HomeMy WebLinkAboutOrdinance 7813 ORDINANCE NO., AN ORDINANCE AMENDING SECTION 415, SECTION 1002 (b) (1) , SEC°PION 1507, AND SECTION 1509 OF EX- HIBIT "A" OF THE MECHANICAL CODE OF THE CITY OF FORT WORTH, BY ADDING A DEFINITION FOR A MACHINERY ROOM TO SECTION 415, BY REQUIRIN(.3 'ITIAT AN APPROVED REIN- FORCED VAPOR BARRIER HAVE A PERM RATING OF NOT GREATER THAN 0.3 PERMS, AS DETERMINED BY ASTM E96, PROCEDURE A IN SECTIOp."7 1002(b) (1) , BY ADDING A RE- QUIREMENT FOR A FIRE RESISTIVE SEPARATION IN ANY ROOM OR SPACE CONTAINING A FUEL-FIRED APPLIANCE TO SECTION 1507, AND BY OMITTING THE WORD "ELECTRICAL" AT THE BEGINNING OF' THE SECOND PARAGRAPH OF SECTION 1509; PROVIDING THAT THIS ORDINANCE SHALL BE CUMULA- TIVE OF ALL OTHER ORDINANCES OR PROVISIONS OF THE MECHANICAL CODE OF THE CITY OF FORT WORTH;REPEALING ALL ORDINANCES OR PROVISIONS OT.,' THE MECHANICAL CODE OF THE CITY OF FORT WORT11 IN CONFLICT HEREWITH; PRO- VIDING A SAVINGS CLAUSE, PROVIDING A SEVERABILITY CLAUSE; PROVIDING A PENAL CLAUSE; DIRECTING PUBLICA- TION; AND NAMING AN EFFECTIVE DATE. BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF FORT WORTH, TEXAS: SECTION 1. That Section 415 - "Machinery Room" - of Chapter 4 - "Defini- tions and Abbreviations" - of Exhibit "A", attached to and incor- porated by reference in the Mechanical Code of the City of Fort Worth (Ordinance No. 7634 duly adopted by the Fort Worth City Council on April 12, 1977) , be and the same is hereby amended to read as follows: "Section 415 "MACHINERY ROOM, Is a room or space housing Group 1 Refrigeration equipment totaling 100 horse- power or more and all Group 2 Refrigeration equip- ment regardless of capacity. This room or space shall have a minimuit of one hour fire-resistive con- struction with all interior openings protected and all doors self closing." SECTION 2. That Subparagraph (b) - "Noni�'tetallic" - of Section 1002 - "Material" - of Chapter 10 - "D�.tcts" - of Exhibit "A", attached to and incorporated by reference in the Mechanical Code of the City of Fort worth (Ordinance No. 7634 duly adopted by the Fort Worth City Council on April 12, 1977) , be and the same is hereby amended to read as follows: "Section 1002. (b) ,,Nonmetallic. iqonmetallic dr,,ict systems shall be approved Tar the use intelided or shall conform to the requirements (-.)f the U.M.C. Standard No. 10-1. Each portion of a Non me tall.i c duct system shall be identified by a label or other suitable identifica- tion. "Nonmetallic fiberglass d u(:,:t systems shall conform to the followia,jq: "l. Shall be a Class 1 Air Duct in accordance with U.L. 181 Test, as required by NFPA-90A. Facing material for round fiberglass ducts and duct board shall have a perm rating of not greater than 0.05 perms. Insu.,Lation material for insulated flexible duct shall be sheathed with an approved reinforced vapor barrier having a perm rating of not greater than 0.3 perms, as determined by ASTM-E96, Procedure A. "Shall have a thermal conductivity (C) at 75 0 F of not greater than .24. C=Btu/hr, sq. ft. deg. F. (ASTM C 177-71 test) . "Shall not be installed where they will be ex- posed to the weather. " SEC',TION 3. That the following subparagraphs of Section 1507 - "Machinery Rooms" - and Section 1509 ­ "Equipment In a Machinery Room" — of Chapter 15 - "Mechanical Refrigeration Equipment" - of Exhibit "A", attached to and incorporated by reference in the Mechanical Code of the City of Fort Worth (Ordinance No. 7634 duly adopted by the Fort Worth City Council on April 12, 1977) be and they are hereby amended to read as follows: "MACHINERY ROOMS SECTION 1507. Every nrachinery room containing any Group 1 refrigeration equipment shall have a one hour fire-resistive separation from any room or space containing ii fuel-fired appliance. This machinery room shall have at least one means of exit. Such exit opening shall be not less than 3 feet by 6 feet 8 inches. "EQUIPMENT IN A MACHINERY ROOM SECTION 1509. Equipment or electrical control or control panel other than listed below shall not be located in any machinery room: 1. Lights and receptacles. 2. machinery room exhaust fans and f:)lowers. 3. Any refrigerating condensing unit or portion thereof. 4. Circulating pumps for condensers, cooling towers, or cooling coils. S. Air compressors servirig only automatic con- trols within the refrigerating or cooling sys- tem. 6. Electrically operated valves for the control of a refrigerant (,,)r for the control of the circu- lation of a cooling fluid. 7. Blowers an(J fans for cooling towers or for con- densers. 8. Any electric control or control j-ranel for any of the above items. 9. Equij.,�megt operating with a heating surface be- low 800°F„” SECTION 4. That this ordinance shall be cumulative of the provisions of the mechanical Code of the City of Fort Worth, except where the provisions of this ordinance are in direct 000fI±^ t with the pro- visions of such Code, in which event conflicting provisions of such Code are hereby repealed. SECTION x' That all zigbt�s or remedies of the City of Fort Worth, Texas, are expressly saved as to any and all violations of the provisions of the Mechanical Code of the City of Fort xmztb, which have accrued at the time of the effective dote of this ordinance; and as to such accrued violations and all pending litigation, both civil and crim- inal, whether pending in court or not, under such chapter or other ordinances, same shall not be affected by this ordinance but may be gzoneootcd until final disposition by the courts. aoCrzom «- That it is hereby declared to be the intention of the City Council of the City of Fort Worth, Texas, that the sections, para- graphs, sentences, clauses and phrases of this ordinance are sever- able and if any section, paragraph, sentence, clause or phrase of this ordinance ahoII be declared void, ineffective or unconstitu- tional by the valid judgment or final decree of a court of compe- tent jurisdiction, such voidness, ineffectiveness or unconstitu- tionality obulI not affect any of the remaining sections, para- graphs, sentences, clauses or phrases of this ordinance since the same would have been enacted by the City Council without the incor- poration herein of any such void, ineffective or unconstitutional section, paragraph, sentence, clause or pbz:ae. SECTION 7, That any person violating any of the provisions of this or- dinance shall be deemed guilty of o misdemeanor and each such per- son shall be deemed guilty of u separate offense for each day or portion thereof during which any violation of any of the provisions of this ordinance is committed, continued wr permitted and each violation shall be punishable by a fine not to exceed Two Hundred Dollars <$300.00> . SECTION W. That the city Secretary of the City of Fort Worth, Texas, is hereby directed to publish the caption, penalty clause and effec- tive date of this ordinance for five (5) days in the official news- paper of the city of Fort Worth, Texas. SECTION 9. That this ordinance shall be in full force and effect from and after the date of its passage avid publication as required by law and it is so ordained. nerm0vCo AS TO Fomm AND LEGALITY: City Attorney 000erEu: ErrEcrzvE: HWK$ City of Fort W'6rth, Texas Mayor and Council Communication ;Wfl,4 DATE Amendment of Mc7hanical Code � REFERENCE JECT; AGE NUMBER Vapor Barrier of Flexible Duvc and /26/78 G-3950 DefinlLion for a Malhivery Rourn i of __2 SUB I "gwEe The current Mechanical Code, Ordinance No. 7634, which became effective January 1, 1978, has a requirement for a vapor barrier on alt ASLIaLion for cooling and heating ducL systems. 'rho three' major manufacturers of insulated flexible duct, after a retest of char products, have found it to be in violation of our Code requirement of 0.1 perm on the vapor barrier. These three manufacturers, through TIMA (Thermal Insulation Manufacturers Association), madc-, a request to the Mechanical Board of Appeals for a Code change. This would be to change the vapor barrier perm rating from 0.1 perm to 0.3 perm for insulated flexible duct. The Board was assured that all three of the manufacturers represented could meet this requirement. The amendment will read as follows: First paragraph of Section 1002(b)(1): "Shall be a Class I air duct in accordance With UL181 Lost, as required by NFTA-90A. Facing material for round fiberglass ducts and duct board shall have a perm rating of not greater than 0.05 perms. Facing material for insulated flexible duct shall be sheathed with a glass net reinforced vapor barrier having a perm rating of not greater than 0.3 perms, as determined by ASTM E96, Procedure A." The current. Mechanical Code is vague on the description of a Machinery Room and the equipment allowed inside such room. To accomplish the intent of the Code and for clarification to those needing this information, an amendment is proposed to Chapter Four defining a Machinery Room, and "viAiq SecKon K07 by adding Fire-resistive Sepayarion between a MwAincry Poom and any room or space containing a fuel-fired appliance. The Mechanical Board of Appeals recommends a Code change to agre-c with the request. This will be more compatible with GSA, HUD, and FHA requirements and remove an existing obstacle to Fort Worth building dcvelnpmcnt. A public hearing on the proposed Amendment was held on August 23, 1978. Notice of the hearing was published in the local newspaper and notices also were sent to fifteen interested local organizationn, No one appeared in opposition to the amendment, Recommendation It is recommen4gdohat the Mechanical Code be amended: 1. To change vapor barrier per rating of 0.1 perm. to 0.3 perm as noted above; 2. To include a definition of Machinery Room in Chapter Four; and ........... . DATE REFERENCE 7efi.nitJon UBJECT: Amendment:: of Mecltanic:al (,ode PAGE NUMBER apor [carrier of Flexible Duct. and /78 G"3� 0 for to Machinery7oom 3) To add a requirement for Fire—resist.ive Separation between a Machinery Room and any room or space cont.ain'i.np a fue:1—fired appliance in Section 1507. GG:11. SUBMITTED BY: DISPOSITION BY COUNCIL: -- PRO ESSEI�, -Ir ,APPROVED f_1 OTHER (DESCRIBE) �� o i, ECRETA RY DATE CI CITY MANAGER