specimens and weight
change specimens shall be exposed to the following solutions for a period of 112 days at
770F±5° (25°C+3°)..
At 28-day intervals, tensile specimens and weight change specimens shall be removed
from each of the chemical solutions and tested in accordance with paragraph 2.3 C. If any
specimen fails to meet the 112-day requirements before completion, the material will be
subject to rejection.
Chemical Solution Concentration
Sulfuric acid 20%**
Sodium hydroxide 5%
Ammonium hydroxide 5%**
Nitric acid 1/%**
Ferric chloride 1%
Soap 0. 1%
Detergent(linear alkyl benzyl
sulfonate or LAS) 0.1%
Bacteriological BOD not less
than 700 ppm.
*This is to be used as a pre-qualification test and when material formulations are changed.
**Volumetric percentages of concentrated C.P. grade reagents.
3. Details and dimensions of basic size sheets (4-foot widths)
a) Liner sheets shall be a minimum of 0.065 inch (1.65 mm) in thickness. Locking
extensions (T-shaped) of the same material as that of the liner shall be integrally
extruded with the sheet. Locking extensions shall be approximately 2'f inches (64mm)
apart and shall be at least.0.375-inch (9-mm) high.
11/02/04 Revised ASC-31 R Add ndunU
i Jrl ,a
PART DA - ADDITIONAL SPECIAL CONDITIONS
b) Sheets shall have a nominal width of 48 inches (1200 mm) and a length of no more
than 24 feet (7200 mm), except that longer lengths may be supplied on special order.
Lengths specified shall include a tolerance at a ratio of ±114 inches (6 mm) for each
100 inches (2500 mm).
c) Sheets not used for shop fabrication into larger sheets shall be shop tested for
pinholes using an electrical spark tester set. between 18,000 and 22,000 volts. Any
holes shall be repaired and retested.
d) Special sized, factory prewelded and tested sheets shall be available on special order.
= 2. Pipe-size sheets and accessories
a) Pipe linings shall be supplied as pipe-size sheets, fabricated by shop-welding the
basic-size sheets together. Shop welds shall be made by lapping sheets a minimum of
Y2 inch and applying heat and pressure to the lap to produce a continuous welded
joint. Tensile strength measure across shop-welded joints in accordance with ASTM
D412 shall be at least 2000 psi (14 MPa).
b) If required, strap channels shall be 1-inch (25-mm)wide maximum of 3/16 inch (5mm)
remains.
c) Sheets also can be supplied in prefabricated, pipe-size tubular-shaped sheets, ready
to lower onto the inner pipe forms. These normally do not require the use of strap
channels.
d) Transverse flaps may be provided at the ends of sheets for pipe. Locking extensions
shall be removed from flaps so that a maximum of 1/32 inch (1 mm)of the base of the
locking extension is left on the sheet.
e) Welding strips shall be approximately 1-inch (25-mm) wide with a minimum width of
7/8 inch (22mm). The edges of weld strips shall be beveled in the manufacturing
process. Thickness of weld strip shall be a normal 1/8 inch (3 mm).
f) Joint strips for pipe shall be 4-inches (100mm) wide with a minimum width of 33/4
inches (94 mm). Thickness of joint strips shall be a nominal of 3/32 inch(2.3 mm)
g) Prior to preparing the sheets for shipment, they shall be tested for pinholes using an
electrical spark tester set between 18,000 and 22,000 volts. Any holes shall be
repaired and retested.
C. Installation of Lining
1. General
a) Installation of the lining, including preheating of sheets in cold weather and the
welding of all joints, shall be done in accordance with the recommendations of the
finer manufacturer. All welding shall be completed by a certified welder.
b) Coverage of the lining shall not be less than the minimum shown on the plans.
11/02/04 Revised ASC-32R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
c) The lining shall be installed with the locking extensions running parallel with the
longitudinal avis of the pipe.
d) The lining shall be held snugly in place against inner forms.
e) Locking extensions shall terminate not more than 1 l2 inches (38 mm) from the end of
the inside surface of the pipe section. Joint flaps when used shall extend
approximately 4 inches (100 mm)beyond the end of the inside surface..
f) Concrete poured against lining shall be vibrated, spaded or compacted in a careful
manner so as to protect the lining and produce a dense, homogenous concrete,
_ securely anchoring the locking extensions into the concrete.
g) In removing forms, care should be taken to protect the lining from damage. Sharp
instruments shall not be used to pry forms from lined surfaces. When forms are
removed, any nails that remain in the lining shall be pulled, without tearing the lining,
and the resulting holes clearly marked.
- h) All nail and tie holes and all cut, torn and seriously abraded areas in the lining shall be
patched. Patches made entirely with welding strip shall be fused to the liner over the
entire patch area. Larger patches may consist of smooth liner sheet applied over the
damaged area with adhesive. All edges must be covered with welding strip fused to
the patch and the sound lining adjoining the damaged area.
i) Hot joint compounds, such as coal tar, shall not be poured or applied to the lining.
j) The contractor shall take all necessary measures to prevent damage to installed lining
from equipment and materials used in or taken through the work.
2. Application to Concrete Pipe-Special requirements.
a) The lining shall be set flush with the inner edges of the bell or spigot end of a pipe
section and shall extend to the opposite end or to approximately 4 inches (100 mm)
beyond the opposite end depending upon the type of lining joint to be made with the
adjoining concrete pipe.
b) Wherever concrete pipe or cast-in-place structures protected with lining, join
structures not so lined (such as brick structures, concrete pipe or cast-in-place
structures with clay lining or clay pipe), the lining shall be extended over and around
the end of the pipe and back into the structure for not less than 4 inches (100 mm).
this protecting cap may be molded or fabricated from the lining material but need not
be locked into the pipe.
�. c) Where a pipe lateral (not of plastic lined concrete) is installed through lined concrete
pipe, the seal between the lined portion and the lateral shall be made by the method
prescribed for cast-in-place structures under Paragraph 3.4 B.
d) Lined concrete pipe may be cured by standard curing methods.
11/02/04 Revised ASC-33R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
e) Care shall be exercised in handling, transporting and placing lined pipe to prevent
damage to the lining. No interior hooks or slings shall be used in lifting pipe. All
handling operations shall be done with an exterior sling or with a suitable fork lift.
f) On pipe having a 3600 liner coverage, the longitudinal edges of the sheet shall be butt
welded. When pipe tubes are furnished, these are shop-welded joints made in
accordance with 2.6 A.
g) No pipe with damaged lining will be accepted until the damage has been repaired to
the satisfaction of the engineer.
3. Field joints in lining for concrete pipe
a) The joint between sections of lined pipe shall be prepared in the fallowing manner:
If required, the inside joint shall be filled and carefully pointed with cement mortar in
such a manner that the mortar shall not, at any point, extend into the pipe beyond the
straight line connecting the surfaces of the adjacent pipe sections..
Pipe joints must be dry before lining joints are made.
b) All mortar and other foreign materials shall be removed from lining surfaces adjacent
to the pipe joint, leaving them clean and dry,
c) Field joints in the lining at pipe joints may be either of the following described types:
Type P-1: The joint shall be made with a separate 4-inch (100-mm)joint strip and two
welding strips. The 4-inch (100-mm) joint strip shall be centered over the joint, heat-
sealed to the lining, then welded along each edge to adjacent liner sheets with a 1-
inch (25-mm) weld strip. The 4-inch (100-mm) joint strip shall iap over each sheet a
minimum of Y2 inch (13 mm).
,.� Type P-2 The joint shall be made with a joint flap with locking extensions removed
per Paragraph 2.6 D and extending approximately 4 inches (100 mm) beyond the pipe
end. The joint flap shall overlap the lining in the adjacent pipe section a minimum of%
inch (13 mm) and be heat-sealed in place prior to welding. The field joint shall be
completed by welding the flap to the lining of the adjacent pipe using 1-inch (25-mm)
weld strip.
Care shall be taken to protect the flap from damage. Excessive tension and distortion
in bending back the flap to expose the pipe during laying and joint mortaring shall be
avoided. At temperatures below 50° F (10° C), heating of the liner may be required to
avoid damage.
d) The joint flap or strip on beveled pipe shall be trimmed to a width (measured from the
end of the spigot) of approximately 4 inches (100 mm) for the entire circumferential
length of the lining.
e) All welding of joints is to be in strict conformance with the specifications and
instructions of the lining manufacture. Welding shall fuse both sheets and weld strip
together to provide a continuous joint equal in corrosion resistance and impermeability
to the liner plate. Hot air welding tools shall provide effluent air to the sheets to be
joined at a temperature between 500° and 600°F (2600 and 316° C). Welding tools
shall be held approximately Y2 inch (13 mm) from and moved back and forth over the
11/02104 Revised ASC-34R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
junction of the two materials to be joined. The welding tool shall be moved slowly
enough as the weld progresses to cause a small bead of molten material to be visible
along both edges and in front of the weld strip.
Q The following special requirement shall apply when the liner coverage is 360 degrees:
When groundwater is encountered the lining joint shall not be made until pumping of
groundwater has been discontinued for at least three days and no visible leakage is
evident at the joint. When welding the downstream side of a joint strip or flap, do not
weld 6 to 8 inches (150 to 200 mm) at the pipe invert to provide relief of potential
future groundwater buildup.
4. Application to cast-in-place concrete structures - Special requirements.
a) Linear sheets shall be closely fitted and properly secured to the inner forms. Sheets
shall be cut to fit curved and warped surfaces using a minimum number of separate
pieces.
b) Unless otherwise shown on the plans, the lining shall be returned at least 3 inches (75
mm) at the surfaces of contact between the concrete structure and items not of
concrete (including manhole frames, gate guides, clay pipe or brick manholes and clay
or cast iron pipes). The same procedure shall be followed at joints where the type of
protective lining is changed or the new work is built to join existing unlined concrete. At
each return, the returned liner shall be seated to the item in contact with the plastic-
lined concrete using Amer-Plate 19Y adhesive system. If the liner cannot be sealed
with this adhesive because of the joint at the return being too wide or rough or
because of safety regulations, the joint space shall be densely caulked with lead wool
or other approved caulking material to a depth of 2 inches (50 mm) and finished with a
- minimum of 1 inch (25 mm)of an approved corrosion resistant material.
5. Joints in lining for cast-in-place concrete structures.
a) Lining at joints shall be free of all mortar and other foreign material and shall be clean
and dry before joints are made.
b) Field joints in the lining shall be of the following described types, used as prescribed:
Type C-1: The joint shall be made with a separate 4-inch (100-mm)joint strip and two
welding strips. The 4-inch (100-mm) joint strip shall be centered over the joint, heat-
sealed to the liner then welded along each edge to adjacent sheets with a 1-inch (25-
mm) wide welding strip. The width of the space between adjacent sheets shall not
exceed 2 inches (50 mm). The 4-inch (100-mm)joint strip shall lap over each sheet a
minimum of Y2 inch (13 mm). It may be used at any transverse or longitudinal joint.
Type C-2 The joint shall be made by lapping sheets not less than Y2 inch (13 mm).
One 1-inch (25-mm) welding strip is required. The upstream sheet shall overlap the
one'downstream. The lap shall be heat-sealed into place prior to welding on the 1-inch
(25-mm)welding strip.
Type C-3: The joint shall be made by applying 2-inch (50-mm)-wide waterproof tape
or 1-inch (25-mm)-wide welding strip on the back of the maximum %-inch (6-mm) gap
butt joint or by some other method approved by the engineer to prevent wet concrete
11/02/04 Revised ASC-35R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
from getting under the sheet. After the forms have been stripped, a 1-inch (25 mm)
welding strip shall be applied over the face of the sheet,
c) All welding is to be in strict conformance with the specifications of the lining
manufacturer and Paragraph 3.3 E.
6. Testing and repairing damaged surfaces.
a) After the pipe is installed in the trench, all surfaces covered with lining, including
welds, shall be tested with an approved electrical holiday detector (Tinker & Rasor
Model No. AP-W with power pack) with the instrument set between 18,00 and 22,00
volts.
All welds shall be physically tested by a nondestructive probing method. All patches
over holes, or repairs to the liner wherever damage has occurred, shall be
accomplished in accordance with Paragraph 3.1 H.
b) Each transverse welding strip which extends to a lower edge of the liner will be tested
by the purchasing agency. The welding strips shall extend 2 inches(50 mm) below the
liner to provide a tab, A 10-pound (5kg) pull will be applied to each tab. The force will
be applied normal to the face of the structure by means of a spring balance. Liner
adjoining the welding strip will be held against the concrete during application of the
force. The 10-pound (5 kg) pull will be maintained if a weld failure develops, until no
further separation occurs. Defective welds will be retested after repairs have been
made. Tabs shall be trimmed away neatly by the installer of the liner after the welding
strip has passed inspection. Inspection shall be made within 2 days after the joint has
been completed in order to prevent tearing the projecting weld strip and consequently
damage to the liner from equipment and materials used in or taken through the work.
D. MEASUREMENT AND PAYMENT
Payment shall be based on the Contract Unit Price per vertical foot for manholes and
incidental to the Contract Unit Price per Structure 1 and Structure 2, measured from the
bottom of the frame to the top of the bench. The Contract Unit Price shall be payment in full
for performing the work and for furnishing all labor, supervision, materials, equipment all
testing necessary to complete the work. Payment for providing corrosion protection on
ceiling and exposed pipe on "Typical Sanitary Manhole", grouting of pipe seals, bench and
trough and manhole walls shall be included in the Contract Unit Price for each manhole or
structure.
DA-122 PASSIVE ODOR CONTROL FOR VENTING PIPE
A. GENERAL
1. SECTION INCLUDES
a, Media Adsorption Hardware
b. Media
C. Manufacturer's Services
2. REFERENCES
11/02/04 Revised ASC-36R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
a. American Society of testing and Materials (ASTM }:
1. ASTM D-3299-88 Standard Specification for Filament Wound Glass
Fiber Reinforced Thermosetting Resin Chemically Resistant Tanks.
b. Voluntary Product Standard
1. PS 15-69
C. Uniform Building Code ( UBC }
3. DEFINITIONS
a. PPL: polypropylene
b. PVC: polyvinyl chloride
C. CFM Cubic Feet per Minute
4. SYSTEM DESCRIPTION
a. The Contractor shall furnish and install the self-contained
canister described herein. The purpose of these canisters
shall be to remove 1-12S and other odors or VOCs emanating
from ambient emissions. Each canister includes the
following:
1. Adsorber Canister
2. Media
b. The canister and media function as a system and shall be
the end products of Bay Products, Inc. or equal, to achieve
standardization for appearance, operation, maintenance,
spare parts, and manufacturer's services. . The unit must be
capable of being submersed with out the media becoming
wet.
C. There will be ( } absorption canisters required, as delineated
below:
System Quantity CFM- Vessel Dimensions
Designation maximum
VENT-A-SORB 15 30"L x 6.50"W
OCU
5. SUBMITTALS
a. Submit the following items at the same time under one
cover( 1 weeks after receipt of order):
1. Documentation to demonstrate that the reaction system is the
standard product of the supplier.
2. Documentation to demonstrate that the manufacturer has been
regularly engaged in fabricating odor control systems for at least 5
years..
3. Shop drawings and/or catalog cuts of supplied items.
b. Submit also the following ( 1 weeks after receipt of order}:
1. Installation Instructions
2. Operation and Maintenance Instructions
B. PRODUCTSv; ' � 1�, i
11/02/04 Revised ASC-37R AddenXI Y OF- �� ?
I 's'vElm, 01
PART DA - ADDITIONAL SPECIAL CONDITIONS
1. GENERAL
a. The Contract Documents indicate specific required features
of the equipment, but do not purport to cover all details of
design and construction.
2. ADSORPER CANISTER (S)
a. The self-contained, adsorber canister shall be a VENT-A-
SORB Canister, as supplied by Bay Products, Inc. (1-800-
429-8175) or equal.
u b. The adsorber canister shall be manufactured of Schedule 40
PVC, or equal. The canister shall have no moving parts.
G. The adsorber canister shall contain the carbon bed with a
polyethylene screen on both ends of mesh size 0.94"and a
weight of 96 Ibs/MSF. Adsorber design shall utilize"Plug
Flow" air distribution (the air passes through the media bed
uniformly, exiting through the outlet)
d. The canister shall have the following features:
1. Inlet: 80 ANSI 150# Flanged, PVC Sch 40
construction
2. Outlet: 2"opening with screen with 2" PVC
ball check valve with EPDM seal
e. The canister shall be rated at+/-20 psig
f. The canister shall be capable of operating at an air flow rate
of up to 15 CFM
g. The flanged inlet shall be provided with a EPDM or
Neoprene gasket for water tight seal on vent pipe.
3. MEDIA
a. The media utilized by the reactor vessel shall be provided by
the system supplier and supplied separately to be installed
by others after vessel installation.
b. MEDIA:
The amount of media (OdorSorb-max) contained is 10 pounds and shall
have the following properties:
Carbon Tetrachloride Activity (wt. %) 60 min.
Hardness Number 99% min.
Moisture Content 10% max.
Ash Content 10% max.
Mean Particle Diameter (MPD) 4 mm, pellets
Apparent Density (g/ml) 0.480 to 0.520
11/02/04 Revised ASC-38R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
Total Surface Area (N2-- BET method) 1050 to 1150 m2fgm
Ignition Temperature (ASTM) 450?C
Typical H2S Capacity 0.22 g/cc
*The determination of H2S breakthrough capacity will be
made by passing a moist ( 85% R.H. )air stream containing
1% 1-12S at a rate of 1,450 cc/min, through a 1 inch diameter
by 9 inch deep bed of uniformly packed activated carbon
and monitored to 50 ppm breakthrough. Results are
expressed in grams H2S removed per cc of carbon.
C. EXECUTION
1. MANUFACTURER'S SERVICES
a. No on-site assistance shall be required. The adsorber canister
shall come with installation instructions,which allow the operator
to install the unit without Manufacture's supervision.
2. QUALITY ASSURANCE
a. The engineer may provide and direct inspectors to inspect the
equipment at the place of manufacture or upon arrival at the job
y site. The manufacturer shall furnish all reasonable assistance, if
required by the engineer or inspector, for the proper inspection
of the work. Inspection shall not relieve the manufacturer from
any obligation to perform the work strictly in accordance with
this specification. Work not so performed shall be replaced by
the manufacturer at his own expense.
D. LOCATIONS
Odor Control devices for vent pipes are to be located at Sta.M-503R
350+67, and at RET-2538 Sta.114+58 and 126+44.
DA-123 STOP LOGS
A. GENERAL
`- 1. SCOPE
This specification relates to the design, materials of construction, fabrication of guide frames and
accessories,required for the complete and proper operation of stop logs.
The Contractor shall furnish and install guide frame in the locations and of the dimensions shown,
complete and operable,in accordance with the requirements of the Contract Documents.
Equipment provided under this item shall be fabricated, assembled, erected, and placed in proper
operating condition in full conformity with drawings, specifications, engineering data, instructions,
and recommendations of the equipment stop log manufacturers, unless exceptions are noted by the
Engineer.
2. ACCEPTABLE MANUFACTURERS FOR REFERENCE DATA
a. Rodney Hunt
11/02/04 Revised ASC-39R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
b. Waterman Industries
C. Hydro Gate Corp.
d. Others as Approved by Engineer
3. SUBMITTALS
a. Submit three copies of all materials required to establish compliance with
this section. Submittals shall include the following;
1, Complete description of all materials
2. Certified shop and installation drawings showing materials,details of
construction,dimensions,and anchorage,
3. Descriptive literature,bulletins and/or catalogs of the equipment.
4. A complete bill of materials
5. Evidence of structural analysis and testing as specified herein
6. A list of manufacturer's recommended spare parts.
b. Operation and Maintenance Data
1. Operating and maintenance instructions shall be prepared specifically for
this installation and shall include all required cuts,drawings,equipment
lists,descriptions that are required to instruct operating and maintenance
personnel unfamiliar with such equipment. The maintenance instructions
shall include trouble shooting data and full preventive maintenance
schedules.
2. A factory representative who has complete knowledge of proper operation
and maintenance shall attend the leakage test.
f 4. ALLOWABLE LEAFAGE
Stop logs shall be substantially watertight under the design head condition. The maximum
permissible leakage will be limited to 0.2 gallons per minute per foot of seating length.
S. WARRANTY
The stop log guides,and appurtenances shall be furnished by a single manufacturer who is
fully experienced,reputable,and qualified in the manufacture of the equipment.
Manufacturer shall warrant the entire stop log guide assembly from defects for a period of
two years from the date of delivery. Manufacturer representative shall attend stop log
leakage testing.
B. PRODUCTS
1. GENERAL SERVICE CONDITIONS
11/02104 Revised ASC-40R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
Service conditions are as designated on the contract drawings. The maximum
height of the guides shall meet or exceed the maximum head of water. Furnish the
total height as shown on the drawings.
1 STOP LOG GUIDE FRAME
a. Guide Frame: Stop log guide frames shall be manufactured of 6063-T6
aluminum alloy with factory welded corners. Stop log guide frames shall be
embedded into the concrete. Guide invert shall be flush with channel invert
and shall form a seating surface for the resilient seal mounted on the stop
logs. Guide seating surfaces shall be faced with bearing strips of
polyethylene or other material compatible with the stop log seal to provide
low friction operation and prevent bonding, striping, or seizure. Guides
shall be of fabricated steel with fiberglass coating or completely fiberglass,
and designed. for embedding in the concrete. All material, such as anchors
and bolts, shall be type 304 stainless steel when ever possible.
Guides shall be designed and constructed to withstand the total thrust caused
by water pressure.
b. Typical Stop Log Panels: Stop log panels shall be manufactured of one
piece extruded 6061-T6 aluminum. The stop log panel shall not deflect
more than 1/360 span of the log under the design head. The bottom of the
log shall be extruded in a manner to accept a resilient seal to provide a flush.
bottom closure. The resilient seal along the bottom of each log shall seal on
the sill plate or top of another log. Seals may also be required within the
frame guide itself in order to prevent leakage.
Furnish aluminum guide and support shoes on the ends and bottoms of each
stop log in order to hold the unit squarely in place. Stop log panels shall be
equipped with three attachment points in the top of each stop log, one in the
center and one near each end. Stop log panels shall be of sufficient weight
to resist buoyancy.
Shop drawings shall include dimensions, materials and weight as a
minimum for each piece of equipment. Drawings shall also show
fabrication, assemble and installation.
C. Typical Seals: Stop log seals shall be made of neoprene rubber and shall
provide a lip-type seal. The shape of the seal shall provide a seating surface
having a minimum width of 3/4". The seals shall be located along the
bottom of each log section and along both ends of each log and shall be
mechanically attached to the log. Adhesives alone are not an acceptable
mounting method. Attaching hardware for seals shall be stainless steel.
Seals shall be mounted in a manner that allows for easy replacement in the
event of damage.
11/02104 Revised ASC-41 R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
d. Typical Seat: Stop log seat shall be flush mounted,neoprene material.
e. Anchor Bolts and Hardware: All assembly anchor bolts and hardware shall
be stainless steel,Type 304 or Type 316. All anchor bolts and hardware
shall be furnished by the stop log manufacturer.
f Grout: Non-shrink,per specifications.
3. ALLOWABLE LENGTHS
In order to standardize stop log lengths,the Fort Worth Water Department has
limited the stop logs sizes. The Contractor shall provide a guide frames set(one per
stop log slot)and associated parts for the following:
Atiprox.Required Width Number to Provide
8.7' 66
The Contractor shall contact the City of Fort Worth to verify the exact dimensions
of existing stop logs.
C. EXECUTION
1. INSTALLATION
a. Stop log assemblies shall.be installed in strict accordance with the
manufacturer's printed recommendations and the requirements herein.
b. During construction,the surfaces of the guide frame and stop log panels
shall be covered or otherwise protected from.concrete spillage,paint,or
debris. Any damage that occurs to the stop log assembly shall be corrected
prior to installation and testing of the stop log assembly.
C. Guide frames shall be accurately positioned and supported to prevent
shifting during the pouring of concrete or grouting, Guide frames shall be
carefully braced both horizontally and vertically to prevent distortion.
Guides shall be installed in a true vertical plane. If there are any difficulties
in operation of the equipment due to the manufacturer's fabrication or the
contractor's installation,additional service shall be provided at no additional
cost to the owner,
The Contractor is responsible to provide adequate clearance(per
manufacturer)between the stop log and the guide frame.
11/02/04 Revised ASC-42R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
d.. Field Leakage Test: A field leakage test shall be performed by the
Contractor after installation of the stop log frame assembly. The
manufacturer shall be notified of the test in sufficient time to enable him to
have a representative present at the test. In the event that the unit fails the
leakage test,the necessary changes shall be made and the unit reinspected
and retested. If any unit remains unable to meet the test requirements,it
shall be removed and replaced with satisfactory equipment at no additional
cost to the owner.
e. The stop logs to be used on this project are owned by the City. The
Contractor shall contact the project representative to obtain stop logs prior
to the completion of the junction structures with stop log slots. These logs
will be available for temporary use. The logs shall also be used to verify
there proper fit once the structure is in service as stated previously.
f. The City has the right to withhold payment until the junction structure stop
logs operation has been determined to be satisfactory.
DA-124 REINFORCED CONCRETE PIPE
Description. This Item shall govern reinforced concrete pipe (RCP)ASTM C76.
Approved manufacturer is Hanson Pipe & Products or approved equal. Installation and
testing shall equal or exceed the manufacturer's standards, but not override Fort Worth
standards.
The Contractor shall verify the pipe class breakout below, as information may be different
per manufacturer or installation conditions. The class of pipe below is based on HS20
traffic loads, the ground cover and flood levels indicated on the plans, bedding type 2, soil
density at 120 Ib/cft, class B wall thickness and a maximum trench width of OD +4': The
criteria of determining the class of pipe does not override the specification in other
locations of the contract documents.
Start End
Station Station Diameter Class
M-503R 350+22 353+75 54" III
353+75 355+75 54" IV
355+75 361+18 54" 111
M-257R 95+19 95+85 39" 111
95+85 97+27 54" 111
105+80 126+44 54" 111
126+44 127+05 36" 111
Contractor shall not use the Fort Worth Water Department Material Specification E2-9.7c
Exfiltration Test Pneumatic Method: Air Test. The Contractor shall test according to the
11/02/04 Revised ASC-43R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
current edition of NCTCOG - Standard Specification for Public Works, 6.72f Low Pressure
Air Test—3) Test Methods. The Time Pressure Drop Method will be used for this project
DA-125 MYERS PROPERTY RESTORATION
The Myers property work area will be limited to the existing and proposed easements. All
construction vehicles shall enter the property from the north (Kay Dr.)with all trenched material
hauled off site. Orange construction fencing will be placed along easements. Contractor shall not
proceed off the easement without prior permission. All areas disturbed by the Contractor shall be
graded with 5" of sand loam topsoil and replanted with Bermuda coastal grass sprigs per owner's
instructions. Sprigs will be obtained and delivered by the Contractor. Coastal Bermuda grass
shall be spread over disturbed areas between the spring to early summer season. Sprig
replanting will require rolling and watering.
The construction activities shall not turn off the water supply to the K- Mar Mobile Home Park for
any extended duration. Contractor shall use the shut-off valve along Kay Dr. on the north side of
the mobile home park. Opening and closing of this valve shall be done at a slow pace to avoid
damaging existing water lines in the mobile home park.
The Contractor will provide a 6" flex base road near Junction Structure 2 as shown on the plans.
DA-126 FILTER FABRIC
A. DESCRIPTION
Filter fabric is to be use to support and reduce vegetation under proposed stone roadways
and parking areas as shown in the plans.
A. INSTALLATION: The geotextile shall be placed in the manner and at the locations shown on
the drawings. At the time of installation, the geotextile shall be rejected if it has defects, rips,
holes, flaws, deterioration or damage incurred during manufacture, transportation or storage.
The surface to receive the geotextile shall be prepared to a relatively smooth condition free of
obstructions, depressions, debris, and soft or low density pockets of material. Erosion
features such as rills, gullies, etc. must be graded out of the surface before geotextile
placement. The geotextile shall be placed with the long dimension perpendicular to the
centerline of the channel, if applicable, and laid smooth and free of tension, stress, folds,
wrinkles, or creases. The strips shall be placed to provide a minimum width of 24-inches of
overlap for each joint. Temporary pinning of the textile to help hold it in place until the rock is
placed. The temporary pins shall be removed as the rock is placed to relieve high tensile
stress which may occur during placement of material on the geotextile. The specified
placement procedure requires that the length of the geotextile be greater than the actual
slope length. The Contractor shall adjust the actual length of the geotextile used based on
initial installation experience. The geotextile shall be protected at all times during construction
from contamination by surface runoff and any geotextile so contaminated shall be removed
and replaced with uncontaminated geotextile. Any geotextile damaged during its installation
or during placement of riprap shall be replaced by the Contractor at no cost to the Owner.
The work shall be scheduled so that the covering of the geotextile with a layer of the specified
material is accomplished within seven (7) calendar days after placement of the geotextile.
Failure to comply shall require replacement of geotextile. The geotextile shall be protected
from damage prior to and during the placement of rock. Before placement of gablon units,
11/02/04 Revised ASC-44R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
the Contractor shall demonstrate that the placement technique will prevent damage to the
geotextile. in no case shall any type of equipment be allowed on the unprotected geotextile.
B. REQUIREMENTS
The fiber fabric manufacture must be on the City approved product list or approved by the
Engineer.
C. PAYMENT
- This item is incidental to the project
DA-127 FLOWABLE FILL
A. DESCRIPTION
Flowable is to placed in abandoned utilities lines as stated in the plans. The material must be
able to fill the indicated pipe with the appropriate.equipment.
B. INSTALLATION
Flowable fill shall be installed into manholes or openings in the indicated locations per
supplier recommendations. Flowable fill may need to be vibrated to place the material.
Delivery of the material into the pipe could be by mixing truck or pump truck depending on the
situation.
C. Material
The material and ingredients of the flowable fill shall be approved by the City. The material
must be non-hazardous. Acceptable mix designs are Southern Star mix X0034 or approved
equal. The mix shall have compressive strength of 250 psi at 28 days and an air entrainment
of approximately 25%. The mix includes:
50 lbs cement
300lbs ash
2400 lbs sand
215 lbs water
3 oz WR Grace Darafill (air entrainer)
D. Payment
Payment of Flowable fill is incidental to the abandonment pay item.
DA-128 NEW STRUCTURE INTERIOR MANHOLE COATING - RAVEN LINING SYSTEM
This specification covers work, materials and equipment required for protecting and/or
rehabilitating concrete and masonry manholes and other underground structures by monolithic
spray-application of a high-build, solvent-free epoxy coating to eliminate infiltration, provide
corrosion protection, repair voids and enhance structural integrity. Procedures for surface
preparation, cleaning, application and testing are described
PART 1 GENERAL
1. SECTION INCLUDES
11/02/04 Revised ASC-45R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
A. Requirements for surface preparation, repairs and solvent-free epoxy coating
application to specified surfaces.
2. RELATED SECTIONS
A. Concrete Repair.
B. Environmental, Health and Safety.
3. REFERENCES
A. ASTM D638-Tensile Properties of Plastics.
B. ASTM D790- Flexural Properties of Unreinforced and Reinforced
Plastics.
C. ASTM D695-Compressive Properties of Rigid Plastics.
D. ASTM D4541 - Pull-off Strength of Coatings Using a Portable Adhesion
Tester.
E. ASTM D2584-Volatile Matter Content.
F. ASTM D2240- Durometer Hardness, Type D.
G. ASTM D543- Resistance of Plastics to Chemical Reagents.
H. ASTM C109 - Compressive Strength Hydraulic Cement Mortars.
1. ACI 506.2-77- Specifications for Materials, Proportioning, and
Application of Shotcrete.
J. ASTM C579- Compressive Strength of Chemically Setting Silicate and
Silica Chemical Resistant Mortars.
K. ASTM-The published standards of the American Society for Testing
and Materials, West Conshohocken, PA.
L. NAGE-The published standards of National Association of Corrosion
Engineers (NAGE International), Houston, TX
M. SSPC-The published standards of the Society of Protective Coatings,
Pittsburgh, PA.
N. Los Angeles County Sanitation District—Evaluation of Protective Coatings for
Concrete
O. SSPWC 210-2.3.3- Chemical resistance testing published in the Standard
Specifications for Public Works Construction, 1997 edition (otherwise known as
"The Greenbook")
4. SUBMITTALS
A. The following items shall be submitted:
1. Technical data sheet on each product used, including ASTM test results
indicating the product conforms to and is suitable for its intended use per
these specifications.
2. Material Safety Data Sheets (MSDS)for each product used.
3. Project specific guidelines and recommendations.
4. Applicator Qualifications:
a. Manufacturer certification that Applicator has been trained and
approved in the handling, mixing and application of the products to
be used.
b. Certification by the protective coating manufacturer that the
equipment to be used for applying the products has been approved
and Applicator personnel have been trained and certified for proper
use of the equipment.
C. Two (2) years contracting experience under current company name
and three (3) recent references of projects of similar size and
11/02/04 Revised ASC-46R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
scope, Applicator must also provide references indicating
successful application on underground concrete or masonary
substrates of a minimum 10,000 of of 100% solids, high-build
solvent-free epoxy coating by heated, plural component spray
application.
d. Proof of any necessary federal, state or local permits or licenses
necessary for the project.
5. Design details for any additional ancillary systems and equipment to be used in
site and surface preparation, application and testing.
6. Or Equal Submittal: In order to be considered as an equal product, said
product will have to meet the minimum characteristics as measured by the
applicable ASTM standards referenced in paragraph Part 2. 4 as measured by
the applicable ASTM standards referenced in paragraph Part 1.3. Testing
results must be performed and presented by a bonded, third-party testing
laboratory.
Note: Equal products must be approved a minimum of two (2) weeks prior to
bid date. In order for a product to be considered equal the submitted product
must provide proof of successfully passing the Los Angeles County Sanitation
Districts Coating Evaluation Study or evidence from the City of Los Angeles
Department of General Services Standards Division indicating the Department
tested and the product "passed" SSPWC Section 210-2.3 Chemical
Resistance Test. An applicator that has been trained and certified by the
manufacturer must install all products.
Prior pre-approval is required to determine if the prospective product may be
bid on this project. A product may be rejected as unacceptable should
submittal to Owner not be received a minimum of two (2) weeks prior to bid
- date.
5. QUALITY ASSURANCE
A. Applicator shall initiate and enforce quality control procedures consistent with
applicable ASTM, NACE and SSPC standards and the epoxy coating
manufacturer's recommendations.
B. A NACE certified coating inspector ("Inspector") shall be provided by Owner. The
Inspector will observe surface preparation, application and material handling
procedures to ensure adherence to the specifications.
6. STORAGE AND HANDLING
A. Products are to be kept dry, protected from weather and stored under cover.
B. Products are to be stored and handled according to their material safety data
sheets.
7. SITE CONDITIONS
A. Applicator shall conform with all local, state and federal regulations including those
set forth by OSHA, RCRA and the EPA and any other applicable authorities.
& WARRANTY
A. Applicator shall warrant all work against defects in materials and workmanship for
a period of one (1)year, unless otherwise noted, from the date of final acceptance
of the project. Applicator shall, within a reasonable time after receipt of written
notice thereof, repair defects in materials or workmanship which may develop
during said one (1) year period, and any damage to other work caused by such
defects or the repairing of same, at his own expense and without cost to the
Owner.
11/02104 Revised ASC-47R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
PART 2 - PRODUCTS
1. EXISTING PRODUCTS
A. Standard Portland cement or new concrete (not quick setting high strength
cement) must be well cured prior to application of the epoxy coating.
B. Cementitious patching and repair materials should not be used unless proof of
suitability and procedures for topcoating with an epoxy coating are approved by
the epoxy coating manufacturer. Project specific submittals should be provided
including application, cure time and surface preparation procedures which permit
optimum bond strength with the epoxy coating.
C. Remove existing coatings prior to application of the new epoxy coating. Applicator
is to maintain strict adherence to applicable NACE and SSPC recommendations
with regard to proper surface preparation and compatibility with existing coatings.
2. EPDXY COATING MANUFACTURER
A. Raven Lining Systems, Inc., Tulsa, Oklahoma 800-324-2810 or 918-584-2810 or
FAX 918-582-4311.
B. Pre-approved equal.
3. REPAIR MATERIALS
A. Repair materials shall be used to fill voids, structurally reinforce and/or rebuild
surfaces, etc. as determined necessary by the Owner and epoxy crating
applicator. Repair materials must be compatible with the specified epoxy coating
and shall be applied in accordance with the manufacturer's recommendations.
B. The following products may be accepted and approved as compatible repair
basecoat materials for epoxy topcoating for use within the specifications:
- 1. 100% solids, solvent-free epoxy grout specifically formulated for epoxy
topcoating compatibility. The epoxy grout manufacturer shall provide
instructions for trowel or spray application and for epoxy topcoating
procedures.
2. Factory blended, rapid setting, high early strength, fiber reinforced, non-
shrink repair mortar that can be trowelled or pneumatically spray applied
may be approved if specifically formulated to be suitable for epoxy
topcoating.
4. EPDXY COATING
A. Raven Lining Systems' Raven 405 epoxy coating system - a 100% solids, solvent-
free two-component epoxy resin system thixotropic in nature and filled with select
fillers to minimize permeability and provide sag resistance acceptable to these
specifications, shall be applied at 125 mil average thickness.
Product type Amine cured epoxy
Color Light Blue
Solids Content (vol %) 100
Mix Ratio 3:1
Compressive Strength, psi 18,000
Tensile Strength, psi 7,600
Tensile Elongation, % 1.50
Flexural Modulus, psi 600,000
Hardness, Type D 88
Bond Strength -Concrete >Tensile Strength of Concrete
11/02/04 Revised ASC-48R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
Chemical Resistance:
Severe Municipal Sewer: All types of service
Successful Pass: Sanitation District of L.A. County
Coating Evaulation Study
or SSPWC 210.2.3.3
5. EPDXY COATING APPLICATION EQUIPMENT
A. Manufacturer approved heated plural component spray equipment shall be used
in the application of the specified epoxy coating.
6. REPAIR MATERIAL SPRAT'APPLICATION EQUIPMENT (if spray applied)
A. Spray applied repair materials shall be applied with manufacturer approved
equipment.
PART 3-EXECUTION
1. ACCEPTABLE APPLICATORS
A. Repair material applicators shall be trained to properly apply the cementitious
mortar according to manufacturers recommendations.
B. Epoxy coating must be applied by a Certified Applicator of the epoxy coating
manufacturer and according to manufacturer specifications,
2. EXAMINATION
A. All structures to be coated shall be readily accessible to Applicator.
B. Appropriate actions shall be taken to comply with local, state and federal
regulatory and other applicable agencies with regard to environment, health and
safety,
C. Any active flows shall be dammed, plugged or diverted as required to ensure that
the liquid flow is maintained below the surfaces to be coated. Flows should be
totally plugged and/or diverted when coating the invert. All extraneous flows into
the manhole or vaults at or above the area coated shall be plugged and/or diverted
until the epoxy has set hard to the touch.
D, Installation of the epoxy coating shall not commence until the concrete substrate
has properly cured in accordance with these specifications.
E. Temperature of the surface to be coated should be maintained between 40 deg
F and 120 deg F during application. Prior to and during application, care should
be taken to avoid exposure of direct sunlight or other intense heat source to the
structure being coated.
3. SURFACE PREPARATION
A. Applicator shall inspect all specified surfaces prior to surface preparation.
Applicator shall notify Owner of any noticeable disparity in the surfaces which may
interfere with the proper preparation or application of the repair material and/or
epoxy coating.
B, Applicator shall perform all surface preparation and epoxy coating installation.
C. All contaminants including: oils, grease, incompatible existing coatings, waxes,
form release, curing compounds, efflorescence, sealers, salts, or other
contaminants shall be removed. All concrete or mortar that is not sound or has
been damaged by chemical exposure shall be removed to a sound concrete
surface or replaced.
D. Surface preparation method(s) should be based upon the conditions of the
substrate, service environment and the requirements of the repair materials and/or
epoxy coating to be applied. Surfaces to receive repair materials and/or epoxy
11/02/04 Revised ASC-49R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
coating shall be cleaned and abraded to produce a sound surface with adequate
profile and porosity to provide a strong bond between the repair materials and/or
epoxy coating and the substrate.
E. Infiltration shall be stopped by using a material which is compatible with the repair
materials and is suitable for topcoating with the epoxy coating.
F. All surfaces should be inspected by the Inspector during and after preparation and
before the repair material is applied.
s 4. APPLICATION OF REPAIR MATERIALS
A. Areas where structural steel has been exposed or removed shall be repaired in
accordance with the Owner's recommendations.
B. Repair materials shall meet the specifications herein. The materials shall be
trowel or spray applied utilizing proper equipment on to specified surfaces. The
material thickness shall be specified by the Owner according to the projects'
requirements and manufacturer's recommendations.
C. Cementitious repair materials shall be trowelled to provide a smooth surface with
an average profile equivalent to coarse sandpaper to optimally receive the epoxy
coating. No bugholes or honeycomb surfaces should remain.
D. The repair materials shall be permitted to cure according to manufacturer
recommendations. Curing compounds should not be used unless approved for
compatibility with the specified epoxy coating.
E. After abrasive blast and leak repair is performed, all surfaces shall be inspected
for remaining laitance prior to epoxy coating application. Any evidence of
remaining contamination or laitance shall be removed by additional abrasive blast,
shotblast or other approved method. If repair materials are used, refer to these
specifications for surface preparation. Areas to be coated must also be prepared
in accordance with these specifications after receiving a cementitious repair
material and prior to application of the epoxy coating.
F. All surfaces should be inspected by Inspector during and after preparation and
before the epoxy coating is applied.
5. APPLICATION OF EPDXY COATING
A. Application procedures shall conform to the recommendations of the epoxy coating
manufacturer, including material handling, mixing, environmental controls during
application, safety, and spray equipment.
B. The spray equipment shall be specifically designed to accurately ratio and apply
the specified epoxy coating materials and shall be regularly maintained and in
proper working order.
C. The epoxy coating material must be spray applied by a Certified Applicator of the
epoxy coating manufacturer.
D. Specified surfaces shall be coated by spray application of a moisture tolerant,
solvent-free, 100% solids, epoxy coating as further described herein.. Spray
application shall be to a minimum wet and dry film thickness as defined below:
Concrete, New/Smooth Manholes: 125 mils average for immersion, 60-80 mils
average for atmospheric, splash and spill
service
Concrete, New/Smooth Lift Stations 125 mils average, thicker coating
Wet Wells or Junction Boxes: may be required based upon prepared
surface profile
11/02104 Revised ASC-50R Addendum 1
PART DA - ADDITIONAL SPECIAL CONDITIONS
Concrete, New/Smooth Deep 125 mils average, thicker coating
- Tunnel Shafts or RCP Pipe: may be required based upon prepared
surface profile.
F. If necessary, subsequent topcoating or additional coats of the epoxy coating
should occur as soon as the basecoat becomes tack free, but no later than the
recoat window for the specified products. Additional surface preparation
procedures will be required if this recoat window is exceeded.
G. (Optional) Fiberglass woven-roving fabric may be rolled into the resin or chopped
glass spray applied with the resin for added tensile and flexural strength where
desired. Sloped surfaces of the floor may be made non-skid by broadcasting
aluminum oxide or silica sand into the surface prior to gelation.
H. (Optional) Depending on flow levels and how long flow can be stopped, inverts
may be lined with an approved 100% solids, fast setting epoxy coating.
6. TESTING AND INSPECTION
A. During application, Applicator shall regularly perform and record epoxy coating
thickness readings with a wet film thickness gage, such as those available through
Paul N. Gardner Company, Inc. meeting ASTM D4414 - Standard Practice for
Measurement of Wet Film Thickness of Organic Coatings by Notched Gages, to
ensure a monolithic coating and uniform thickness during application. A minimum
of three readings per 200 square foot area shall be recorded. Applicator will
submit all documentation on thickness readings to Inspector on a daily basis when
coating application occurs.
B. Applicator may perform holiday detection on all surfaces coated with the epoxy
coating in the presence of Inspector. After the epoxy coating has set hard to the
- touch, surfaces shall first be dried, an induced holiday may then be made on to the
coated concrete surface and shall serve to determine the minimum/maximum
voltage to be used to test the coating for holidays at that particular area. The
spark tester shall be initially set at 100 volts per 1 mil (25 microns)of film thickness
applied but may be adjusted as necessary to detect the induced holiday (refer to
NACE RP0188-99). All detected holidays shall be marked and repaired by
abrading the coating surface with grit disk paper or other hand tooling method.
After abrading and cleaning, additional epoxy coating material can be hand applied
to the repair area. All touch-up/repair procedures shall follow the epoxy coating
manufacturer's recommendations. (Note: This procedure is sometimes difficult or
impossible to perform in tight manhole or vault structures or may provide unreliable
readings when testing coatings applied to concrete.)
C. Upon Owner's request a minimum of 10% of the total structures coated in each
basin and or subdivision may be subjected to random adhesion (bond) testing per
this section. Measurement of bond strength of the epoxy coating to the substrate
may be examined in accordance with ASTM D4541. Any areas detected to have
inadequate bond strength shall be evaluated by the Owner.
The adhesion (bond) testing shall be conducted by using 3 test dollys per
structure. One test dolly shall be affixed within 2 ft of the bench arealbottom of
structure, one test dolly shall be affixed in the middle of the structures wall area
and the final test dolly shall be affixed within two foot of the top of the chimney
area/top of the structure. Further bond tests may be performed in that area to
11/02/04 Revised ASC-51 R Addendum 1
x
PART DA - ADDITIONAL SPECIAL CONDITIONS
determine the extent of potentially deficient bonded area and repairs shall be
made by Applicator in strict accordance with manufacturer's recommendations.
D. (Optional) Manholes coated in their entirety may be vacuum tested. All pipes
entering the manhole should be plugged, taking care to securely place the plug
from being drawn into the manhole. The test head shall be placed and the seal
inflated in accordance with the manufacturer's recommendations. A vacuum pump
of ten (10) inches of mercury shall be drawn and the vacuum pump shut off. With
the valves closed, the time shall be measured for the vacuum to drop to nine (9)
inches. Following are minimum allowable test times for manhole acceptance at
the specified vacuum drop:
DEPTH (FEET) TIME (SECONDS)
48"diameter 60"diameter 72" diameter
4 10 13 16
8 20 26 33
12 30 39 49
16 40 52 67
20 50 65 81
24 59 78 97
Add for 2ft. more depth: 5 6.66 8
Note: These numbers have been taken from ASTM C 1244-93(reapproved 2000).Latest standard edition will
govern.
If the manhole fails the initial test, repairs and adjustments necessary due to
extenuating circumstances (ie, pipe joint, liner, plug sealing) should be made.
Retesting shall proceed until a satisfactory test is obtained.
E. A final visual inspection shall be made by the Inspector and Applicator. Any
deficiencies in the finished coating shall be marked and repaired by Applicator
according to the procedures set forth herein.
F. The municipal sewer system may be put back into non-severe operational service
as soon as the final inspection has taken place. Consult epoxy coating
manufacturer for further recommendations.
PART 4
1. MEASUREMENT AND PAYMENT
Payment shall be based on the Contract Unit Price per vertical foot for manholes and
incidental to the Contract Unit Price per Structure 1 and Structure 2, measured from the
bottom of the frame to the top of the bench. The Contract Unit Price shall be payment in full
for performing the work and for furnishing all labor, supervision, materials, equipment all
testing necessary to complete the work. Payment for providing corrosion protection on
ceiling and top of exposed pipe on "Typical Sanitary Manhole" (5' diameter), grouting of pipe
seals, bench and trough and manhole walls shall be included in the Contract Unit Price for
each manhole or structure.
11/02/04 Revised ASC-52R Addendum 1
�s r
i
PART DA - ADDITIONAL SPECIAL CONDITIONS
END OF SECTION
11/02/04 Revised ASC-53R Addendum 1
I 1EI l I�I W
ACKFILL
SEEESPEC BE1-2.4
MINIMUM 6" INITIAL — I(— G.C.D.
BACKFILL COVER " +```
SAND MATERIAL EMBEDMENT
INITIAL BACKFILL
=III II- O
>� SEE SPEC. E1-2.3 G.C.D. LL_
MINIMUM 6`
EMBEDMENT I I I1—
III-III-I I: Z
—III—III—III=III=III=III— —
WATER: SIZES UP TO AND INCLUDING 12" J
U
Ln m
TYPE "C` BACKFILL
SEE SPEC. E1-2.4 F_
MINIMUM INITIAL BACKFILL COVER; G.C.D.
WATER — 6" _ �t _- '�-'~ III: W
SEWER — 12` I CRUSHED STONE OR SAND
I�-I-" - >- III o
STORM DRAIN — 12" _ MATERIAL INITIAL BACKFILL
SEE SPEC. E1-2.4(b) OR m
m—M
IEt-2.3 G.C.D. WMINIMUM 6"
EMBEDMENT =1 I I-_° CRUSHED STONE z
— III I I I I I I I I I I I I I I I I I I I I I I I I I G.C.D.SEE EC. E1-2.3 z
O
WATER: SIZES 16" AND LARGER =
SEWER: ALL SIZES cn
STORM DRAIN: ALL SIZES
4
F—
W
MATERIAL SPECIFICATIONS
— Q
SAND GRADATION L.Li
*LESS THAN 10% PASSING 0
#200 SIEVE THE EMBEDMENT AND BACKFILL DETAILS PROVIDED ON THIS co
P.I. = 10 OR LESS SHEET SHALL REPLACE APPROPRIATE PROVISIONS OF BOTH
J
THE EI-2.4(b) AND E1-2.3 OF THE G.C.D. AND STD. SPEC. O
ITEM 402 OF THE TPW STANDARD SPECIFICATIONS FOR Of
STREET & STORM DRAIN CONSTRUCTION. ALL OTHER
CRUSHED STONE GRADATION PROVISIONS OF THESE ITEMS SHALL APPLY. z
O
SIEVE SIZE % RETAINED U
1" 0-10
1/2' 40-75 WATER, SEWER & STORM DRAIN Q
3/80 55-90 EMBEDMENT AND ._BACKFILL DETAILS w
#4 90=100 ..-- _ _.. _ _.._ _. _ 0
#8 95-100 CITY OF FORT WORTH—CONSTRUCTION STANDARD cn
FIGURE A DATE:2-19-02 I—
TABLE OF CONTENTS
Part A-Notice to Bidders
Special Instructions to Bidders (Water Department)
City of Fort Worth Minority/Women Business Enterprise Policy
Part B -Proposal
Part C - General Conditions
Part C1 —Supplementary Conditions to section C
Part D- Special Conditions
Part DA-Additional Special Conditions
Certificate of Insurance
Part F-Bonds (City of Fort Worth)
0 Performance Bond
0 Payment Bond
0 Maintenance Bond
Part G-Contract(City of Fort Worth)
Appendix A-Easement
G.IFW0 W591SpewlContrad I-ray1X.dx
TC-1
Part A - Notice to Bidders
NOTICE TO BIDDERS
Sealed proposals for the following
For: Village Creek Drainage Basin Contract LXIX(69)—Contract 1,
D.O.E.No.4157
Sewer Project No.PS58-070580176170
Water Project No.PW53-060530177980
Addressed to Mr. Charles R. Boswell, City Manager of the City of Fort Worth, Texas, will be received at
the Purchasing Office until 1:30 P.M., Thursday June 30,2005, and then publicly opened and read aloud at
2:00 P.M. in the Council Chambers. Plans for this project may be obtained at the office of the Department
of Engineering,Municipal Office Building, 1000 Throck morton Street,Fort Worth,Texas. One set of plans
and documents will be provided for a fee of sixty dollars ($60.00), such deposit being non-refundable.
Additional sets may be purchased on a nonrefundable basis for sixty dollars($60.00)per set.
There will be a pre-bid conference Tuesday June 21, 2005 at 11:30 am, in the Transportation and
Public Works Conference Room No. 270, 2°d floor, City Municipal Building, 1000 Throckmorton
Street,Fort Worth,Texas 76102.
Bid security is required in accordance with the Special Instruction to Bidders. Bidders are responsible for
obtaining all Addenda to the contract documents and acknowledging receipt of the Addenda by initialing the
appropriate spaces on the PROPOSAL form. Bids that do not acknowledge receipt of all Addenda maybe
rejected as being non-responsive. Information regarding the status of Addenda may be obtained by
contacting the Department of Engineering at 817-392-7910.
The Affidavit Statement of the City of Fort Worth Minority and Women Business enterprises Specifications
must be submitted with the bid at the time of bid opening. Failure to submit the affidavit statement with the
bid shall result in the rejection of the bid as non-responsive.
For additional information concerning this project,please contact Gopal Sahu, P.E., City Project Manager,
at 817-392-7949 or Joseph C. Masterson, P.E. (Project Manager)and Kent Lunda,P.E. (Project Engineer),
r at 817-339-8950.
Advertising Dates:
May 26,2005
June 2,2005
Fort Worth,Texas
G:TW03100591SpealContract 1-KayWB.doc
NB-1
+.
,R PART A - COMPREHENSIVE NOTICE TO BIDDERS
Sealed proposals for the following:
For: Village Creek Drainage Basin Contract LM(69)—Contract 1,
D.O.E.No.4157
Sewer Project No.PS58-070580176170
Water Project No.PW53-060530177980
Addressed to Mr. Charles R. Boswell, City Manager of the City of Fort Worth, Texas, will be received at
the Purchasing Office until 1:30 P.M.,Thursday June 30, 2005, and then publicly opened and read aloud at
2:00 P.M. in the Council Chambers. Plans for this project may be obtained at the office of the Department
of Engineering,Municipal Office Building, 1000 Throckmorton Street,Fort Worth,Texas. One set of plans
and documents will be provided for a fee of sixty dollars ($60.00), such deposit being non-refundable.
Additional sets may be purchased on a nonrefundable basis for sixty dollars($60.00)per set.
All bidders will be required to comply with Provisions 5159a of"Vernon's Annotated Civil Statutes"of the
State of Texas with respect to the payment of prevailing wage rates and City Ordinance No. 7278, as
amended by City Ordinance No. 7400, Fort Worth City Code Sections 13-A-21 through 13-A-29),
prohibiting discrimination in employment practices.
There will be a pre-bid conference Tuesday June 21, 2005 at 11:30 am, in the Transportation and
Public Works Conference Room No. 270, 2°d floor, City Municipal Building, 1000 Throckmorton
Street,Fort Worth,Texas 76102.
The major work on the above project shall consist of the following:
17 EA 5'Diameter Manholes
12 LF 4'Diameter Manholes
3303 LF 54-inch Sanitary Sewer by Open Cut
2277 LF 8-inch Sanitary Sewer by Open Cut
2 EA Junction Structures
2457 LF 84nch Water Line by Open Cut
9 EA 8-inch Gate Valve and Boz
Included in the above will be all other miscellaneous items of construction as outlined in the Plans and
Specifications. The improvements included in this project must be performed by a contractor who is pre-
qualified by the Traffic Department at the time of bid opening. The procedures for pre-qualification are
outlined in the"Special Instructions to Bidders(Transportation and Public Works)".
The City reserves the right to reject any and/or all bids and waive any and/or all formalities. AWARD OF
CONTRACT: No bid may be withdrawn until the expiration of ninety (90) days from the date the
MBE/WBE UTILIZATION FORM, PRIME CONTRACTOR WAIVER FORM and/or the GOOD FAITH
EFFORT FORM("Documentation")as appropriate is received by the City. The award of contract,if made,
will be within ninety(90) days after this documentation is received,but in no case will the award be made
until all the necessary investigations are made as to the responsibility of the bidder to whom it is proposed to
award the contract.
Bidders are responsible for obtaining all addenda to the contract documents and acknowledging receipt of
the addenda by initialing the appropriate spaces on the PROPOSAL form. Bids that do not acknowledge
G:TW031005MpecslContract 1-KayWB2.doc CNB-1
PART A - COMPREHENSIVE NOTICE TO BIDDERS
receipt of all addenda may be rejected as being non-responsive. Information regarding the status of addenda
may be obtained by contacting the Department of Engineering at(817)392-7910.
Bidders shall not separate, detach or remove any portion, segment or sheets from the contract
document at any time. Bidders shall submit complete specifications book or risk rejection of bid. In
accord with the City of Fort Worth Ordinance, No. 15530, the City of Fort Worth has goals for the
participation of minority enterprises and women business enterprises in City contracts. A copy of the
Ordinance can be obtained from the Office of the City Secretary. The Bidder shall submit the
MBE/WBE UTILIZATION FORM, PRIlVIE CONTRACTOR WAIVER FORM and/or the GOOD
FAITH EFFORT FORM ("Documentation") as appropriate. The documentation must be received
by the contracting department no later than 5:00 PM, five (5) City business days after the bid
opening date. The bidder shall obtain a receipt from the appropriate employee of the contracting
department to whom the delivery was made. Such receipt shall be evidence that Documentation was
received by the City. Failure to comply shall render the bid non-responsive.
The Managing Department for this project is the Department of Engineering.
For additional information concerning this project, please contact Mr. Gopal Sahu, P.E., City Project
Manager, at 817-392-7949 or Joseph C.Masterson, P.E. (Project Manager) and Kent Lunski,P.E. (Project
Engineer),at 817-339-8950.
Charles R Boswell
City Manager
Marty Hendrix
City Secretary
A.Douglas Rademaker,P.E.,Director
Department of Engineering
t
Rick Trice,P.E.
Assistant Director
Advertising Dates:
May 26,2005
June 2,2005
Fort Worth,Texas
.s
C.Documents and SettingslsahuglLocal Settings7emporary Internet Fi1es10LK7BINB2.doc CNB-2