HomeMy WebLinkAboutOrdinance 25771-09-2022 ORDINANCE NO.25771-09-2022
AN ORDINANCE BY THE CITY COUNCIL OF THE CITY OF FORT
WORTH, APPROVING RESOLUTION NOS. 2022-06-121 AND 2022-08-
174, ADOPTED BY THE DALLAS FORT WORTH INTERNATIONAL
AIRPORT BOARD ON JUNE 2, 2002 AND AUGUST 4, 2022,
RESPECTIVELY, FOR THE PURPOSE OF AMENDING THE
CONSTRUCTION AND FIRE PREVENTION STANDARDS AND
CHAPTERS 2 AND 8 OF THE CODE OF RULES AND REGULATIONS
OF THE DALLAS FORT WORTH INTERNATIONAL AIRPORT
BOARD.
WHEREAS, Section 8.17. of the 1968 Contract and Agreement, as amended, between the
City of Dallas, Texas and the City of Fort Worth, Texas, provides that the Dallas Fort Worth
International Airport Board shall have the power, by a duly adopted order, to adopt and enforce
rules and regulations for the orderly, safe, efficient, and sanitary operation of the airport and to
prescribe reasonable penalties for the breach of any rule or regulation not to exceed the
maximum fines authorized by state law; and
WHEREAS, state law currently authorizes fines of up to $500 for all violations of the
airport's rules and regulations, except for those violations relating to fire safety,public health and
sanitation, or the dumping of refuse, for which the maximum fine is $2,000, and except when
another fine is fixed by state law; and
WHEREAS, Sections 22.082 of the Texas Transportation Code, as amended, and
Section 8.17. of the 1968 Contract and Agreement, as amended, provide that such rules,
regulations or orders by the Dallas Fort Worth International Airport Board will become effective
only upon approval of the governing bodies of the Cities of Dallas and Fort Worth and proper
publication; and
WHEREAS, pursuant to the foregoing, the Dallas Fort Worth International Airport
Board adopted the Code of Rules and Regulations, which regulates traffic, travel, and conduct
within the Dallas-Fort Worth International Airport ("Airport") and establishes certain procedures
for the adoption of additional rules, regulations and orders; and
WHEREAS, on June 2, 2022 and August 4, 2022, respectively, the Dallas-Fort Worth
International Airport Board passed, approved, and ordered (i) Resolution No. 2022-06-121 which
would amend the Construction and Fire Prevention Standards at the Airport; and (ii) and
Resolution No. 2022-08-174 which would amend Chapter 2 (Traffic Regulation) and Chapter 8
(Commercial Activities) of the Code of Rules and Regulations of the Dallas Fort Worth
International Airport Board; and
WHEREAS, in accordance with Section 1-8 of Chapter 1 of the Code of Rules and
Regulations of the Dallas-Fort Worth International Airport Board, as amended, the Dallas-Fort
Worth International Airport Board has requested that the City Councils of the Cities of Dallas
and Fort Worth approve Resolution Nos. 2022-06-121 and 2022-08-174 in order that it may
become effective.
NOW, THEREFORE,BE IT ORDAINED BY THE CITY COUNCIL OF THE
CITY OF FORT WORTH TEXAS:
SECTION 1.
That all of the declarations and findings contained in the preambles of this ordinance are
made a part hereof and shall be fully effective as a part of the ordained subject matter of this
ordinance.
SECTION 2.
That Resolution Nos. 2022-06-121 and 2022-08-174 of the Dallas Fort Worth
International Airport Board, duly certified copies of which are attached hereto as Exhibit "A"
and Exhibit"B", respectively, made a part of this ordinance by reference, are hereby approved.
SECTION 3.
That after publication of a substantive statement relating to the contents of Resolution
Nos. 2022-06-121 and 2022-08-174 of the Dallas Fort Worth International Airport Board in a
newspaper of general circulation in each of the counties of Dallas and Tarrant, stating that a
breach of any provision of Resolution No. 2022-06-121 and 2022-08-174 will subject the
violator to a penalty and stating that the full text of Resolution Nos. 2022-06-121 and 2022-08-
174 and any attachments are on file in the principal office of the Dallas Fort Worth International
Airport Board to be read by any interested party, Resolution Nos. 2022-06-121 and 2022-08-174
shall thereafter have the same force and effect within the boundaries of the Dallas-Fort Worth
2
International Airport as an ordinance by the City Council of the City of Fort Worth would have
in the City of Fort Worth, and the penalty shall be enforced in the same manner in which
penalties prescribed by other ordinances of the City of Fort Worth are enforced.
SECTION 4.
That the sections, paragraphs, sentences, clauses, and phrases of this ordinance and
Resolution Nos. 2022-06-121 and 2022-08-174 are severable, and if any phrase, clause,
sentence, paragraph, or section shall be declared unconstitutional or invalid by the valid
judgment or decree of any court of competent jurisdiction, the unconstitutionality or invalidity
shall not affect any of the remaining phrases, clauses, sentences, paragraphs, and sections of
these ordinances or Resolution Nos. 2022-06-121 and 2022-08-174, since the same would have
been enacted without the incorporation of any unconstitutional phrase, clause, sentence,
paragraph, or section.
SECTION 5.
That this ordinance will take effect immediately from and after its passage and
publication in accordance with the provisions of the Charter of the City of Fort Worth, and it is
accordingly so ordained.
APPROVED AS TO FORM AND LEGALITY: ATTEST:
Leann Guzman(Sep 30,202215:12 CDT) ette S.Goodall(Sep 30,2022150 CDT)
Leann Guzman, Jannette S. Goodall
City Attorney City Secretary
Adopted and Effective: September 27, 2022 �yof FART
r
� XAS
3
® AI
V V
September 13, 2022
STATE OF TEXAS §
COUNTY OF DALLAS §
COUNTY OF TARRANT §
1, Donna J. Schnell, Board Staff Secretary of the Dallas Fort Worth International Airport
Board, do hereby certify that the attached is a true and correct copy of Resolution No.
2022-06-121, approved by the Dallas-Fort Worth International Airport Board of Directors
at its Board Meeting held on June 2, 2022.
WITNESS MY HAND AND SEAL OF THE DALLAS-FORT WORTH INTERNATIONAL
AIRPORT BOARD, this 13h day of September 2022.
Donna J. Schnell
Board Staff Secretary
Dallas Fort Worth
International Airport
P.O.Box 619428
DFW Airport,TX 75261-9428
DALLAS FORT WORTH INTERNATIONAL AIRPORT BOARD
OFFICIAL BOARD ACTION/RESOLUTION
Date Committee Subject Resolution #
06/02/2022 Operations Amend Construction and Fire Prevention Standards 2022-06-121
Action
That the Board approves amendments to the Construction and Fire Prevention Standards and Codes, as set
forth in Exhibit A attached, and further recommends to the Cities of Dallas and Fort Worth that they approve
such amendments.
Description
• Approve amendments to the Construction and Fire Prevention Standards to adopt the State Adopted
Electrical Code and certain 2021 series model codes published by the International Code Council,
Inc., (ICC) as listed in Exhibit A, each with proposed local amendments.
Justification
• Model codes set minimum requirements for building design, construction and operation to protect
public health, safety and the natural resources that sustain us.
• The International Codes are developed with several goals in mind; to safeguard public health, safety
and welfare and to provide for the safety of firefighters and emergency responders.
• Updated model construction and fire codes are adopted from time to time to ensure the health, safety
and welfare of the public and to stay current with state and federal regulations.
D/S/M/WBE Information
• Not Applicable
Contract# Agreement# Purchase Order# Action Amount Revised Amount
$0 $0
For Information contact Fund Project# External Funding Source Amount
Tammy Huddleston $0
3-6132
Resolution # 2022-06-121
Additional Information
• On October 29, 2015, by Resolution No. 2015-11-224, the Board approved Amendments to the
Construction and Fire Prevention Standards and Codes.
Additional Attachments: Y
BE IT RESOLVED BY THE DALLAS FORT WORTH INTERNATIONAL AIRPORT BOARD
That the Board approves amendments to the Construction and Fire Prevention Standards and Codes, as set
forth in Exhibit A attached, and further recommends to the Cities of Dallas and Fort Worth that they approve
such amendments.
Approved as to Form by Approved as to Funding by Approved as to M/WBE by
ell
Rodriguez, Elaine Palacios, Abel Burks Lee, Tamela
Legal Counsel Vice President Finance Vice President Business Diversity
May 18, 2022 5:04 pm Finance and Development
May 18, 2022 5:26 pm Business Diversity and
Development
May 19, 2022 9:56 am
SIGNATURE REQUIRED FOR APPROVAL
Approved by I
�Ov�r.rYL
Department Head
Jun 3, 2022 4:58 pm
May 18, 2022 12:55 pm Chief Executive Officer Date
EXHIBIT A
DALLAS-FORT WORTH INTERNATIONAL AIRPORT
CONSTRUCTION AND FIRE PREVENTION STANDARDS RESOLUTION
AND
AMENDMENTS TO THE CODES
06tohe F 2021
TABLE OF CONTENTS
PART ONE -- CONSTRUCTION AND FIRE PREVENTION STANDARDS
RESOLUTION 1
SECTION1 TITLE........................................................................................................... 1
SECTION2 PURPOSE ................................................................................................... 1
SECTION 3 CREATION OF BOARD OF APPEALS (BOA)..............................................2
SECTION 4 COMPOSITION OF BOA.............................................................................2
SECTION 5 EX-OFFICIO MEMBERS..............................................................................4
SECTION 6 MEETINGS: QUORUM ................................................................................4
SECTION 7 BYLAWS AND RECORDS............................................................................4
SECTION 8 AUTHORITY AND POWER...........................................................................5
SECTION 9 RIGHT OF APPEAL.....................................................................................5
SECTION 10 AGENDA AND RECORDS..........................................................................6
SECTION 11 HEARING ..................................................................................................6
SECTION 12 STAY OF PROCEEDINGS.........................................................................6
SECTION 13 202'. INTERNATIONAL BUILDING CODE ADOPTED ..............................6
2021 INTERNATIONAL EXISTING BUILDING CODE ADOPTED........... 6
SECTION 14 202` INTERNATIONAL FIRE CODE ADOPTED........................................7
SECTION 15 202( NATIONAL ELECTRICAL CODE ADOPTED....................................7
SECTION 16 2021 INTERNATIONAL MECHANICAL CODE ADOPTED. ........................7
SECTION 17 202' INTERNATIONAL PLUMBING CODE ADOPTED.............................7
SECTION 18 202' INTERNATIONAL FUEL GAS CODE ADOPTED..............................7
SECTION 19 - 12' INTERNATIONAL ENERGY CONSERVATION CODE ADOPTED .. 8
SECTION 20 REQUIRED PERMITS ...............................................................................8
SECTION 21 REQUIRED FEES......................................................................................8
SECTION 22 LICENSES REQUIRED .............................................................................8
SECTION 23 ENFORCEMENT........................................................................................9
SECTION 24 SPECIAL ENACTMENT.............................................................................9
SECTION 25 CONFLICTING PROVISIONS....................................................................9
SECTION 26 SEVERABILITY CLAUSE ..........................................................................9
SECTION 27 PENAL CLAUSE...................................................................................... 10
SECTION 28 SAVINGS CLAUSE.................................................................................. 10
SECTION 29 PUBLICATION......................................................................................... 10
SECTION 30 EFFECTIVE DATE................................................................................... 10
PART TWO- BUILDING CODE AMENDMENTS 1
SECTION 101 GENERAL................................................................................................ 1
SECTION 102 EXISTING STRUCTURES ....................................................................... 1
SECTION 103 DEPARTMENT OF BUILDING SAFETY................................................... 1
TOC
1
SECTION 105 PERMITS.................................................................................................. 2
SECTION 106 FLOOR AND ROOF DESIGN LOADS ..................................................... 2
SECTION109 FEES........................................................................................................ 2
SECTION 111 CERTOFOCATE OF OCCUPANCY......................................................... 2
SECTION 113 BOARD OF APPEALS.............................................................................. 2
SECTION 114 VIOLATIONS ............................................................................................ 3
SECTION 202 DEFINITIONS .......................................................................................... 3
SECTION 402 COVERED MALLS AND OPEN MALL BUILDING ................................. 3
SECTION 403 HIGH-RISE BUILDINGS .......................................................................... 5
SECTION 412 AIRCRAFT RELATED OCCUPANCIES .................................................... 6
SECTION 903 AUTOMATIC SPRINKLER SYSTEMS...................................................... 6
SECTION 907 FIRE ALARM AND DETECTION SYSTEMS............................................. 7
SECTION 1003 GENERAL MEANS OF EGRESS............................................................ 8
SECTION 1004 OCCUPANT LOAD................................................................................. 9
SECTION 1010 DOORS, GATES, AND TURNSTILES..................................................... 9
SECTION 1023 INTERIOR EXIT STAIRWAYS AND RAMPS.......................................... 9
SECTION 1025 LUMINOUS EGRESS PATH MARKINGS ............................................. 10
CHAPTER 11 ACCESSIBILITY...................................................................................... 10
SECTION 3002 HOISTWAY ENCLOSURES.................................................................. 10
CHAPTER 35 REFERENCED STANDARDS.................................................................. 10
ADOPTION OF APPENDIX CHAPTER H SIGNS........................................................... 11
PART THREE - FIRE CODE AMENDMENTS 1
SECTION 101 SCOPE AND GENERAL REQUIREMENTS .............................................. 1
SECTION 102 APPLICABILITY...................................................................................... 1
SECTION 103 DEPARTMENT OF FIRE PREVENTION ................................................... 1
SECTION 105 PERMITS................................................................................................. 1
SECTION 107 MAINTENANCE.......................................................................................2
SECTION 108 BOARD OF APPEALS..............................................................................2
SECTION 109 VIOLATIONS ...........................................................................................2
SECTION 202 DEFINITIONS ..........................................................................................2
SECTION 307 OPEN BURNING, RECREATIONAL FIRES AND PORTABLE
OUTDOOR FIREPLACES...............................................................................................3
SECTION 503 FIRE APPARATUS ACCESS ROADS......................................................4
SECTION 507 FIRE PROTECTION WATER SUPPLIES.................................................5
SECTION 903 AUTOMATIC SPRINKLER SYSTEMS.................................................... 10
SECTION 907 FIRE ALARM AND DETECTION SYSTEMS........................................... 12
SECTION 1003 GENERAL MEANS OF EGRESS.......................................................... 13
SECTION 1004 OCCUPANT LOAD............................................................................... 13
SECTION 1023 INTERIOR EXIT STAIRWAYS AND RAMPS........................................ 14
SECTION 5005 USE, DISPENSING AND HANDLING................................................... 14
SECTION 5704 STORAGE ........................................................................................... 14
CHAPTER 80 REFERENCED STANDARDS.................................................................. 15
ADOPTION OF APPENDIX CHAPTERS........................................................................ 15
TOC
2
PART FOUR- ELECTRICAL CODE AMENDMENTS 1
ARTICLE 89 TITLE .......................................................................................................... 1
PART FIVE - MECHANICAL CODE AMENDMENTS 1
SECTION 101 GENERAL................................................................................................ 1
SECTION 103 DEPARTMENT OF MECHANICAL INSPECTION ..................................... 1
SECTION 106 PERMITS................................................................................................. 1
SECTION 108 VIOLATIONS ........................................................................................... 1
SECTION 109 MEANS OF APPEAL ............................................................................... 1
PART SIX - PLUMBING CODE AMENDMENTS 1
SECTION 101 GENERAL................................................................................................ 1
SECTION 103 DEPARTMENT OF PLUMBING INSPECTION.......................................... 1
SECTION 106 PERMITS................................................................................................. 1
SECTION 108 VIOLATIONS ........................................................................................... 1
SECTION 109 MEANS OF APPEAL ............................................................................... 1
SECTION 312 TESTS AND INSPECTIONS......................................................................2
TABLE 403.1 MINIMUM NUMBER OF REQUIRED PLUMBING FACILITIES..................2
SECTION 404 ACCESSIBLE PLUMBING FACILITIES....................................................2
SECTION 1106 SIZES OF CONDUCTORS, LEADERS AND STORM DRAINS...............2
SECTION 1109 COMBINED SANITARY AND STORM SYSTEM ....................................3
PART SEVEN - FUEL GAS CODE AMENDMENTS 1
SECTION 101 GENERAL................................................................................................ 1
SECTION 103 DEPARTMENT OF INSPECTION ............................................................. 1
SECTION 106 PERMITS................................................................................................. 1
SECTION 108 VIOLATIONS ........................................................................................... 1
SECTION 109 MEANS OF APPEAL ...............................................................................2
PART EIGHT - ENERGY CODE AMENDMENTS 1
SECTION C101 SCOPE AND GENERAL REQUIREMENTS............................................ 1
SECTION C110 VIOLATION PENALTIES...................................................................... 1
SECTION 202 GENERAL DEFINITIONS.......................................................................... 1
TOC
3
PART NINE-OIL AND GAS EXPLORATION AND PRODUCTION 1
SECTION 1 GENERAL INFORMATION ........................................................................... 1
SECTION 2 DEFINITIONS .............................................................................................. 1
SECTION 3 AIRPORT OVERSIGHT ................................................................................ 4
SECTION 4 OPERATOR'S AGENT................................................................................ 5
SECTION 5 SEISMIC SURVEY PERMIT REQUIREMENTS............................................. 5
SECTION 6 GAS WELL AND DISPOSAL WELL PERMIT REQUIREMENTS................. 6
SECTION 7 PERMIT APPLICATION................................................................................ 7
SECTION 8 PERMITTING PROCEDURE...................................................................... 10
SECTION 9 AMENDED GAS WELL PERMITS.............................................................. 10
SECTION 10 SUSPENSION OR REVOCATION OF WELL PERMITS.......................... 11
SECTION 11 PERIODIC REPORTS.............................................................................. 12
SECTION 12 BOND, LETTERS OF CREDIT, INDEMNITY INSURANCE....................... 13
SECTION 13 SETBACK REQUIREMENTS.................................................................... 16
SECTION 14 ON SITE AND TECHNICAL REGULATIONS............................................ 17
(A)SECTION 15 SCREENING ........................................................................................ 27
SECTION 16 CLEANUP AND MAINTENANCE.............................................................. 29
SECTION 17 PLUGGED AND ABANDONED WELLS................................................... 30
SECTION 18 TECHNICAL ADVISOR ............................................................................ 31
SECTION 19 MEANS OF APPEAL................................................................................ 31
SECTION 20 VARIANCE RESOLUTION COMMITTEE.................................................. 31
SECTION 21 SEVERABILITY CLAUSE ........................................................................ 33
TOC
4
PART ONE --CONSTRUCTION AND FIRE PREVENTION STANDARDS
RESOLUTION
A Board Resolution creating the Board of Appeals (BOA) of the Dallas-Fort Worth
International Airport (the Airport); providing for the selection and term of office of
members; providing for public hearings, meetings and procedures therefore; prescribing
the authority and powers of the Board of Appeals; providing for appeal from decisions
of the Building Official and Fire Chief; providing for a stay of proceedings upon appeal;
providing for the adoption of the Building Code; providing for the adoption of the Fire
Code; providing for the adoption of the Electrical Code; providing for the adoption of the
Mechanical Code; providing for the adoption of the Plumbing Code; providing for the
adoption of the Fuel Gas Code; providing for the adoption of the Energy Code; providing
for the regulation of oil and gas exploration and production; making it unlawful to perform
construction work or oil and gas exploration and production without a permit; making it
unlawful to undertake the contracted installation of fire protection, mechanical, plumbing,
irrigation or electrical equipment without a proper license to do such work; providing
for the termination of the Board of Airport Building Code of Appeals; providing that this
resolution shall be cumulative; providing a severability clause; providing a penal
clause; providing a savings clause; providing for publication in pamphlet form;
providing for publication in a newspaper; and providing an effective date.
SECTION 1
TITLE
This resolution shall be known as the Dallas-Fort Worth International Airport
Construction and Fire Prevention Standards Resolution, and referred to herein as (this
Resolution).
SECTION 2
PURPOSE
It is the specific intent of the Dallas-Fort Worth International Airport Board (the Airport
Board) that standards for construction and fire prevention be used for the health, safety
and welfare of all persons at the Airport. The Airport Board finds that construction and
fire prevention standards change from time to time and that these standards should
stay current with modern practices of construction and fire safety. In carrying out these
purposes, it is the intent of the Airport Board that such construction and fire prevention
standards be adopted as outlined herein and that a Board of Appeals (BOA) be given
limited authority over matters pertaining thereto. The scope of the BOA is as set forth
below.
It is the intent of the Airport Board that compliance with the construction and fire
prevention standards contained herein is the responsibility of those persons and
businesses to which they apply; and that neither the BOA nor the Airport Board, its
Part One— Construction and Fire Prevention Standards
Part One — Pg. 1
members, agents and employees, shall be liable or responsible for any errors or
omissions arising out of the enforcement or failure to enforce these standards.
SECTION 3
CREATION OF BOARD OF APPEALS (BOA)
The Airport Board hereby establishes a Board of Appeals (BOA) for the purpose of
determining the acceptability and adequacy of materials, equipment and methods of
construction and for interpretation of these standards. The Airport Board shall adopt
construction and fire prevention standards, which will be applicable throughout the
Airport. The Construction and Fire Prevention Standards shall include but not be limited
to the Building Code, Fire Code, Electrical Code, Mechanical Code, Plumbing Code,
Fuel Gas Code and Energy Code and Part Nine of this Resolution for Oil and Gas
Exploration and Production as adopted by the Airport Board and amended from time to
time.
SECTION 4
COMPOSITION OF BOA
The BOA shall consist of seven voting members who shall serve without compensation
and shall be selected in the following manner:
Place 1: An architect, registered to practice as an architect in the State of Texas - The
selection of the architect shall be made alternatively by the Dal„as a d
F=E)Ft VVE)Fth Ghapt of I\mAYI R Inc+i a of I\FGhiteGts gird
���,��e�s� ,��ea„—R,�Rt�t shall e
confirmed by the Airport Board. The initial term will be filled by a
selection of the Dallas Chapter and will extend from the Airport Board's
confirmation of the selection through December 31, 1990. Thereafter,
terms will be for two years extending from January 1 of odd-numbered
years through December 31 of even-numbered years.
Place 2: An electrical engineer, registered to practice as a professional engineer in the
State of Texas whose practice is or has been the design of electrical
systems for buildings th
- ,The selection of the electrical enginee}r�,,shall e
rmR ade-alt�ci��-at+v the he Dallas j aR Peet \ eFth� s of pceFe Tex�.cs
SE)Giety Of ❑Yr1fessk al F=RgiReeFs aR d shall be confirmed by the Airport
Board. The initial term will be filled by a selection of the Fort Worth
Chapter and will extend from the Airport Board's confirmation of the
selection through December 31, 1990. Thereafter, terms will be for two
years extending from January 1 of odd-numbered years through December
31 of even-numbered years.
Place 3: A mechanical engineer, registered to practice as a professional engineer
in the State of Texas whose practice is or has been the design of
mechanical systems for buildings - The selection of the mechanical
engineer shall be FRade altematively by the ul„as aR d Peet VV944
Part One— Construction and Fire Prevention Standards
Part One — Pg. 2
vimapteFS E)f the Texas Seemety Of DrE)fess l ErirYiri�� 4d shall be
confirmed by the Airport Board. The initial term wil`b`:7e filled by a selection
of the Fort Worth Chapter and will extend from the Airport Board's
confirmation of the selection through December 31, 1991. Thereafter,
terms will be for two years extending from January 1 of even-numbered
years through December 31 of odd-numbered years.
Place 4: A structural engineer, registered to practice as a professional engineer in the
State of Texas whose practice is or has been the design of structural
systems for buildings - The selection of the structural engineer shall be
made alteMative�yt�� C \A
� and .,rt E)rth� �the TpteFsex
SGGiety of ❑Fefess eRal F=RgiReeFs aR d shall be confirmed by the Airport
Board. The initial term will be filled by a selection of the Fort Worth
Chapter and will extend from the Airport Board's confirmation of the
selection through December 31, 1991. Thereafter, terms will be for two
years extending from January 1 of even-numbered years through
December 31 of odd-numbered years.
Place 5: A fire protection specialist - The selection of the fire protection specialist
be made by the DaII�CeFt Woortrh Gh'rapteF of the SOG etas of Ciro
❑Y/1teGtiE)R F=RgiReeFs and shall be confirmed by the Airport Board. The
initial term will extend from the Airport Board's confirmation of the
selection through December 31, 1991. Thereafter, terms will be for two
years extending from January 1 of even-numbered years through
December 31 of odd-numbered years.
Place 6: A design professional, registered to practice as an architect or as a professional
engineer in the State of Texas, and whose profession relates to the design
of facilities, structures or systems that are constructed — The selection of
the design professional for Place 6 shall�„--b — Dallasade by the Dallas
Mek)plex AIl� Ex"�'Ri t n Ghapte Of the
NatE)R"rial SE)G♦i Gel
F=RgiReeFS and shall be confirmed by the Airport Board. The initial term
shall extend from the Airport Board's confirmation of the selection
through December 31, 2005. Thereafter, terms will be for two years
extending from January 1 of even-numbered years through December 31
of odd-numbered years.
Place 7: A design professional registered to practice as an architect or as a professional
engineer in the State of Texas, and whose profession relates to the design
of facilities, structures or systems that are constructed — The selection of
the design professional for Place 7 shall made b the Dallas
VGF aptee-Efthe Seemet i E)f Hispania PFE)fessienal—EngineeFs—a and
shall be confirmed by the Airport Board. The initial term will extend from
the Airport Board's confirmation of the selection through December 31,
2004.* Thereafter, terms will be for two years extending
Part One— Construction and Fire Prevention Standards
Part One — Pg. 3
from January 1 of odd-numbered years through December 31 of even-
numbered years.
There is no limit on the number of terms an individual may serve on the BOA; however,
only in Places 5, 6 and 7 may an individual serve in consecutive terms. Any term
scheduled to end on December 31, shall be automatically extended until a successor
for that place is selected, confirmed, and sworn in.
In the event that any professional organization, designated to select a candidate to fill a
term on the BOA, is unable to make such a selection, and the professional organization
notifies the Building Official that a selection cannot be made, then the Building Official
shall designate the unfilled seat as officially vacant, and it shall remain vacant until the
next scheduled term for that seat.
SECTION 5
EX-OFFICIO MEMBERS
The Building Official and the Fire Chief or their designated representatives shall be ex-
officio non-voting members of the BOA. The BOA may make recommendations through
the Building Official or Fire Chief to the Airport Board for amendments to the standards
accordingly.
The Building Official of the Dallas/Fort Worth International Airport Board is the official in
charge of the Code Compliance Section of the Design, Code & Construction
Department.
The Director of the Department of Public Safety of the Dallas/Fort Worth International
Airport Board or his designee is hereby designated as the Fire Chief.
SECTION 6
MEETINGS: QUORUM
All meetings of the BOA shall be open to the public except as permitted by law and as
is in the interest of the Airport. Three (3) members of the BOA shall constitute a
quorum to transact business. Every matter before the BOA for vote shall require for
final passage the affirmative vote of a majority of the members present and voting. The
first meeting of the BOA following its appointment shall be at such time and place as
called by the Building Official. Thereafter the BOA shall hold meetings at such time and
place as called by the Chairman or one lawfully acting in that capacity.
SECTION 7
BYLAWS AND RECORDS
At its first meeting the BOA shall elect one of its members as Chairman, and he shall
keep a record of the proceedings and decisions, and a copy of same shall be filed in
the office of the Building Official. Each year thereafter, following the Airport Board's
Part One— Construction and Fire Prevention Standards
Part One — Pg. 4
confirmation of the composition of the BOA, the BOA shall hold an organizational
meeting, at which time it shall elect a Chairman before proceeding to other matters of
business. The BOA shall establish its own rules of procedure and shall amend them
from time to time as it deems necessary. The Building Official shall serve as Secretary
to the BOA.
SECTION 8
AUTHORITY AND POWER
The BOA shall have the authority and power to:
1. Hear appeals on interpretations by the Building Official of the Building Code,
Electrical Code, Mechanical Code, Plumbing Code, Fuel Gas Code and Energy Code.
The BOA may modify in whole or in part or may affirm the interpretation of the Building
Official. The Building Official shall render a written interpretation within thirty (30) days
of a request by a person who has been aggrieved by a decision of the Building Official.
No interpretations shall be heard by the BOA until the Building Official has rendered a
written interpretation.
2. Hear appeals on interpretations by the Fire Chief of the Fire Code. The BOA
may modify in whole or in part or may affirm the interpretation of the Fire Chief. The
Fire Chief shall render a written interpretation within thirty (30) days of a request by a
person who has been aggrieved by a decision of the Fire Chief. No interpretations shall
be heard by the BOA until the Fire Chief has rendered a written interpretation.
3. Approve alternate methods of construction and fire prevention where it is
impractical to meet the adopted construction and fire prevention standards, provided
that the BOA finds the same degree of suitability, strength, effectiveness, fire
resistance, durability, sanitation and safety exists in the alternate method as intended
by the standards.
4. Approve new methods of construction and fire prevention not covered by the
construction and fire prevention standards, provided that the BOA finds the same
degree of suitability, strength, effectiveness, fire resistance, durability, sanitation and
safety exists in the new method as intended by the standards.
The BOA shall have no power to otherwise limit, modify or change these construction
and fire prevention standards.
SECTION 9
RIGHT OF APPEAL
Any person, firm, company or corporation aggrieved by any decision or order of the
Building Official or Fire Chief may appeal such decision or order to the BOA. Every
appeal must be in writing and must be filed in triplicate with the Building Official within
thirty (30) days from the date of the decision or order appealed from. The BOA shall
Part One— Construction and Fire Prevention Standards
Part One — Pg. 5
not consider any appeal that is filed after the thirty (30) day period. Such appeal shall
contain appropriate reference to the decision or order appealed from, as well as the
grounds for the appeal.
SECTION 10
AGENDA AND RECORDS
The agenda for the BOA shall be prepared by the Building Official and shall be posted
as required by law. All records and evidence pertinent to any appeal shall be transmitted
to the BOA and to the aggrieved party prior to the hearing. Records of all appeals shall
be kept in the office of the Building Official. The Building Official shall transmit copies
of appeal records to the Fire Chief.
SECTION 11
HEARING
The BOA shall fix a reasonable time for the hearing of an appeal and shall give notice
of the hearing in writing to the parties in interest. Parties may appear before the BOA in
person, by agent or by attorney. The BOA shall establish rules for the fair and efficient
conduct of the hearing and the just resolution to an appeal. The BOA shall notify the
appellant of its decision.
SECTION 12
STAY OF PROCEEDINGS
An appeal shall stay all proceedings in connection with the decision or order appealed
from, unless and until the Building Official or Fire Chief shall have certified to the BOA
after notice of appeal has been filed that a stay would cause an unreasonable risk of
harm to life or damage to property. Any work done contrary to the order of the Building
Official or Fire Chief after filing an appeal hereunder, pending the determination of such
appeal, shall be subject to removal or repair should the order be affirmed. The cost of
removal or repair of the work done shall be borne solely by the person, firm, company
or corporation who was responsible for the work without consideration of mitigating or
extenuating circumstances.
SECTION 13
202 INTERNATIONAL BUILDING CODE ADOPTED
The Building Code of the Dallas-Fort Worth International Airport Board is hereby
revised and amended to conform to the 202- International Building Code of the
International Code Council, Inc. except as amended by separate exhibit attached
hereto and is hereby adopted as the Building Code and forms a part of the Construction
and Fire Prevention Standards from the effective date hereof.
Part One— Construction and Fire Prevention Standards
Part One — Pg. 6
SECTION
2021 INTERNATIONAL EXISTING BUILDING CODE ADOPTED
The Existing Building of the Dallas-Fort Worth International Airport Board is hereby revised and
amended to conform to the 2021 International Existing Building Code of the International Code Council,
Inc. except as amended by separate exhibit attached hereto and is hereby adopted as the Existing
Building Code and forms a part of the Construction and Fire Prevention Standards from the effective date
hereof
SECTION 14
INTERNATIONAL FIRE CODE ADOPTED
The Fire Code of the Dallas-Fort Worth International Airport Board is hereby revised and
amended to conform to the 2021 International Fire Code, except as further
amended by separate exhibit attached hereto and is hereby adopted as the
Fire Code and forms a part of the Construction and Fire Prevention Standards
from the effective date hereof.
SECTION 15
2020 NATIONAL ELECTRICAL CODE ADOPTED
The Electrical Code of the Dallas-Fort Worth International Airport Board is hereby
revised and amended to conform to the zuzu National Electrical Code (NFAP 70) of the
National Fire Protection Association except as amended by separate exhibit attached
hereto and together are hereby adopted as the Electrical Code and form a part of
the Construction and Fire Prevention Standards from the effective date hereof.
SECTION 16
1021 INTERNATIONAL MECHANICAL CODE ADOPTED
The Mechanical Code of the Dallas-Fort Worth International Airport Board is
hereby revised and amended to conform to the International Mechanical
Code of the International Code Council, Inc. except as amended by separate exhibit
attached hereto and is hereby adopted as the Mechanical Code and forms a part of
the Construction and Fire Prevention Standards from the effective date hereof.
SECTION 17
202' INTERNATIONAL PLUMBING CODE ADOPTED
The Plumbing Code of the Dallas-Fort Worth International Airport Board is hereby
revised and amended to conform to the 20` -' International Plumbing Code of the
International Code Council, Inc. except as amended by separate exhibit attached
hereto and is hereby adopted as the Plumbing Code and forms a part of the
Construction and Fire Prevention Standards from the effective date hereof.
SECTION 18
INTERNATIONAL FUEL GAS CODE ADOPTED
Part One— Construction and Fire Prevention Standards
Part One — Pg. 7
The Fuel Gas Code of the Dallas-Fort Worth International Airport Board is hereby
revised and amended to conform to the International Fuel Gas Code of the
International Code Council, Inc. except as amended by separate exhibit attached hereto
and is hereby adopted as the Fuel Gas Code and forms a part of the Construction and
Fire Prevention Standards from the effective date hereof.
SECTION 19
202 INTERNATIONAL ENERGY CONSERVATION CODE ADOPTED
The Energy Code of the Dallas-Fort Worth International Airport Board is hereby revised
and amended to conform to the International Energy Conservation Code of
the International Code Council, Inc. except as amended by separate exhibit attached
hereto and is hereby adopted as the Energy Code and forms a part of the
Construction and Fire Prevention Standards from the effective date hereof.
SECTION 20
REQUIRED PERMITS
The following activities shall not be performed within the boundaries of the Dallas-Fort
Worth International Airport unless a permit for such work has first been obtained from
the building official.
1. Construction
2. Oil and Gas Exploration and Production
3. Erection or Alteration of Signs
SECTION 21
REQUIRED FEES
All construction projects for which construction permits are required are subject to a
construction permit fee and a plan review fee except where otherwise prohibited by law.
All permit and plan review fees shall be in accordance with the Construction Permit
Fee Schedule found in the DFW Schedule of Charges.
SECTION 22
LICENSES REQUIRED
Contractors providing the following work within the boundaries of Dallas-Fort Worth
International Airport shall be licensed respectively for the category of work performed as
regulated by the following:
28 TEX. ADMIN. CODE, Part 1, Subchapter E, Fire Extinguisher Rules § 34.511, Fire
Extinguisher Licenses
28 TEX. ADMIN. CODE, Part 1, Subchapter F, Fire Alarm Rules § 34.611, Licenses
28 TEX. ADMIN. CODE, Part 1, Subchapter G, Fire Sprinkler Rules § 34.710, Certificates
of Registration
Part One— Construction and Fire Prevention Standards
Part One — Pg. 8
The Air Conditioning and Refrigeration Contractor License Law, Title 8, Occupations
Code, Chapter 1302
The Plumbing License Law, Occupations Code, Chapter 1301
Irrigators, Occupations Code, Chapter 1903
Electricians, Title 8, Occupations Code, Chapter 1305
SECTION 23
ENFORCEMENT
The Building Official and Fire Chief shall enforce and execute all decisions and orders
of the BOA for which they are respectively responsible. Upon adoption by the Airport
Board and the City Councils of the Cities of Dallas and Fort Worth, this resolution shall
become effective and shall be enforceable in the municipal courts of a municipality
within whose boundaries a violation occurs.
SECTION 24
SPECIAL ENACTMENT
The provisions of this Resolution and the Codes which are a part hereof constitute a
special enactment in effect only within the boundaries of the Dallas-Fort Worth
International Airport, and are adopted in recognition of the unique and special
requirements connected with the planning, building, improvement, maintenance,
operation, regulation, protection and policing of the Dallas-Fort Worth International
Airport. Neither the Resolution nor the Codes shall be construed to waive or set aside
any provisions contained in any law of the State of Texas.
SECTION 25
CONFLICTING PROVISIONS
This resolution shall be cumulative of all provisions of previous actions of the Airport
Board except where the provisions of this resolution are in direct conflict with the
provisions of previous Board Actions, in which event conflicting provisions of such
previous Board Actions are hereby repealed.
SECTION 26
SEVERABILITY CLAUSE
It is hereby declared to be the intention of the Airport Board that the sections,
paragraphs, sentences, clauses and phrases of this resolution are severable, and if any
phrase, clause, sentence, paragraph or section of this resolution shall be declared
unconstitutional by the valid judgment or decree of any court of competent jurisdiction
such unconstitutionality shall not affect any of the remaining phrases, clauses,
sentences, paragraphs and sections of this resolution, since the same would have been
enacted by the Airport Board without the incorporation in this resolution of any such
unconstitutional phrase, clause, sentence, paragraph or section.
Part One— Construction and Fire Prevention Standards
Part One — Pg. 9
SECTION 27
PENALCLAUSE
Section 8.F. of the 1968 Contract and Agreement, as amended, between the City of
Dallas, Texas and the City of Fort Worth, Texas, provides that the Dallas-Fort Worth
International Airport Board shall have the power, by a duly adopted order, to adopt and
enforce rules and regulations for the orderly, safe efficient and sanitary operation of the
airport and to prescribe penalties for the breach of any rule or regulation not to exceed
the maximum fines authorized by state law. State law currently authorizes fines of up to
$500 for all violations of the airport's rules and regulations, except for those violations
relating to fire safety, public health and sanitation, or the dumping of refuse, for which
the maximum fine is $2,000, and except when another fine is fixed by state law. Each
day that a violation is permitted to exist shall constitute a separate offense.
SECTION 28
SAVINGS CLAUSE
All rights and remedies of the Airport Board are expressly saved as to any and all
violations of the provisions of the Building Code, the Fire Code or any other codes
affecting construction or fire prevention which have accrued at the time of the effective
date of this resolution and, as to such accrued violations and all pending litigation, both
civil and criminal, whether pending in court or not, under such codes, same shall not be
affected by this resolution but may be prosecuted until final disposition by the courts.
SECTION 29
PUBLICATION
The Building Official is hereby authorized to publish this resolution in pamphlet form for
general distribution among the public, and the operative provisions of this resolution as
so published shall be admissible in evidence in all courts without further proof than the
production thereof. The Building Official is hereby directed to publish a caption of this
Resolution which summarizes the purposes thereof for two (2) days in major
newspapers of the Cities of Dallas and Fort Worth Texas, as authorized by V.T.C.A.,
Local Government Code '52.013.
SECTION 30
EFFECTIVE DATE
This resolution shall be in full force and effect from and after its passage and publication
as required by law and it is so ordained.
PART TWO — BUILDING CODE AMENDMENTS
SECTION 101
GENERAL
101.1 Title. The International Building Code as amended herein is the Building
Part Two— Building Code Amendments
Part Two — Pg. 10
Code of Dallas-Fort Worth International Airport. References to the International Building
Code shall be construed to reference the Building Code as adopted herein with its local
amendments.
Amend Section 101.4 to read as follows:
101.4 Referenced codes. The other codes listed in Sections 101.4.1 through 101.4.7
(except 101.4.4 and 101.4.7) and referenced elsewhere in this code, when specifically
adopted, shall be considered part of the requirements of this code to the prescribed
extent of each such reference.
101.4 Referenced codes.
The other codes specified in Sections 101.4.1 through 101.4.7 and referenced elsewhere
in this code shall be considered to be part of the requirements of this code to the
prescribed extent of each such reference.
101.4.4 Property maintenance.
The provisions of the International Property Maintenance Code shall apply to existing
structures and premises; equipment and facilities; light, ventilation, space heating,
sanitation, life and fire safety hazards; responsibilities of owners, operators and occupants;
and occupancy of existing premises and structures.
101.4.7 Existing buildings.
The provisions of the International Existing Building Code shall apply to matters governing
the repair, alteration, change of occupancy, addition to and relocation of existing buildings.
SECTION 102
EXISTING STRUCTURES
Amend Section 102.6 to read as follows:
102.6 Existing structures. The legal occupancy of any structure existing on the date
of adoption of this code shall be permitted to continue without change, except as
specifically covered in this code or the Fire Code, or as is deemed necessary by the
building official for the general safety and welfare of the occupants and the public.
SECTION 103
DEPARTMENT OF BUILDING SAFETY
Amend Section 103.1 as follows:
103.1 Creation of enforcement agency. The Department of Building Safety is hereby
created, and the official in charge thereof shall be known as the building official.
References to the Department of Building Safety shall mean the Code Compliance
Part Two— Building Code Amendments
Part Two — Pg. 11
Section of the Design, Code & Construction Department
SECTION 105
PERMITS
105.1 Required. Refer to Part One, Section 20 for general permit requirements. Any
owner or authorized agent who intends to construct, enlarge, alter, repair, move
demolish or change the occupancy of a building or structure, or to erect, install, enlarge,
alter, repair, remove, convert or replace any electrical, gas, mechanical or plumbing
system, the installation of which is regulated by this code, or to cause any such work to
be done, shall first make application to the building official and obtain the required
permit.
SECTION 106
FLOOR AND ROOF DESIGN LOADS
106.1 Live loads posted. Where the live loads for which each floor or portion thereof of
a commercial or industrial building is or has been designed to exceed 50 psf (2.40
kN/m2), such design live loads, when required by the building official, shall be posted by
the owner in that part of each story in which they apply, using durable signs. It shall be
unlawful to remove or deface such notices.
SECTION 109
FEES
109.2 Schedule of permit fees. On buildings, structures, electrical, gas, mechanical
and plumbing systems or alterations requiring a permit, a fee for each permit shall be
paid as required, in accordance with the Construction Permit Fee Schedule found in the
DFW Airport Schedule of Charges.
SECTION 111
CERTIFICATE OF OCCUPANCY
111.2 Certificate issued. After the building official inspects the building or structure
and finds no violations of this code or other laws that are enforced by the department of
building safety, the building official shall issue a certificate that contains, as deemed
necessary, the following:
SECTION 113
BOARD OF APPEALS
Section 113.1 — Board of Appeals Refer to Part One, Construction and Fire
Prevention Standards Resolution for Board of Appeals.
Part Two— Building Code Amendments
Part Two — Pg. 12
SECTION 114
VIOLATIONS
Refer to Part One, Construction and Fire Prevention Standards Resolution, Section 27,
Penal Clause.
SECTION 202
DEFINITIONS
ADDRESSABLE FIRE DETECTION SYSTEM. Any fire alarm system capable of
providing identification of each individual alarm initiating device. The identification shall
be in clear English and shall identify the type and location of the device in alarm. The
system shall have the ability of alarm verification.
Following the definition of AGRICULTURE BUILDING, add the following definition:
AIRPORT. Airport is the area within the boundaries of the Dallas-Fort Worth
International Airport.
ANALOG INTELLIGENT ADDRESSABLE FIRE DETECTION SYSTEM. Any system
capable of calculating a change in value by directly measurable quantities (voltage,
resistance, etc.) at the sensing point. The physical analog may be conducted at the
sensing point or at the main control panel. The system shall be capable of
compensating for long-term changes in sensor response while maintaining a constant
sensitivity. The compensation shall have a preset point at which a detector
maintenance signal shall be transmitted to the control panel. The sensor shall remain
capable of detecting and transmitting an alarm while in maintenance alert.
HIGH-RISE BUILDING. A building with an occupied floor located more than 55 feet (16
764 mm) above the lowest level of fire department vehicle access.
SECTION 402
COVERED MALLS AND OPEN MALL BUILDINGS
402.3
Exception: DFW International Airport Terminal Buildings.
402.4.2.1
Exceptions:
1. All tenants whose activities are directly related to terminal operations and
purpose. This shall include, but not be limited to airline ticketing, airline
offices, baggage handling and gate operations.
Part Two— Building Code Amendments
Part Two — Pg. 13
2. Concession and other tenants within transportation terminals that use a
common, open return-air system for the HVAC operations, when
approved by the building official.
3. Food courts within transportation terminals shall be considered one
tenant.
402.8 Means of egress. Covered mall buildings, open mall buildings and each tenant
space within a mall building shall be provided with a means of egress as required by
this section and this code. Where there is a conflict between the requirements of this
code and the requirements of Sections 402.8.1 through 4.2.8.8 shall apply.
Exception: Transportation terminals "A", "B", "C" and "E" at DFW International
Airport shall be allowed to maintain the current egress plans which allow a
maximum of 250 feet from the most remote within the terminals to an exit.
Terminal "D" shall maintain the maximum egress distance allowed from the most
current, approved Terminal D Fire Strategy. Other provisions found in Chapter
10 shall be applicable for egress.
402.8.1 Mall Width. For the purpose of providing required egress, malls are permitted
to be considered as corridors but need not comply with the requirements of Section
1005.1 of this code where the width of the mall is as specified in this section. In the
transportation terminals at DFW International Airport the mall width shall be defined as
the identified concourse width.
402.8.1.1 Minimum Width. The aggregate clear egress width of the mall in either
a covered or open mall building shall be not less than 20 feet (6096 mm). The
mall width shall be sufficient to accommodate the occupant load served. No
portion of the minimum required aggregate egress width shall be less than 10
feet (3048 mm) measured to a height of 8 feet (2438 mm) between any
projection of a tenant space bordering the mall and the nearest kiosk, vending
machine, bench, display opening, food court or other obstruction to means of
egress travel.
Exception: The terminal buildings at DFW International Airport in existence and
in operation of the date of the adoption of this code that have concourse width of
less than 20 feet shall be allowed to maintain the existing concourse width.
402.8.6
Exceptions:
1. Access to exits are permitted by way of a dead-end mall which does not
exceed a length equal to twice the width of the mall measured at the
narrowest location within the dead-end portion of the mall.
Part Two— Building Code Amendments
Part Two — Pg. 14
2. Terminal buildings at DFW International Airport in existence and in
operation on the date of the adoption of this code shall be allowed to
retain the exit configuration currently in operation. Any changes in this
configuration shall meet the above criteria.
SECTION 403
HIGH-RISE BUILDINGS
Applicability add the following exception
Exceptions:
6. Train platforms for fixed guideway transit systems in accordance with
Section 412.10.
SECTION 412
AIRCRAFT RELATED OCCUPANCIES
Add new section 412.9 as follows:
Aircraft fueling ramp drainage and aircraft loading walkways. Except for
references to airport terminal buildings, comply with NFPA 415, 2014 Edition for aircraft
fueling ramp drainage and aircraft loading walkways.
Exceptions:
1. Attached or adjacent fixed loading walkways, gate houses and similar
structures accessory to airport terminal buildings may be constructed
of Type II-A Construction, provided the floor area of individual
structures does not exceed 500 square feet. An approved automatic
sprinkler system in accordance with Section 903.3.1.1 shall be allowed
to be substituted for 1-hour fire-resistance-rated construction. If the
automatic sprinkler system substitution is provided, exterior walls of
such structures shall not be required to be of 1-hour fire-resistance-
rated construction and openings in such walls shall not be required to
be protected.
2. Canopies over baggage conveyors attached to or adjacent to airport
terminal buildings may be of Type II-B Construction.
412.10 Fixed guideway transit systems. Fixed guideway transit systems shall comply
with NFPA 130, 2014 Edition.
SECTION 903
AUTOMATIC SPRINKLER SYSTEMS
Part Two— Building Code Amendments
Part Two — Pg. 15
Buildings 55 feet or more in height. An automatic sprinkler system shall be installed
throughout buildings with a floor level other than penthouses, that is located 55 feet (16
764 mm) or more above the lowest level of fire department vehicle access.
Exception:
Open parking structures.
High-piled combustible storage. For any building with a clear height exceeding 12
feet (4572 mm), see Chapter 23 of the International Fire Code to determine if those
provisions apply.
Buildings with floor areas exceeding 4,000 square feet. An automatic sprinkler
system shall be installed throughout all buildings with a building area exceeding
4,000 square feet. For purposes of this provision, fire walls shall not define separate
buildings.
Exception:
1. Open parking garages
Self-service storage facilities. An approved automatic sprinkler system shall be
installed throughout all self-storage facilities.
Exception:
Open parking garages
SECTION 907
FIRE ALARM AND DETECTION SYSTEMS
Add the following two paragraphs after the exceptions under Section 907.2:
All buildings or occupancies, occupied, operated, maintained or monitored by the Dallas-
Fort Worth International Airport Board shall have a complete operational manual and
automatic fire alarm system in accordance with this code. The system shall be
designed and installed in accordance with the DFW Airport Design Criteria Manual and
applicable standards.
All buildings or occupancies, other than those described in the preceding paragraph,
hereafter constructed or moved on to the airport and having a total floor area of 1,000
square feet or more, regardless of height or occupant load shall have a complete
operational manual and automatic fire alarm system in accordance with the requirements
of this code.
Exceptions:
1. Open parking garages may use other approved means for fire
Part Two— Building Code Amendments
Part Two — Pg. 16
department notification.
2. Temporary structures or buildings erected for less than 365 days
when approved by the fire chief.
[F] 907.2.1.1 System initiation in Group A occupancies with an occupant load of
1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant
load of 1,000 or more shall initiate a signal using an emergency voice/alarm
communications system in accordance with NFPA 72.
Exceptions:
1 Where approved, the prerecorded announcement is allowed to be manually
deactivated for a period of time, not to exceed 3 minutes, for the sole purpose
of allowing a live voice announcement from an approved, constantly attended
location.
2 Where approved by the code official in airport terminal buildings, and where
the fire alarm is monitored directly by the Dallas/Fort Worth International
Airport Board Department of Public Safety, the activation of the fire alarm
notification signal shall be manually initiated by emergency responders.
Amend Section 907.2.13 as follows with the exceptions unchanged:
[F] 907.2.13 High-rise buildings. Buildings having floors used for human occupancy
located more than 55 feet (16 764 mm) above the lowest level of fire department
vehicle access shall be provided with an automatic smoke detection system in
accordance with Section 907.2.13.1, a fire department communication system in
accordance with Section 907.2.13.2 and an emergency voice/alarm communication
system in accordance with Section 907.5.2.2.
Amend Section 907.4.2 by to read as follows:
[F] 907.4.2 Manual fire alarm boxes. Where a manual fire alarm system is required
by another section of this code, it shall be activated by fire alarm boxes installed in
accordance with Sections 907.4.2.1 through 907.4.2.5. Manual alarm actuating devices
shall be an approved double action type.
[F] 907.4.2.1 Location. Manual fire alarm boxes shall be located not more than 5 feet
(1524 mm) from the entrance to each exit.
SECTION 1003
GENERAL MEANS OF EGRESS
Add Exception 4 under Section 1003.5 to read as follows:
At entrances to mechanical penthouses from roofed areas, the door sill
elevation may be up to 8 inches (203 mm) above the elevation of the
Part Two— Building Code Amendments
Part Two — Pg. 17
landing on either or both sides of the door.
SECTION 1004
OCCUPANTLOAD
Multiple function occupant load.
Where an area under consideration contains multiple functions having different occupant
load factors, the design occupant load for such area shall be based on the floor area of
each function calculated independently
Exception:
Assembly occupancies within airport terminal buildings are not required to have
the occupant load posted unless required by the Building Official.
SECTION 1010
DOORS, GATES, AND TURNSTILES
1010.1.9.10 Locking arrangements in correctional facilities and high security
hallways in transportation terminals. In occupancies in Groups A-2, A-3, A-4, B, E,
F, I-2, M and S within correctional and detention facilities, doors in means of egress
serving rooms or spaces occupied by persons whose movement are controlled for
security reasons shall be permitted to be locked when equipped with egress control
devices which shall unlock manually and by at least one of the following means:
1. Activation of an automatic sprinkler system installed in accordance with Section
903.3.1.1;
2. Activation of an approved manual alarm box; or
3. A signal from a constantly attended location.
Doors providing access to high security hallways, including, but limited to employee
access, within transportation terminals may be permitted to be locked when equipped
with egress control devices which shall unlock manually and by at least one of the
means listed above when approved by the building official and fire chief.
SECTION 1023
INTERIOR EXIT STAIRWAYS AND RAMPS
Tactile floor-level signs.
Where floor level signs are provided in interior exit stairways and ramps, a floor-level sign
identifying the floor level in visual characters, raised characters and braille complying
with ICC A 1 17.1 shall be located at each floor-level landing adjacent to the door leading
from the interior exit stairway and ramp into the corridor.
Exception: Fixed guideway train stations
Part Two— Building Code Amendments
Part Two — Pg. 18
SECTION 1025
LUMINOUS EGRESS PATH MARKINGS
1025.1
Exceptions:
2. Train platforms for fixed guideway transit systems in accordance with Section
412.10.
CHAPTER 11
ACCESSIBILITY
Spaces and elements of buildings and facilities shall be designed and constructed to
standards consistent with the Texas Accessibility Standards as administered by the
Texas Department of Licensing and Regulation, except for the following:
Unisex toilet rooms. Assembly areas shall be provided with one unisex toilet room for
each instance where the total fixture count (water closets and urinals) in a set of men
and women's toilet rooms exceeds 20 fixtures. In assembly areas of airport terminal
buildings, one unisex toilet room shall be provided in each instance where the total
fixture count (water closets and urinals) in a set of men and women's toilet rooms
exceeds 6 fixtures. The unisex toilet room shall be located adjacent to the men and
women's toilet rooms, which are used to determine that the unisex toilet room is
required.
SECTION 3002 HOISTWAY
ENCLOSURES
3002.4 Elevator car to accommodate ambulance stretcher. Where elevators are
provided in buildings four or more stories above grade plane or four or more stories
below grade plane, at least one elevator shall be provided for fire department
emergency access to all floors. The elevator car shall be of such size and arrangement
to accommodate a 31- by 90-inch (788 mm by 2286 mm) ambulance stretcher in the
horizontal open position and shall be identified by the international symbol for
emergency medical services (star of life). The symbol shall not be less than 3 inches
(76 mm) high and shall be placed inside on both sides of the hoist way door frame.
CHAPTER 35
REFERENCED STANDARDS
NFPA
Standard Reference Number 72-2013 National Fire Alarm Code
Part Two— Building Code Amendments
Part Two — Pg. 19
ADOPTION OF APPENDIX CHAPTER H
SIGNS
Appendix Chapter H — Signs is specifically adopted as part of the Building Code.
Amend Section H101.2 as follows:
H- 101.2 Signs exempt from permits. The following signs are exempt from the
requirements to obtain a permit before erection:
1. Signs erected by transportation authorities.
2. The changing of movable parts of an approved sign that is designed for such
changes, or the repainting or repositioning of display matter shall not be deemed
an alteration.
PART THREE — FIRE CODE AMENDMENTS
SECTION 101
SCOPE AND GENERAL REQUIREMENTS
101.1 Title. The 2021 International Fire Code as amended herein is the Fire Code of
Dallas-Fort Worth International Airport. References to International Fire Code
shall be construed to reference the Fire Code as adopted herein with its local
amendments.
SECTION 102
APPLICABILITY
102.7 Referenced codes and standards. The codes and standards referenced in this
code shall be those that are listed in Chapter 80 and such codes and standards, when
specifically adopted, shall be considered part of the requirements of this code to the
prescribed extent of each such reference. Where differences occur between the
provisions of this code and the referenced standards, the provisions of this code shall
apply. Whenever amendments have been adopted to the referenced codes and
standards, each reference to said code and standard shall be considered to reference
the amendments as well.
Conflicts.
Where conflicts occur between provisions of this code and referenced codes and standards, the
provisions of this code shall apply.
Provisions in referenced codes and standards.
Part Three — Fire Code Amendments
Part Three — Pg. 20
Where the extent of the reference to a referenced code or standard includes subject matter that is
within the scope of this code, the provisions of this code, as applicable, shall take precedence over
the provisions in the referenced code or standard.
SECTION 103
DEPARTMENT OF FIRE PREVENTION
103.1 General. The department of fire prevention is established within the jurisdiction
under the direction of the fire code official. The function of the department shall be the
implementation, administration and enforcement of the provisions of this code.
References to the department of fire prevention shall mean the Department of Public
Safety, Fire Prevention and Planning Office.
SECTION 105
PERMITS
105.6.7 Combustible dust-producing operations. Combustible dust-producing
operations, as defined in this code, shall be prohibited within the airport.
105.6.19 Fruit and crop ripening. Fruit and crop ripening operations using ethylene or
other flammable gases shall be prohibited within the airport.
105.6.35 Organic coatings. The manufacturing of organic coatings, as defined in this
code, shall be prohibited within the airport.
Fire pumps and related equipment.
A construction permit is required for installation of or modification to fire pumps and related fuel
tanks,jockey pumps, controllers and generators. Maintenance performed in accordance with this
code is not considered to be a modification and does not require a construction permit
Pyroxylin plastics. An operational permit is required for storage or handling of any amount of
cellulose nitrate (pyroxylin) plastics and for the assembly or manufacture of articles involving pyroxylin
plastics.
105.7.19 Electronic access control systems. Construction permits are required for
the installation or modification of an electronic access control system, as specified in
Chapter 10. A separate construction permit is required for the installation or
modification of a fire alarm system that may be connected to the access control system.
Maintenance performed in accordance with this code is not considered a modification
and does not require a permit.
Part Three — Fire Code Amendments
Part Three — Pg. 21
SECTION 107
MAINTENANCE
Fees for re-inspections or for inspections outside of normal business hours shall be
reimbursed as required by the fire chief in accordance with the DFW Airport Schedule
of Charges, Development Charges.
SECTION 108
BOARD OF APPEALS
108.1 Board of appeals. Refer to Part One, Construction and Fire Prevention
Standards Resolution for Board of Appeals.
SECTION 109
VIOLATIONS
109.4 Violation penalties. Refer to Part One, Construction and Fire Prevention
Standards Resolution, Section 27, Penal Clause.
SECTION 202
DEFINITIONS
ADDRESSABLE FIRE DETECTION SYSTEM. Any fire alarm system capable of
providing identification of each individual alarm-initiating device. The identification shall
be in clear English and shall identify the type and location of the device in alarm. The
system shall have the ability of alarm verification.
ANALOG INTELLIGENT ADDRESSABLE FIRE DETECTION SYSTEM. Any system
capable of calculating a change in value by directly measurable quantities (voltage,
resistance, etc.) at the sensing point. The physical analog may be conducted at the
sensing point or at the main control panel. The system shall be capable of
compensating for long-term changes in sensor response while maintaining a constant
sensitivity. The compensation shall have a preset point at which a
detectomaintenance signal shall be transmitted to the control panel. The sensor shall
remain capable of detecting and transmitting an alarm while in maintenance alert.
HIGH-PILED COMBUSTIBLE STORAGE. Any building classified as a group S
occupancy or Speculative building exceeding 12,000 sq.ft. that has a clear height in
excess of 14 feet which permits storage in excess of 12 feet shall be considered high-
piled storage.
HIGH-RISE BUILDINGS. Buildings with a floor used for human occupancy located
more than 55 feet (16 764 mm) above the lowest level of fire department vehicle
access.
REPAIR GARAGE. A building structure or portion thereof used for servicing or
Part Three — Fire Code Amendments
Part Three — Pg. 22
repairing motor vehicles. This definition shall also include garages involved in minor
repair, modification and servicing of motor vehicles for items such as oil/lube changes,
Inspections, windshield repair or replacement, shocks, minor part replacement and
other such minor repairs.
SELF-SERVICE STORAGE FACILITY. Real property designed and used for the
purpose of renting or leasing individual storage spaces to customers for the purpose of
storing and removing personal property on a self-service basis.
SECTION 307
OPEN BURNING, RECREATIONAL FIRES AND PORTABLE OUTDOOR
FIREPLACES
307.4.1 Bonfires. Bonfires shall be prohibited within the airport.
SECTION 404
FIRE SAFETY, EVACUATION AND LOCKDOWN PLANS
4.10 Fire extinguishing system controls.
SECTION 501
GENERAL
501.4 Timing of installation. When fire apparatus access roads or a water supply for
fire protection is required for any structure or development, they shall be installed,
tested and approved upon the completion of the foundation structure and prior to any
additional construction taking place.
SECTION 503
FIRE APPARATUS ACCESS ROADS
503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of
not less than 24 feet (7315 mm), exclusive of shoulders, except for approved security
gates in accordance with Section 503.6, and an unobstructed vertical clearance of not
less than 14 feet (4267 mm).
503.2.2 Authority. The fire code official shall have the authority to require an increase
or decrease in the minimum access widths and vertical clearances where they are
inadequate for fire or rescue operations.
503.2.3 Surface. Fire apparatus roads shall be designed and maintained to support
imposed loads of 82,000 lbs. for fire apparatus and shall be surfaced so as to provide
all-weather driving capabilities.
503.3 Marking. Striping, signs, or other markings, when approved by the fire code
official, shall be provided for fire apparatus access roads to identify such roads or
prohibit the obstruction thereof. Striping, signs and other markings shall be maintained
in a clean and legible condition at all times and replaced or repaired when necessary to
Part Three — Fire Code Amendments
Part Three — Pg. 23
provide adequate visibility.
(1) Striping — Fire apparatus access roads shall be continuously marked by painted
lines of red traffic paint six inches (6") in width to show the boundaries of the lane.
The words "NO PARKING FIRE LANE" or"FIRE LANE NO PARKING" shall appear in
four- inch (4") white letters at 25 feet intervals on the red border markings along both
sides of the fire lanes. Where a curb is available, the striping shall be on the vertical
face of the curb.
(2) Signs — Signs shall read "NO PARKING FIRE LANE" or "FIRE LANE NO
PARKING" and shall be 12" wide and 18" high. Signs shall be painted on a white
background with letters and borders in red, using not less than 2" lettering. Signs shall
be permanently affixed to a stationary post and the bottom of the sign shall be six feet,
six inches (6'6") above finished grade. Signs shall be spaced not more than fifty feet
(50') apart along both sides of the fire lane. Signs may be installed on permanent
buildings or walls or as approved by the Fire Chief.
503.4 Obstruction of fire apparatus access roads. Fire apparatus access roads shall
not be obstructed in any manner, including the parking of vehicles. The minimum widths
and clearances established in Section 503.2.1 and any area marked as a fire lane as
described in Section 503.3 shall be maintained at all times.
SECTION 505
PREMISES IDENTIFICATION
Address identification. New and existing buildings shall be provided with approved
address identification. The address identification shall be legible and placed in a
position that is visible from the street or road fronting the property. Address
identification characters shall contrast with their background. Address numbers shall be
Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each
character shall be not less than b inches (152.4 mm) high with a minimum stroke width
of 1/2 inch (12.7 mm). Where required by the fire code official, address numbers shall
be provided in additional approved locations to facilitate emergency response. Where
access is by means of a private road, buildings do not immediately front a street, and/or
the building cannot be viewed from the public way, a monument, pole or other sign with
approved 6 inch (152.4 mm) height building numerals or addresses and 4 inch (101.6
mm) height suite/apartment numerals of a color contrasting with the background of the
building or other approved means shall be used to identify the structure. Numerals or
addresses shall be posted on a minimum 20 inch (508 mm) by 30 inch (762 mm)
background on border. Address identification shall be maintained.
SECTION 507
FIRE PROTECTION WATER SUPPLIES
Water supply test date and information. The water supply test used for hydraulic
calculation of fire protection systems shall be conducted in accordance with NFPA 291
"Recommended Practice for Fire Flow Testing and Marking of Hydrants" and within one
year of sprinkler plan submittal. The fire code official shall be notified prior to the water
supply test. Water supply tests shall be witnessed by the fire code official, as required.
Part Three — Fire Code Amendments
Part Three — Pg. 24
The exact location of the static/residual hydrant and the flow hydrant shall be indicated
on the design drawings. All fire protection plan submittals shall be accompanied by a
hard copy of the water flow test report, or as approved by the fire code official. The
report must indicate the dominant water tank level at the time of the test and the
maximum and minimum operating levels of the tank, as well, or identify applicable
water supply fluctuation. The licensed contractor must then design the fire protection
system based on this fluctuation information, as per the applicable referenced NFPA
standard. Reference Section 903.3.5 for additional design requirements.
Where required. The location, number and type of fire hydrants connected to a water
supply capable of delivering the required fire flow shall be provided on the public
street or on the site to be protected or both as required by the fire chief. Fire hydrants
shall be installed at intervals not to exceed 250 feet (76 200 mm) along new roadways,
and at such locations that no part of a building exterior wall is in excess of a hose lay,
300 feet (91 440 mm) in length from the hydrant as measured along an approved
route around the exterior of the building.
507.5.4 Obstruction. Unobstructed access to fire hydrants shall be maintained at all
times. Posts, fences, vehicles, growth, trash, storage and other materials or objects
shall not be placed or kept near fire hydrants, fire department inlet connections or fire
protection system control valves in a manner that would prevent such equipment or fire
hydrants from being immediately discernible. The fire department shall not be deterred
or hindered from gaining immediate access to fire protection equipment or fire hydrants.
507.5.1.1Hydrant for standpipe systems.
Buildings equipped with a standpipe system installed in accordance with Section 905 shall have a fire
hydrant within 100 feet(30 480 mm) of the fire department connections.
Exception: The distance shall be permitted to exceed 100 feet (30 480 mm) where approved by
theJ ire code official.from City of Dallas Ordinance No.30135
SECTION 604
EMERGENCY AND STANDBY POWER SYSTEMS
604.1.2 Installation. Emergency power systems and standby power systems shall be
installed in accordance with the International Building Code, NFPA 70, NFPA 110 and
NFPA 111. Existing installations shall be maintained in accordance with the original
approval, except as specified in Chapter 11.
604.1.9 Critical Operations Power Systems (COPS). For Critical Operations Power
Systems necessary to maintain continuous power supply to facilities or parts of facilities
that require continuous operation for the reasons of public safety, emergency
management, national security, or business continuity, see NFPA 70. Amend Section
604.2 to read as follows:
604.2 Where required. Emergency and standby power systems shall be provided
where required by Sections 604.2.1 through 604.2.24 or elsewhere identified in this
Part Three — Fire Code Amendments
Part Three — Pg. 25
code or any other referenced code.
604.2.4 Group A occupancies. Emergency voice/alarm communications systems.
Emergency power shall be provided for emergency voice/alarm communications
systems in the following occupancies, or as specified elsewhere in this code, as
required in Section 907.5.2.2.5. The system shall be capable of powering the required
load for a duration of not less than 24 hours, as required in NFPA 72.
Covered and Open Malls, Section 907.2.20 and 914.2.3
Group A occupancies, Sections 907.2.1 and
907.5.2.2.4. Special Amusement buildings,
Section 907.2.12.3
High-rise buildings, Section 907.2.13
Atriums, Section 907.2.14
Deep Underground buildings, Section 907.2.19
604.2.15 Smoke Control Systems. Standby power shall be provided for smoke control
systems in the following occupancies, or as specified elsewhere in this code, as
required in Section 909.11:
Covered mall building, International Building Code, Section 402.7
Atriums, International Building Code, Section 404.7
Underground buildings, International Building Code, Section 405.8
Group 1-3, International Building Code, Section 408.4.2 Stages, International Building
Code, Section 410.3.7.2
Special Amusement buildings (as applicable to Group A's ), International
Building Code, Section 411.1 Smoke protected seating, Section 1029.6.2.1
604.2.17 vered and open mall buildings. Emergency power shall be provided in
accordance with Section 907.2.20 and 914.2.3.
604.2.18 Airport traffic control towers. A standby power system shall be provided in
airport traffic control towers more than 65 ft. in height. Power shall be provided to the
following equipment:
1. Pressurization equipment, mechanical equipment and lighting.
2. Elevator operating equipment.
3. Fire alarm and smoke detection systems.
604.2.19 enclosures and Stair Pressurization Alternative. Standby power shall be
provided for smoke proof enclosures, stair pressurization alternative and associated
automatic fire detection systems as required by the International Building Code, Section
909.20.6.2.
604.2.20 evator pressurization. Standby power shall be provided for elevator
pressurization system as required by the International Building Code, Section 909.21.5.
Part Three — Fire Code Amendments
Part Three — Pg. 26
604.2.21 Shaft Penetrations. Standby power shall be provided when eliminating the
smoke dampers in ducts penetrating shafts in accordance with the International
Building Code, Section 717.5.3, exception 2.3.
604.2.22 st systems for clothes dryers. Standby power shall be provided for common
exhaust systems for clothes dryers located in multistory structures in accordance with
the International Mechanical Code, Section 504.10, Item 7.
604.2.23 hydrogen Cutoff Rooms. Standby power shall be provided for mechanical
ventilation and gas detection systems of Hydrogen Cutoff Rooms in accordance with
the International Building Code, Section 421.8.
604.2.24 means of Egress Illumination in Existing Buildings. Emergency power
shall be provided for means of egress illumination in accordance with Section 1104.5
when required by the fire code official. (90 minutes in 1-2, 60 minutes elsewhere.)
604.8 Energy time duration. Unless a time limit is specified by the fire code official, in
this chapter or elsewhere in this code, or in any other referenced code or standard, the
emergency and standby power system shall be supplied with enough fuel or
energy storage capacity for not less than 2-hour full-demand operation of the system.
Exception: Where the system is supplied with natural gas from a
utility provider and is approved.
SECTION 609
COMMERCIAL KITCHEN HOODS
609.2 Where required. A Type I hood shall be installed at or above
all commercial cooking appliances and domestic cooking appliances
used for commercial purposes that produce grease vapors, including
but not limited to cooking equipment used in fixed, mobile, or
temporary concessions, such as trucks, buses, trailers, pavilions, or
any form of roofed enclosure, as required by the fire code official.
SECTION 704
FLOOR OPENINGS AND SHAFTS
704.1 Enclosure. Interior vertical shafts including, but not limited to,
stairways, elevator hoist ways, service and utility shafts, that connect
two or more stories of a building shall be enclosed or protected in
accordance with the codes in effect at the time of construction but,
regardless of when constructed, not less than as required in Chapter
11. New floor openings in existing buildings shall comply with the
International Building Code.
SECTION 901
GENERAL
Part Three — Fire Code Amendments
Part Three — Pg. 27
901.6.1.1 Standpipe Testing. Building owners/managers must
maintain and test standpipe systems as per NFPA 25 requirements.
The following additional requirements shall be applied to the testing
that is required every 5 years:
1. The piping between the Fire Department Connection (FDC) and
the standpipe shall be back flushed when foreign material is
present, and also hydrostatically tested for all FDC's on any
type of standpipe system. Hydrostatic testing shall also be
conducted in accordance with NFPA 25 requirements for the
different types of standpipe systems.
2. For any manual (dry or wet) standpipe system not having an
automatic water supply capable of flowing water through the
standpipe, the tester shall connect hose from a fire hydrant or
portable pumping system (as approved by the fire code
official) to each FDC, and flow water through the standpipe
system to the roof outlet to verify that each inlet connection
functions properly. Confirm that there are no open hose valves
prior to introducing water into a dry standpipe. There
is no required pressure criteria at the outlet. Verify that check
valves function properly and that there are no closed control
valves on the system.
3. Any pressure relief, reducing, or control valves shall be tested
in accordance with the requirements of NFPA 25. All hose
valves shall be exercised.
4. If the FDC is not already provided with approved caps, the
contractor shall install such caps for all FDC's as required by the
fire code official.
5. Upon successful completion of standpipe test, place a blue tag
(as per Texas Administrative Code, Fire Sprinkler Rules for
Inspection, Test and Maintenance Service (ITM) Tag) at the
bottom of each standpipe riser in the building. The tag shall
be check-marked as "Fifth Year" for Type of ITM, and the note
on the back of the tag shall read "5 Year Standpipe Test" at a
minimum.
6. The procedures required by Texas Administrative Code Fire
Sprinkler Rules with regard to Yellow Tags and Red Tags or any
deficiencies noted during the testing, including the required
notification of the local Authority Having Jurisdiction (fire code
official) shall be followed.
Part Three — Fire Code Amendments
Part Three — Pg. 28
7. Additionally, records of the testing shall be maintained by the
owner and contractor, if applicable, as required by the State
Rules mentioned above and NFPA 25.
901.6.3 False Alarms and Nuisance Alarms. False alarms and nuisance alarms shall
not be given, signaled or transmitted or caused or permitted to be given, signaled for
transmitted in any manner.
901.7 Systems out of service. Where a required fire protection system is out of
service or in the event of an excessive number of activations, the fire department and
the fire code official shall be notified immediately and, where required by the fire code
official, the building shall either be evacuated or an approved fire watch shall be
provided for all occupants left unprotected by the shut down until the fire protection
system has been returned to service.
SECTION 903
AUTOMATIC SPRINKLER SYSTEMS
903.2.11.3 Buildings more than 55 feet in height. An automatic sprinkler system
shall be installed throughout buildings that have one or more stories with an occupant
load of 30 or more, other than penthouses in compliance with Section 1509 of the
Building Code, that is located more than 55 feet (16 764 mm) or more above the lowest
level of fire department vehicle access measured to the finished floor.
Exception:
Open parking structures in compliance with Section 406.5 of the
International Building Code, having no other occupancies above the
subject garage.
903.2.11.7 High-piled combustible storage. For any building with a clear height
exceeding 12 feet (4572 mm), see Chapter 32 to determine if those provisions apply.
903.2.11.8 Buildings with a floor area exceeding 4,000 square feet. An automatic
sprinkler system shall be installed throughout all buildings with a building area
exceeding 4,000 square feet. For the purpose of this provision, fire walls shall not
define separate buildings.
Exception:
Open parking garages.
903.2.11.9 Self-service storage facilities. An approved automatic sprinkler system
shall be installed throughout all self-storage facilities.
903.3.1.1.1 Exempt locations. When approved by the fire code official, automatic
sprinklers shall not be required in the following rooms or areas where it is damp, of fire-
resistance-rated construction or contains electrical equipment.
Part Three — Fire Code Amendments
Part Three — Pg. 29
1. Any room where the application of water, or flame and water, constitutes a
serious life or fire hazard.
2. Any room or space where sprinklers are considered undesirable because of
the nature of the contents, when approved by the code official.
3. Generator and transformer rooms, under the direct control of a public utility,
separated from the remainder of the building by walls and floor/ceiling or
roof/ceiling assemblies having a fire- resistance rating of not less than 2 hours.
4. Elevator machine rooms, machinery spaces, and hoist ways, other than pits
where such sprinklers would not necessitate shunt trip requirements under any
circumstances.
SECTION 905
STANDPIPE SYSTEMS
905.3.9 Buildings exceeding 10,000 sq. ft. In buildings exceeding 10,000 square feet
in area per story and where any portion of the building's interior area is more than 200
feet (60960 mm) of travel, vertically and horizontally, from the nearest point of fire
department vehicle access, Class I automatic wet or manual wet standpipes shall
be provided.
Exceptions:
1. Automatic dry and semi-automatic dry standpipes are allowed as provided for
in NFPA 14.
2. R-2 occupancies of four stories or less in height having no interior corridors.
905.4 i
Location of Class I s ndpipe hose connection?. Class
tandpipe hose connections shag be provided n all of the ollowing
locations:
1. In every required exit stairway, a hose connection shall be provided for each
story above and below grade plane. Hose connections shall be located at an
intermediate landing between stories, unless otherwise approved by the fire code
official.
2. {No Change)
3. In every exit passageway, at the entrance from the exit passageway to other
areas of a building.
Exception: Where floor areas adjacent to an exit passageway are reachable
from an exit stairway hose connection by a 30-foot (9144 mm) hose stream from
a nozzle attached to 100 feet (30 480 mm) of hose, a hose connection shall not
be required at the horizontal exit.
4. {No Change)
5. Where the roof has a slope less than four units vertical in 12 units horizontal
(33.3-percent slope), each standpipe shall be provided with a two-way a hose
connection shall be located to serve the roof or at the highest landing of an exit
Part Three — Fire Code Amendments
Part Three — Pg. 30
stairway with stair access to the roof provided in accordance with Section
1011.12.
6. When required by this Chapter, standpipe connections shall be placed
adjacent to all required exits to the structure and at two hundred feet (200')
intervals along major corridors thereafter, or as otherwise approved
SECTION 907
FIRE ALARM AND DETECTION SYSTEMS
All buildings or occupancies, occupied, operated, maintained or monitored by the Dallas-
Fort Worth International Airport Board shall have a complete operational manual and
automatic fire alarm system in accordance with this code. The system shall be
designed and installed in accordance with the DFW Airport Design Criteria Manual and
applicable standards.
All buildings, other than those described in the preceding paragraph, hereafter
constructed or moved on to the airport and having a total floor area of 1,000 square feet
or more, regardless of height or occupant load, shall have a complete operational
manual and automatic fire alarm system in accordance with the occupancy requirements
of this code.
Exceptions:
1. Open parking garages may use other approved means for fire
department notification.
2. Temporary structures or buildings erected for less than 365 days when
approved by the AHJ.
907.2.13 High-rise buildings. Buildings having floors used for human occupancy
located more than 55 feet (16 764 mm) above the lowest level of fire department
vehicle access shall be provided with an automatic smoke detection system in
accordance with Section 907.2.13.1, a fire department communication system in
accordance with Section 907.2.13.2 and an emergency voice/alarm communication
system in accordance with Section 907.6.2.2.
907.4.2 Manual fire alarm boxes. Where a Manual fire alarm system is required by
another section of this code, it shall be activated by fire alarm boxes installed in
accordance with sections 907.4.2.1 through 907.4.2.6. Manual alarm actuating devices
shall be of an approved double action type.
907.5
Exceptions:
1. Where approved by the code official in airport terminal buildings, and
where the fire alarm is monitored directly by the Dallas/Fort Worth
International Airport Board, Department of Public Safety, the activation of
Part Three — Fire Code Amendments
Part Three — Pg. 31
the fire alarm notification signal shall be manually initiated by emergency
responders.
SECTION 910
SMOKE AND HEAT REMOVAL
901.2.3 Group H. Buildings and portions thereof used as a Group H occupancy as
follows:
1. In occupancies classified as Group H-2 or H-3, any of which are more than
15,000 square feet (1394 sqm) in single floor area.
Exception: Buildings of noncombustible construction containing only
noncombustible materials.
2. In areas of buildings in Group H used for storing Class 2, 3 and 4 liquid and
solid oxidizers, Class 1 and unclassified detonable organic peroxides, Class 3
and 4 unstable (reactive) materials, or Class 2 or 3 water-reactive materials as
required for a high-hazard commodity classification.
Exception: Buildings of noncombustible construction containing only
noncombustible materials.
913.2.1 When located on the ground level at an exterior wall, the fire pump room shall
be provided with an exterior fire department access door that is not less than 3 ft. in
width and 6 ft. — 8 in. in height, regardless of any interior doors that are provided. A key
box shall be provided at this door, as required by Section 506.1.
Exception: When it is necessary to locate the fire pump room on other levels for
not at an exterior wall, the corridor leading to the fire pump room access from the
exterior of the building shall be provided with equivalent fire resistance as that
required for the pump room, or as approved by the fire code official. Access keys
shall be provided in the key box as required by Section 506.1.
SECTION 1003
GENERAL MEANS OF EGRESS
1003.5
Exception: 4. At entrances to mechanical penthouses from roofed areas, the
door sill elevation may be up to 8 inches (203 mm) above the elevation of the
landing on either or both sides of the door.
SECTION 1004
OCCUPANTLOAD
[B] 1004.3 Posting of occupant load. Every room or space that is an assembly
occupancy shall have the occupant load of the room or space posted in a conspicuous
place, near the main exit or exit access doorway from the room or space. Posted signs
Part Three — Fire Code Amendments
Part Three — Pg. 32
shall be of an approved legible permanent design and shall be maintained by the owner
or authorized agent. Assembly occupancies within airport terminal buildings are not
required to have the occupant load posted unless required by the Building Official.
SECTION 1023
INTERIOR EXIT STAIRWAYS AND RAMPS
1023.11 Smokeproof enclosures. In buildings required to comply with Section 403 or
405 of the International Building Code, each of the exit enclosures serving a story with a
floor surface located more than 55 feet (16 764 mm) above the lowest level of fire
department vehicle access or more than 30 feet (9144 mm) below the finished floor of a
level of exit discharge serving such stories shall be a smoke proof enclosure or
pressurized stairway in accordance with Section 909.20 of the International Building
Code.
Exception:
Fixed guideway train stations.
SECTION 5005
USE, DISPENSING AND HANDLING
5005.1.8 Gas cabinets, exhaust enclosures and exhaust ducts with a cross sectional
dimension of 10 inches (255 mm) or greater shall be internally sprinklered.
SECTION 5704
STORAGE
5704.2.9.5.3 Combustible liquid storage tanks inside of buildings. The maximum
aggregate allowable quantity limit shall be 3,000 gallons (11 356 L) of Class II or III
combustible liquid for storage in protected aboveground tanks complying with Section
when all of the following conditions are met:
1. The entire 3,000 gallon (11 356 L) quantity shall be stored in protected above-
ground tanks;
2. The 3,000 gallon (11 356 L) capacity shall be permitted to be stored in a
single tank or multiple smaller tanks;
3. The tanks shall be located in a room protected by an automatic sprinkler
system complying with Section 903.3.1 .1; and
4. Tanks shall be connected to fuel-burning equipment, including generators,
utilizing an approved closed piping system.
The quantity of combustible liquid stored in tanks complying with this section shall not
be counted towards the maximum allowable quantity set forth in Table 5003.1.1(1), and
Part Three — Fire Code Amendments
Part Three — Pg. 33
such tanks shall not be required to be located in a control area. Such tanks shall not be
located more than two stories below grade.
SECTION 5706
SPECIAL OPERATIONS
5706.3.1.3.3 Natural gas pipeline setback from buildings. No building hereinafter
erected shall be located within 50 feet (15 240 mm) of a natural gas gathering pipeline.
SECTION 6003
HIGHLY TOXIC AND TOXIC SOLIDS AND LIQUIDS
6003.5
Exception:
Sprinklers are not required for certain water reactive materials when sprinklers
would not be effective in controlling the fire.
CHAPTER 80 REFERENCED
STANDARDS
Standard Reference Number 130-2014 — NFPA 130, Standard for Fixed Guideway
Transit and Passenger Rail Systems
ADOPTION OF APPENDIX CHAPTERS
The following appendix chapters are specifically adopted as part of the Fire Code.
Appendix B Fire Flow Requirements for Buildings (Except B105.3 — Water
supply for buildings equipped with an automatic sprinkler system
Appendix C Fire Hydrant Locations and Distribution (Except hydrant spacing as
required by Section 507.5.1.)
Appendix D Fire Apparatus Access Roads (except that minimum width of fire
apparatus access roads shall be in accordance with Section
503.2.1 of the Fire Code)
Appendix G Cryogenic Fluids —Weight and Volume Equivalents
Appendix L Requirements for Fire Fighter Air Replenishment System
Part Three — Fire Code Amendments
Part Three — Pg. 34
PART FOUR— ELECTRICAL CODE AMENDMENTS
ARTICLE 89
TITLE
CleGtFoGal Go de of Dallas PE)Ft VVE)Fth I.,t FRatl/wal I\iFP9 t
PesigRThe fWRGtiGR of the depaFtmeRt shall be to assist the buildiRg effiGial ..A. the
• e e
SeGti
109 for fees
89.4
. .fie ,
Reselwt+eR, SeEt+eR 2ReRal Clause.
ReselwtmeR f9F 139aF d of Appeals.
8" Energized Electrical. All electrical energy which requires an electrical inspection by
the DFW Building Official or their representatives, shall first receive an approved inspection
prior to energizing the equipment and/ or the conductors.
Electrical equipment energized without an approved inspection shall be deemed unsafe
electrical.
894 Approval. The conductors and equipment required or permitted by this Code shall be
acceptable only if approved. Approval of equipment may be evident by listing and labeling
of equipment by a Nationally Recognized Testing Lab (NRTL) with a certification mark of
that laboratory or a qualified third party inspection agency approved by the AHJ.
Part Four— Electrical Code Amendments
Part Four— Pg. 1
PART FIVE - MECHANICAL CODE AMENDMENTS
SECTION 101
GENERAL
101.1 Title. The `nil International Mechanical Code as amended herein is
the Mechanical Code of Dallas-Fort Worth International Airport. References to
the International Mechanical Code shall be construed to reference the Mechanical Code
as adopted herein with its local amendments.
502.4 Stationary Storage Battery Systems
Stationary storage battery systems shall be regulated and ventilated in accordance with Section
izut.u. i or the inrernauonai rive uuue "Added to DFW Couw .IJlC aiiiciiuiiiciits below and the
other general requirements of this chapter.
Ventilation Bas„d on exhaust Rate
Mechanical exhaust ventilation shall be provided at a rate of not less than 1 ft3/min/ft2 (5.1
L/sec/m2) of floor area of the room, area or walk-in unit. The ventilation shall be either continuous
or shall be activated by a gas detection system.
Standby Power
Mechanical exhaust ventilation shall be provided with a minimum of 2 hours of standby power.
Commercial kitchen exhaust hood systems
Shall operate during the cooking operation. The hood exhaust rate shall comply with the listing of
the hood or shall comply with Section 507.5. The exhaust fan serving a Type I hood shall have
automatic controls that will activate the fan when any appliance that requires such Type I hood is
turned on, or a means of interlock shall be provided that will prevent operation of
such appliances when the exhaust fan is not turned on. Where one or more temperature or radiant
energy sensors are used to activate a Type I hood exhaust fan, the fan shall activate not more than
15 minutes after the first appliance served by that hood has been turned on. A method
of interlock between an exhaust hood system and appliances equipped with standing pilot burners
shall not cause the pilot burners to be extinguished. A method of interlock between an
exhaust hood system and cooking appliances shall not involve or depend on any component of a
fire-extinguishing system. Airflow sensors shall continuously monitor air flow optimizing
performance and grease removal while an interlocking system will not allow cooking appliances to
function if filters are missing, clogged, or in the event of a fire.
Part Five— Mechanical Code Amendments
Part Five — Pg. 1
SECTION 103
DEPARTMENT OF MECHANICAL INSPECTION
103.1 General. The department of mechanical inspection is hereby created and the
executive official in charge thereof shall be known as the building official. References
to the department of mechanical inspection shall mean the Code Compliance Section
of the Design, Code & Construction.
SECTION 106
PERMITS
106.5.2 Fee schedule. Refer to Part Two, Building Code Amendments, Section 109
for fees.
106.5.3 Fee refunds. The building official is authorized to establish a refund policy.
SECTION 108
VIOLATIONS
108.4 Violation penalties. Refer to Part One, Construction and Fire Prevention
Standards Resolution, Section 27, Penal Clause.
SECTION 109
MEANS OF APPEAL
Replace Section 109 with the following reference:
Refer to Part One, Construction and Fire Prevention Standards Resolution for Board of
Appeals.
Part Five— Mechanical Code Amendments
Part Five — Pg. 1
PART SIX - PLUMBING CODE AMENDMENTS
SECTION 101
GENERAL
101.1 Title. The 2021 International Plumbing Code as amended herein is the Plumbing
Code of Dallas-Fort Worth International Airport. References to the
International Plumbing Code shall be construed to reference the Plumbing Code as
adopted herein with its local amendments.
HANGERS. See shall be installed with all thread rods and clevis hangers, Unistrut
with pipe clamps, pipe titans or an approved equal.
Risers. See ��vva�er pipe, nser Cleanouts shall be required above the floor on risers or
vents for at all lavatories, sinks, urinals, mop sinks, roof drains, automatic clothes washers,
and drinking fountains.
307.3 Penetrations of Floor/Ceiling Assemblies and Fire-Resistance-Rated Assemblies
Penetrations of floor/ceiling assemblies and assemblies required to have a fire-resistance rating
shall be protected in accordance with the International Building Code. PVC larger than 2" which
penetrates through a 2-hour fire rated upper floor shall be equipped with 2-hour intumescent fire
protection coupling.
606.1 Location of Full-Open Valves
6. On the entrance to every water supply pipe to a dwelling unit.
fixt ire equipped with iRdiVid al steps
608.4 Potable Water Handling and Treatment Equipment
Added to DFW Code": An RPZ shall be installed prior to Water pumps, filters, softeners, tanks
and other appliances and devices that handle or treat potable water to be supplied to the potable
water distribution system shall be located to prevent contamination from entering the appliances
and devices. Overflow, relief valve and waste discharge pipes from such appliances and devices
shall terminate through an air gap,
708.1 Cleanouts Required
Cleanouts shall be provided for drainage piping in accordance with
Sections 708.1.1 through 708.1.12. All main building drains and branch drains below the
floor shall either be wall cleanouts above the floor of floor cleanouts.
717.3 Pre-Installation Inspection
The existing piping sections to be replaced or connected to shall be inspected internally by
Part Six - Plumbing Code Amendments
Part Six — Pg. 1
a recorded video camera survey. The survey shall include notations of the position
of cleanouts and the depth of connections to the existing piping.
Post Installation Inspection
The building drain and building sewer shall be inspected internally by a recorded video
camera survey. A copy of the video will be provided to the building official prior to concrete
being installed
915.2.3 Connection
The combination waste and vent system shall be provided with a dry vent connected at
any point within the system or the system shall connect to a horizontal drain that serves
vented fixtures located on the same floor. Combination waste and vent systems connecting
to building drains receiving only the discharge from one or more stacks shall be provided
with a dry vent. The area of a vent installed in a combination waste and vent system shall
be ,lot lets than one pipe size smaller than the drain pipe served. The vent connection to
the combination waste and vent pipe shall extend vertically to a point not less than 6
inches (152 mm) above the flood level rim of the highest fixture being vented before
offsetting horizontally. P-Traps Tor a combination waste and vent system snail reduce at
the main or the trap inlet, one pipe size.
1003.3.1 Grease Interceptors and Automatic Grease Removal Devices Required
A grease interceptor or automatic grease removal device shall be required to receive
the drainage from fixtures and equipment with grease laden waste located in food
preparation areas, such as in restaurants, hotel kitchens, hospitals, school kitchens,
bars, factory cafeterias and clubs. Additionally, floor drains which are located by trash
compactors or any other piece of equipment, or devices where wash down stations
are located to rinse grease laden products shall require a grease interceptor. Fixtures
and equipment shall include pot sinks, prerinse sinks; soup kettles or similar devices;
work stations; floor drains or sinks into which kettles are drained; automatic hood
wash units and dishwashers without prerinse sinks. Grease interceptors and
automatic grease removal devices shall receivewaste only from fixtures and
equipment that allow fats, oils or grease to be discharged. Where lack of space or
other constraints prevent the installation or replacement of a grease interceptor, one
or more grease interceptors shall be permitted to be installed on or above the floor
and upstream of an existing grease interceptor .
Part Six - Plumbing Code Amendments
Part Six — Pg. 2
*-SUPPLY
FIGURE 408.4METHOD OF INSTALLING AT EE FITTING SEDIMENT TRAP
SECTION 103
DEPARTMENT OF PLUMBING INSPECTION
103.1 General. The department of Plumbing inspection is hereby created and the
executive official in charge thereof shall be known as the building official. References
to the department of plumbing inspection shall mean the Code Compliance Section of
the Design, Code & Construction Department.
SECTION 106
PERMITS
106.6.2 Fee schedule. Refer to Part Two, Building Code Amendments, Section 109 for
fees.
106.6.3 Fee refunds. The building official is authorized to establish a refund policy.
SECTION 108
VIOLATIONS
108.4 Violation penalties. Refer to Part One, Construction and Fire Prevention
Standards Resolution, Section 27, Penal Clause.
SECTION 109
MEANS OF APPEAL
Refer to Part One, Construction and Fire Prevention Standards Resolution for Board of
Appeals.
Part Six - Plumbing Code Amendments
Part Six — Pg. 3
SECTION 312
TESTS AND INSPECTIONS
312.10 Inspection and testing of backflow prevention assemblies. Backflow
prevention assemblies shall be inspected and tested as required by Texas Administrative
Code, Title 30, Part 1, Chapter 290 Public Drinking Water.
TABLE 403.1
MINIMUM NUMBER OF REQUIRED PLUMBING FACILITIES
WATER
CLOSETS
(Urinals see BATHTU DRINKING
Section 419.2) BS/ FOUNTAINS
OCCUPANC Femal LAVATORI SHOWER (See Section OTHER
Y Male a ES S 410.1 S
Public
assembly
areas of 1
passenger 1 per 1 per 1 per 200 --- 1 per 1,000 service
terminals and 100 100 sink
transportation
facilities
SECTION 404
ACCESSIBLE PLUMBING FACILITIES
Refer to Part Two, Building Code Amendments, Chapter 11 for accessibility standards.
SECTION 1106
SIZES OF CONDUCTORS, LEADERS AND STORM DRAINS
1106.1 General. The size of the vertical conductors and leaders, building storm drains,
building storm sewers and any horizontal branches of such drains or sewers shall be
based on 5 inches per hour rainfall rate.
SECTION 1109
COMBINED SANITARY AND STORM SYSTEM
1109 Combined sanitary and storm sewer systems shall be prohibited within the
airport.
Part Six - Plumbing Code Amendments
Part Six — Pg. 4
PART SEVEN - FUEL GAS CODE AMENDMENTS
SECTION 101
GENERAL
101.1 Title. The ?nil International Fuel Gas Code as amended herein is the Fuel Gas
Code of Dallas-Fort Worth International Airport. References to the International Fuel
Gas Code shall be construed to reference the Fuel Gas Code as adopted herein with its
local amendments.
SECTION 103
DEPARTMENT OF INSPECTION
103.1 General. The Department of Inspection is hereby created and the executive
official in charge thereof shall be known as the building official. References to the
department of inspection shall mean the Code Compliance Section of the Design, Code
& Construction Department.
SECTION 106
PERMITS
106.5.2 Fee schedule. Refer to Part Two, Building Code Amendments, Section 109 for
fees.
106.5.3 Fee refunds. The building official is authorized to establish a refund policy.
SECTION 108
VIOLATIONS
108.4 Violation penalties. Refer to Part One, Construction and Fire Prevention
Standards Resolution, Section 27, Penal Clause.
Part Seven — Fuel Gas Code Amendments
Part Seven — Pg. 1
SECTION 109
MEANS OF APPEAL
Refer to Part One, Construction and Fire Prevention Standards Resolution for Board of
Appeals.
SECTION 202 (IFGC)
GENERAL DEFINITIONS
BUTT WELD JOINT. A welded pipe joint made with the ends of the two pipes butting
each other.
SOCKET WELD JOINT. A pipe attachment in which a pipe is inserted into a recessed
area of a valve, fitting or flange, generally for small bore piping.
SECTION 403
PIPING MATERIALS
403.10.1.1 All fuel gas piping 2 '/2 inches and above shall be butt welded. All fuel gas
piping 2 inches to '/2 inches shall be socket weld. All pipe and fittings shall comply with
ASME B 36.10, 10M.
Part Seven — Fuel Gas Code Amendments
Part Seven — Pg. 2
PART EIGHT - ENERGY CODE AMENDMENTS
SECTION C101
SCOPE AND GENERAL REQUIREMENTS
C101.1 Title. The 2021 International Energy Conservation Code as amended herein
is the Energy Code of Dallas-Fort Worth International Airport. References to
the International Energy Conservation Code shall be construed to reference the
Energy Code as adopted herein with its local amendments.
C101.1.1 General. The building official is hereby authorized and directed to enforce
the provisions of this code. The building official shall have the authority to render
interpretations of this code and to adopt policies and procedures in order to clarify the
application of its provisions. Such interpretations, policies and procedures shall be in
compliance with the intent and purpose of this code.
SECTION C110
VIOLATION PENALTIES
C110&C110.1 Violation penalties. Refer to Part One, Construction and Fire
Prevention Standards Resolution, Section 27, Penal Clause.
SECTION 202 GENERAL
DEFINITIONS
CODE OFFICIAL. The building official is charged with the administration and
enforcement of this code.
Part Eight - Energy Code Amendments
Part Eight — Pg. 1
PART NINE —OIL AND GAS EXPLORATION AND PRODUCTION
SECTION 1
GENERAL INFORMATION
The Exploration, development and Production of Gas on the Airport property are
activities which make necessary regulations to establish uniform limitations, safeguards
and requirements for operations related to the Exploration, Drilling, developing,
producing, transporting and storing of Gas and other substances produced in
association with Gas within the Airport to protect the health, safety and general welfare
of the public, minimize the potential impact to property, protect the quality of the
environment and encourage the orderly production of available mineral, and gas
resources.
SECTION 2
DEFINITIONS
The following words, terms and phrases, when used in this Part, shall have the meanings
ascribed to them in this section:
Abandonment: means "abandonment" as defined by the Commission and includes the
plugging of a Well and the restoration of the area used during the Production of a Well
as required by this Part.
All-Weather Hard Surface: means a permanent surface that as a minimum is a base
course constructed such that it meets the requirements of the Fire Code, is at least
twenty two feet (22') wide, has an overhead clearance of fourteen feet (14'), drains
appropriately, remains water resistant, is free of litter, debris, weeds, grass or other
objectionable materials or objects and is visibly dust free.
API: means the American Petroleum Institute.
Berm: means a mound of soil, either natural or manmade, used to obstruct a view.
The side slope shall not exceed a three-foot (3') horizontal and a one-foot (1') vertical
slope.
Blowout Preventer means a mechanical, hydraulic, pneumatic or other device or
combination of such devices, including valves, fittings and control mechanisms
connected therewith, which can be closed around the drill pipe, or other tubular goods
which completely close the top of the casing and are designed for preventing blowouts.
Brackish Water means flow back water used in the fracturing and re-fracturing process
and other waste liquids produced in association with the production, treatment,
processing or transportation of hydrocarbons.
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 1
Building: means any structure used or intended for supporting or sheltering any use or
occupancy. Buildings with an occupant load of 3 or fewer in accordance with Table
1004.1.1 of the Building Code are not subject to the setback requirements of this Part.
Building Code: as defined in Part Two.
Building Official: as defined in Section 5, Part 1.
Closed Loop System: means a system utilized while drilling so that the reserve pits are
not used and instead steel bins are used to collect all drilling waste.
Commission: means the Texas Railroad Commission and all state rules.
Completion: means the earlier of the date the work is completed for the Drilling, re-
drilling or reworking of a Well and the crew involved in such activities is released or the
date the rig is released.
Compliant well: means a well that is actively producing, actively used for injection or
disposal, or has a valid Statewide Rule 14(b)(2) plugging extension.
Derrick: means any portable framework, tower, mast and/or structure, which is required
or used in connection with Drilling or re-working a Well for the production of Gas.
Disposal Well: means a well drilled for the purpose of disposing of Brackish Water.
Drilling: means digging or boring a new Well for the purpose of exploring for, developing
or producing Gas or for the purpose of injecting Gas, water or any other fluid or substance
into the earth.
Drill Site: means the immediate area used during the Drilling, re-drilling or re-working of
a Well.
Electrical Code: as defined in Part Four.
Emergency Response Plan: means a plan put in place to deal with emergency
situations that may occur at the Drill Site and/or the Operation Site.
Energy Code: as defined in Part Eight.
Exploration: means geologic or geophysical activities, including seismic surveys,
related to the search for Gas or other subsurface hydrocarbons.
FEMA: means the Federal Emergency Management Agency.
FIRM: means the Flood Insurance Rate Map.
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 2
Fire Chief. as defined in Section 5, Part 1
Fire Code: as defined in Part Three.
Fire Department: means the Fire Department of the Airport.
Frac Tank: means an enclosed steel tank used to hold Brackish Water.
Fracturing: means the injecting of a substance into a Well or formation so as to cause
underground channels in hydro-carbon-bearing formations to open.
Fresh Water Fracing Pit: means a pond open to the atmosphere, used to hold fresh
water for Fracturing.
Fuel Gas Code: as defined in Part Seven.
Gas: means any fluid, either combustible or noncombustible, which is produced in a
natural state from the earth and which maintains a gaseous or rarefied state at standard
temperature and pressure conditions and/or the gaseous components or vapors
occurring in or derived from petroleum or Gas.
Gas Well: means any Well drilled, to be drilled, or used for the intended or actual
production of natural gas.
Inactive well: means a well that is compliant or noncompliant well that is not actively
producing, injecting, or disposing.
Mechanical Code: as defined in Part Five.
Non-compliant well: means a well that has been shut-in for a period in excess of twelve
(12) months, has not been plugged, and does not have a valid Statewide Rule 14(b)(2)
extension.
Oil: means crude petroleum oil and other hydrocarbons regardless of gravity which are
produced at the wellhead in liquid form and the liquid hydrocarbons known as distillate
or condensate recovered or extracted from Gas, other than gas produced in association
with oil and commonly known as casing head gas.
Oil Well: means any Well drilled, to be drilled, or used for the intended or actual
production of Oil.
Operation Site: means the area used for development and production and all
operational activities associated with Gas after Drilling activities are complete.
Operator means, for each Well, the person listed on the Commission's Form W-1 or
Form P-4 for a Gas Well or Oil Well that is, or will be actually in charge and in control of
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 3
Drilling, maintaining, operating, pumping or controlling any Well, including, without
limitation, a unit operator.
Permit: means any written license granted by the Airport authorizing the Operator to
undertake activity on the Airport.
Plumbing Code: as defined in Part Six.
Production: means the period between Completion of Drilling and the Abandonment of
the Well.
Re-Drill: means the Drilling of a new Well located in essentially the same place as an
earlier Well or the re-completion of an existing well by deepening or sidetrack
operations extending more than one hundred fifty feet (150') from the existing Well
bore.
Re-working: means re-completion or re-entry of an existing well within the existing bore
hole or by deepening or sidetrack operations which do not extend more than one
hundred fifty feet (150') from the existing well bore, or replacement of well liners or
casings.
Statewide Rule 14(b) (2) extension: A Texas Railroad Commission administratively
granted extension of one year to plug a well, if: the well is in compliance with all other
laws and Railroad Commission rules; the well and associated facilities are not a pollution
hazard; the operator's report is current and active; and the operator has, and upon
request, provides evidence of a good faith claim to operate the well.
Street: means any street, highway, sidewalk, alley, or avenue that is open to public use
or is in support of Airport operations.
SWPPP: means storm water pollution prevention plan.
TCEQ: means the Texas Commission on Environmental Quality.
USEPA: means the United States Environmental Protection Agency.
Well: means any single hole or bore to any horizon, formation, or strata, for the
purpose of producing Gas and/or Oil from the Airport.
SECTION 3
AIRPORT OVERSIGHT
The Building Official is charged with the administration and enforcement of this part.
The Building Official and the Fire Chief shall have the authority to enter and inspect any
Drill Site or Operation Site to determine compliance with this Resolution and all
applicable laws, rules, regulations, standards or directives adopted by the Airport Board
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 4
or State. Failure of any person to permit access to the Building Official or Fire Chief
shall constitute a violation of this Resolution. Additionally, the Building Official or Fire
Chief and other Airport officials shall have the authority to issue any orders or directives
required to implement the intent and purpose of this Resolution and its provisions. The
Building Official or Fire Chief shall have the authority to request and receive any
records, including any records sent to the Commission, logs, reports and the like,
relating to the status or condition of any Well necessary to establish and determine
compliance with a Permit. Failure of any person to provide any such requested material
shall be deemed a violation of this Resolution.
SECTION 4
OPERATOR'S AGENT
Every Operator shall designate an agent, who is a resident of the State of Texas, upon
whom all orders and notices provided in this Resolution may be served in person or by
registered or certified mail. Every Operator designating such agent shall within ten (10)
days notify the Building Official in writing of any change in such agent or such mailing
address unless operations within the Airport are discontinued. Failure to do so shall be
deemed a violation of this Resolution.
SECTION 5
SEISMIC SURVEY PERMIT REQUIREMENTS
A Permit shall be required for all geophysical tests, including but not limited to seismic
surveys. All applications for a Permit to conduct geophysical tests, including but not
limited to seismic surveys, shall be submitted to the Building Official for approval. No
geophysical tests shall begin prior to the issuance of a Permit from the Airport Board. A
Permit application shall include, but is not limited to, the following information:
(a) Operator/applicant name, phone number, fax number, physical address, and e-
mail address.
(b) Detailed mapping of location and extent of the proposed geophysical test.
(c) Detailed explanation of the survey or testing method to be used.
(d) Frequency and strength of all radio frequency (RF) signals.
(e) Under no circumstances may explosive charges, including, but not limited to, the
use of dynamite, be used in any way related to the preparation for and/or
conducting of a geophysical test.
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 5
SECTION 6
GAS WELL AND DISPOSAL WELL PERMIT REQUIREMENTS
(a) No person acting either for himself or acting as an agent, employee, independent
contractor, or servant of any person shall drill any Well or Disposal Well, assist in
any way in the site preparation, re-working, Fracturing or operation of any Well or
Disposal Well or to conduct any activity related to the production of Gas without
first obtaining a Permit issued by the Building Official in accordance with this
Resolution. Such activities include, but are not limited to, initial site preparation,
re-working, Drilling, operations, construction of rigs, Fresh Water Fracing Pit or
tank batteries, Fracturing and pressurizing.
(b) The Operator must apply for and obtain a Permit for the Drilling of each Well or
Disposal Well. The Operator shall neither apply for nor obtain a "blanket" Permit
for more than one (1) well. A Disposal Well permit will only be issued for disposal
of Brackish Water from oil and gas exploration and production, treatment or
transportation of hydrocarbons within the boundaries of Dallas/Fort Worth
International Airport property. All Disposal Wells must deposit Brackish Water
into the Ellenberger formation. Each new Well or Disposal Well established at
the ground surface will be considered a new Well or Disposal Well as applicable.
(c) An existing Permit shall not constitute authority for the re-entering and Drilling of
a Well the subject of Abandonment. An Operator shall obtain a new Permit in
accordance with the provisions of this Resolution if the Operator is re-entering
and Drilling an abandoned Well.
(d) When a Permit has been issued to the Operator for the Drilling, re-entering,
activating or converting of a Well, such Permit shall constitute sufficient authority
for Drilling, operation, production gathering or production maintenance, repair,
re-working, testing, plugging and Abandonment of the Well and/or any other
activity associated with mineral exploration at an Operation Site. An amended
Permit shall be obtained before such Well may be modified for purposes of re-
drilling, deepening or converting such Well to a depth or use other than that set
forth in the then-current Permit for such Well.
(e) Any person who intends to re-work a Well using a Drilling rig or to engage in
Fracturing a Well after initial Completion shall give written notice to, and receive
written approval from, the Building Official. The notice must identify where the
activities will be conducted and must describe the activities in detail, including,
but not limited to the duration of the activities and the time the activities will be
conducted. The notice must also provide the address and twenty-four (24) hour
telephone number of the person conducting the activities.
(f) A Permit shall automatically terminate, unless extended, if Drilling is not
commenced within one year from the date of the issuance of the Permit. A
Permit may be extended by the Building Official upon written request by the
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 6
Operator and proof that the regulatory standards of the requested Permit for
such location have not changed.
(g) Permits required by this Resolution are in addition to and are not in lieu of any
permit, which may be required by any other governmental agency.
(h) No Permit shall be issued for any Well to be drilled within the floodway identified
by FEMA on the most current FIRM. Wells proposed in the floodplain outside of
the floodway shall comply with the requirements of the Building Official.
(i) No Permit shall be issued for any Well to be drilled that is not in compliance with
this Resolution.
Q) By acceptance of any Permit issued pursuant to this Resolution, the Operator
expressly stipulates and agrees to be bound by and comply with the provisions
of this Resolution. The terms of this Resolution shall be deemed to be
incorporated in any Permit issued pursuant to this Resolution with the same
force and effect as if this Resolution was set forth verbatim in such Permit.
(k) Operator must provide to the Building Official, a copy of all H-5 and mechanical
integrity tests required by the Commission.
(1) All wells located at DFW Airport must be compliant with Texas Railroad
Commission rules. Wells that have not been in operation for a year must be
plugged and abandoned in accordance with Railroad Commission Statewide
Rule 14(b) (2). This rule requires that plugging operations on each inactive well
commence within one year after operations have ceased. Prior to abandonment,
wells must be plugged consistent with Railroad Commission rules, with cement in
a manner that will not allow movement of fluids into or between Underground
Sources of Drinking Water (USDWs).
SECTION 7
PERMIT APPLICATION
(a) Every application for a Permit issued pursuant to this Resolution shall be on
forms required by the Building Official, shall include payment of the construction
permit and plan review fees and shall be signed by the Operator, or some person
duly authorized to sign on his behalf, and filed with the Building Official. The
application shall include the following information:
(1) The date of the application and type of Permit requested.
(2) Map showing proposed transportation route and road(s) for equipment,
chemicals or waste products used or produced under the Permit.
(3) Proposed Well name and Well depth.
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 7
(4) Name, telephone number, fax number, physical address of individual
designated to receive notice, and, if possible, e-mail address.
(5) Names and addresses of representatives or Operator's agent with
supervisory authority over the Drill Site or Operation Site and a twenty-four
(24) hour telephone number.
(6) Location and description of all improvements and structures within eight
hundred feet (800') of the Well. Such locations and descriptions shall be
prepared by a Registered Professional Land Surveyor.
(7) A site plan of the proposed Drill Site and Operation Site showing the
location of all improvements and equipment, including the location of the
proposed Well and other facilities including, but not limited to, Fresh Water
Fracing Pit, Disposal Well, tanks, pipelines, compressors, separators and
storage tanks or storage sheds. All site plans must include the following
criteria:
a. Location of proposed Buildings and structures indicating sizes in square
feet.
b. The location and intensity of exterior lighting fixtures.
c. The location of mechanical equipment.
d. Outside storage areas.
e. Curb cut locations.
f. Parking, loading, and maneuvering areas.
g. The location, materials and dimensions of screening improvements as
required.
h. Waste disposal locations.
i. Streets immediately adjacent to the Operation Site.
j. Drill Site and Operation Site plans shall be submitted on a sheet size of
24" x 36" minimum, or as approved by the Building Official.
k. Airport boundaries where applicable.
I. Date the drawing was prepared with name, address, and phone number
of preparer.
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 8
m. North arrow, at a maximum scale of 1:50 immediately adjacent to the
Drill Site or Operation Site.
n. Title Block identifying the Drill Site or Operation Site location.
o. Vicinity location map at 1" = 2000'.
p. Location of 100-year flood limits where applicable.
q. Texas NAD83 State Plane Coordinates for all four corners.
(8) Copy of all reports and permits required by the Commission, specifically
including a copy of the approved Commission Form W-1, H-5 and/or P-4.
(9) A description of public utilities required during Drilling and Production.
(10) A description of the water source to be used during Drilling.
(11) A copy of the Erosion Control Plan as required by the Airport Board.
(12) A copy of the determination by the TCEQ of the depth of useable quality
ground water.
(13) A copy of the TCEQ permit.
(14) A statement, under oath, signed by the Operator or designated
representative, that the information submitted with the application is, to the
best knowledge and belief of the Operator or designated representative,
true and correct.
(15) Three copies of a Hazardous Material Management Plan and additionally,
all material safety data sheets for all hazardous materials that will be located,
stored, transported and/or temporarily used on the Drill Site shall be
provided to the Building Official.
(16) Three copies of the Hazardous Materials Inventory Statement.
(17) Operator shall submit to the Building Official, for review and approval, an
Emergency Response Plan establishing written procedures to minimize any
hazard resulting from Drilling, Completion or producing of a Gas Well. Said
plan shall use existing guidelines established by the Commission, TCEQ,
Texas Department of Transportation, the Fire Code and/or the USEPA. A
copy of the Emergency Response Plan shall be kept on site.
(18) A map showing the location of all underground transmission pipelines.
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 9
SECTION 8
PERMITTING PROCEDURE
(a) All Well Permit applications will be filed through the Building Official.
(b) It is the responsibility of the Building Official to review and approve or disapprove
all applications for Permits based on the criteria established by this Resolution.
(c) After the filing of a completed application, payment of permit and plan review
fees and remittance of all insurance and security per the requirements of this
Resolution for a Permit, the Building Official will determine whether the Permit
application shall be approved or denied.
(d) The provisions of this Resolution shall apply to any application for a Permit that
is filed with the Building Official.
(e) If all the requirements of this Resolution are met, the Building Official shall issue
a Permit for the activity for which the Permit application was made.
(f) If the Building Official denies a Permit application, the Building Official shall notify
the Operator in writing of such denial stating the reasons for the denial. The
Operator may cure those conditions that caused the denial and resubmit the
application to the Building Official for approval and issuance of the Permit.
SECTION 9
AMENDED GAS WELL PERMITS
(a) An amended Permit may be issued for, but not limited to, the following changes
in Drill Site or Operation Site activities:
(1) Re-drilling;
(2) Deepening beyond one hundred fifty feet (150') of the permitted depth;
(3) Site access; and
(4) Locations and/or quantities of equipment as determined by the Building
Official;
(b) Applications for amended Permits shall be in writing, shall be signed by the
Operator, and shall include the following:
(1) A description of the proposed amendments;
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 10
(2) Any changes to the information submitted with the application for the existing
Permit (if such information has not previously been provided to the Airport
Board);
(3) Such additional information as is reasonably required by the Building Official
to demonstrate compliance with the Permit;
(4) Such additional information as is reasonably required by the Building Official
to prevent imminent destruction of property or injury to persons; and
(5) An amended site plan and plat indicating the new bottom-hole location.
(c) All applications for amended Permits shall be filed with the Building Official for
review. Incomplete applications may be returned to the applicant, in which case
the Building Official shall provide a written explanation of the deficiencies.
(d) If the activities proposed by the amendment are not materially different from the
activities covered by the existing Permit then the Building Official shall approve
or disapprove the amendment after the application is filed.
(e) If the activities proposed by the amendment are materially different from the
activities covered by the existing Permit, and do not create a risk of destruction
of property or injury to persons, then the Building Official shall approve or
disapprove the amendment. If, however, the activities proposed by the
amendment are materially different and, in the judgment of the Building Official
might create a risk of destruction of property or injury to persons that were not
associated with the activities covered by the existing Permit or that were not
otherwise taken into consideration by the existing Permit, the Building Official
may require the amendment to be processed as a new Permit application.
SECTION 10
SUSPENSION OR REVOCATION OF WELL PERMITS
(a) If an Operator (or its officers, employees, agents, contractors, or representatives)
fails to comply with any requirement of a Permit (including any requirement
incorporated by reference as part of the Permit), the Airport Board shall give
written notice to the Operator specifying the nature of the failure and giving the
Operator a reasonable time to cure, taking into consideration the nature and
extent of the failure, the extent of the efforts required to cure, and the potential
impact on the health, safety, and welfare of the public. In no event, however,
shall the cure period be less than ten (10) days unless the failure presents a risk
of imminent danger to property or injury to persons or unless the failure involves
the Operator's failure to provide periodic reports as required by this Resolution.
(b) If the Operator fails to correct the noncompliance, the Airport Board may suspend
or revoke the Permit pursuant to the provisions of this Resolution.
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 11
(c) No person shall carry on any operations performed under the terms of a Permit
issued under this Resolution during any period of any suspension or revocation
of the Permit or pending a review of the decision or order of the Airport Board in
suspending or revoking the Permit. Nothing contained herein shall be construed
to prevent the necessary, diligent and bona fide efforts to cure and remedy the
default or violation for which the suspension or revocation of the Permit was
ordered for the safety of persons or as required by the Building Official or the
Fire Chief.
(d) If the Operator does not cure the noncompliance within the time specified in this
Resolution, the Airport Board, upon written notice to the Operator, may notify the
Commission and request that the Commission take any appropriate action.
SECTION 11
PERIODIC REPORTS
(a) The Operator shall notify the Building Official of any changes to the following
information within ten (10) days after the change occurs:
(1) The name, physical address, telephone number, and fax number of the
Operator;
(2) The name, address, and telephone number of the person designated to
receive notices from the Airport Board (which person must be a resident of
Texas that can be served in person or by registered or certified mail); and
(3) The Operator's emergency action response plan (including "drive-to-maps"
from rights-of-way to each Drill Site or Operation Site).
(b) The Operator shall notify in writing the Building Official of any change to the
name, address, and twenty-four (24) hour phone number of the person(s) with
supervisory authority over Drilling or operations activities within one (1) business
day.
(c) The Operator shall provide a copy of any "incident reports" or written complaints
submitted to the Commission and a copy to the Airport Board within thirty (30)
days after the Operator has notice of the existence of such reports or complaints.
(d) Beginning on December 31 st after each Well is completed, and continuing on
each December 31St thereafter until the Operator notifies the Building Official that
there has been an Abandonment of the Well and the Operation Site is restored,
the Operator shall submit a written report to the Building Official identifying any
changes to the information that was included in the application for the applicable
Permit that have not been previously reported to the Building Official.
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 12
SECTION 12
BOND, LETTERS OF CREDIT, INDEMNITY INSURANCE
(a) General requirements. The Operator shall be required to:
(1) Comply with the terms and conditions of this Resolution and the Permit
issued hereunder.
(2) Promptly clear each Drill Site and Operation Site of all litter, trash, waste
and other substances used, allowed, or occurring in the operations, and
after Abandonment or Completion grade, level and restore such property to
the same surface conditions as nearly as possible as existed before
operations as determined by the Building Official.
(3) Promptly pay all fines, penalties and other assessments imposed due to
breach of any terms of the Permit.
(4) Promptly restore to its former condition any property damaged by the
Operator.
(b) Bond, irrevocable letter of credit. Prior to the issuance of a Permit the Operator
shall provide the Building Official with a security instrument in the form of a bond
or an irrevocable letter of credit as follows:
(1) Bond. A bond shall be executed by a reliable bonding or insurance institution
authorized to do business in Texas, acceptable to the Airport Board. The
bond shall become effective on or before the date the Permit is issued and
shall remain in force and effect for at least a period of six (6) months after
the expiration of the Permit term or until there has been an Abandonment
of the Well and the Operation Site is restored, whichever occurs last.
The Operator shall be listed as principal and the instrument shall run to
the Airport Board, as obligee, and shall be conditioned that the Operator will
comply with the terms and regulations of this Resolution and all other laws
and regulations. The original bond shall be submitted to the Building Official.
(2) Letter of Credit. A letter of credit shall be issued by a reliable bank authorized
to do business in Texas and shall become effective on or before the date
the Permit is issued. The letter of credit shall remain in force and effect for
at least a period of six (6) months after the expiration of the Permit term or
until there has been an Abandonment of the Well and the Drill Site or
Operation Site is restored, whichever occurs last. The Airport Board shall
be authorized to draw upon such letter of credit to recover any fines,
penalties or costs to remedy assessed under this Resolution. Evidence of
the execution of a letter of credit shall be submitted to the Building Official
by submitting an original signed letter of credit from the banking institution.
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 13
(3) The principal amount of any security instrument shall be fifty thousand
dollars ($50,000)for any single well. After Completion of a Well, the Operator
may submit a request to the Building Official to reduce the existing bond to
ten thousand dollars ($10,000) for the remainder of the time the Well
produces without reworking. During reworking operations, the amount of the
bond or letter of credit shall be maintained at fifty thousand dollars
($50,000). If at any time after no less than a fifteen (15) day written notice
to the Operator, the Airport Board shall deem any Operator's bond or letter
of credit to be insufficient, it may require the Operator to increase the
amount of the bond or letter of credit up to a maximum of two hundred fifty
thousand dollars ($250,000) per Well.
(4) Whenever the Building Official finds that a default has occurred in the
performance of any requirement or condition imposed by this Resolution, a
written notice shall be given to the Operator. Such notice shall specify the
work to be done, the estimated cost and the period of time deemed by the
Building Official to be reasonably necessary for the completion of such
work. After receipt of such notice, the Operator shall, within the time therein
specified, either cause or require the work to be performed, or failing to do
so, shall pay over to the Airport Board one hundred twenty-five percent
(125%) of the estimated cost of doing the work as set forth in the notice. In
no event, however, shall the cure period be less than thirty (30) days unless
the failure presents a risk of imminent destruction of property or injury to
persons or unless the failure involves the Operator's failure to provide
periodic reports as required by this Resolution. The Airport Board shall be
authorized to draw against any irrevocable letter of credit or bond to recover
such amount due from the Operator. Upon receipt of such monies, the
Airport Board shall proceed by such mode as deemed convenient to cause
the required work to be performed and completed, but no liability shall be
incurred other than for the expenditure of said sum in hand. In the event
there has not been a proper Abandonment of the Well under the regulations
of the Commission, such additional money may be demanded from the
Operator as is necessary to properly plug and abandon the Well and restore
the Drill Site or Operation Site in conformity with the regulations of this
Resolution.
(5) In the event the Operator does not cause the work to be performed and fails
or refuses to pay over to the Airport Board the estimated cost of the work to
be done as set forth in the notice, or the issuer of the security instrument
refuses to honor any draft by the Airport Board against the applicable
irrevocable letter of credit or bond, the Airport Board may proceed to obtain
compliance and abate the default by way of civil action against the
Operator, or by criminal action against the Operator, or by both such
methods.
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 14
(6) When there has been a proper Abandonment of the Well or Wells covered
by said irrevocable letters of credit or bond in conformity with all regulations
of this Resolution, and in conformity with all regulations of the Commission
and notice to that effect has been received by the Airport Board, or upon
receipt of a satisfactory substitute, the irrevocable letter of credit or bond
issued in compliance with these regulations shall be terminated and
cancelled.
(c) Insurance. The Operator must at all times maintain the specific coverages listed
below.
(1) Environmental pollution liability coverage. Operator shall purchase and
maintain in force for the duration of the Permit, insurance for environmental
pollution liability applicable to bodily injury; property damage, including loss
of use of damaged property or of property that has not been physically
injured or destroyed; cleanup costs; and defense, including costs and
expenses incurred in the investigation, defense or settlement of claims; all
in connection with any loss arising from the insured site. Coverage shall be
maintained in an amount of at least one million dollars ($1,000,000) per
loss, with an annual aggregate of at least ten million dollars ($10,000,000).
a. Coverage shall apply to sudden and accidental pollution conditions
resulting from the escape or release of smoke, vapors, fumes, acids,
alkalis, toxic chemicals, liquids or gases, waste material or other irritants,
contaminants or pollutants.
b. The Operator shall maintain continuous coverage and shall purchase
extended coverage period insurance when necessary. The extended
coverage period insurance must provide that any retroactive date
applicable to coverage under the policy precedes the effective date of the
issuance of the Permit by the Building Official.
(2) Control of Well. The policy should cover the cost of controlling a Well that
is out of control, re-drilling or restoration expenses, seepage and pollution
damage as first party recovery for the Operator and related expenses,
including, but not limited to, loss of equipment, experts and evacuation of
residents, in the amount of five million dollars ($5,000,000) per
occurrence/no aggregate, if available, otherwise an aggregate of ten million
dollars ($10,000,000). Five hundred thousand dollars ($500,000) sub-limit
endorsement may be added for damage to property for which the Operator
has care, custody and control.
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 15
SECTION 13
SETBACK REQUIREMENTS
The following are minimum setbacks.
(a) It shall be unlawful to drill, re-drill, deepen, re-enter, activate or convert any Well
or Disposal Well, the center of which, at the surface of the ground, is located:
(1) Within six hundred feet (600') from any Building; or
(2) Within one hundred feet (100') from any Building accessory to, but not
necessary to the operation of the well; or
(3) Within seventy-five feet (75') of any existing or planned right of way for
street, highway or rail; or
(4) Within two hundred feet (200') of any existing potable water well.
(b) Tank batteries, separators and compressors and their associated vents and
flares shall be located at least three hundred feet (300') from any Street or
Building not used in operations on the Drill Site or Operations Site, nor less than
five hundred feet (500') from any flammable bulk storage facility.
(c) Fresh Water Fracking Pits shall be located at least one hundred feet (100') from
any Street or Building.
(d) The measurement of all distances shall be calculated from the proposed Well
bore, Disposal Well bore, tank battery, separator, compressor or Fresh Water
Fracking Pit in a straight line, without regard to intervening structures or objects
to the closest exterior point of the object listed in items (a) through (c) above.
The above calculations shall be prepared by a Registered Professional Land
Surveyor.
(e) As to any public park, residence, religious institution, hospital building, school or
other public building that is outside the boundaries of the Airport, the distances
set out in subsections (a) through (c) of this section may not be reduced without
both of the following:
(1) Written notarized waivers granted by all the surface owners must be filed,
at the expense of the Operator, in the applicable county records. All
waivers must identify the property address, block and lot number,
subdivision name and plat volume and page number.
(2) With an approved variance obtained in accordance with procedures
outlined under Section 20 of this Part.
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 16
(f) As to any Building that is within the boundaries of the Airport, the distances set
out in subsections (a) through (c) of this section may be reduced with an
approved variance in accordance with procedures outlined under Section 20 of
this Part but may not be reduced to less than that permitted by the Fire Code.
SECTION 14
ON SITE AND TECHNICAL REGULATIONS
(a) Abandoned Wells. All Wells shall be plugged and abandoned in accordance
with the rules of the Commission; however, all Well casings shall be cut and
removed to a depth of at least three feet (3') below the surface. No Building
shall be built over an abandoned well. A well marker, with the well number
displayed on it, must be welded to the top of the cut off well pipe.
(b) Blowout prevention. In all cases, blowout prevention equipment shall be used
on all wells being drilled, worked-over or in which tubing is being changed.
Protection shall be provided to prevent blowout during petroleum or gas
operations as required by and in conformance with the requirements of the
Commission and the recommendations of the American Petroleum Institute.
The Operator must equip all Drilling Wells with adequate blowout preventers,
flow lines and valves commensurate with the working pressures involved as
required by the Commission.
The ram-type blowout preventers, valves, and manifolds shall be pressure
tested as follows:
1.) at the time of installation,
2.) whenever any seal subject to test pressure is broken,
3.) following related repairs and
4.) at 30 day intervals thereafter.
A period of more than thirty (30) days between blowout preventer tests may be
allowed, with the Building Official's approval, when well operations prevent
testing, provided the tests will be conducted as soon as possible before normal
operations resume. The record of communications with the Building Official
shall be entered in the driller's log.
During drilling and completion operations, the ram-type blowout preventers
shall be tested by closing at least once each trip, and the annular-type preventer
shall be tested by closing on drill pipe once each week. All of the above
described tests and/or drills shall be recorded in the drilling log and made
available to the Building Official upon request.
(c) Hazardous materials storage. All chemicals and/or hazardous materials shall
be stored in such a manner as to prevent, contain, and facilitate rapid
remediation and cleanup of any accidental spill, leak, or discharge of a
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 17
hazardous material. Operator shall have all material safety data sheets for all
hazardous materials on site. All applicable federal and state regulatory
requirements for the proper labeling of containers shall be followed. All
hazardous materials and/or special hazards at the Well sites shall be protected
in accordance with National Fire Protection Association standards, and the Fire
Code. Appropriate pollution prevention actions shall be required and include,
but are not limited to, chemical and materials raised from the ground (e.g.,
wooden pallets), bulk storage, installation and maintenance of secondary
containment systems, and protection from storm water and weather elements.
(d) The following requirements shall apply to all Fracturing operations performed
on a Well:
(1) A watchperson shall be required at all times during such operations; and
(2) At no time shall the Well be allowed to flow or vent directly to the
atmosphere without first directing the flow through separation equipment
or into a portable tank.
(e) Compliance. Operator shall comply at all times with all applicable federal, state
and Airport Board requirements. In the event of any conflicts between the
provisions of this Resolution, and the Commission rules and regulations, the
more restrictive provision shall apply. Whenever necessary to protect health,
safety or welfare, the Building Official or the Fire Chief may direct any Operator
to locate, relocate, remove or replace any Well surface facilities located within
a particular Operation Site.
(f) Discharge. No person shall place, deposit, discharge, or cause or permit to be
placed, deposited or discharged, any oil, naphtha, petroleum, asphalt, tar,
hydrocarbon substances or any refuse including wastewater or brine from any
gas operation or the contents of any container used in connection with any gas
operation in, into, or upon any Streets, lots, storm drain, ditch or sewer, sanitary
drain or any body of water or any property of the Airport.
(g) Drill stem testing. All open hole formation or drill stem testing shall be done
during daylight hours, with adequate advance notification thereof to the
Building Official to enable him to be present during such testing. Drill stem
tests may be conducted only if the Well effluent during the test is produced
through an adequate gas separator to storage tanks and the effluent remaining
in the drill pipe at the time the tool is closed is flushed to the surface by
circulating drilling fluid down the annulus and up the drill pipe.
(h) Drip pans and other containment devices. All materials on location (liquids,
semi-liquids and solids) and any tanks, containers, pumps, lubricating systems,
engines, fuel and chemical storage tanks or systems containing such materials
shall be provided with drips pans or other containment devices appropriate to
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 18
the risks and hazards that those materials pose to workers, the public and the
environment.
(i) Dust, vibration, odors. All Drilling and production operations shall be conducted
in such a manner as to minimize, so far as practicable, dust, vibration, or
noxious odors, and shall be in accordance with the best accepted practices
incident to Drilling for the production of Gas and other hydrocarbon substances.
All equipment used shall be so constructed and operated so that, vibrations,
dust, odor or other harmful or annoying substances or effect will be minimized
by the operations carried on at any Drilling or production site or from anything
incident thereto; nor shall the site or structures thereon be permitted to become
dilapidated, unsightly or unsafe. Proven technological improvements as
identified by the Building Official in industry standards of Drilling and
production in this area may be adopted as they become available if capable of
reducing dust, vibration and odor.
Q) Electric lines. All electric lines to production facilities shall be located in a
manner compatible to those already installed in the surrounding area.
(k) Emergency Response Plan. Prior to the commencement of any Gas or other
hydrocarbons site activities, Operator shall submit to the Building Official an
Emergency Response Plan establishing written procedures to minimize any
hazard resulting from Drilling, Completion or producing of a Gas Well. Said
plan shall use existing guidelines established by the Commission, TCEQ, Texas
Department of Transportation and/or the USEPA. The Emergency Response
Plan shall be kept current with any additions, modifications, and/or
amendments concerning all construction-related activities, natural gas
operations and, and/or natural gas production. Those updates to the Plan
which might materially impact the needs or actions of first responders or the
DFW Airport Emergency Management Plan shall be submitted to the approved
distribution list as soon as practical. A copy of the Emergency Response Plan
shall be kept on site.
(1) Explosives. Use of explosives within Airport property shall require an Operational
Permit issued by the DFW Department of Public Safety Fire Prevention Office.
Each use of explosives will be limited to down-hole activities during a single
period of time, individual locations and use for jet perforation of wells or other
technical applications such as pipe recovery, as described to and approved by
the DFW DPS Fire Prevention Office prior to use..
(m) Fire prevention; sources of ignition. Firefighting apparatus and supplies as
approved by the Fire Department and required by any applicable federal, state,
local law, or the Fire Code shall be provided by the Operator, at the Operator's
cost, and shall be maintained on the Drill Site at all times. The Operator shall
be responsible for the maintenance and upkeep of such equipment. At a
minimum, the Operator shall provide at each Drill Site at least four portable fire
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 19
extinguishers, the size, rating, distribution and maintenance of which shall be in
accordance with the National Fire Protection Association Standard #10 and
Standard #30. The Fire Department may require more fire extinguishers based
on an evaluation of the hazards at the individual sites. Each Well shall be
equipped with an automated valve that closes the Well in the event of an
abnormal change in operating pressure. All wellheads shall contain an
emergency shut off valve to the well distribution line. Lightning protection
equipment shall be installed as required at every site in accordance with the
National Fire Protection Association Standard 780. Tank battery facilities shall
be equipped with a remote foam line and a lightning arrestor system.
(n) Gas emission or burning restricted. No person shall allow, cause or permit Gas
to be vented into the atmosphere or to be burned by open flame except as
provided by law or as permitted by the Commission.
(o) Grass, weeds, trash. Each Drill Site and Operation Site shall be kept clear of
high grass, weeds, and combustible trash.
(p) Lights. No person shall permit any lights located on any Drill Site or Operation
Site to be directed in such a manner so that they shine directly on Streets or
Buildings. To the extent practicable, and taking into account safety
considerations, Drill Site and Operation Site lighting shall be directed
downward and shielded so as to both prevent direct illumination of and minimize
glare on Streets and Buildings within six hundred feet (600').
(q) Muffling exhaust. Exhaust from any internal combustion engine, stationary or
mounted on wheels, used in connection with the Drilling or for use on any
production equipment shall not be discharged into the open air unless it is
equipped with an exhaust muffler, or mufflers or an exhaust muffler box
constructed of noncombustible materials sufficient to suppress noise and
prevent the escape of noxious gases, fumes or ignited carbon or soot. All
Fracturing operations shall be conducted during daylight hours unless the
Operator has notified the Building Official that Fracturing will occur before or
after daylight hours, and the Building Official has approved of such procedures.
(r) Organic solvents. Organic solvents, such as trichloroethylene and carbon
tetrachloride, shall not be used for cleaning any element, structure, or
component of the Derrick, drilling rig, platform, and/or associated equipment,
tools, or pipes. To the maximum extent practicable, high flash point mineral
spirits shall be used.
(s) Pipe dope for thread protection. Lead-free pipe dope shall be substituted for
API specified pipe dope.
(t) Pits. All Drilling and Wells drilled shall utilize a Closed Loop System. Fresh
Water Fracing Pits must be netted at all times to exclude access by waterfowl.
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 20
(u) Private roads and Drill Sites. Prior to the commencement of any Drilling, all
roads used for access to the Drill Site and the Operation Site itself shall be at
least twenty-two feet (22') wide, have an overhead clearance of fourteen feet
(14') and shall be an All-Weather Hard Surface and maintained in accordance
with the Fire Code, and to be non-erodible. In particular cases these
requirements governing surfacing of roads may be altered at the discretion of
the Fire Chief after consideration of all circumstances including, but not limited
to, the following: distances from Streets and Buildings; topographical features;
nature of the soil; and exposure to wind. All access roads must be kept clean
and unobstructed at all times.
(v) Signs (Refer to Part 2 for sign permitting requirements).
(1) A sign shall be immediately and prominently displayed at the gate on the
temporary and permanent site fencing erected pursuant to this Resolution.
Such sign shall be of durable material, maintained in good condition and,
unless otherwise required by the Commission, shall have a surface area
of not less than sixteen (16) square feet with contrasting lettering not less
than four inches (4") tall and shall be lettered with the following:
a. Location Name and Pad Name;
b. Name of Operator;
c. The emergency 911 number; and
d. 24 Hour telephone numbers of two (2) persons responsible for the
Well who may be contacted in case of emergency.
(2) Permanent weatherproof signs reading "DANGER NO SMOKING
ALLOWED" in both English and Spanish shall be posted immediately
upon Completion at the Operation Site fencing at the entrance of each
Operation Site and tank battery or in any other location approved or
designated by the Fire Department. Sign lettering shall be four inches (4")
in height and shall be red on a white background or white on a red
background. Well and lease designation signage shall be posted in those
locations and sizes as required by the Commission in Rule 3.3
Identification of Properties, Wells, and Tanks.
(w) Storage of equipment. On-site storage is prohibited on the Operation Site. No
equipment shall be stored on the Drill Site or Operation Site, unless it is
necessary to the everyday operation of the Well. Lumber, pipes, tubing and
casing shall not be left on the Operation Site except when Drilling or Well
servicing operations are being conducted on the Operation Site. No vehicle or
item of machinery shall be parked or stored on any Street, or upon any
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 21
Operation Site which constitutes a fire hazard or an obstruction to or
interference with fighting or controlling fires except that equipment which is
necessary for Drilling or production operations on the Drill Site or Operation
Site. The Fire Department shall determine whether equipment constitutes a
fire hazard.
(x) Storage tanks. All tanks intended to contain hydrocarbons and permanent
structures shall conform to the API specifications unless other or additional
specifications are approved by the Fire Department. All tanks shall require a
Fire Code permit and application must be made in accordance with the Fire
Code. All storage tanks shall be equipped with a secondary containment system
including lining with an impervious material. The secondary containment system
shall be a minimum of one and one-half (1-1/2) times the contents of the largest
tank in accordance with the Fire Code. Drip pots shall be provided at the pump
out connection to contain the liquids from the storage tank. All tanks shall be
set back pursuant to the standards of the Commission and the Fire Code. Each
storage tank system shall be equipped with a level control device that will
automatically activate a valve to close the Well in the event of excess liquid
accumulation in the tank system. No meters, storage tanks, separation
facilities, or other above ground facilities, other than the wellhead and flow
lines, shall be placed in a floodway identified by FEMA on the most current
FIRM. Meters, storage tanks, separation facilities, or other above ground
facilities proposed in the floodplain shall be outside of the floodway and shall be
subject to approval by the Building Official.
(y) Swabbing, bailing and purging Wells. No person shall begin the operation of
swabbing a Well without first complying with the provisions of this Section. In
swabbing, bailing or purging a Well, all deleterious substances removed from
the borehole shall be placed in appropriate tanks and no substances shall be
permitted to pollute any surface or subsurface fresh water. No Well shall be
swabbed before a device, commonly known as a lubricator, has been placed
on the flow casing above all outlets or flow lines of the Well. The lubricator
shall be not less in diameter than the flow casing and equipped with an adequate
oil saver or stuffing box at the top. The total inside length of the lubricator
shall be not less than five feet (5') more than the total length of swab and turn
back on swab line. The lubricator shall have a nipple not less than two inches
(2") in diameter nor more than four inches (4") in length, placed not more than
six inches (6") from the top of the flow line or lines between the gate valve on
the flow lines and flow casings. The nipple shall be provided with a gate valve
not less than two inches (2") in size. All equipment and parts of the lubricator
shall be of a type designed and tested to withstand a pressure of 3,000
pounds per square inch. All pressure tests shall be by the hydrostatic method.
(z) No refinery, processing, treating or absorption plant of any kind, shall be
constructed, established or maintained within the Airport except as necessary
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 22
to render gas into a quality suitable for delivery to third party pipelines. Natural
gas fractionation will require a separate permit.
(aa) Surface casing. Surface casing shall be in full compliance with the applicable
rules and regulations of the Commission. Surface casing shall have a
centralizer in the middle of the shoe joint, a centralizer on the top of the second
joint of casing, and centralizers every fourth joint. Surface casing must be new
pipe of API grade J or K or higher grade and have a minimum burst pressure
rating of 2,900 psi. In the event a rupture, break or opening occurs in the
surface or production casing, the Operator or drilling contractor shall promptly
report the incident to the Building Official. Immediate action shall be taken to
repair such casing and the Building Official shall be given the opportunity to
witness the repairs.
(bb) Valves. Each well must have a shutoff valve to terminate the Well's production.
The Fire Department shall have access to the Well site to enable it to close
the shut-off valve in an emergency.
(cc) Storage. Any permanent, temporary or portable tank, vessel, container, pit or
impoundment used for storage of products, materials or wastes shall be
selected and maintained to be fit for the purpose and capacity in which it will be
used. Any such storage shall only be used for materials and wastes from oil
and gas exploration and production activities within the boundaries of
Dallas/Fort Worth Airport. All waste shall be disposed of in such time, place
and manner as to comply with the air and water pollution control regulations of
the Federal Government, the State, this Resolution and any other applicable
requirement of the Airport Board.
(dd) Watchperson. The Operator must keep a watchman or security personnel on
site during the Drilling or re-working of a Well when other workers are not on
the premises.
(ee) Installation of pipelines on, under or across Airport property. The Operator
shall apply to the Airport Board for a Permit to use the Airport for the purpose
of constructing, laying, maintaining, operating, repairing, replacing and
removing pipelines. Prior to installation, the owner of the pipeline shall submit
to the Building Official the pipeline design criteria, including but not limited to,
operating pressures, pipeline gradient and elevation to sea level, location, pipe
ASTM grade, and pipe wall thickness. Prior to and subsequent to installation
of each segment of new or replacement pipeline, the pipe and pipeline must
receive and pass on-site inspection of compliance with the design criteria and
the process of installation. All new or replacement pipe or pipelines shall be
covered and must be at least 48 inches below the existing ground level as
verified and approved by the Building Official. Operator shall:
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 23
(1) Not interfere with or damage existing water, sewer or gas lines or the
facilities of public utilities located on, under or across a Street.
(2) Furnish to the Building Official a site plan showing the location of such
pipelines.
(3) Design, construct, maintain and operate natural gas pipelines in
accordance with 49 U.S.C. 60101, et seq.; 49 Code of Federal
Regulations (CFR) Part 191, Transportation of Natural and Other Gas by
Pipeline; Annual Reports, Incident Reports, and Safety-Related Condition
Reports; 49 CFR Part 192, Transportation of Natural and Other Gas by
Pipeline: Minimum Federal Safety Standards; and 49 CFR Part 193,
Liquefied Natural Gas Facilities: Federal Safety Standards.
(4) Grade, level and restore such property to the same surface condition, as
nearly as practicable, as existed prior to the laying of the pipeline.
(5) If a pipeline becomes unsafe or is not properly maintained, or in the event
a leak is detected, the Operator of the line shall immediately evaluate the
leak or release and either shut in the pipeline or, as soon as possible,
shall initiate repairs according to the procedure in section (oo) below.
(6) As mandated by DOT requirements under CFR 192.701, each owner or
operator of a gas pipeline for which a Permit is required under this
Resolution shall have it surveyed at least twice each year with intervals
not to exceed 7.5 months for the purpose of determining whether it is in
safe condition and free from leaks, breaks or open spaces. The owner or
operator shall provide a copy of the leakage survey report required under
DOT CFR 192.706 supported by an affidavit by the person making the
survey to the DFW Department of Public Safety Fire Prevention Office,
within 30 days of completion of the survey. For failure to timely make the
survey and report, or if the report discloses or it otherwise appears that
any line is leaking, defective or unsafe, the pipeline shall be closed and
shut-in until such time as the leak has been repaired, or a repair plan or
report has been approved by the Building Official.
(7) The location of all new or replacement pipe or pipelines shall be marked
by the owner(s) thereof or by the person installing or operating the pipe or
pipeline. Marker signs shall be placed at all locations where pipe or
pipelines cross property boundary lines and at each side of a Street which
the pipe or pipeline crosses. The top of all marker signs shall be a
minimum of four feet (4') above ground level, and the support post must
be sufficient to support the marker sign and shall be painted yellow or
such other color as may be approved by the Building Official. All marker
signs shall comply with US Department of Transportation standards
regarding size, shape, color, installation, positioning, maintenance and
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 24
other related signage requirements. It is the joint and severable
responsibility of the owner and the operator of any and all pipelines to
maintain the markers in accordance with this Section.
(ff) Streets. No Permit shall be issued for any Well to be drilled within any Street,
and no Street shall be blocked, encumbered, or closed due to any Exploration,
Drilling or production operations.
(gg) Vehicle routes. Vehicles associated with Drilling and/or production in excess of
three (3) tons shall be restricted to those arterials or routes designated by the
Airport.
(hh) Tank specifications for a Gas Well. All tanks and permanent structures shall
conform to the API specifications unless other specifications are approved by
the Airport Board. The top of the tanks shall be no higher than twelve feet (12')
above the terrain surrounding the tanks.
(ii) All Drilling, re-entry and operations at any Well shall be conducted using the
best available technology. All casing, valves, Blowout Preventers, drilling fluids,
tubing, Braden head, Christmas tree and wellhead connections shall be of a
type and quality consistent with sound engineering practices. The setting and
cementing of casing and running of drill stem tests shall be performed in a
manner consistent with the best available technology. All persons engaged in
Drilling or production operations shall observe and follow the recommendations
and regulations of the API and the Commission, except in those instances
specifically addressed by this Resolution.
Upon Completion of the Well, the Operator shall provide a copy of the
Commission Completion Report W15, and certify by affidavit that the Well has
been completed according to good engineering practices. The affidavit shall
stipulate the number of sacks of cement, the class of cement, blended
materials, and weight of cement in pounds per gallon; cement displacement
pressure, final pumping pressure and whether check valves held the pressure.
Commencement and completion times of such operation shall be stipulated.
The affidavit must be completed by a cementing service company and signed
by both the Operator and the cementing service company.
(kk) No person shall commence any operation to change the equipment of a Well
for the purpose of cleaning, repairing or reconditioning any such Well, before
notifying the Building Official that such operation is to be commenced. No
person shall commence such operation unless he receives approval. The
Building Official shall give approval for converting from natural to artificial
production if it appears that the provisions of this Resolution have been and
are being complied with.
(II) In no case shall Gas or air be transported through any pipeline at a working
pressure in excess of 1,000 pounds. If it is necessary to use greater working
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 25
pressure, a gas or air booster plant shall be installed not closer than 75 feet
from the Derrick floor of a Well or tank battery and the compressor unit not less
than 100 feet from the Derrick floor of the Well being served. In no event shall
more than 1,500 pounds working pressure be used in flowing a Well by artificial
means.
(mm) All Gas gathering lines and pipelines on DFW Airport shall be designed, installed,
tested and maintained in accordance with the most current version of 49CFR192
— Transportation of Natural or Other Gas by Pipeline: Minimum Federal Safety
Standards. All permanent fresh water and Brackish water HDPE lines shall be
tested to ASTM D-2837 following installation or repair.
(nn) At each Well where air or gas lift is used, there shall be placed on the air or gas
lift an indicating pressure gauge which shall show the working pressure of air or
gas delivered to the Well at all times. All gauges installed on lines shall be
tested and corrected every six (6) months.
(oo) The Building Official shall inspect all pressure lines in use at any Well or at any
project to ensure that tubing, fittings, equipment or connections are reasonably
tight, safe and free from leaks. If it becomes necessary to change or remove
any pipeline, the entire expense of change or removal shall be borne by the
owner of the line requiring repair. Each leak noted shall be classified by a
qualified person as to its risk to people and property based on the leak location,
line use and content, line pressure, surrounding land use and other
considerations. Each leak shall be classified upon discovery, and a repair
schedule shall be developed to make repairs as soon as possible, but not to
exceed one month. The leak shall be monitored regularly until repairs are
made. All such repair plans shall be submitted to and approved by the Building
Official.
(pp) All pipelines, connections and fixtures installed or used for the purpose of gas
transportation shall be operated and maintained in a safe manner at all times
so as to prevent all leakage or escape of their contents.
(qq) The Building Official shall have the authority to require the immediate shutting
in or closing of any Well if he finds there exists, within a 100-foot radius of any
Well, any Gas or gasoline vapor in a quantity sufficient to constitute, in his sole
judgment, or in the sole judgment of the Fire Chief, a fire hazard. The Well
shall remain shut in or closed in until the hazard and its cause have been
remedied.
(rr) In the event of a fire or discovery of a fire, smoke, or unauthorized release of
flammable or hazardous materials, the Operator shall immediately report such
condition to the Fire Department.
(ss) Every Disposal Well shall be constructed so as to seal the injection zone from
the upper portion of the casing. Cement shall be circulated to the surface for
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 26
injection zone casing. The annulus between the casings shall be filled with a
non-corrosive fluid, then sealed and a 1/4—inch female fitting with cutoff valve
shall be attached so that the pressure annulus may be measured by the
Building Official by attaching a gauge with a '/4-inch male fitting. The annulus
between the production casing and the injection tubing shall be pressure tested
to a pressure at least 250 psi greater than the injection pressure proposed for
the Well. The Building Official shall be given the opportunity to witness and
approve the pressure testing. A copy of all H-5 test reports must be provided
to the Building Official. A pressure shall be maintained in the annulus sufficient
to monitor the fluids in the annulus. Any significant deviation from the
established pressure shall be cause to shut down the Well, and may result in
cancellation of the operating Permit, until the established pressure can once
again be maintained.
(1) The DFW Airport Permit for Disposal Well shall reflect the maximum
injection pressure as permitted by the Commission. Exceeding this
injection pressure shall be considered a violation of this Section.
(2) Injection lines for such wells shall be buried to a minimum depth of four
feet (4'), and shall be pressure tested (static) annually at a minimum of
150 percent of the pressure normally encountered at the injection pump
discharge for a period of hours to be fixed by the Building Official. The
Building Official shall be notified in writing five (5) days in advance of such
test and may supervise it. Test results shall be filed with the Building
Official upon completion.
(3) Before performing any down-hole work on a Disposal Well, the Operator
shall notify the Building Official at least five (5) days in advance of
performing the work, or as soon as practical in the event of emergency
repair work. The Building Official shall be given the opportunity to witness
the installation of tubing and packer in the Disposal Well. The annulus
between the injection tubing and the production casing shall then be
pressure tested as required by Commission Rule 3.9.12 Testing. The
Building Official shall be given the opportunity to witness the pressure
testing of this annulus.
(3) The Operator of the well shall submit to the Building Official all reports
and notifications at the same frequency that such reports and
notifications are required under TX RRC Rule 3.9 Disposal Wells, or its
equivalent.
SECTION 15
SCREENING
Throughout the entire Exploration, Drilling, and production process there shall be
screening improvements (fences, walls, Berms and landscaping) required during each
phase of the process if the Drill Site or Operation Site is visible from a Building or
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 27
Street, exclusive of construction roads, haul roads or access roads. Without regard to
visibility, each Fresh Water Fracking Pit that is open to the atmosphere or surface shall
be screened.
(1) During Drilling. A temporary chain link fence with all-weather screening
fabric at least six feet (6) in height shall be established around the entire
Operation Site to obscure view of the Drilling activities. A secured entrance
gate shall be required. All gates are to be kept locked when the Operator
or his employees are not within the enclosure. A "Knox Padlock" or "Knox
Box with a key" shall be provided to access the Well site to be used only
in case of an emergency.
(2) Completion through Abandonment (production phase). A painted
architectural metal fence or other approved fencing and/or screening shall
be required to enclose and visually screen the Well and all associated
equipment. An earthen Berm may also be required. The masonry walls,
Berms, and landscaping shall be in compliance with standard engineering
and design practices and shall meet the following minimum requirements:
a. The painted architectural fence or other approved fencing and/or
screening material and design shall be generally compatible with the
design of similar facilities, Building and structures on and/or adjacent
to the site as approved by the Building Official; and
b. Painted architectural fences shall be at least eight feet (8') in height.
(3) Each Fresh Water Fracking Pit shall be surrounded by a temporary chain
link fence with all-weather screening fabric at least six feet (6) in height.
A secured entrance gate shall be required. All gates are to be kept locked
when the Operator or his employees are not within the enclosure. A
"Knox Padlock" or "Knox Box with a key" shall be provided to access the
Well site to be used only in case of an emergency. If the Fresh Water
Fracing Pit is open to the atmosphere or the surface, it shall be covered
by netting sufficient to inhibit access to the pit by fowl.
(b) Gate specifications. All temporary fences and masonry walls shall be equipped
with at least one (1) gate. The gate shall meet the following specifications:
(1) At least one gate shall be not less than twelve feet (12') wide and be
composed of two (2) gates, each of which is not less than six feet (6) wide,
or one (1) sliding gate not less than twelve feet (12') wide. If two (2) gates
are used, gates shall latch and lock in the center of the span;
(2) The gates shall be of chain link construction, with all-weather screening
fabric, that meets the applicable specifications, or of other approved
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 28
material that, for safety reasons, shall be at least as secure as a chain link
fence;
(3) The gates shall be provided with a combination catch and locking
attachment device for a padlock, and shall be kept locked except when
being used for access to the site; and
(4) Operator must provide the Fire Department with a "Knox Padlock" or "Knox
Box with a key" to access the Well site to be used only in case of an
emergency.
SECTION 16
CLEANUP AND MAINTENANCE
(a) Cleanup after well servicing. After the Well has been completed or there has
been an Abandonment, the Operator shall clean the Drill Site or Operation Site,
complete restoration activities and repair all damage to property caused by such
operations within sixty (60) days.
(b) Clean-up after spills, leaks and malfunctions. After any spill, leak or malfunction,
the Operator shall remove or cause to be removed to the satisfaction of the Fire
Department and the Building Official all waste materials from any property
affected by such spill, leak or malfunction. Clean-up operations must begin
immediately. If the Operator fails to begin clean-up within twenty-four (24) hours,
the Airport Board shall have the right to contact the Commission in order to
facilitate the removal of all waste materials from the property affected by such
spill, leak or malfunction.
(c) Painting. All production equipment shall be painted and maintained at all times,
including wellheads, pumping units, tanks, and Buildings. When requiring
painting of such facilities, the Building Official shall consider the deterioration of
the quality of the material of which such facility or structure is constructed, the
degree of rust, and its appearance. Paint shall be non-reflective and of a neutral
color, compatible with surrounding uses. Neutral colors shall include sand, gray
and unobtrusive shades of green, blue and brown, or other neutral colors
approved by the Building Official.
(d) Blowouts. In the event of the loss of control of any Well, Operator shall
immediately take all reasonable steps to regain control regardless of any other
provision of this Resolution and shall notify the Building Official and Fire Chief as
soon as practicable. If in the opinion of the Building Official or the Fire Chief, a
danger to persons and/or property exists because of such loss of Well control
and that the Operator is not taking or is unable to take all reasonable and
necessary steps to regain control of such Well, the Building Official may then
employ any well control expert or experts or other contractors or suppliers of
special services, or may incur any other expenses for labor and material which
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 29
the Building Official deems necessary to regain control of such Well. The Airport
Board shall then have a valid lien against the interest in the Well of all working
interest owners to secure payment of any expenditure made by the Airport Board
pursuant to such action of the Building Official in gaining control of said Well.
SECTION 17
PLUGGED AND ABANDONED WELLS
(a) Surface requirements for the Abandonment of a Well. Whenever Abandonment
occurs pursuant to the requirements of the Commission, the Operator shall be
responsible for the restoration of the Well site to its original condition as nearly
as practicable, in conformity with the regulation of this Resolution.
(b) Abandonment shall be approved by the Building Official after restoration of the
Drill Site and/or Operation Site has been accomplished in conformity with the
following requirements at the discretion of the Building Official:
(1)The Derrick and all appurtenant equipment thereto shall be removed from the
site;
(2)All tanks, towers, and other surface installations shall be removed from the
site;
(3) All concrete foundations, piping, wood, guy anchors and other foreign
materials regardless of depth, except surface casing, shall be removed from
the site, unless otherwise directed by the Commission;
(4) If any soil was contaminated, it shall be removed in accordance with local,
State and Federal regulations;
(5)All holes and depressions shall be filled to grade with clean, compactable soil;
(6) All waste, refuse or waste material shall be removed; and
(7) During Abandonment, Operator shall comply with all applicable sections in
this Resolution.
(c) Abandoned Well requirement. The Operator shall furnish the following to the
Building Official:
(1) A copy of the approval of the Commission confirming compliance with all
Abandonment proceedings under state law; and
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 30
(2) A notice of intention to abandon under the provisions of this Section and
stating the date such work will be commenced. Abandonment may then be
commenced on or subsequent to the date so stated.
(d) Abandonment requirements prior to new construction. A Well Site or Drill Site
where there has been Abandonment shall meet the most current Abandonment
requirements of the Commission prior to the issuance of any Permit for
development of the property. No structure shall be built over an abandoned well.
(e) The Operator can only abandon a Well if the Building Official has reviewed and
approved the Abandonment.
SECTION 18
TECHNICAL ADVISOR
The Airport Board may from time to time employ a technical advisor or advisors who are
experienced and educated in the gas industry or the law as it pertains to gas matters.
The function of such advisor(s) shall be to advise, counsel or represent the Airport
Board on such matters relating to gas operations within the Airport as the Airport Board
may want or require and the effect thereof, both present and future, on the health,
welfare, comfort and safety of the public. In the event such technical advisor(s) is (are)
employed for the purpose of advising, counseling or representing the Airport Board
relative to an Operator's unique and particular set of circumstances, case or request
relating to this Resolution, then the cost for such services of such technical advisor(s)
shall be assessed against and paid for by such Operator in addition to any fees or
charges assessed pursuant to this Resolution. Prior to the employment of a technical
advisor, the Airport Board shall inform the Operator of the intended scope of work and
the estimated costs and expenses.
SECTION 19
MEANS OF APPEAL
Refer to Part One, Construction and Fire Prevention Standards Resolution for Board of
Appeals.
SECTION 20
VARIANCE RESOLUTION COMMITTEE
The Airport Board hereby establishes a Variance Resolution Committee for Gas
Exploration and Production, hereinafter referred to as the Variance Resolution
Committee, for the purpose of considering variances to the requirements of Part Nine.
The Variance Resolution Committee shall consist of the following Airport staff positions:
Vice President, Commercial Development or successor department
Vice President, Department of Public Safety or successor department
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 31
Vice President, Finance or successor department
Vice President, Operations or successor department
Vice President, Planning or successor department
(a) An Applicant for a Permit required by this Part may apply for a variance from the
requirements of this Part by submitting to the Building Official a written request
for variance. The request must include the following:
(1) Description of the requested variance and an explanation of why it should be
granted;
(2) Description of alternatives considered and why each is not the preferred
alternative;
(3) Description of the economic consequences if the variance is not granted;
and
(4) Description of how the level of health, safety and welfare of the public will be
maintained if the variance is granted.
(b) The Building Official shall forward copies of the variance request to the Variance
Resolution Committee members. On a case-by-case basis, the Variance
Resolution Committee shall consider the following in granting a variance:
(1)Whether the operations proposed are safe and reasonable under the
circumstances and conditions prevailing in the area, considering the
particular location and the character of the improvements located there;
(2) How the operations proposed compare to available alternatives;
(3)Whether the operations proposed would conflict with the orderly growth and
development of the Airport;
(4) The economic consequence if the variance is not granted;
(5)Whether the operations proposed adequately protect the health, safety and
welfare of the public; and
(6) Whether the operations proposed provide acceptable access for fire
personnel and firefighting equipment.
(c) Approval of a variance requires that a minimum of three Variance Resolution
Committee members vote in favor of the approval. The Variance Resolution
Committee shall notify the Airport tenants affected by any request for variance
and allow them to address the request in writing within twenty (20) days of the
notice. Only variances that would result in a setback distance between any Well
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 32
or Disposal Well and a Building to less than the minimum setback outlined in
Section 13 of this Part will be deemed to affect an Airport tenant.
The Variance Resolution Committee shall not be required to hold public
hearings, except upon request of two Committee members. The Variance
Resolution Committee shall notify the Airport Board in writing of each variance
request at least twenty (20) days prior to the granting of such variance. Upon
request of two voting Airport Board members, a variance shall be placed on a
public meeting agenda of the Airport Board. The Variance Resolution Committee
shall not thereafter grant the variance request without consent of the Airport
Board.
The details of each action granting or denying the requested variance shall be
recorded and entered in the files of the Office of the Building Official, and the
Building Official shall forward a letter to the Applicant stating whether the
Variance Resolution Committee has approved or denied the variance request
and listing any conditions placed upon an approval. The Variance Resolution
Committee shall report each such action to the Airport Board on at least a
quarterly basis.
SECTION 21
SEVERABILITY CLAUSE
It is the intention of the Airport that the phrases, clauses, sentences, paragraphs and
sections of this Resolution are severable, and if any phrase, clause, sentence,
paragraph or section of this Resolution shall be declared unconstitutional or
unenforceable by the valid judgment or decree of any court of competent jurisdiction,
such unconstitutionality or unenforceability shall not affect any of the remaining
phrases, clauses, sentences, paragraphs and sections of this Resolution.
Part Nine — Oil and Gas Exploration and Production
Part Nine — Pg. 33
r1 \ A /
LJ V V
September 13, 2022
STATE OF TEXAS §
COUNTY OF DALLAS §
COUNTY OF TARRANT §
I, Donna J. Schnell, Board Staff Secretary of the Dallas Fort Worth International Airport
Board, do hereby certify that the attached is a true and correct copy of Resolution No.
2022-08-174, approved by the Dallas-Fort Worth International Airport Board of Directors
at its Board Meeting held on August 4, 2022.
WITNESS MY HAND AND SEAL OF THE DALLAS-FORT WORTH INTERNATIONAL
AIRPORT BOARD, this 13h day of September 2022.
Donna J. Schnel
Board Staff Secretary
Dallas Fort Worth
International Airport
P.O.Box 619428
DFVV Airport.TX 75261-9428
DALLAS FORT WORTH INTERNATIONAL AIRPORT BOARD
OFFICIAL BOARD ACTION/RESOLUTION
Date Committee Subject Resolution #
08/04/2022 Finance/Audit Amendments to DFW Airport Code of Rules and Regulations 2022-08-174
Action
That the Airport Board approve, and request the Cities of Dallas and Fort Worth to approve, amendments to
DFW International Airport's Code of Rules and Regulations.
Description of Code Changes:
• Chapter 2 (Traffic Regulation): In Section 2-4, the requirement that a vehicle parked in violation of
this Code must also represent an operational hazard before it can be towed will be deleted.
• Chapter 8 (Commercial Activities): A new Section 8-18 is being added to require that certificate of
occupancy holders on any building at the airport more than 30 years old must comply with a
self-inspection program to be approved by the Board.
Justification
• The first change will allow the Board greater flexibility to enforce the rules against illegal commercial
activity in the parking facilities.
• The second change will provide much greater assurance that older buildings do not constitute a
safety hazard.
D/S/M/WBE Information
Contract# Agreement# Purchase Order# Action Amount Revised Amount
$0 $0
For Information contact Fund Project# External Funding Source Amount
Elaine Rodriguez $0
3-5480
Resolution # 2022-08-174
Additional Information
Additional Attachments: Y
BE IT RESOLVED BY THE DALLAS FORT WORTH INTERNATIONAL AIRPORT BOARD
That the Airport Board approve, and request the Cities of Dallas and Fort Worth to approve, amendments to
DFW International Airport's Code of Rules and Regulations.
Approved as to Form by Approved as to Funding by Approved as to M/WBE by
Y
Rodriguez, Elaine Palacios, Abel Lee, Tamela
Legal Counsel Vice President Finance Vice President Business Diversity
Jul 19, 2022 3:34 pm Finance and Development
Jul 19, 2022 4:42 pm Business Diversity and
Development
Jul 20, 2022 9:59 am
SIGNATURE REQUIRED FOR APPROVAL
Approved by
Department Head
Legal � � Aug 4, 2022 2:37 pm
Jul 19, 2022 3:25 pm Chief Executive Officer Date
Chapter 2
Traffic Regulation
ARTICLE I.
IN GENERAL.
Sec. 2-1. Traffic Control Installations.
Sec. 2-2. Definitions.
Sec. 2-3. Law Enforcement.
Sec. 2-4. Towing.
Sec. 2-5. Speed Limits.
ARTICLE II.
AIRSIDE TRAFFIC.
Sec. 2-6. Authority to Operate on the AOA.
Sec. 2-7. Reckless Driving.
Sec. 2-8. Obedience to Signs.
Sec. 2-9. Parking on the AOA.
Sec. 2-10. Motor Vehicle Accidents.
Sec. 2-11. Driving Under the Influence.
Sec. 2-12. Safety Belts.
ARTICLE III.
PARKING VIOLATIONS.
Sec. 2-13. Obedience to Signs.
Sec. 2-14. Fire Lane.
Sec. 2-15. Failure to Park in Marked Space.
Sec. 2-16. Employee Parking Areas.
Sec. 2-17. Parking by Air Operation Areas Fences.
Sec. 2-18. Passenger Loading Zones — No Unattended Vehicle.
Sec. 2-19. Impeding Flow of Traffic.
Sec. 2-20. Material Loading Zones.
Sec. 2-21. Failure to Pay Parking and Access Charges
Sec. 2-22. Parking Defenses.
ARTICLE IV.
ADMINISTRATIVE ADJUDICATION OF PARKING VIOLATIONS.
Sec. 2-23. Parking Violations Made Civil Offenses.
Sec. 2-24. Hearing Requirement.
Sec. 2-25. Hearing Officers; Powers, Duties and Functions.
Sec. 2-26. Parking Citations Form.
Sec. 2-27. Service of a Parking Citation; Presumption of Service.
Sec. 2-28. Liability of the Vehicle Owner and Operator; Presumption of
Liability.
Sec. 2-29. Answering a Parking Citation.
Sec. 2-30. Adjudication by Mail, Electronic Mail or through the Online
Citation Appeal System
Sec. 2-31. Hearings for Disposition of a Parking Citation; Notice of
Decision.
Sec. 2-32. Civil Fine Schedule.
Sec. 2-33. Enforcement of Order.
Sec. 2-34. Removal of Immobilization Device.
Sec. 2-35. Immobilization/Impoundment Hearing.
Sec. 2-36. Appeal from Hearing.
Sec. 2-37. Disposition of Civil Fines, Penalties, and Costs.
2
ARTICLE I.
IN GENERAL.
SEC. 2-1. TRAFFIC CONTROL INSTALLATIONS.
The Airport Board is authorized to establish all traffic control devices, signs, signals,
markings and insignias on the Airport.
SEC. 2-2. DEFINITIONS.
The definition of a term in this chapter shall apply only to this chapter.
ABANDONED VEHICLE shall have the meaning assigned in Section 683.002 of
the Texas Transportation Code.
ADMINISTRATOR shall mean the Vice President of the Transportation Business
Unit of the Dallas-Fort Worth International Airport Board.
AIR OPERATIONS AREA or "AOA" shall mean the area of the Dallas-Fort
Worth International Airport bounded by a fence or to which access is otherwise
restricted and which is primarily used or intended to be used for landing, taking-off or
surface maneuvering of aircraft. The AOA does not include those leasehold areas within
or having direct access to the AOA which are subject to security requirements imposed
on the lessee or tenant under appropriate federal regulations or agreement incorporated
in a signed lease.
AIRCRAFT RESCUE AND FIRE FIGHTER ROAD (AARF) or EMERGENCY
ACCESS ROADS shall mean roads on the AOA that are maintained to support
emergency responses.
AUTHORIZATION or AUTHORIZED shall mean acting under or pursuant to a
written contract, permit, authorization or other evidence of right issued by the CEO or
his designee.
BADGE shall mean an identification card issued by the Airport to identify a
person with access authorization.
DISABLED PARKING PLACARD shall mean the placard issued by the state
under section 681.002 of the Texas Transportation Code, as amended.
DISABLED PERSON shall mean a person who has a permanent or temporary
disability within the meaning of Section 681.001 in the Texas Transportation Code, as
amended, and who has applied for and received:
(a) a disabled person or disabled veteran license plate from the state;
(b) a disabled parking placard from the state; or
3
(c) a license plate or placard bearing the international symbol of access
issued by a U.S. state or by a state or province of a foreign country.
DISABLED PERSON LICENSE PLATE shall mean the specially designed
license plate of a vehicle, issued by the state to a permanently disabled person under
Section 504.201 of the Texas Transportation Code, as amended.
DISABLED VETERAN LICENSE PLATE shall mean the specially designed
license plate of a vehicle, issued by the state to a disabled veteran under Section
504.202 of the Texas Transportation Code, as amended.
ESCORT shall mean to accompany and monitor the activities of an individual
who does not have unescorted access authority into or within a sterile area, secured
area or SIDA.
INTERNATIONAL SYMBOL OF ACCESS shall have the meaning defined in
Section 681.001 of the Texas Transportation Code, as amended.
JUNKED VEHICLE shall have the meaning defined in Section 683.071 of the
Texas Transportation Code.
MOVEMENT AREA shall mean the area of the AOA utilized for taxiing, takeoff,
and landing of aircraft and includes adjacent undeveloped areas. The movement area
does not include loading ramps and parking area ramps.
NON-MOVEMENT AREA shall mean the area that includes all aircraft parking
areas, loading ramps and aircraft maintenance ramps.
OPERATOR shall mean any person in control of a vehicle, including a railroad
train or a vehicle being towed.
OWNER shall mean a person in whose name the legal title of an aircraft or a
motor vehicle is held or vested.
PARK or PARKING shall mean to stand an occupied or unoccupied vehicle,
other than temporarily while loading or unloading merchandise or passengers.
PARKING and ACCESS CHARGES are specified in the Dallas-Fort Worth
International Airport Board Schedule of Charges.
PARKING BAN shall mean certain hours or times during which standing,
parking, or stopping of a vehicle is prohibited along the curb of designated street as
indicated by signs.
REGULATED VEHICLE means a taxicab or prearranged service vehicle.
RESTRICTED AREA shall mean any area locked or posted by the Airport to
either prohibit or limit entry or access to specific authorized persons.
4
STAND or STANDING shall mean to halt an occupied or unoccupied vehicle,
other than temporarily while receiving or discharging passengers.
STOP or STOPPING shall mean:
(a) when required, to completely cease movement; and,
(b) when prohibited, to halt, including momentarily halting, an occupied or
unoccupied vehicle, unless necessary to avoid conflict with other traffic
or to comply with the directions of a police officer or a traffic control
sign or signal.
UNATTENDED VEHICLE shall mean a vehicle that is stopped or parked and
whose driver and passengers have exited the vehicle and moved more than 50 feet
away from the vehicle leaving, it unoccupied.
VEHICLE shall mean and include automobiles, trucks, buses, motorcycles,
horse-drawn vehicles, bicycles, pushcarts and any other device in or upon or by which
any person or property is or may be transported, carried, or drawn upon land.
VEHICULAR PARKING AREA shall mean those portions of the Airport
designated and made available temporarily or permanently by the Airport Board for the
parking of vehicles.
SEC. 2-3. LAW ENFORCEMENT.
Texas peace officers commissioned by the Airport Board shall have primary law
enforcement authority within the boundaries of the Airport. In addition to DPS law
enforcement officers, the Administrator, and the representatives and agents designated
by the Administrator, shall have enforcement authority as to civil offenses related to
parking or stopping a vehicle.
SEC. 2-4. TOWING.
(a) Any vehicle which is abandoned or junked, or parked in violation of this Code,
aRaFepFeseRts R eperat+eRal—hazaFd- at the Ai Fpert, may be removed or
towed away and impounded, all at the operator's or owner's expense and
without liability for any damage to the vehicle. Such expense shall be a lien
against the vehicle and payment in full shall be a prerequisite to the
reclaiming of the vehicle by the operator or owner.
(b) Any boat, trailer, storage compartment or other like property left in any
parking facility on the Airport without authorization from the CEO will be towed
away and impounded all at the operator's or owner's expense and without
liability for any damage to the vehicle.
5
SEC. 2-5. SPEED LIMITS.
The speed limits upon the streets, ways, passages and vehicular routes within
the boundaries and confines of the Airport are set, affirmed and ratified as described in
Appendix I of this Code. Unless otherwise provided, the maximum speed limit on
streets, ways, passages and vehicular routes within the boundaries and confines of the
Airport shall be thirty (30) miles per hour. The streets, ways, passages and vehicular
routes, and their corresponding block numbers within the boundaries and confines of
the Airport, are set, affirmed, and ratified as described in Appendix I of this Code.
ARTICLE II.
AIRSIDE TRAFFIC.
SEC. 2-6. AUTHORITY TO OPERATE ON THE AOA.
(a) A person commits an offense if he is on the AOA and:
(1) does not display evidence of authorization issued by the Airport Board;
or
(2) is not under authorized escort as described in Chapter 9.
(b) A person commits an offense if he operates a motor vehicle on the AOA and:
(1) does not have a valid government issued driver's license in his
possession;
(2) does not have a license in his possession that is appropriate for the
type of vehicle being operated; or,
(3) does not display or refuses to present a driver's license upon demand
by a peace officer.
SEC. 2-7. RECKLESS DRIVING.
A person commits an offense if he operates a motor vehicle on the AOA in a
willful or wanton disregard for the safety of persons or property.
SEC. 2-8. OBEDIENCE TO SIGNS.
A person commits an offense if while on foot or operating any vehicle on the
AOA:
(a) he disregards a posted regulatory sign, special sign, signal, marking or device
used to regulate, warn, or guide traffic; or
6
(b) fails to comply with directions given by the control tower, a law enforcement
officer, or a person designated by the Airport to control traffic.
SEC. 2-9. PARKING ON THE AOA.
A person commits an offense if he parks a motor vehicle, vehicle, trailer, or other
equipment on the AOA:
(a) in a manner contrary to any posted regulatory signs, traffic control devices or
pavement markings; or
(b) in any manner that prevents the passage or movement of aircraft, vehicles,
trailers or pedestrians; or
(c) in any manner that obstructs access to fuel shutoff valves, fire suppression
equipment, or other emergency systems; or
(d) that is inoperable or undergoing maintenance; or
(e) that the Administrator or his designee instructed the person to remove from
the AOA.
SEC. 2-10. MOTOR VEHICLE ACCIDENTS.
Any person operating a motor vehicle on the AOA which is involved in an
accident resulting in injury to any person or damage to another's property shall:
(a) immediately stop at the scene or as close as possible;
(b) render aid if necessary;
(c) exchange driver, vehicle, and insurance information if necessary; and
(d) notify the DFW Airport DPS and the Airport Operations Center.
SEC. 2-11. DRIVING UNDER THE INFLUENCE.
A person commits an offense if he operates a motor vehicle on the AOA and:
(a) has any detectable amount of alcohol in the person's system;
(b) has any detectable amount of a dangerous drug in the person's system; or,
(c) does not have the normal use of his mental or physical faculties by reason of
the introduction of a controlled substance, a drug, a combination of two or
more substances or any other substance into the body.
SEC. 2-12. SAFETY BELTS.
(a) A person commits an offense if the person:
(1) is operating or riding in a vehicle,
(2) is occupying a seat that is equipped with a safety belt, and
(3) is not secured by a safety belt while the vehicle is being operated in either
the movement area or non-movement area of the Air Operations Area.
(b) In this section, "safety belt" and "secured" have the meanings assigned by
Section 545.412 of the Texas Transportation Code.
(c) It is a defense to prosecution under this section that:
(1) the person is engaged in servicing an aircraft and is driving or riding in a
vehicle located within 25 feet of that aircraft;
(2) the person is driving or riding in a vehicle within a baggage make-up area
and the person is present for the purpose of positioning equipment;
(3) the person is an emergency service provider performing his official
duties;
(4) the person possesses a written statement from a licensed physician stating
that for a medical reason the person should not wear a safety belt; or
(5) the person presents to the court, not later than the 10t" day after the date of
the offense, a written statement from a licensed physician stating that for a
medical reason the person should not wear a safety belt.
ARTICLE III.
PARKING VIOLATIONS.
SEC. 2-13. OBEDIENCE TO SIGNS.
(a) A person commits an offense if, as the operator of a vehicle, he stops, stands,
or parks a vehicle within the boundaries of the Airport in violation of an official
sign, curb marking, or street marking prohibiting, regulating, or restricting the
parking, stopping, or standing of vehicles, except when necessary to avoid
conflict with other traffic or to be in compliance with the law or the directions of
a police officer.
(b) A person commits an offense if he:
(1) is not a disabled person or transporting a disabled person and stops,
stands, or parks a vehicle with a valid disabled person license plate, a
disabled veteran license plate, a disabled parking placard, or a license
8
plate or placard bearing the international symbol of access in a parking
space or area designated specifically for the disabled;
(2) stops, stands, or parks a vehicle that does not display a valid disabled
person license plate, a disabled veteran license plate, a disabled parking
placard, or a license plate or placard bearing the international symbol of
access in a parking space or area designated specifically for the disabled;
or
(3) stops, stands, or parks a vehicle in such a manner that the vehicle blocks
an access or curb ramp or any other architectural improvement designed
to aid the disabled.
SEC. 2-14. FIRE LANE.
A person commits an offense if the person stops, stands, or parks a vehicle in a
fire lane except when necessary to avoid conflict with other traffic or to be in compliance
with the law or the directions of a police officer.
SEC. 2-15. FAILURE TO PARK IN MARKED SPACE.
A person commits an offense if, in an Airport operated parking area, he parks a
vehicle in a marked parking space and fails to park within the lines as designated.
SEC. 2-16. EMPLOYEE PARKING AREAS.
A person commits an offense if he operates, parks, or stands a motor vehicle
within an Airport operated parking area designated for employee parking unless a valid
permit, decal, or other authorization issued by the Airport is displayed on the vehicle in a
manner established by the Administrator.
SEC. 2-17. PARKING BY AIR OPERATION AREAS FENCE.
A person commits an offense if he parks a vehicle or leaves other property within
ten (10) feet of an AOA fence.
SEC. 2-18. PASSENGER LOADING ZONES — NO UNATTENDED VEHICLE.
A person commits an offense if the person parks, stops, or stands any vehicle
and leaves it unattended in any passenger loading or no unattended vehicle zone.
SEC. 2-19. IMPEDING FLOW OF TRAFFIC.
A person commits an offense if he parks, stops or stands a vehicle in any Airport
roadway, crosswalk, sidewalk, driveway, AOA, taxiway, parking area, passenger
loading zone, material loading zone, at the taxi queue, or in front of or near any
9
entrance or exit to any building at the Airport so as to block, obstruct or impede the free
passage of any vehicles or pedestrians.
SEC. 2-20. MATERIAL LOADING ZONES.
A person commits an offense if he:
(1) stops, stands or parks any vehicle in a loading zone other than for
unloading and delivery, pickup and loading of material by a vehicle
authorized by the Airport Board for such use; or,
(2) stops, stands or parks any delivery vehicle authorized by the Airport
Board in a loading zone and exceeds the time limit or specified time
window established by the Airport Board and posted in such loading
zone.
SEC. 2-21. FAILURE TO PAY PARKING AND ACCESS CHARGES
A person commits an offense by failing to pay accrued parking or access charges
at the Airport exits. This offense includes, but is not limited to, tow truck operators who
remove vehicles from the Airport without paying the charges accrued by the vehicle
being removed.
SEC. 2-22. PARKING DEFENSES.
(a) Law Enforcement and Emergency Service Vehicles.
It is a defense to prosecution under this Chapter that a vehicle in violation
was owned or operated by a law enforcement agency, fire department
or Emergency Medical Service provider and parked to support the
performance of official duties.
(b) Authorized persons.
(1) It is a defense to prosecution under this Chapter that a vehicle in
violation:
(A)was parked in a limited parking space and had parking
authorization, in a form approved by the CEO and authorization
was placed to be clearly visible on either the front windshield or
rear window of the vehicle; or
(B)stopped, stood, or parked at the direction of a law enforcement
officer, a traffic or parking controller, or an official traffic control
device.
10
ARTICLE IV.
ADMINISTRATIVE ADJUDICATION OF PARKING VIOLATIONS.
SEC. 2-23. PARKING VIOLATIONS MADE CIVIL OFFENSES.
Every violation of this chapter governing the stopping, standing, or parking of a
vehicle is a civil offense.
SEC. 2-24. HEARING REQUIREMENT.
A person charged with a stopping, standing, or parking offense is entitled to a
hearing within 15 calendar days of issuance of the citation.
SEC. 2-25. HEARING OFFICERS; POWERS, DUTIES, AND FUNCTIONS.
(a) Hearing officers shall be appointed by the Administrator to administratively
adjudicate all parking violations for which a parking citation has been issued
under this chapter of this Code.
(b) Hearing officers shall have the following powers, duties, and functions:
(1) to administer oaths;
(2) to accept admissions to, and to hear and determine contests of,
parking violations under this section;
(3) to issue orders compelling the attendance of witnesses and the
production of documents, which orders may be enforced by a
municipal court;
(4) to assess civil fines, penalties, and other costs for a parking violation in
accordance with this chapter;
(5) to waive penalties assessed for a parking violation in accordance with
this chapter; and
(6) to preside over, hear evidence, and make findings at an immobilization
or impoundment hearing in accordance with this chapter.
SEC. 2-26. PARKING CITATIONS; FORM.
(a) A parking citation serves as the summons and complaint for purposes of this
chapter.
(b) A parking citation must be on a form prescribed by the Administrator, and
must include the following information:
11
(1) the nature, date, time, and location of the alleged parking violation;
(2) the license plate number of the illegally parked vehicle, or if not visible
or legible, the vehicle identification number or the inspection tag
number;
(3) the make of the illegally parked vehicle; and
(4) all other information required by state law.
SEC. 2-27. SERVICE OF A PARKING CITATION; PRESUMPTION OF SERVICE.
(a) A parking citation must be served personally upon the operator of a vehicle, if
the operator is present at the time of service. If the operator is not present, or
cannot otherwise be personally served, the parking citation must be affixed to
the vehicle in a conspicuous place.
(b) An operator of a vehicle who is not the vehicle's owner, but who uses or
operates the vehicle with the express or implied permission of the owner,
shall be considered the owner's agent authorized to receive a parking citation
required to be served upon the registered owner or operator of a vehicle in
accordance with the provisions of this section.
(c) If the owner or operator of a vehicle drives the vehicle away from or in any
manner leaves the site of the parking violation while the issuing officer is
preparing the parking citation, or refuses service of the parking citation, this
fact shall be noted on the original and all copies of the parking citation.
(d) The original parking citation must be signed by the issuing officer who shall
affirm the truth of the facts set forth in the citation. An electronic signature
satisfies the signature requirement.
(e) The original and all copies, including all electronic copies, of a parking citation
are prima facie evidence that the parking citation was issued and that an
attempt at service was made in accordance with the provisions of this section.
SEC. 2-28. LIABILITY OF THE VEHICLE OWNER AND OPERATOR;
PRESUMPTION OF LIABILITY.
(a) Except as provided in subsection (b), the registered owner and the operator
of a vehicle, when not the same, shall both be liable to the Airport Board for a
parking violation charge, except that the operator of a vehicle shall be solely
liable if the owner can prove that the vehicle was operated without the
owner's express or implied consent.
12
(b) A vehicle owner who is engaged in the business of renting or leasing vehicles
under written rental or leasing agreements shall not be liable for parking fines,
penalties, and costs imposed by the Airport Board on a rented or leased
vehicle if, within 30 days after receiving written notice of a parking violation,
the vehicle owner provides in affidavit form the true name, address, driver's
license number and state or country of issuance of the person in possession
of the vehicle at the time the parking citation was issued, and a true copy of
the lease or rental agreement in effect at the time the parking citation was
issued. A lessor of a vehicle who fails to provide such information and
documentation shall be treated as any other vehicle owner and shall be liable
with the vehicle operator for a parking violation charge.
(c) It is a defense to any charge of a parking violation that, at the time of the
violation, the illegally parked vehicle was reported to a police department as
having been stolen prior to the time of the violation and had not yet been
recovered.
SEC. 2-29. ANSWERING A PARKING CITATION.
(a) A person who has been issued a parking citation shall answer to the charge
of the parking violation by the date shown on the citation. An answer may be
made in any of the following ways:
(1) an admission of liability with payment of the applicable civil fine, and
any additional penalties and costs;
(2) a denial of liability made before a hearing officer at an administrative
adjudication hearing on a date specified in the parking citation or at an
instanter hearing before that date;
(3) an admission of liability with an explanation made before a hearing
officer at an administrative adjudication hearing on a date specified in
the parking citation or at an instanter hearing before that date;
(4) a request for permission from a hearing officer to adjudicate by mail; or
electronic mail;
(5) a request to reset a scheduled administrative adjudication hearing from
the date shown on the parking citation. A scheduled hearing may not
be reset more than once unless the person charged pays to the
Administrator, or his designated representative, an amount equal to the
applicable civil fine for the parking violation, with any additional
penalties and costs.
(b) The Administrator, or his designated representative, shall issue a receipt for
any amounts paid under this section. After presentation of the receipt, all
13
amounts paid will be refunded to the person charged if the hearing officer, or
a municipal court on appeal, finds that the person is not liable for the parking
violation.
(c) Payment of the civil fine and any additional penalties and costs may be made
in person or by mailing to the Airport Board the parking citation accompanied
by payment of the amount shown on the citation. Payment by mail may be
made only by money order, check, or in a manner prescribed by the
Administrator. Payment of the civil fine and all penalties and costs assessed
pursuant to this section shall operate as a final disposition of the parking
violation charge, except when payment is made to reset a scheduled hearing
or to file an appeal.
SEC. 2-30. ADJUDICATION BY MAIL, ELECTRONIC MAIL, OR THROUGH THE
ONLINE CITATION APPEAL SYSTEM.
(a) If a person charged with a parking violation shows good cause for not
attending a hearing, either personally or through a representative, the hearing
officer may permit the matter to be adjudicated by mail, electronic mail, or
through the online citation appeal system, which adjudication must be
completed within 90 calendar days of the date of the citation.
(b) Letters, memoranda, affidavits, photographs, and other documentary
materials shall be admissible as evidence for the purposes of adjudication by
mail, electronic mail or through the online citation appeal system. The hearing
officer may exclude from consideration any material that is not relevant to the
adjudication of the alleged violation.
(c) Failure of the person charged to proceed with an adjudication by mail,
electronic mail or through the online citation appeal system, after requesting
and receiving permission to adjudicate by mail, electronic mail or through the
online citation appeal system, is an admission by the person charged of
liability for the parking violation and shall subject the person who requested
the adjudication by mail, electronic mail or through the online citation appeal
system, to the appropriate civil fines, penalties, and costs assessed by the
hearing officer.
(d) If a hearing officer determines that an adjudication cannot proceed by mail,
electronic mail or through the online citation appeal system, the hearing
officer shall advise the person charged by first class mail that the person must
appear to answer the charge at a hearing.
SEC. 2-31. HEARINGS FOR DISPOSITION OF A PARKING CITATION; NOTICE
OF DECISION.
14
(a) Every hearing for the adjudication of a parking violation charge under this
section shall be held before a hearing officer.
(b) At a hearing, the parking citation is prima facie proof of its contents. The
officer or other authorized person who issued the parking citation is not
required to be present at a scheduled administrative hearing unless
requested at least three days in advance of the hearing by the person
charged or by the hearing officer.
(c) At a hearing, the hearing officer shall hear and consider evidence presented
by the Airport Board and by the person charged. The Texas rules of evidence
do not apply to a hearing under this section, and the hearing officer shall
make a decision based upon a preponderance of the evidence presented at
the hearing, after giving due weight to all presumptions and prima facie
evidence established by this section or other applicable law.
(d) At the conclusion of an instanter or a scheduled administrative adjudication
hearing, the hearing officer shall immediately render an order or decision as
to liability for the violation. The person charged shall also be notified of the
right to appeal to municipal court, that failure to pay can result in
immobilization and impoundment of the vehicle, and that the debt may be
placed on the person's credit report for seven years or until the debt is paid.
(e) If the person charged with a parking violation fails to answer the charge or to
appear at a scheduled hearing, then within 7 calendar days after filing an
order of liability issued under this section, a hearing officer shall notify the
registered owner or operator of the vehicle in writing of the order. The notice
must be sent by first class mail to the last address of the registered owner on
record with the Texas Department of Transportation, or to the address of the
registered owner or operator last known to the hearing officer.
SEC. 2-32. CIVIL FINE SCHEDULE.
(a) All civil offenses under this chapter shall be punishable by a civil penalty of
$58.00, except for the following offenses:
Violation Civil Penalty
Disabled Parking Space $ 500.00
Parking in a Fire Lane $ 68.00
(b) Civil penalties for failure to pay parking fees shall be in addition to the parking
fees themselves. When a vehicle is booted, a fee of $100.00 shall also be
assessed.
(c) If a civil penalty is assessed, it must be in accordance with this section. A
civil penalty may not be waived or modified by a hearing officer, or by a
15
municipal court on appeal, except that additional penalties and other costs
may be added in accordance with this section.
(d) An additional penalty in an amount equal to the original civil penalty will be
assessed if a vehicle owner or operator or the agent of the owner or operator
fails to:
(1) answer to a parking violation charge within 15 calendar days after the
date of issuance of the parking citation or fails to appear at any hearing
scheduled after 15 calendar days from the date of the parking citation;
or
(2)after being found liable, pay all civil fines, fees, and costs assessed for
a parking violation within the time designated by the hearing officer.
(e) A penalty assessed under subsection (c) of this section may be waived by a
hearing officer, or by a municipal court on appeal, if the vehicle owner or
operator, or agent of the vehicle owner or operator, can establish that:
(1)through no fault of the vehicle owner or operator, or agent of the
vehicle owner or operator:
(A)no notice of the parking violation was received as required by
this chapter;
(B)no notice of the hearing officer's order was received as required
by this chapter; or
(C)payment of the civil penalty assessed for the parking violation
was not posted in a timely manner;
(2) the penalty was assessed in error; or
(3)the vehicle was at the time of the violation stopped, standing, or parked
in response to a medical emergency.
SEC. 2-33. ENFORCEMENT OF ORDER.
In addition to the enforcement remedies allowed by state law, a hearing officer's order
may be enforced by:
(a) impounding the vehicle that is the subject of the order when it is found within
the boundaries of the Airport, if the person charged has committed three or
more parking violations in any calendar year that have not been resolved
either by a finding of no liability or by payment of all civil fines, penalties, and
costs assessed by the hearing officer;
16
(b) placing a boot on the vehicle that is the subject of the order when it is found
within the boundaries of the Airport, if the person charged has committed
three or more parking violations in any calendar year that have not been
resolved either by a finding of no liability or by payment of all civil fines,
penalties, and costs assessed by the hearing officer;
(c) canceling or denying any permit to park or operate a transportation service at
the Airport; and
(d) reporting the debt to a credit reporting bureau, or any other civil remedy
available at law.
SEC. 2-34. REMOVAL OF IMMOBILIZATION DEVICE.
(a) The registered owner of an immobilized or impounded vehicle, or other
authorized person, may secure the release of the vehicle upon:
(1) payment of the amount of the civil fine and late fees, if any, for each
delinquent parking citation plus the applicable boot fees and towing and
storage fees; or
(2) the posting of a cash bond in the amount of such civil fines, late fees,
boot fees and towing and storage fees to ensure appearance at the
immobilization/impoundment hearing.
(b) Payment of the civil fines, late fees, boot fees, and any towing and storage
fees shall constitute a waiver of the right to contest such civil fines and fees.
(c) It shall be unlawful for any person, other than an officer or employee of the
Airport Board acting in the course and scope of his duties under this section,
to remove or attempt to remove or to tamper in any manner with an
immobilization device (boot) installed on any vehicle pursuant to this section.
(d) It shall be unlawful for any person, except under the direction of a peace
officer, or an employee of the Airport Board, to tow, move, or to cause to be
towed or moved any vehicle on which a boot is then installed pursuant to this
section from the place where it was booted.
(e) It shall be unlawful for any person, other than a peace officer or employee of
the Airport Board acting in the course and scope of his duties, to remove or
relocate any notice placed upon a booted vehicle under this section.
(f) An offense under this section shall be a criminal offense punishable upon
conviction by a criminal fine not to exceed Five Hundred Dollars ($500).
17
SEC. 2-35. IMMOBILIZATION/IMPOUNDMENT HEARING.
(a) The registered owner of a vehicle that is immobilized or impounded for the
purpose of enforcing a hearing officer's order shall have the right to a prompt
immobilization/impoundment hearing before a hearing officer.
(b) The request for an immobilization/impoundment hearing must be made in
writing to the Administrator, or his designated representative, on a form
provided for that purpose, within 3 calendar days from the date the vehicle
was immobilized or impounded, whichever occurred first.
(c) An immobilization/impoundment hearing must be held within 48 hours after
the Administrator, or his designated representative, receives the request for a
hearing, excluding Saturdays, Sundays, and Airport Board holidays, at the
parking adjudication office or at such other convenient and reasonable place
as the hearing officer may designate.
(d) The issue to be determined at the immobilization/impoundment hearing is
whether the immobilization or impoundment of the vehicle was authorized by
this chapter.
(e) The immobilization or impoundment of a vehicle is valid if it complies with the
requirements of this chapter, unless the vehicle owner or operator, or agent of
the vehicle owner or operator, can establish that:
(1) the vehicle was registered to or operated by another person at the time
the unresolved parking violations occurred;
(2) the vehicle was being operated without the owner's express or implied
consent at the time the unresolved parking violations occurred; or
(3) through no fault of the owner, notice of the unresolved parking
violations was never received as required by this section; and
(4) if the defective citations are dismissed, it would leave no more than two
unresolved parking violations within the calendar year.
(f) If the hearing officer determines that immobilization or impoundment of a
vehicle was not valid, all fees paid for immobilization, towage, storage, and
impoundment of the vehicle and any other amount paid to redeem the vehicle
shall be refunded, including any civil fines, penalties, and costs for any
parking violation that the hearing officer determines should not have been
considered in counting parking violations for the purposes of immobilizing or
impounding the vehicle. Any civil fines, penalties, and costs paid for a parking
violation for which the registered owner was liable will not be refunded.
18
SEC. 2-36. APPEAL FROM HEARING.
(a) A person determined by a hearing officer at a hearing, or by failure to answer
a parking citation or appear at a hearing in the time required, to be in violation
of a parking ordinance may appeal this determination to the municipal court in
the manner and within the time allowed by state law.
(b) The officer or other authorized person who issued the parking citation is not
required to be present at the appeal hearing unless requested by the person
charged or by the municipal court.
(c) The appeal hearing must be a trial de novo in municipal court and is a civil
proceeding for the purpose of affirming or reversing the hearing officer's
order.
(d) Service of notice of appeal under this section does not stay the enforcement
and collection of any order of a hearing officer, unless the person filing the
appeal pays to the Administrator an amount equal to all civil fines, penalties,
and costs assessed against the person charged. The Administrator shall
issue a receipt for any amounts paid under this subsection. After
presentation of the receipt, all amounts paid will be refunded if the hearing
officer's order is overturned on appeal.
SEC. 2-37. DISPOSITION OF CIVIL FINES, PENALTIES, AND COSTS.
All civil fines, penalties, and costs collected by the Airport Board under this
chapter shall be paid into the Airport Board's general fund for the use and benefit of the
Airport Board.
19
Chapter 8
Commercial Activities
ARTICLE I.
GENERAL COMMERCIAL ACTIVITIES.
Sec. 8-1. Commercial Activity.
Sec. 8-2. Advertising.
Sec. 8-3. Commercial Photography and Moving Picture Production.
Sec. 8-4. News Racks.
ARTICLE II.
FOOD ESTABLISHMENTS.
Sec. 8-5. Designation of Health Authority.
Sec. 8-6. State Regulations Adopted.
Sec. 8-7. Definitions.
Sec. 8-8. Food Permits.
Sec. 8-9. Inspections.
Sec. 8-10. Food Manager Certification.
Sec. 8-11. Options.
ARTICLE III.
POOLS AND SPAS.
Sec. 8-12. Designation of Health Authority.
Sec. 8-13 State Regulations Adopted.
Sec. 8-14. Definitions.
Sec. 8-15. Public Swimming Pool and Spa Permits.
Sec. 8-16. Inspections.
Sec. 8-17. Public Pool/Spa Manager Certification.
1
ARTICLE IV.
BUILDING SAFETY INSPECTION PROGRAM
Sec. 8-18. Certificate of Occupancy Holder Self-Inspection.
ARTICLE I.
GENERAL COMMERCIAL ACTIVITIES.
SEC. 8-1. COMMERCIAL ACTIVITY.
A person commits an offense if he conducts any commercial activity at the
Airport without a permit, license, lease or other agreement with the Airport Board,
except for the operation of aircraft. Commercial activity at the Airport includes the
delivery of goods at the Airport for compensation (including rentals), the performance of
services at the Airport for compensation, or the solicitation or facilitation of either type of
business, regardless of how or where the solicitation or facilitation occurs. Commercial
activity at the Airport specifically includes, but is not limited to, the transport of people or
baggage from the Airport for compensation, and the transport of vehicles to or from the
Airport for compensation. It also specifically includes the transport of people, baggage
or vehicles to or from the Airport as a courtesy incidental to the parking business, the
rental car business, or the hotel business.
SEC. 8-2. ADVERTISING.
A person commits an offense if he posts, distributes or displays any signs,
advertisements, handbill, circular or printed or written matter of a commercial nature at
the Airport or electronically advertises products or services available at the Airport
without a concession or permit granted by the CEO.
SEC. 8-3. COMMERCIAL PHOTOGRAPHY AND MOVING PICTURE
PRODUCTION.
(a) A person commits an offense if he takes still or motion pictures for
commercial use or public exhibition, publication, or display on any portion of
the Airport grounds without a permit.
(b) A person commits an offense if he produces any motion picture, television
program or commercial advertisement on any portion of the Airport grounds
without a permit.
(c) No permits are needed for the taking of still or motion pictures or videotaping
by:
(1) Airport users for personal non-commercial purposes; or
2
(2) news media in covering news events or filming documentary
productions at the Airport.
(d) An application shall be submitted to the Airport Board at least five (5)
business days in advance of the first day sought for photographic or other
similar production, and shall include the following:
(1) the full name and street address of the applicant;
(2) the full name and street address of the organization sponsoring,
conducting, or promoting the production;
(3) whether the producing organization is a branch or division of a national
organization and, if so, the name and street address thereof;
(4) if the producing organization is a Texas corporation, a copy of its
certificate of incorporation, as amended, shall be furnished; if it is a
foreign corporation, a copy of its certificate to do business in the State
of Texas shall accompany the application;
(5) the purpose of the production;
(6) the date or dates and hours of the production;
(7) the location(s) proposed for such production; and
(8) the total number and size of production equipment required for the
production and total number of personnel.
(e) The permit will be issued within three (3) business days of receipt of the
application; however, the permit application may be denied or a permit
granted hereunder revoked if one or more of the statements in the application
is found to be untrue.
(f) Time, location and manner: When permits are granted, the following rules and
standards will apply:
(1) location: Permittees shall be escorted by Airport Board Personnel at all
times and shall only be permitted to conduct the permitted activity in
those locations specified in the permit.
(2) Permits will be issued for a period of not more than thirty (30) days.
(3) manner of operation:
3
(A) a person may not engage in such production unless he carries
such permit granted under this section at all times while
conducting production activities.
(B) a person conducting production activities hereunder shall, in
that connection, obey all applicable state and federal laws and
all applicable rules and regulations of the Airport Board. Unless
specified in the permit, permittees will not be permitted to
conduct the activity for which the permit is issued:
(i) in Airport roadways,
(ii) inside airline gate departure lounges,
(iii) in areas restricted to airline or Airport personnel,
(iv) in restrooms,
(v) in premises leased to a concessionaire,
(vi) in stairwells, staircases, elevators or escalators,
(vii) in baggage claim areas, or
(viii) in any area temporarily or permanently restricted for
conducting or promoting the production.
SEC. 8-4. NEWSRACKS.
A person commits an offense if he sells or distributes any publication on the
Airport premises by means of newspaper stand, racks or other similar devices, except
by franchise, concession or permit granted by the Airport Board.
ARTICLE II.
FOOD ESTABLISHMENTS.
SEC. 8-5. DESIGNATION OF HEALTH AUTHORITY.
The Airport Board shall by resolution designate from time to time a health
authority for the purpose of ensuring minimum standards of environmental health and
sanitation within the scope of that department's function.
SEC. 8-6. STATE REGULATIONS ADOPTED.
4
(a) The following statutory provisions are hereby adopted by reference: Texas
Board of Health's "Texas Food Establishment Rules" 25 TAC sections
229.161-229.171, 229.173-229.175; Health and Safety Code, Chapter 431-
"Texas Food, Drug and Cosmetic Act"; and Health and Safety Code Chapter
341-"Minimum Standards of Sanitation and Health Protection."
(b) A certified copy of each rule manual (above) shall be kept on file in the office
of the Airport Concessions Department.
SEC. 8-7. DEFINITIONS.
All definitions in the "Texas Food Establishment Rules" are hereby incorporated
by reference. In addition, the following definitions shall be understood.
HEALTH AUTHORITY shall be understood to mean the representatives of any
health department or health agency designated by the Airport Board to enforce the
provisions herein by resolution of the Airport Board.
SERVICE OF NOTICE shall mean a notice provided for in these rules is properly
served when it is delivered to the holder of the permit or the person in charge, or when it
is sent by registered or certified mail, return receipt requested, to the last known
address of the holder of the permit.
FOOD ESTABLISHMENT shall mean all places where food or drink are stored,
sold, commercially prepared, or otherwise handled, whether offered for sale, given in
exchange, or given away for use as food or furnished for human consumption. The
location of commercially packaged single portion non-potentially hazardous snack items
and wrapped candy sold over the counter, or by vending machine, is excluded.
SEC. 8-8. FOOD PERMITS.
(a) Requirement: A person commits an offense if he operates a food
establishment at the Airport without possessing a current and valid health
permit issued by the health authority designated by resolution of the Airport
Board.
(b) Posting: A valid permit shall be posted in public view in a conspicuous place
at the food establishment for which it is issued.
(c) Non-transference (Change of ownership): Permits issued under the
provisions of this article are not transferable. Upon change of ownership of a
business the new business owner will be required to meet current standards
as defined herein and Texas law before a permit will be issued.
5
(d) Multiple permits: A separate permit shall be required for every type food
establishment and temporary food establishment whether situated in the
same building or at a separate location, except that:
(1) lounge operations located in the same building operating under the
same liquor license will not require a separate permit unless potentially
hazardous food is being served; and
(2) establishments with minimal food handling involving limited preparation
of potentially hazardous food (such as a snack bar) and under
common ownership may be grouped under one permit. All
establishments with extensive food handling or open potentially
hazardous foods will be required to have a separate permit.
(e) Suspension of permit: The health authority may suspend any permit to
operate a food establishment if the operation of the establishment does not
comply with the requirements of this chapter, Texas laws, or the operation of
the food establishment otherwise constitutes an imminent health hazard.
Before a permit is suspended, the holder of the permit, or the person in
charge, shall be notified in writing that their permit may be suspended and
that they are entitled to a hearing, if a request for hearing is made in writing to
the authority within ten (10) days from the date the notice of suspension is
received. If no written request for hearing is filed within ten (10) days, the
permit will be suspended. The health authority may end the suspension any
time if reasons for suspension no longer exist. When a permit is suspended,
food service operations shall immediately cease.
(f) Revocation of permit: The health authority may, after providing notice and an
opportunity for a hearing, revoke a permit for serious or repeated violations of
any of the requirements of these rules or for interference with the health
authority in the performance of its duties. Prior to revocation, the health
authority shall notify the holder of the permit, or the person in charge, in
writing of the reason for which the permit is subject to revocation and that the
permit shall be revoked at the end of ten (10) days following service of such
notice unless a written request for a hearing is filed with the health authority
by the holder of the permit within the ten (10) day period. If no written request
for hearing is filed within the ten (10) days, revocation will be final.
(g) Service of notices: Notices shall be served in accordance with the definition of
"service of notice", above. A copy of the notice shall be filed in the records of
the health authority and in the office of the Vice President of Airport
Concessions, or to such other person as may be designated by the Airport
Board.
(h) Hearings: The hearings provided for in these rules shall be conducted by the
health authority at a time and place designated by it. Based upon the
6
recorded evidence of such hearings, the health authority shall make a final
finding, and shall sustain, modify or rescind any notice or order considered in
the hearing. A written report of the hearing decision shall be furnished to the
office of the Airport Concessions Department and the holder of the permit,
license, or certificate.
(i) Right of appeal: Any permit holder who wishes to dispute the decision of a
hearing may appeal the decision to the director of the health authority issuing
the order being appealed.
(j) Application after revocation: When a revocation of a permit has become final,
the holder of the revoked permit may make written application to the health
authority for a new permit.
(k) Permit fees: Health permit fees, as established by the health authority, are
due and payable directly to the health authority in the amounts and at the
times specified by the health authority.
SEC. 8-9. INSPECTIONS.
(a) Pre-operational inspection: The health authority shall inspect any food
establishment prior to its beginning operation to determine compliance with
this chapter.
(b) On-going operations: The health authority shall be entitled to inspect any food
establishment at any time without prior notice in order to determine
compliance with this chapter.
SEC. 8-10. FOOD MANAGER CERTIFICATION.
(a) Requirements: A person commits an offense if he operates a food
establishment at the Airport without a manager, or person in charge, who
possesses a valid and current food manager's certificate, or equivalent,
approved by the health authority designated by resolution of the Airport
Board. A certified manager, or person in charge, must be on duty during all
hours of operation of any nonexempt food service establishment employing
six (6) or more employees; provided that, only one certified manager, or
person in charge, shall be required to be on duty during all hours of operation
in each terminal building for food establishments under common ownership
and operation. Only one certified manager, or person in charge, shall be
required to be on duty during all hours of operation at each hotel.
(b) Manager's certification: Upon written application and presentation of evidence
of satisfactory completion of a food manager's course, equivalent training or
examination as approved by the health authority, the health authority shall
issue a food manager's certificate valid for three (3) years from the date of
training or evaluation unless sooner revoked. Suspension or revocation of an
establishment's health permit by the health authority shall constitute cause for
revocation of that manager's certification. Whenever the food service operator
holding the manager's certificate terminates employment, is terminated, or is
transferred to another food establishment, the person owning, operating or
managing the food establishment shall be allowed sixty (60) days from the
date of termination or transfer of the certificate holder to comply with this
section.
(c) Exemptions from certificate requirement: Temporary food establishments and
persons participating as volunteer food handlers performing charitable
activities for periods of fourteen (14) days or less may be exempted from the
requirement for manager's certificate. Exemptions are within the discretion of
the health authority.
SEC. 8-11. OPTIONS.
Notwithstanding the provisions of this chapter which provide for grouping of food
establishments under one permit, and one certified manager for food establishments
under common ownership and operation, each business owner shall have the option to
waive the grouping provisions and obtain one permit for each food establishment or
temporary food establishment, and to maintain one certified manager, or person in
charge, for each food establishment location.
ARTICLE III.
POOLS AND SPAS.
SEC. 8-12. DESIGNATION OF HEALTH AUTHORITY.
The Airport Board shall by resolution designate from time to time a health
authority for the purpose of ensuring minimum standards of environmental health and
sanitation within the scope of that department's function.
SEC. 8-13. STATE REGULATIONS ADOPTED.
(a) The following statutory provisions are hereby adopted by reference: Texas
Department of Health Minimum Standards of Sanitation and Health Protection
Measures, Chapter 341, Subchapter D, Section 341.064 and Design
Standards for Public Swimming Pool Construction, 25 TAC, Chapter 337,
Section 337.71 through 337.96.
(b) A certified copy of each rule manual (above) shall be kept on file in the office
of the Commercial Development Department.
SEC. 8-14. DEFINITIONS.
8
All definitions in the Texas Minimum Standards and Health Protection Measures
and Design Standards for Public Swimming Pool Construction are hereby incorporated
by reference. In addition, the following definitions shall be understood.
HEALTH AUTHORITY shall be understood to mean the representatives of any
health department or health agency designated by the Airport Board to enforce the
provisions herein by resolution of the Airport Board.
SERVICE OF NOTICE provided for in these rules is properly served when it is
delivered to the holder of the permit or the person in charge, or when it is sent by
registered or certified mail, return receipt requested, to the last known address of the
holder of the permit.
PUBLIC SWIMMING POOL shall mean an artificial body of water, including a
spa, maintained expressly for public recreational purposes, swimming and similar
aquatic sports or therapeutic purposes.
SEC. 8-15. PUBLIC SWIMMING POOL AND SPA PERMITS.
(a) Requirement: A person commits an offense if he operates a public swimming
pool or public spa at the Airport without possessing a current and valid health
permit issued by the health authority designated by resolution of the Airport
Board.
(b) Posting: A valid permit shall be posted in public view in a conspicuous place
at the public swimming pool and public spa.
(c) Non-transference (Change of ownership): Permits issued under the
provisions of this article are not transferable. Upon change of ownership of a
business the new business owner will be required to meet current standards
as defined herein and State law before a permit will be issued.
(d) Separate permits: A separate permit shall be required for every public
swimming pool and public spa, whether situated in the same building or at a
separate location.
(e) Suspension of permit: The health authority may suspend any permit to
operate a public swimming pool or public spa if the operation of the
establishment does not comply with the requirements of this chapter, Texas
laws or the operation of the establishment otherwise constitutes an imminent
health hazard. Before a permit is suspended, the holder of the permit or the
person in charge, shall be notified in writing that their permit may be
suspended and that they are entitled to a hearing if a request for hearing is
made in writing to the authority within ten (10) days from the date the notice of
suspension is received. If no written request for hearing is filed within ten (10)
9
days, the permit will be suspended. The health authority may end the
suspension any time if reasons for suspension no longer exist. When a permit
is suspended, use of the public swimming pool or public spa shall
immediately cease.
(f) Revocation of permit: The health authority may, after providing notice and an
opportunity for a hearing, revoke a permit for serious or repeated violations of
any of the requirements of these rules or for interference with the health
authority in the performance of its duties. Prior to revocation, the health
authority shall notify the holder of the permit, or the person in charge, in
writing of the reason for which the permit is subject to revocation and that the
permit shall be revoked at the end of ten (10) days following service of such
notice unless a written request for a hearing is filed with the health authority
by the holder of the permit within the ten (10) day period. If no written request
for hearing is filed within the ten (10) days, revocation will be final.
(g) Service of Notices: Notices shall be served in accordance with the definition
of "service of notice" above. A copy of the notice shall be filed in the records
of the health authority and in the office of the Vice President of Commercial
Development, or to such other person as may be designated by the Airport
Board.
(h) Hearings: The hearings provided for in these rules shall be conducted by the
health authority at a time and place designated by it. Based upon the
recorded evidence of such hearings, the health authority shall make a final
finding, and shall sustain, modify or rescind any notice or order considered in
the hearing. A written report of the hearing decision shall be furnished to the
office of the Vice President of Commercial Development and the holder of the
permit, license, or certificate.
(i) Right of appeal: Any permit holder who wishes to dispute the decision of a
hearing may appeal the decision to the director of the health authority issuing
the order being appealed.
(j) Application after revocation: When a revocation of a permit has become final,
the holder of the revoked permit may make written application to the health
authority for a new permit.
(k) Permit fees: Health permit fees, as established by the health authority, are
due and payable directly to the health authority in the amounts and at the
times specified by the health authority.
SEC. 8-16. INSPECTIONS.
10
(a) Pre-operational inspection: The health authority shall inspect any public
swimming pool and public spa prior to its beginning operation to determine
compliance with these rules.
(b) On-going operations: The health authority shall be entitled to inspect any
public swimming pool and public spa at any time without prior notice in order
to determine compliance with these rules.
SEC. 8-17. PUBLIC POOL/SPA MANAGER CERTIFICATION.
(a) Requirement: A person commits an offense if he operates a public swimming
pool or spa at the Airport without a manager or person in charge, who
possesses a valid and current pool/spa manager's certificate or equivalent,
approved by the health authority designated by resolution of the Airport
Board. Pool or spa managers shall have at least one certified pool manager
employed to maintain the pools/spas per location.
(b) Manager's certification: Upon written application and presentation of evidence
of satisfactory completion of a pool/spa manager's course, equivalent training
or examination as approved by the health authority, the health authority shall
issue a pool/spa manager's certificate valid for one (1) year from the date of
training or evaluation unless sooner revoked. Suspension or revocation of an
establishment's health permit by the health authority shall constitute cause for
revocation of that manager's certification. Whenever the public pool/spa
manager holding the certificate terminates employment or is terminated or
transferred, the business shall be allowed sixty (60) days from this termination
or transfer date to provide a new certificate holder.
(c) This requirement is applicable even if pool maintenance operations are
contracted to an outside company.
ARTICLE IV.
BUILDING SAFETY INSPECTION PROGRAM.
SEC. 8-18. CERTIFICATE OF OCCUPANCY HOLDER SELF-INSPECTION.
The holder of a certificate of occupancy for any building at DFW International Airport
shall be required to comply with the requirements of the Airport's Building Safety
Inspection Program, as approved by the Airport Board. Certificate holders shall be
required to hire professional engineers to inspect properties that are at least 30 years
old for code compliance and life safety, and to submit a written report to DFW Airport
code enforcement officials, detailing and certifying their findings. After the first of such
inspections, certificate holders are required to obtain and submit reinspection reports
every 10 years. Nothing in this inspection program shall restrict the authority of DFW
11
Airport to perform its own inspections to determine whether repairs or other
modifications are necessary. Nothing in this inspection program shall restrict the
certificate holder's right to rely on grandfather privileges under applicable codes,
provided that no such grandfather privileges shall justify conditions that make any
building unsafe for occupancy. The inspection reports shall be submitted within six
months of the date this Code section is enacted, or the date the building reaches 30
years of age, whichever occurs later. Reinspection reports shall be submitted within six
months of the loth anniversary of the prior report. Failure to comply with the
requirements of this section shall be an offense under this Code, in addition to
administrative penalties such as revocation of certificates of occupancy.