CHANGE ORDER REQUEST CONTRACT NO .. f:-15:97 /[02
CHANGE ORDER NO . DAT E 9 .G.e.l>!G . ' PROJEC T NO . City Project 00186
3 March 25, 2013 P275-701300018683
PROJ ECT DESCRIPTION : Village Creek WRF Modifications to Bar Screen Bldg . 3 and C ITY SECRETARY CONTRACT NO .
Junction Box Rehabilitation 41592
ORIGINAL CONTRACT AMOUNT .......................................... $. ___ 7-'--""-'37'-'-9=3-"45"-'-.o=o
EXTRAS TO DATE .............................................. $. ___ .,_,I =66=0.,_,1"""'95""".7-'--"-0
CREDITS TO DATE .............................................. $ ___ ~<~I =8,~73~0~.7~2)
CONTRACT COST TO DA TE ............................................................................................................................................................... $ __ ~9~0~2~0=8~09~.9-8
AMOUNT OF PROPOSED CHANG E ORD ER .................................................................................................................................... $ ___ __,_4.,_.,1 =35""'5~.8=1
REVIS ED CONTRACT AMOUNT ....................................................................................................................................................... $ __ ~9~0~6=2=1~65~.7=9
ORIGINAL FUNDS AVAILABLE FOR CHANG E ORDERS .............................................................................................................. $ ____ 2=2~1=0~00~.0~0
ADDITIONAL FUNDING (IF NECESSARY) ...................................................................................................................................... $ ______ 0~.o~o
REMAINING FUNDS AV AI LAB LE FOR CHANG E ORDER ............................................................................................................ $ ___ ~17~9=6~44~·~19
IN ACCORDANC E WITH THIS CHANG E ORD ER, THE CONTRACTOR SHALL: modify /chan ge the contract as shown belo w to provide a complet e,
functional , and operational plant. These ch anges are as li sted below. Further de scription s and Co st Breakdown s are attached .
PCM-008 COST TO MODIFY GAS DETECTION SYSTEM ----------------------------------------------------------------------------------$ 41,355.81
The Contractor shall modify the gas detection system in Bar Screen Building No . 3 . The contract documents specified gas detection
equipment and the location for the power and communication connections . The locations for power and communication connections and the
equipment for the gas detection require modification due to differing site conditions . The Contractor provided a cost of$ 41 ,355.81 for this
work and requested 42 additional calendar days.
TOT AL CREDI T FOR CHAN GE ORD ER NO . 3 -----------------------------------------------------------------------------------------------------------------$41 ,355 .8 I
The Revised Final Completion date for this contract is November 22 , 2012 .
It i s unde rs tood and agr eed th at th e a cce ptance o f thi s C h an ge Ord er by the contracto r con s titut es an ac c ord a nd sati s fa c ti on and r e prese nt s pa y me nt in full (both in time and mo n ey) fo r all
costs ari si n g o ut of, o r incidenta l to, th e C h a nge O r der.
ORIGINAL CONTRAC T T IME
360 Ca lendar Days
AD DITIONA L AP PROVE D T IM E TO DATE
180 Calendar Days
OFFICIAL RECORD
CITY SECRETARY
FT. WORTH, TX
RECEIVED APR -9 20i3
APPROVED CONTRACT TIME TO DATE
582 Calendar Days
ADDITIONAL T IM E FOR TH IS CHAN GE ORDER
42 Calendar Days .
FLE LD ENGINEER hu,i'&M_, DA~ 3 2 '5' /13 ith , Inc .
DIRECTOR/MANAGING DEPT. DAT E
DATE
. ~' i 3
DAT E
CJ APP ROVED CJ DI SAPPROVE D CJ OTHER
MEMORANDUM
DATE: FEBRUARY 25, 20 I 3
To : AMY ROBI NSON . P.E .. CAMP DR ESSER & MCKEE, INC .
FROM: MADELENE RAFALKO. P.E .. FORT WORTH WATER DEPA RT ME T
SUBJECT: MODIFICATIONS TO BAR SCREEN BUILDI NG 3 AND J UNCTION Bo x REHABILIT AT ION
AT VILLAGE CREEK WRF
CITY PROJECT No. 00 I 86 AN DO 1 I 30
PCM-008: MODIFICATIONS TO BAR SCREEN BLDG 3 GAS DETECTO R SYSTEM
This office has re viewed yo ur correspondence dated February I 5, 2013 regarding the proposed
contract modification (PCM-008) to modify the gas detection sys tem in Bar Screen Building No. ,
.) .
The Water Department agrees with your recommendation that the contractor 's cost of
$4 1.355.8 I should be accepted, as the cost is fair and reasonable. The Contractor has requested
42 days additional calendar days to complete this work. This office will recommend to the City
Council (and/or the City Manager's Office) the approval and acceptance of this cost in the form
of a change order.
Madelene Rafalko , P.E.
Fort Worth Water Department
CC: David Townsend
Files
\ lfwwc fsO I\ wa ter\Gro up s\E ngi nccri ng\rnra folk o\, \A_ M adcl ene \13ar Screen Bui !ding 3\Co nstru cti on\changes \PCM ROOS . doc
CDM Smith
10 0 Throc kmorton Street, Su it e 600
Fo rt Worth, Texa s 76102
tel : 817 332 -8727
f ax: 817 820 -0450
February 15, 2013
Ms. Madelene Rafalko
Fort Worth Water Department
1000 Throckmorton Street
Fort Worth, Texas 76102
Subject: City Secretary Contract 41721
Construction Management Services Contract
Village Creek WRF
Modifications to Bar Screen Building 3 and Junction Box Rehabilitation
Proposed Contract Modification No. 8
. Dear Madelene:
Transmitted herewith please find a copy of ARK's proposed contract modification (PCM) 008 to
modify the gas detector system at Bar Screen Building 3. ARK has requested 42 calendar days be
added to the Contract Time for delivery and installation of the new equ ipment.
COM Smith and has reviewed this price proposal and is of the opinion that it is a fair and
e quitable price. COM Smith recommends the City accept this PCM and issue a Change Order
in the amoun t of S41,355.81 with 42 additional calendar days to the Contract Time. Please advise
if the Water Department desires this PCM be incorporated in a Change Order.
Very truly yours,
~~o~~
Amy Robinson, PE
Senior Project Manager
COM Smith Inc .
cc: Kent Riker, CDM Smith
PW File 0515-83443-05 .06.30.PCM-008
WATER + ENVIRONMEN T + TRANSPO RTATI ON + ENE RG Y+ FACI LI TIE S
PROPOSED CONTRACT MODIFICATION (PCM)
OWNER: C ITY OF FORT WORTH , TEXAS PROJ ECT NO .
PROJECT :VCWWTP PART I -MODIFICATIONS TO BAR OWNER: P275-701300018683
SCREEN BUILDING 3 AND PART II -JUNCTION BOX
REHABILITATION PROJECT
CONTRACTOR : ARK CONTRACT ING SERVICES CONTRACTOR: 10-124
ENGINEER : COM ENGINEER :
MALCOLM PIRN IE
ENGINEER 'S CONTACT AMY ROBINSON PCM NO. 008
NOTIFICATION TO CONTRACTOR:
WE ARE CONSIDER ING MAKING THE CHANGE TO THE CON T RACT DESCR IBED IN THE ATTACHED
MATERIALS AND REQUEST THAT YOU TAKE THE FOLLOWING ACTION :
0 NOTIFY US THAT YOU CONCUR THAT THIS CHANGE DOES NOT REQUIRE A CHANGE IN CONTRACT
TIME OR AMOUNT. A FIELD ORDER WILL BE ISSUED.
~ SUBMIT A PRICE PROPOSAL WITH DETAILED COST BREAKDOWN AND REVISED SCHEDULE FOR
PERFORMING THE DESCRIBED CHANGE.
lJ A CHANGE ORDER WILL BE ISSUED FOR PAYMENT AT THE UNIT PRICE BID
D PROCEED WITH THE CHANGE UNDER THE TIME AND MATERIALS PROVISIONS OF THE CONTRACT .
BY : Amy Robinson DATE : 08/07/12
DESCRIPTION OF PROPOSED CHANGE: 181 DESCRIBED HEREIN ~ SEE ATTACHED
See attached drawings for clarification on where to power the H2S and methane detectors for
Bar Screen Building 3 and changes to H2S and methane detector models and the alarm
system. Provide local alarm for detectors as shown in attached drawings instead of routing to
RTU cabinet for SCADA alarm as noted on sheet H-2 . See attached specification for H2S and
methane detectors to be prov ided instead of what's noted on drawing H-2.
CONTRACTOR 'S RESPONSE :
WE RESPOND TO YOUR REQUEST AS FOLLOWS :
D WE CONCUR THAT THIS IS A NO COST OR TIME CHANGE , ISSUE FIELD ORDER.
X WE SUBMIT THE ATTACHED PRICE PROPOSAL WITH DETAILED COST BREAKDOWN AND REVISED
SCHEDULE FOR PERFORM ING THE DESCRIBED CHANGE .
0 WE ARE PROCEEDING WITH THE CHANGE AT THE UNIT PRICE BID
D l(!~-~ITHT
BY :GON-rRAmcf/~ .c
ACT ION TAKEN :
DATE :
0 PROPOSED CONTRACT MOD IFICAT ION REJECTED . CONTRACTOR NOTIFIED NOT TO PROCEED.
BY : DATE :------
0 FIELD ORDER ISSUED : NO . DATE : BY :-------
0 CHANGE ORDER ISSUED : NO . DATE : BY :
f
i
�
�v �
1 1
( (
w��carnoua � �
H�.�.�TP��� II
To �r ooa� �a�,a« �,
S!E IF1 i0N COtlittilJA�qN. I I
'
�)
RENIONfIX�fTYpFM � �
D`1C��l�TOEJUlTY�WI�OPR ( (
I
� �
� �
1�
1� �
� i ``t�.._
' I
. I��
FPP TO gE REM�VEO f
iROM TW POM
i I� 70 REIMM �
FRON TNIS ►Ortii
�
�
b
1
0
0
OI
N
�
��
— �1
�
�
�
Ne eAtC ORwN CMW
���
vau�u: ss,�+OG
�
4
�
:�
�
�
�
� '
�9,A�R B�RE�N BUILDING #3 - DEMOLITlON �
`�.� NORTH
NiwVMi
0
V V
0
�ta v!
s�ec��et�
YOIUTAl: t�,ptG
M
�
N[W HO►t►RcttO
►IION TM� rOIPIT
NEW H'fiV PIpNA
FRONtMbfOU'R
^OWNEII PRdNOED°
RE1l(1VI EXRiINO fR►
ouCT
CVT t1'ktY MOIEf M/0
EXq1W6►NSONRY WAII MV
CONCRlT! KOOR t0
ACCOM00�1lHEWOOd1
CONiROI OUCMWIK
fElO COOMNAT! EXACi tOCATIONA
as•r
NE�y N'0 FRP OVCt
BAUNCt IOI.ODO CfM
�� V� �I�
�
�
V�
F'7
( (
� �
4
•
Nf W ]6'0 fqM
ouc.. '��"�--�„` wu:
800E1.•lN.O� .,r` �
, �-------
�Si�.Ei:�.�l�L�O A I�d
x
votuufr t�.�o1C►
i' MD, 6EttMWiNCO1t1ECT�ON
4� , �eL'r-�xocz
`�►1?�. �
��} V
�
� YMQlEtIMOVINCp�NECTqN
� Uf4TAt1. FRP ftENVM W%TQ EJOl71N0 W V�'ER
APPRO}L f OT Wq! 1t {7 HRN �Y it' D�
70' O EI�WV WRN
N'O TM N TUI1N
',� �-� - NEW70"OFAI
s t oucr. eoo �.�xr
MUiHGE THq ERIVICH
MOOIfYENDOfPfV " tOt1,600CFY
tNlCi iOACCONNOG�tR 2�A
CANHECi10N �O NEW OIICiWONsi
��.5 DE`��i►C 12JR.
� OALANCi NEW 2�nt Tfw0U0N i100H
TO 1,�00 Ci1,1
�� 'CYr
sz�
��.... �:........ *,
CNARLES S. PAGADUAN
r� ;:: ...9Q51.7.....:;�'i
��� �`FS� �� E N 5�;�• G���`'�'�
�
1, `,'l�\�tt �'~�.r
�•3a-�Z
�
a ��,�a��„�
��---�....= ,o.���,
� a \� �
Q G�.r�Y K � M�N,a�Bsr�.
\ V
���: `\ {� VOIV►t6:55.fldCF
^`����_ � q
GENERAL NOTES:
��.
i. 1R'DROGEN i1AfIDf iENtORt W Wl �t NtTALtEO/�DYCENf TO
rnt WA�I MAIaN N EACN 1Nt 6CREENCIbt ICV�OHOMU MA
WUN �CNEENN6t ROOM. TO �E CWHECTE010 tOC�LL AN� PtAMf
---- - wwusrsm�t
�. ►�tt��ru �Erao+u awut e[ rror�o �r �avr noor
tTRUCtUH! N UQi IN! BCNEfNNOt l0ADM0 NiEA fNC MNM
bClt�tANW R004t TO t! OONlECiEO TO tOGI 111'OPV Wi NMy
tratar.
1 AfLOW�WITCM�FW,tORNfU1llE00NIkWJD'OtlCiiFRYN9
TN/ FWN iClIE[MNO�l100A1 TO �E CONNlCTEO tOIOW AM�
rurn,�,vu+w..c�+,
�, i/000iWt141•1 N7t MEUqEMt 6ENi011 WIfNlNMM RflAT0. t
lAUIT IIEUY. DIOITAI p VlAY.1-f0lqN�L, A�000t1�11l�t. M�
GMllMTION A►!'OUt[� PoII I i G4lMT101tf.
f. iiit /IYDAOOdf oUlf10i DEtECipl �H4t �E AIODEI
6�OOOTFI-04�1 �YOlNlML 40WT011� tlYliH 430A1�1 WirUT�
\ tOCJ�10131RAY.NiDCN.idU710lIlJ1rOULGidt1lWil�T►3�!
(HpAEt/1Yi�
♦ iMrtOWt/ViTCNaNMt�tF�00El1MISE11R1LF10CfAND
� 3 ,� ����.�o.r�.
� ' 1. TMWilIAM�OKTECMRiHALl��6At�.W411AlODElW00l001V.
�� l NdK/FNNTMiONONIDIWYiMWEN70HY0ROGfl'�{UIFWi
_ � su+aauuuoonoosaun+-�sveaa�aanr�uEnwr
o¢rEcraR c.w r[ oAo�o mn� w�t aeneoaf • a+e ra�
Nfi1WA ANDTHf OTNE11FdlM'�NOfiEMIUIFqf.
' NO E
U� f. TMlWSTRlN1EM{fHKt�lT1EDN(fOi/llRNCAf11EYlOCAfE9
% � ONTN[YhEtT61DROflM6C11EENMI4qN0iANACENITOTNE
uca. currrucratcrMu000nan��a wm�orn+cn
,, RFPqEtENtATHR TO FEIO IOCATt RN WOit�.
t0. REfE�ITOTNtUtEilEqiIONQFNfPl1�20FptM7ENflriNOR!
«���o�,.«,�,�.�«,�,���.
SYf�GL ALlCONOUTANO YMNO @qTALUO N ClAplfl'DARW
5f4K106NfOR4 TOl1E UtEfi Eqf10NDf iHQ NAiIONAI
EtECtPoCAI OODE (NCC) MtICLE i00.
11. AtlCCNOlNTNqfiR/d8lSNAt1�/PVCGOAtFORM3�DK1lAMtAA
cona�r �no emwoa muu x twneoNn nEo www�cn+uo
fY ROlNO'/ NOWTRIE! OR ECUK. ALL WI�Uf iFWI �! 6REQ
VEII iH[ UTEtT EDRION Of TH[ N�TIONK EIECifhCAt OOOE p�EC}
�t. fNOC►OWERAiACONTR04M/AtlFWt�liTflA110EDCd'PER.
IIU�M'Q N3UUTIONM!]041WdAlMM1U/AC,tURE0�1liH!
OKONTlCAlt[OOMVM//ptEGIW.
ix �.awc�wosaanu�aa�wvnneuuueeanae�Nq»M
CONOUCTOI� �IMYfO, TMNEO l(PANOEO OOPPEIl1YM�E0 WIM
top% 6W[tO NpDll N1A�lR Nt� lW1UfACNI�EO SYlFl00N pt
EWAL.
i�. conrnr,cions�tKte�w+tc��nnmvea.00noriomt
OtNMifE1 SlqWN ON DMWMW.
NOTES BY SYM80L"(�"
t. MPECIEI(1�iHQH•ONAiTE11FR►AUITEIIFIYDMIPER7MlD
IOCKMI[ ACIUATORlAND fIF.OIACt A! NECfdS4CY.
1 EKt7Tlq�041VERlTOREANIN.
�. NEY7WDlAMlfERiM0AWE11W1iNlOC1U0lQACNATplblVAl�
6E DE6�fWE0 TO N1iHlTAIN 11 diiEMENM10i F) IO' W.0. ACROS�
iACEOF pA4YEl�
1. NEWlMDI�MEiE11fRPWMPEAN7MlOCKAlI�ACiW100.Ml�LLl
6E OESN3NfD TO'MiNiTANO AOIFFEPENi1K Of ytp W.0. ACR066
lACF d QMIGER
{. R011WTO►NTCMEXqiWOiPrEtEVATqNAtPE0U1NE0.
L SUPPMT►1PEi11046Rd1N[IPERANNUfN.TURfR!
AECp.fAENOAf qN�. PROV10� IODRqNi1l &IPPd1i� A! PECUR�EO
sY iW MANUfACTtHER OOONOIINTE LOGfpN� WfITI NEW
a��u�s vwe
/. SfXPENETitAT10NAROUNOHEWFRPOUCTN11TpFR.
l MANflTAHOMDpryWiN1TCK '
�. ru�rtctu�ouno►+�nunEocrEcto�.
�a vure�Tum►tnmoaocsewa+uaeontecioa
� �_ ... _.S S.r .� ... .� `.j�.� � (�/�� GU'�TI:G�i e�JyAnt14� �, i� _..
l' �— 3 5
_ �,AR SCREEN 8U1LDfNG #3 - NEW WORK ��
� SCAtE:118' • t'-0' NORiH
�K mc� - (isx
�--�--_- �?c �A N k G, $�X Co
�,�„m �, o c�orD v[R�n sc,acs � CITY OF FORT WORTH, TEXAS
`'""�' °' °� °"'�'� °R"""�� ��^+"^���•��•°�°^� VILLAG� CREEK WASTEWATER YREATMENT PIANT
vKet a4�o er J SPEC,�t �..,.
„re�p o, if NOi UNE p:CH ON MOQIFICATIONS TO BAR SCREEN BUI�DING NO. 3
n�: s�ncr. �o�usr PART I
p�7� $fPIfSA(KR 20t0 SCNES ACCD1tD�NQY
_ ....................�..._ ., ..: ... _ ..., _ , , ...
� r --�' . . �
6AR SCREEN BUILDIN(i #3
ODOR CONTROL MODIFICATIONS
..�.
;*'` °`'`�'�
���,.
��� QOAO[YQON
�r �.m...
���y�,kt,,,,,Nn,�
, ,,.
y��" �#.as
Mc� a�
`�`.a .� '
�;:�.. :K.:' :;w.",.�
eww. aa n
eAaEcr ra 76�a9
ru wr.c t+-z
SnCO Na
�
V
V
V
V
�
N
�
�
0
O
Z
�
¢
t-=-
�
N
i
O
U
ti
O
�
0
w
2
�
W
�
Z
W
�
Z
�
�
O
�
0
�
Z
U
�
W
�
J
Q
Z
O
�
k
O
�
a
m
�
�
5
0
a
�n =
z F-
c� �
w N
0 �
o �
�U
�..
N �
�z
wo
���
00
wa
~w
tn �
w�
�w
�_
U
�
o�
�o
o ,-__-
��
N �
W U
� W
O �
>
w�
� 4
N
�a
��
0
� <<
�
�a
N 4'
0
�
0
�� �
N =
�3
�?
1 5/8'MIN
1 i�/3Y QEPTH x 17110' NiQE
. , ON�SiRUT PT000 pf CWAL
GKVANZEQ aR
�� a SiAPIlE54 Bp.T, NUt !t
NASHER AS REWIRm
1 ' '-
CONqiETE EIfPAN90M ANCt10R
MI�4IMUN 3/�' pAMETER-SIZEd . � 3 8�
IAFtGEA AS REWI�O BASED �
ON SUPPORTFO IOAD o ; ` �� �
O O
o _ �
o _ , "
O 0
car+ca� --"'�� .
WMy, t
Q 6
EOUiPNQIT ENCLOSURE
riihl EXIEHNAL MWNi1N0
iEET (S�MII.M MWNIINC
i0R ENCl09URE4 NiTN
INTEqNAL MWNTWO HOl£S)
e , ,
�{�{�( yO' �• 0 �
I-i�l�l�l�l�
6 �
NO7E
u�uc�e� ron Au r+a+ cAST-wor+ ovaosur�a an eo�s
EQUIPMENT ENCLOSURE MOUNTING ON CONCRETE WALL
DETA14 �
N.T.S.
RED P YETFiriENE SU8 BASE
WLEARGNI D TAPE EFU p
BELO FINFSHEONC�E• �(�FlN15HE0 GRADE
j
�
1
� I ��) ��� {��
`� � BACK�Fl�LI� pOF�5pELECT COMMON
~ 6��OEPTH YARIESIN UFTS Of
`. • COMPACTEDOSAND 6' (MIN)
, 1:::.:•...�::. .. Pll AROUN
� :.. t""� ORREN ICATEO OtOPUN5s)
7.5' MIN CS
1� � =
UNDIS'fUR8E0 EARTH
DIRECT HURIED CONDUTT
DETAIL �
N.t.S,
�
� UN5� NA�KEDC
h�S POSSI LE�D STRN� PAf;1C AND SEAI..
WATERTIG SEAL AS � ' �CONDUR
SPECIFl�
ORICK OR CMU WALL C��N��SMOOTN E
pVC �SLEpEVE REHQUIyqEO 81�• SURFACE3
5� MANU�ACNRER
�
WATER77GHT CONDUIT PENE�RATION
DETAIL �
N.T.S.
CONCAE7E
INSERF OR
1 S6' MA7C BETViEEH HAHCERS � SUPPLflAQITK
�---------------------------�'� g� 5
• ANGH�QI� . CNANNEI fRANIN4
PLA78E FlTTINO (iYP)T � INS�ER7�5 (RE1E� :�SUPPoRi
n�F'I
o \
-,— e�=. ���� ��) c�sr r�at��
CNANHq, FRANINC iRIX/ SPACER_Mj,D
SUPPORT . ..-. . E HOLE Sinnr
�' � � '_ � >j�
� •'• F•
� CONDUIT CllMf+. �ZE _ . •. .
AS REWCiW (rn
N �a i .
- ��` STAINIESS StEEI
CKVANIZEp SCAESP
I -- C�APSS (M)� 3� �TtP� �• �- A9REWIR£�D (f1T�ZE • IN�R�TONCREIE
1' MtM�I � �����T����1 /Y (� IN) tLLL WALL•MOUMiEO W� NWNIED
CF N
OH
`�EAbED R00
)
itAPE2E 1AOUN7ED
t20VAC
AtMM CONTACT FRaM
GAS DETECTION
CONTROILER y;����_�_
� i �—
PVMP-1 LENCAGE
CR1 �M
LOW FIOW AIARM
I ' PUMP-1A�
/�lARM
ALARM BEACON SCHEMATIC
24VOC
(FROM OEfECTOR PANEL)
�
�-------�
; If i �"
! �-
1 1
�-------�
now swrrcr+
a.ow swrrcH scHErrunc
(RELAY BOX)
GENERAL NOTES:
CONDUR MOUNTING
DETAI4 �
N.T.S.
1. AlL WIRING IN CIASSIFIED HAZARDOUS LOCATIONS SHALL CONFORM TO THE REQUIREMENIS
OF NEC ARTICLES 500, 501, AND 504.
2. ALL EXPOSED CONDUIT SNALI BE RIGID GA�VANIZEO STEEI UNLESS NOTED OTHERWISE.
KEY NOTES (REFER 70 FiGURE 1)
�j AREA IS � CLASS 1 DIViS10N 2 HAZAftDOUS IOCATION PER NFPA 820 TA9LE 5.2 RaW t b.
ALL WIRING MEfNODS SHALL CONFORM WITH NEC CHAPER 5 REQUIREMETNS.
AREA WITNIN 3 FEET OF FLOW SWITCH IS A CIASS 1 DIVISION 2 HAZARDOUS IOCATION
02 PER NfPA 820 TABLE 5.2 ROW 26b. Al� WIRINC A�ETHOOS SHAl4 CONFORM WITH NEC
CHAPER 5 REQUIREMETNS.
�j ROTATING BEACON, t00W HAIOGEN LAMP, RED IENS, 12aVAC, NEMA 4X, EOWAROS �j
58R-N5-t00HW OR EQUAL.
O MOUN7 BEACON AT SRME HEIGHT AS EXISTING UGHT FIXTURE, WEST 51DE OF ROLI-UP
DOOR.
�5 M6UNT BEACON ABOV£ PANEL AT 8'-0" AFF.
Us PROVIDE AND INSTALL NEW LIGHTING PANEL INTER�OR BREAKER COVER. PROVIOE NEW
TYPEWRIiTEN PANEI SCHEDULE.
�7 CONOUIT SEAL, 407. fILL
VILLAGE CREEK WASTEWAQTER TREATMENT PLANT
BAR SCREEN BUILDING
GAS DETECTOR ADDITION
DATE
FIGURE
NO. 2
JULY 2012
WALL SEAL
�''O+ WNOUIT
�•�
o•. ;
SEAUNO
"'�� OOHR
.: � ru rn,werx wm
�F SEM/N6 Cp1PplND
�. SUITAB�E F011 US£
p•�' IN HAWtDp/7 MEA:
4i�� 'MFR'S�RlSTRUC71Ri3
�.
�0�
.� • 41 CONWLFf
o'. �
CUNOINT
CONDUtT SEALaFF FITi1NG
DETAII O
N.T.9.
�
/* � � `ilT lj' •' *�11
:' �v
,CHARIES.,S:. PAGAOUAN �
► .�,�.,. 90517 ;'�,��
►+rliFss � ENS�o.Gy��; ,,�
� .�r
,��\h��.� � "� 2
FIGURE
NO.
FIGURE 2
i �
0
�u
N
�
W
m
O
f-
F--
O
Z
W
Q
�Z
Q
2
/-
i
�
0
O
K
w
O
d
w
h=-
�
z
w
�
W
2
0
�
0
a
�
O
U
Z
W
U
�
�
�
O
W
0
a
m
0
�
O
�
�z
z ti--
� �
N Ul
w
o�
o�
Z U
¢ O
� Z
w 0
� ��
U —
��tv
W Q
H Z
.. �
N �
Z '�
W w
�z
U ~
O F..
o�
�Q
o fz--
w 3
� �
�
�.. �
��
" a
�W
�
�o
��
U ¢
�o
��
_¢
H q
s
N O
��
0
U �
N T
0 3
o?
U
�
�
W�
a�
a
��
m�u
� N
r
U N
°� fp
K �
W �
O ti
a ..
:..
l�
i
�
N
��
>� 0
N �
GAS DETECTION C�NTROLLER
�.
f V
U U V
W �
r �
a � � cv
,o u
� Y
U ,.N.� � it
.
~ N N .Yi
A
� N (xl� Y
S �
_
o � � a
�
Oc
i
a
RELAY HOX
�
U
�
`�
W
oW
aa
��
mu
� F�.
sN
ad g
n, U
W�
�
a�
u
Y
\
Y
R
�
s
d
i
a
FS
GAS GAS
DETECTOR DETECTOR
U U U U
r Y V Y
c�'� � n �
� K a% ¢
Z Z E S
� � � �
� �N N N
�1 N � N
I lEL GqS
SENSUR
H2S GAS I � LEL GAS � � N2S GAS I
SENSOR SENSaR SENS�R
CQM
�m�th
1JOAM►LNIH�RE�NB! EKISTNIGALLENBRADIEYPAIlELBOARDBS% �oc.�florcx�cx
.^i0 MIP �Uf MTfiO �2 iOl[t tl KA i1/011f CNCUIilU�NO ENCIDfUAE RATP�O: I/BJA �,
:an:ovo�n � rw�et � w�e bN., �i}� t]� oJ1poa�ee uo i.uvNn�o: wR��ct
IAAD KVA 1 �7�6f�k�R 6S LAAD �YA
CRCUIT' FNASt illAfE PYW[ MIP� �p CIICUR FHA�E PHAlE �NAfi
1�P ��������PTqH A � C f • f NO. CifCRPlld4 A I I� I G
� ���NA���I lllFf2
_ � � �F ..,_—s ._
1S OAiOFTBCTIO PANEL
�"fZ.. � .�....___�-�...�_
� sP�e`
� ISP r
3PARF
n
b
N
u
]6
»
�
�1
�1 � lPAC[ HEAfiR �UlCfdO
2o n e
�n � �r�f UIdENTMNEI
�t i to v
70�1 __1�__.REC tAClF1.ICG
ao � i_) ie i�l1,1(C`�.
� SPA14F
� /l ' � �Ui'PANEI
.A
2o r.uw
b
+2
N
b
Y
�
u
r:ohs:
3 Fami OF� G�i �y�TBq�%/D�`E[A{qy/, Qi�l(' fyrPAOTECIICN C7JLY MEA7IRALE)
? �MNCHCIRCVITWYt�NQ 3'�'C��12i.1M1i0
l9RANCHCIRCUITP1'RINa fC,a12�1�q0
11.
�i
t5
iLl
If�
ITOTTALfNA EII�{�!O[ p � y O �
a � � � a
'JOTElCbTNT.^4TMRFE FHAf[hVA ]!-0
� �. PR��Cj 4�pKW011M�y, RAl1�P PMf R�AICFRpHAHDL��D IFACPf
e oA►.rx��Lrrwnn�& s.c. �,o i i�z�
B
j t D.
1 �a
j i �.
j tG
� �1.
� 201
i
IPEAF;EII N
N.Iff� �
f�F,} �
roo��
\,
C�i
� : .
I *.:�:... / ................::* I
CHARLES S. PAGADUAN
.� .:....9051.7.....::�i
t�f I�`�:�(�CENSEO,G����.r
it�: �ONAL E�+,'"'
..�-3v-i'�-
VILLAGE CREEK WASTEWAQTER TREATMENT PLANT
BAR SCREEN BUILOING
GAS DETECTOR ADDITlON
FIGURE
NO. 3
DATE JULY 2012
FIGURE
NO.
FIGURE 3
� �
W
W
m
O
H
�-
O
Z
W
_. .. �
!)
a
T
�—
�
�
�
�
U
�
O
�
a
a �
0
K
J
w
�
z
w
�
L
til
�
O
a
�
0
�.i
U
?
�
w
\
ALUMINUkF SVNSMIELD �
FABRICATE fROM 1/8' PLATE
�a/as' oerm x ���e• �toe C�— 4,�
UNIS7AUT P7000 EWK
, 1 S/B'MIN � ����/,II////.�/III/III �
I �
4 a .�.�e
�
1 �
O 3�e, I
o ' • �TYP) x
�
a, a i � 1/8' ALUMINUM���R GUSSET
THERMAL INSUTATOR � , I
MOUNTING 9lOCKS ° �
1
p 0 ��
CONCRETE o
� W�LL � I
a a a
� a' �
� , ��—
a � � ('��
� � �
� /
U CONCREi[ /EXPANSION ANCMOfl 4�1�
p LARGEF A$ REQUIRED BA EO O ''
� ON SUPPORTED 10A0 /�
n_ ��
� _ , ld
z r-
��
� �
w
o�
o �
Za�
�
o EQUIPMENT ENCLOSURE MOUNTING ON CONCRETE WALL WITH SUNSCREEN
W o DETAtL �
� � N.rs.
�no
x -
wV� �-
t.J 4
� Z
w
� � NOTFSu
� I. SUNSH;EID OIMENSIONS SMAII. E%CEEO OENCZ OINENSIONS BY 2' CN ALL 90E4.
z3
ww
�_
��
�
a�
�o
o�
ws
��
_�
W �,,
��
0
�
�a
�
��
l.l W
��`' o
��
�
��
0
J �
� h— �
__
�_ �
� O �
�� ��
q
U �
hl =
N �
O?
�*.�5�`y _. � .. *1
�
� ...............................
CHARLES S. PAGADUAN
.A ....... 9 051.7 .....: ;�i
�r� o,�;,, !/�eNSEp .,��,F.�.'r
ll�����\��.�~~�
i� • �3 - t't2a.
VILLAGE CREEK WASTEWAQTER TREATMENT PLANT
BAR SCREEN BUILDING
GAS DETECTOR ADDITfON
DATE AUGUST 2012
� OEYiCE
STAINLESS BOLY, NUT dc
WASMER AS RFWIREb
DETAIL A
ADDENDUM FIGURE
NO. NO.
LOCATION FIGURE 4
�� 'O l 2 CDM Smith
��ll Rights Reserved
SECTION 13345
INSTRUMENTATION AND CONTROLS — ANALYTICAL DEV[CES
PART 1 GENERAL
L01 SCOPE OF WORK
A. This section covers the furnishing, installation, and services for analytical related
instruments as detailed on the D lawings.
B. Refer to Section 13300. �
_ 1.02 RELATED WORK �
�. E?efer to Section 13300.
1.C3 SUBMITTALS °'
A. Refer to Sections 13300 and 13�40.
1.04 REFERENCE STANDARDS
A. Refer to Section 13300.
1.05 DELIVEI�Y, STORAGE, AND HANDLING
A. Refer to Section 13300.
1.06 QUALITY ASSURANCE
A. Refer to Section 13300.
1.07 NOMENCLATURE AND IUENTIFICATION.
A. Refer to Section 13300.
1.08 MAINTENANCE
.A. Refer to Section 13300.
1.09 SPARES AND ACCESSORIES
A. See Section 13340 for spare parts requirements.
E3. All mounting hardware required for pipe stand, surface, or other mounting shall be
provided.
C. Each instrument sha(1 be provided �vith a manufacturer installed stainless steel tag
identi 'tying the instrument tag number.
1.10 APPROVALS/CERTIFICATIONS
Project No: (133�5) (=�0 91 4�) - I
.._ . . . . . . _ . ... . . . .. . .. . .. . . . . .. . ._ .._ . . __. . __. .. .I
� 2012 CDM Smith
All Rights Reserved
�
A. Instr�m�ents for hazardous locations shall have Factory Mutual (FM), Canadian
Standards Association (CSA), and CENELEC approvals and certitications as specitied
herein and as indicated on the Drawings or in the li�stnilnent Device Schedule. �I'lle
instrument specitications in Part 2 state the Class, Division, and gas groups for
FM/CSA approval, iollowed in parenthesis by the CENELEC certitication; ho�vever,
instruments provided are only required to have the approval%certitication stated above.
-['he instrume�lt shall have a stainless steel tag identitying the r�levant approvat or
certitication.
i.l 1 viANUFACTURER START-UP AND TRAINING SERVICES
A. [f indicated in the instrumentation paragraphs below, the instrument manufacturer or
manufacturer's certitied service representative shall provide start-up and training
services. This work shall not be done by the PCSS or AESS contractor.
E3. The start-up services sl�all be to calibrate, oversee the installations of the sensor, and
start-up the sensor/transmitter in order to provide reliable measurement at the
instrument and to the control system. The vendor shall work with the PCSS and AESS
to verify the transmitter sends correct information to the remote system (i.e., that the
scaling and units are the same at the instrument and on the remote operator interface).
Vendor to submit an instrument calibration report in order to document the calibration
procedure of the instruments.
C. While starting up the analyzers, the manufacturer shall provide training to the Owner's
instrumentation technicians. The training shall be in ho�v to calibrate, install,
troubieshoot, read the diagnostics, and maintain the analyzer and transmitter.
D. [n addition to the above services, provide a written proposal for a maintenance contract
esecuted by the manufacturer tior on-site preventive maintenance services related to the
Instrumentation that requires manu�acturer services below. The cost of this maintenance
contract shall not be included in the Contract Price.
PART 2 PRODUCTS
?.01 COMBUSTIBLE GAS/LEL DETECTOR
A. Sensor
Type:
a. Intrinsically safe.
b. Continuous infrared sensor.
F uncti on/Performance:
Response 'I'ime: 'I'90 in less than 30 seconds.
�. "I'emperature Range: -50 to 90 degrees C.
c. Sensor Life: 3 years typieal.
Project Na (133�5) (�0 91 =�5) - 2
,-g 2012 COM Smith
/\II Rights Reserved
3. Physical:
a. Infrared sensor technology.
b. Suitable for remote wall or ceiling mounting, or directly fitted to transmitter
as indicated on the Drawings.
-+. Accessories Required:
a . Sufficient cable up to 50 ft ( 15 m) of the type recommended by the
manufacturer. shall be provided for installation between sensor and
transmitter as required by the installation indicated on the Drawings.
b. Remote sensor enclosures shall be explosion proof, approved for Class I.
Division I. Groups C and D (EEx d !IC T4) areas.
c. Detectors that are mounted below 6 ft (2 m) above floor level shall be fitted
with splash guards supplied by the manufacturer. to protect the sensor from
accidental wetting.
5. Manufacturer shall match the existing plant standard:
a. MSA Ultima XIR Series.
B. Indicating Transmitter/Controller
I. Type:
a. Electronic, microprocessor based single channel transmitter compatible with
sensor provided.
2. Function/Performance:
a. Accuracy: plus or minus 3 percent up to 50 percent LEL, plus or minus 5
percent for greater than 50 percent LEL.
b. Range: 0 to I 00 percent LEL.
c. Environmental Conditions: -20 to 60 degrees C ; IO to 95 percent relative
humidity.
d. Output: One 4-20 mA output proportional to calibrated range . Two
programmable relay contacts for warning, alarm, and /or fault.
e . Display: Digital display indicating the gas level, alarm or fault messages, and
diagnostic information.
3. Ph ysical:
a. Explosion proof enclosure approved for Class I, Division 1, Groups B, C, and
D (EEx d IIC T4).
Project No: ( 13345) ( 40 91 45) -3
; g 2012 CDM Smith
/\II Rights Reserved
b. Suitable for s urface mounting.
-l. Accessories Required:
a. Handheld programming unit if required for setup and calibration.
5. Manufacturer to match existing plant standard:
c1. MSA Ultima X3 Series with X3 technology .
C. Manufacturer Start-up and Training services
I . Provide manufacturer's start-up and training services as specified in the start-up
and training services paragraph .
2.02 HYDROGEN SULFIDE DETECTOR
A. Sensor:
I. Ty pe:
a. Integral hydrogen sulfide gas sensors shall be the continuous diffusion type,
which change resistance when exposed to hydrogen sulfide.
2. Functional/performance:
a . Continuously measure, indicate, and transmit ppm concentration of hydrogen
s ulfide in air. The speed of response to a step change in gas concentration
s hall be less than IO seconds to 90 percent of final reading.
3. Physical:
a. The sensor shall be compact and of rugged construction to minimize
accidental damage of materials and to resist corrosive atmospheres and
poisoning of the sensor.
b . It s hall have positive flame arresting protection and be s uitable for installation
in atmospheres falling under NEC Class I, Division I, Group D classifications.
c. The sensor s hall be integral with the transmitter and be of explosion proof
construction.
d. The sens or s hall be mounted to prevent moisture acc umulation.
e. The sensor s hall be mounted approximately I ft a bove the floor.
4. Expendables:
a. The sens or s hall have a useful life of2 years under normal operating
conditions.
5. Accesso rie s Required:
Project No: (13345) (40 91 45)-4
g 2012 COM S mith
All Rights Reserve d
a. Sufficient cable up to 100 ft (30 m) of the type recommended by the
manufacturer, shall be provided for installation between sensor and
transmitter as required by the installation indicated on the Drawings.
b. Mounting brackets for mounting as indicated on the drawings.
c. In non-hazardous areas, remote sensor enclosures s hall be NEMA 4X (IP65).
Where indicated in the Instrument Device Schedule or on the Drawings to be
installed in hazardous areas, enclosures s hall be explosion proof, a pproved for
Class I , Division I , Groups C and D (EEx d IIC T4) areas.
d. Detectors that are mounted below 6 ft (2 m) above floor level s hall be fitted
with s plash guards supplied by the manufacturer, to protect the sensor from
accidental wetting.
B. Indicating Transmitter/Controller
I. T y pe:
a. Electronic, microprocessor based transmitter compatible with sensor
provided.
b. Single or dual channel as indicated on the Drawings or in the Instrument
Device Schedule.
2. Function/Performance:
a. Linearity: plus or minus 2 percent of full scale.
b . Repeatability: plus or minus I percent of full scale.
c. Range: 0 to I 00 ppm.
d . Environmental Conditions: -20 to 50 degrees C and Oto 95 percent relative
humidity.
e . Output: One 4-20 mA output proportional to calibrated range. Two relay
co ntacts for alarm and one fault relay contact.
f. Digital display indicating the gas level , alarm or fault me ssages, and
diagnostic information.
3. Ph ys ical:
a. NEMA 4X (IP65) enclosure approved for Class I , Division I, Groups C and
D (EEx d IIC T4).
b . Suitable for s ur fa ce mounting.
c . A DC po we r s uppl y s hall be provided with each tran smitter. The power
s upply s hall be in sta lled in a n e nclosure having the same certification as the
e nclos ure for the transmitter. A/C power will be provided at the voltage a nd
Project No: (13345) (40 91 45)-5
9 2012 COM Smith
All Rights Reserved
frequency stated in Section 13300.
4. Accessories Required:
a. One year supply of calibration and test gas for detectors indicated in the
Instrument Device Schedule or on the Drawings.
b. Calibrator, fittings, hoses , and other devices require for calibration of
detectors.
c. In lieu of the above, if the vendor offers a "Sensor Exchange" program as a
standard offering, a year of this Sensor Exchange program is acceptable. This
program shall deliver a freshly calibrated sensor at manufacturer
recommended calibration intervals for replacement of the existing sensor. All
information shall be uploaded to the transmitter for the new sensor with no
further maintenance required for the new sensor to function properly .
C. Manufacturer to match existing plant standard:
I . MSA Ultima X3 Series.
D. Manufacturer Start-up and Training services
I. Provide manufacturer's start-up and training services as specified in the start-up
and training services paragraph.
2 .03 GAS SYSTEM CONTROLLER
A. Designed for use with the Ul tima X with X3 technology gas monitors.
I. Self-configured and able to monitor up to 25 Ultima X gas monitors
2. Modbus RTU input and Modbus-over-ethernet interface
3. Provide with I OOW power supply.
4. Wall mount.
5. Log up to 2,000 events with nine zone control relays.
6 . Seven-year battery backup.
B. Manufacturer to match existing plant standard:
I . MSA ModCon 75
C. Manufacturer Start-up and Training se rvices
I. Provide manufacturer's s tart-up and training services as s peci tied in the start-up
and training se rvices paragraph.
PART 3 EXECUTION
Project No: (13345) (40 91 45) -6
D 2012 COM Smith
All Rights Reserved
3 .01 GENERAL
A. See execution requirements in Section 13300.
B. Locate gas sensors per manufacturer's recommendations.
END OF SECTrON
Project No: (13345)(40 91 45)-7
Cost Summary :
Alum Conduit
Materials/ Equipment
General Materials
PCM NO . 2
Cred it to Change the Orig inal Conduit to A lum
Sub Contract
Equ ipment (Backhoe, Tamper)
Material Total
Labor hrs
Journeyman 136
Foreman 26
Proj ect Manager 13
Labor Burden @38%
Fringe Benefits @8%
Labor Total
General Conditions
Safety Equ i pment 3.50% Of Labor
Job Tra iler 2% Of Labor
Te lephone 2 .20% Of Labor
Small Tools 7% Of Labor
Pickup Trucks 3.50% Of Labor
Total General Conditions
Sales Tax 8 .25% Material
Bond 2%
Subtotal
Overhead 10%
Profit 5%
Final Amount
Sincerely,
WHF Electrical Contractors, Inc.
Greg M ill e r
V ice Pres ident
rate
$ 32.00
$ 38.00
$ 65 .00
$ 5 ,940 .00
$ (1 ,538.00)
$ 18,306 .00
$ 1,500 .00
$ 24,208.00
$ 4 ,352 .00
$ 988.00
$ 845.00
$ 2 ,350.30
$ 682.82
$ 9,218.12
$ 322 .63
$ 184.36
s 202 .80
$ 645.27
$ 322 .63
$ 1,677.70
$
$ 702.08
$ 35 ,805 .90
$ 3,580 .59
$ 1,969 .32
$ 41,355.81
J ob ID .VCWWTP WH F ELECTRICAL Dalt Paa,
J~b t-~n,o Gu Deteciion System 11/13/2012
R,11p o{1 Combined All. Job Fil e Prtclng Time
' ------
Not~.• !'v ·H,Ji~ Phone : Fax: 0 :47 AM At~h to~:f f e-mst.
Report Genel'llt9d From: Summary . All Level•
Item# Sia llem011c Qty Mat Unit Malhi Lbr Unll Lbr l!xt
Summery:
1 Beacon LlghtS 2.00 550.00 1100 .00 2.00 4.00
2 Relay Pa nel 1.00 500.00 500.00 4 .00 4.00
3 Panel Cover 1.00 250.00 250.00 2.00 2.00
20111 1' PVC SCH 40 UGRD 100.00 0.38 38.00 0.02 2.00
21!02 314' ALUM CONDUIT 190.00 1.06 201 .40 0.07 13.30
2B03 1' ALUM CONDUIT JO O.CO 1.40 420.00 0.08 24.00
40 03 1' ALUMINUN GRNO. BUSHING 1 00 9.81 9.81 0.20 0.20
5059 1' PVC ADPT/FEMALE 4.00 0.18 0 64 0.10 0.40
5112 J/4' ALUM MYERS HUBS 4.00 2.70 10.80 0.30 1.20
5113 1' ALUM MYERS HUBS 4.00 3.21 12.64 0.30 1.20
53911 3/4' ALUM LBW/CVR & GASK 6.00 15 .00 90 00 0.35 2.10
5399 1' ALUM LB W/CVR & GASK B.00 22 .00 178.00 0.40 3.20
5443 1' OZDX 400 125.00 500.00 0.40 1.60
5646 1' LI NK SEAL 6.00 40.00 320.00 0 .35 2.80
7184 3/4' HOLE DRILL & PATCH 3.00 25.00 75 .00 2 .00 6.00
71 85 1· HOLE DRILL & PATCH 8.00 25.00 200.00 2.00 16.00
7292 1/4X4 S.S .ANC HOR 98.00 0.85 83.30 0 .15 14.70
7402 3/8' S.SALLTHREAD ROD 12 .00 4.50 54 .00 0 .0<4 048
7502 3/4" S.S. STRUT STRAO 38.00 1.25 47 .50
7503 1" S.S. STRUT STRAP 60 .00 1.45 87 .00
78711 1 112' 3111 S .S. STRUT 49.00 12.00 588 .00 0.07 3 .43
11Hi7 12 XHHWSTRCU 1395.00 0.25 348.75 0.01 9.77
1B202 20/1 CIRCUIT BREAKER 1 00 35.00 3500 0 .20 020
30031 2X3 BASE SPACER 20.00 1.07 21 .47 0 .10 2.00
30154 6" WARNING TAPE PLAS 5000 0.12 5.85 0.00 0.01
30311 3000, CONCRETE 1.00 1.2 5 1.25
30318 SANO 4.00 18 00 72.00 1.50 8 .00
42057 3/4' EYS2 SEALFTG FE M HUB 10.00 14 00 140 00 0.55 5.50
42058 1" EYS3 SEALFTG FEM HUB 4 .00 1900 76.00 0.60 2.40
43017 1" PVC COATED AL 40MIL 20 .00 6 14 12 2.80 0 .10 2.00
43243 1' PVC CTO 36" ELBOW 4 .00 0900 3511 .00 0.85 340
Grand Total• ror Summary : 5131 ,9' 1)1.14
DS Corp
Gas and Flame Detection
15 June 2012
Jerry Raper
Wheco Controls
817-244-6660
ierry@whecocontrols.com
Re: Quote # TC0615 l 2A
Dear Jerry,
GOS Corp . is pleased to offer the following fixed gas detection equipment for your application . This
proposal is based on your inquiry dated 14 June 2012.
We will be prepared to ship the hardware within 2-4 weeks after receipt oforder.
GOS Corp . provides a wide range of industrial gas detection systems for toxic, oxygen and combustibles.
Applications include Petrochemical, Oil and Gas, Pulp and Paper, Semiconductor, and other industries
requiring affordable gas detection solutions for the most difficult and challenging environments. GOS
Corp. monitors and alarm controllers are truly "state of the art" devices offering unparalleled features and
capabilities along with OSHA approved NRTL (Nationally Recognized Testing Laboratory) certifications.
Our formalized quality process includes twenty-four hour bum-in and calibration of every sensor, detector
and controller shipped from our facility . As a result, our customer list includes some the largest companies
such as ExxonMobil, British Petroleum and BASF Chemical; and diverse companies such as DPT
Laboratories, Halliburton, Duke Energy and Smith Detections.
Please reference this quote number on any subsequent purchase orders. If you have any questions on the
proposal, please do not hesitate to contact us .
13est Regards,
Tibor Cseszko
GOS Corp
(8 32) 704-8865 Mobile
(4 09) 927-2980 xi 13
tcseszko @ gdscorp .com
GOS Corporation
2513 Hwy 646 South Santa Fe , Texas 77510 Ph: (409) 927-2980 Fax: (409) 927-4180
www .gdscorp.com
Quote TC06 l 5 l 2A
A
Gas Detection Equipment
GM II -0 -00 -0 / 1 -70 -6 / 0 -0
GOS Corp. GASMAX II Gas Monitor with (Ch 2)
Local sensor head configured for Catalytic Bead
for Combustibles LEL with range 0-100
Technical Description
GASMAX II Powered Gas Monitor for combustible, toxic /
oxygen applications.
Two independent channels allow simultaneous measurement of
LEL and toxic gas.
The highly visible LCD display shows calibrated engineering
values, bar-graph data, 30-minute trend and setup information.
Front panel flashing LEDs continuously indicate alarm
conditions. Real-time clock time-stamps alarms and calibration
events.
Standard output is 4-20mA; options include form C relays,
isolated 4-20mA and MODBUS.
Magnetic interface eliminates potentiometers and enables all
adjustments to be made without opening the case.
CSA certified for hazardous environments (see manual).
NOTE: lfshippedwith electrochemical sensors, power must be
applied to sensors within 60 days or sensor life may be affected.
GOS Corporation
Page 2 of3
Sl,275 Sl,275
2513 Hwy 646 South Santa Fe, Texas 77510 Ph : (409) 927-2980 Fax : (409) 927-4180
www.gdscorp.com
Quote TC061512A Page 3 of3
GDS Corp Standard Terms and Conditions
Quoted Price
All prices legitimately quoted by GDS Corp or its authorized distributors or representatives are fir m fo r 30 days fro m d ate of
quote. Unless speci fie d in writing, price~ a re subject to c h ange aft er 60 days from date of q uote. Pric es shown here in are accurate
dt time o f printing.
Acceptance of Orders
All o rd ers are subject to acceptance by GDS Corp . Orders are EXW GD S Corp., 2513 Hwy 646, Santa Fe, Texas 7751 0 .
Terms
Standard terms fo r domestic US customers are net 30 days with approved credit unless otherwise s pecified. GDS Corp . reserves
the right to change c red it terms a t any time an d to collect interest prem iums on overdue accounts . International o rders arc cash-
in-advancc unless otherwise speci fied in wri ting.
Warranty
G DS Corp. hardware products carry a 2-year limi ted repai r or replacement warr<1 nty on electron ic s and workmansh ip . For
ambient detection appl ications, electrochemical sen so rs and photoionization detector {PID) sensors carry a on e year wa rranty;
Smart [R infrared sensors carry a two year warranty and GDS-IR sens ors carry a 5 year warranty. All e lectrochemical , PID and
Smart!R sensors used with GDS-58XP sam ple draw systems carry a one year warranty. Sensors used in GOS-68XP and GOS ·
78X P Process Monitors and custom PSM a pplica t io n s are not covered under warranty unles s s pec ified in product manual. GOS
Corp . reserves the right to void warranty claims b ased o n evi d ence of misuse. ab use, or the m isapplication of a specifi c sensor in
an envi ronment known to adversely affect sen sor life . Warranty period start s o n date of sh ipment from GDS Corp.
Delivery
Shipping and handling c harg es will be added to each order. GOS Corp . shall not be held liable for damages or penalties for delay
in delivery or failure to give notice of suc h delay in the event the delay is caused b y the cle ments, acts of God, acts o f p urchaser,
fi re or floods. la bor sto ppages, accidents, riots, acts of terrori sm or other delays beyond the re asonab le control ofGDS Corp. In
the event of such occurrence, purchaser may at thei r option can cel or reschedule the order or that portio n o f the order so affected.
Title to all goods provided under th ese te rms remains with GDS Corp. unti l goo ds s upp lied are paid for . Purchaser is re s ponsible
fo r damage or loss from the time the sh ipme nt leaves GOS Corp .
Export Restrictions
!f the item is intended fo r exp o rt o r re-ex port , it is the Buyer's responsibility to comply with all applicable international and
na tional laws that apply, inc lud ing U.S. Export Administration Regulations, end-user, en d-use, and des tination restrictions issued
by U.S . an d other governm ents. The sale , transfer , transportation or shi pme nt outs ide of the U.S. of any product prohibited or
res tricted fo r export wi thout proper ex p o rt licensing or other c om pl iance with U.S. ex port control laws and regulatio ns is st rictl y
prohibited.
Errors
Clerical or typograph ical errors a rc subject to correction without penalty.
Cancellation or Returns
Con fi rmed orders may not be cancelled or subs tantiall y changed wi thout writte n acceptance by GOS Corp . of cancellation or
return in writing, a nd customer may be charged a cancellati o n or restocking fee. Certain li m ited-shelf-life co mponents (ex:
electrochemical sensors) ordered and subscquentially cancelled or returned may incur a 100 % restocking fee .
If GOS Corp approves a cancdlatiun o r return reqm: t, the following charges will a pp ly:
• Cance llation with in 24 hours o f in itial o rder acceptance -No Charge
• Cance ll ation afte r 24 hours but before initial shi pment -50% of list price on standard items; l 00 % of lis t price o n
lim ited shelf-li fe items and any non-standard parts specific to th is o rder.
• Returns up to 3 months -50% of lis t price res toc king fee on standard items; I 00% of lis t price o n limi ted shelf-life
items and a ny non-standard parts specific to th is order,
Products returned for cred it must be in new and unused cond ition an d com p lete with boxes an d manuals.
GOS Corporat io n
2513 Hwy 646 South S anta Fe, Texa s 77510 Ph : (4 09 ) 927-2980 Fax: (4 09) 927-4180
www .gd scorp .co m
352 D4t
4 IATG. HOtES -� � -
�
/, �f
I a WARNING �
�/!Y Y � m041'I!� 11060 IN tll� t � O� R
mmw �n�u. uah �w oo�R o�r w� sMwme
ro� �r � irmsNa vmi r► rRruE ras
.rM iw ra�a �u. � vr�s rr wrtw
�aua�c m nm w iaa�
�tl'xv�.won�fQ1°�cn�roo �s°Wr�� �i �� ` - ��-
� �iv�ir�ivc a� �t i�-i-�o�r v .�..��.+�
�
/
I
15.30
12.00
�
> !!
r
!!!774��lId►�C
!7!!1�'1�l�*C1 �► L7
*�w���n�n�n�o
M57a
� NEMA 4X FlBERClA55 ENCLOSUf�
�'� �'"` �_` �"�
f � 1 � 1 � t �
�..�� �,: ���� �..��
POWER AND SIGNAL ENTRIES
PUNCHED ON StfE 9Y OTHERS:
AC POWER
IAOD9US NEfWORK
HORN AND ZONE f/0
�
/
�,
�
-� 6.70 �
/ — /R
/ ti
�a
� (
i�.ai
� (
��
�
i
�
�� �
, ! DANGER
�
High voltoge
Disconnect power
before servicing
PARTS LIST
�I'd. 1 ��90GKM t4 IIIEO'DI �Eiptt/ttQ1
y�� �� 'ra
� = N � � 0 inN�
e�uE - e 'MXC�'{
i f
�RAMOE � 0 CA�AY . A �
�ttor - r wmE _ w ,
%Nt � P iN! � T „�r(
GEVIpWs
m���aui IrI f ILE REF� N0. �"� ��n�� wor io[ urtn wr� Nccc ca-
.rr v �r s �ac �v�a,at ro +w
�t[-�wt nlre sK[tr �rn.wcci cor�wr "' cdr�x�cc u,uccr ro rw�v�w w�cs�u�mr it �
❑RIZEll CdUNTRY I�nuu WC ,wm.r a. cu� nw Nar
PIiTlILIIGN, PA T �Y� ��M�IDN� [ort�UO M�[�M t0 SGµ, E
N A� TiQt[ hC �'R�V4fiT[I( �SIi tf' MtK iNC'fT N74- D�IG
� 1 rM rrwiw� oQ riaerrou ww.r �w'�as cai�w ;wvaruc v ra+nn ra
fA fTk�i RAV1! 2T CAt[ jm/6 7GLE
,.�► .�.. • 4 + N.T.S.
, F SWFROCK 4-J-Oli
'. � � t�� � � �� �* � AGENCY CCItVTRt7�LED "`
� r ip�e vtio� 2� R. SCNULZ 4-i t-O7
cv rRc.car uc�.,mr �
� """' �'" �IODCONTs, WALi. MOUNT
� 7 fi.R.T' 3•�0 WN.17T AfiWMCC
� �,� ��,�. j DSK I��`o�-l0 I,�
� P� e37t�t
� NOTES:
f. ------ON SITE M7A!►�.
2. POYYER RECWREMEMIS: 715 VDC • 1.23 AMPS. SfE NOtE 0.
J. AANEL !S GENERAL PURPOS� NEAN 4X.
4. INSTNI1ITION ANp WfRINC 8Y O7MER5.
5. REiAY OUTPNSc
OUiPUT CURRENf: RESISfNE lOAD
SA 11AKIYUM PER OU1PUi
8l1 MA1fM1UM TOTAL FOR COYIMON SEE NOTE 8.
INI)U(:TME I L1AD
1 A W1XqrIUM PER OUTPUT
e. ourPurs ia�s, r uruo µ s►� �►nror�i s��� ourPurs
r�v� �nnu corn�s
7. DIpTAL INPIJiS:
INPUf Vt11JAG'E: SOURt� 0-SVOC h'0!i LOGIC '0'
»-ze.evnc � �oc�c '�'
IkPUT CURREN't &nA 1 24VDC �OR lNPUTS %4 TO j1S
E.OmA � 24VDC FOR INPUfS /0 TO /J
R. IKtFRtJAt, PDWER SUPpLY IS NOT tNTEi�EQ FOR USE WtM SF)VSOR£ SENSOR
� surP�r �s Extaaw. � s�um er oT►�a�s.
9. r�r� w�mxc rs /�e ,twc umtas ra�o.
10. ETHERNET OPTION IS AVARI18lE 8UT MUSf BE FIICTORY CWi1GURED.
tt. MQ08tt5 SftlSOR CONFlCUPoN101t - WKE 7fi� FOCLqP�JC Cf{�WCES;
-D��IlLT ADDRESS IS 247. CFNNGE EACH SENSOR TO A UNqUE ADDRESS
eetwm+ z�wo ze Foa us� wrrtt t►� MoocoN�s or�t ��+c.
12. MODBUS ADOHESS MUST NdT 9E DUPLIGTEO WfTFIRI iHE SAAIE NETYlORK.
13. SYS(Ei/ BAUO RATE IS FlXiD 19,20Q bp�, pp MpT CNANGE 7NE gENSORS 70
ANY OTFIER VALUE.
14. lERMiiF(ATOR RESfSTORS (120 Oiq15 • t/4i1� YUSt � INSfAt1m At fX�ti
E?ID OP THE NEiWORK COMNUNIG110M GBLES,
PARTS L7ST r�wsions
' AIODCON75 CONTROLLER �M w�rt wsrn ia
�r P/N ASKJ204-37 �° mus�rx► �a I�Eo•oI ��1o7)ON
SEE DEfNL C-� K� q B� V� A� N� Y� C' 11� � 0( 11� (V26M� � UGTIOrN —
I0000000000! I0000000000� �
�
■ • � � � � � � ■ ■ ■ � � � � � � � � ■
o�an�in 0
�zQszI�YYl�L` �28Ss===== 0
DIGRAL NAliD 0
AMAl.00
INPUTB
��•
m ■v
9 ■ I �AIN2
B ■ OV
� ■V
a • i �NN,
a ■ ov
�.�
m ., �N�
�_�OV
iWIS1ED PAIR
6 PUCES �L
1K lw l�
AC ACN GND
AC
POWER
SUPPLY
�- —
R \ K
�
�
�o—
�
o—
�— l /
�
�� 5 CDNDUCTOR
� TWISTED
I l f I I I ��
I
R
�
0
CO
0
K W C C
k �o cHo
;•� � �
� I I
�__1J
fUSE 2 NAP, I
5X20MM �
I
i
i
I
115 VAC 0 60 Ftz
AC PCWEA
� 0
O K
2NDC OV �' 0 t--� K
SNAP-IN I/O Ir°'oa' 0 R K—
P�PL01�■ 0 W R
MODULE o,�. 0
(V200-18-E1 B) o�a, . e
Coltn■ 0
�� 012n ■ 0
013n�_0
REUY OUTPUTB
� � o � g � S g S 8 24VDC
l�l�l�Z�l� �ll�lil�.:
�9mBBBBBBB 6989BB�8aa
____ � 1�-- K
0 K 8 K V K A K N K K 0 B V A N K R R K
R
0 R K
0
� � K
I�
( f
I/0 MODULE � � �
� •H ❑
� O
-� O
o �
o ��
�
� O
o �� ��
❑
0
O
ETHERNET
(OPT10N)
(V200-19-ET1)
SEE NOTE 10 � +V
S ov O
i'S �
� ;� ��
�
�— �
� R 0 B V A N Y G W R 0 N
r-__�.�— r��.li-
- O
O
— o
r
HORN AND ZONE
�p}—°---� ALARM RELAY OUTPUTS - DRY CONTACT3
�ooR casE (SEE TABLE 1)
TABLE 1
AtARM REUY FUNCTIONS
QUfPUT �y�jjQb
0 ZONE 1
1 ZONE 2
"70T 2 20NE 3
ISOLATED 3 ZONE 4
4 ZONE 5
s zoNE e
6 ZONE 7
7 ZONE E
8 ZONE 9
9 HORN
;
I+ olil�lal�lslel��+iel��
(+�9 *�
�
REMOTEACKNOWLEDGEINPUTS
(SEE TABLE 2 AND DETAIL C)
TAB(i Q
REMOTE ACKNOWLEDCE (DICfTAL) INPUTS
�0� Z0� N� E�1
1 ZONE 2
2 ZONE 3
3 ZONE 4
4 20NE 5
5 ZONE 6
B ZONE 7
7 ZONE B
8 ZONE 9
9-11 NOT USED
1Z HORN
13-15 NOT USED
FACTORY INSTu � co
CABLE lSSEA18LY
�- P/N ASK3204-4Z
��
� JUYPE1t5
O� ��
a0D 2 PIACES
O�
�
B 1
K W R � !22 AWC
R K - t 11Vi51Ep PNR
L G
cNa--
� O � — FAULT �
_ � O i0 O O REUY r1 I
�
O o—
A B SH Glil — NC C 1
� � i
J I I � NC C2 NO
I 1 �
1 I �
(?-r�
+-4'
i i
AIODBUS RS-485
NETWORK (18200,E,8,1)
i0 ULT11M X3 SENSOR§
(SEE NOTES 11-14)
VIEW B-B
SEE NOTES ON SHEET 1
mcuort cwruira �r
;1fiC►OWltAkC•PM7 I
IAUTHORIZED C�UNTR
�(� � N
� .� �„ _, �N
BROM'N � N BLUE � g I t �
� � R VKKFf � y �
i
� - r° w�nr� - w "�µ� �
pNf - P iN! - T ��fflc�u
BUZZER, 24 WC
AISA P/N 637123
IY K
1
K
��� .�
us �� � � NO CONNECilONS
�
+ �' �no
� �
°M � v�w��wtr as
I UNNERSAL CONVERTEA
(M90-19-R4)
Am�s� f R5232 TO R54B5)
K R
YK 8 R A
1
CIRCUR
PROTECiION
DEVICE
+V--- — ---t1Tt1tTtt---Y—�
OV-------T—�lllflll_� i i
i �Y������� � v� e�
�� I I I
� i i i
� . . . . . . ■ . . . ' 'i���i'
a=o=nnx��ee a=. �
TYPIGL DICRAL INPUT WIRINC - SOURCE
DETAIL C
IF.LE REF, N0. +�aj �u�t.c n t�c nvarr � �c.c urcir i.rR,wcct cw-
�,wr ��in rcMa,�v w� i� w�ec .v.iuu ro ,nr
I a r�reoa�i�wi aaicr r��c ra.mrtw w.veatr.o. �c n�
JMtI�E sKETY M►L1MICES COWAM wn1Cl in N,uM an�q. t�Nmvt O� tci0.att rwf NOT
PliTilll�ltil. PA �v�a un nloMVtu� o� tLtA ca�tu4� ��ce[pr i0 SCAIE
orrm nwr nc nuv wrrn mann or a wcn .rr�-
rr � �twmua 4v nucrtm �v+L� WQf m1wf/ CI4)i ILe tK wWlKlut 7 �fT1Ri7 ra DVG.
�.x uvc�..nawct co�wn.•
i i co s.��aa Inuvw n w+[ � �a crxc
;�'�`�s �� F. SWEROCK 4-3-07I � N.T.S� �
i-i!CLI�.�2r�..�l! •ti�a�o �T AGENCY CONTROLLED
anaasc ircca« s IR. SCHULZ 4-I1-07
�-I FwlcrcGtMl ttn�• r+o�ccr cwirtu
t-I""" _" I MODCON75, WALL MOl1NT
a PL.DEG t.aOO a.wln �taw�ntt
C ��� '� �..K,,.� j DSK I���b�-70 � Z�
0 Self-configuring to Ultima ® X Gas
Monitors with X3 Technology
0 ModBUS RTU input/output
0 ModBUS -over -Ethernet interface
0 Vi ew and control of up to 25 Ultima X
Gas Monitors with X3 Technology
(75 total sensors)
0 All pertinent data displays on
main data screen
O 12/24 voe power supply
0 Seven-year battery backup provides
memory and real-time clock
0 Logs up to 4000 events
0 Eight zone control relays
0 Password -protected
0 cUL listed
Th• perfect partner for your
Ultim1 X Sarin Gas Monitors
with XI Technology.
MSA 's ModCon75 Controller is
designed for use with your Ultima X
Gas Monitor with X' Technology,
enabling self-configuration, saving
t ime and money. This new, economical
choice is su itable for all industrial,
municipal, oil, gas, and petrochemical
applications.
The Safety Compa!}y
C)
Pre-programmed, self-configuring
controller for monitoring up to 25
Ultima ® X Gas Monitors with X3
Technology transmitters (75 sensors
tot al). Compact unit allows for remote
control of many features. ModBUS RTU
in put/output and ModBUS-over-
Ethernet interface capability.
Specifications: ModCon75 Controller
PHYSICAL CHARACTERISTICS
Weight: 3 lbs.
Dimensions : 6.l"H x 10.24"W x 2.8"0
Enclosure type: none
Panel Mount Maximum number of sensors: 75
Front panel is IPB5/NEMA 4X (when mounted)
Mounting prov1s1ons: rnstellat1on designed tor
panel mount
Weight 14.25 lbs
Dimensions: 17.S"H x 15.S"W x 6"D
Enclosure type : NEMA 4X fiberglass enc losure
NEMA with panel mount display and controls
Fiberglass Maximum number of sensors: 75
Mounting provisions: 4 mounting lugs
located on top and bottom (2 each) for
flat surface attachment
GRAPHICAL OISPLA Y SCREEN
Typa
lttum na on
Backtight
Display
Resolution
Temperature
Humidity
Negative blue STN LCD graphical display
CCFL (fluorescent lampl
240 x 64 pixels
Operating temperature range: -10° to +40°C
(14° to 104°F)
peratlng humidity range: 0-90 R ,
11on-condansing
Nalll: Th is Bu ll etin conta in s only a ge neral desc ri ption ca,.,.r111 Httd~-"" MSAMox ioo
Options:
• Choice of panel-or wall-mounted versions
e NEMA 4X or panel mount options
• OPC-comp li ant for graph ics, displays, and datalogging
Typical Display
e Scrolling sensors feature gas type, reading, and
engineering units.
• During in activity unit scrolls through sensor screens.
Main Menu
• Navigates menu options using plain language text for
improved ease of use.
e Offers easy access to add nodes, view and edit alarm
set-points, set zone relays, and set password.
Edit Alarm Set-Points
• Factory set-points are downloaded automatically
from the Ultima X Gas Monitor with X1 Technology
transmitter during setup.
• Alarm set-points are easily modified by user.
• Sensor alarm options include on/off, latching/non-latching
and increasing/decreasing.
e Password-protected against tamper ing.
of I e products shown . Wh i t usu en d perfor mance P.O Box 421. Pittsburgh, Phone 52-55 21 22 sno Olficu and rep11111111tlve1 worldwide
Fer fun:h u infann1 tion :
cap abil~ill 111 dH crib ad , undtr no ci rcumrta ncts PA 15230 USA
sh ai the products ba used by untrained or unquoified Paont 412-917 -JOOO
inaiviooa ls and not unn l !he product in1111Jct ions www.MIAoet.cN1
inc lud ing any warn ings Of cautio ns prov ided hevt b11n u.1. c ... -S.r-.ice Ceotw
lh oroughly rud and understood. Only !hey conta in th e Phone t-800-MSA-IN ST
complete end data,1d informa ti on conc ern ing proper Fu 1·724 ·779-3280
usa and cart of the st producta.
ID 07-2129-MC / Au1 211111
ti MSA 2009 Printed in U.S A
MIAClftaN
Phone 411-620 ·4225
Fu 4t!,12Q-91197
Fu 52 ·55 5359 4330
MSA lnten1atiH1I
Ph one 412 -9f7 ·J3!'>4
FAX 412 ·9'7·3451
Tht Safety CompOfJY
3��' NPT �-3.300
THREADS I85.85]
�-,501
N1.92S I11.917
c�a.so� 1 �
C
I• �
C ___^��-{}-�,
SEE NOTE 5 9.8Et �� �
I251,16] �
_, �
(
� � �
+
�
SENSOR INLET
SENSOR INLET SEE NOTE E
3/16• I.D.
SOFT TU81N6
d�t1E "A' NSD7! JQ 88�1�
MODUL���GHT � 1.�1 LBS.
- 11.554
t293.�77
SEE NOTE 5
3/1 NPT •
THREADS
0
R1,925
f 10. 901
MOUNT XIN WITH SENSOR
ORIENTATION AS SHOWN
1 �
3.3E0
[85.851
� .
.59/
[15.091
MAT� UL: CAS AlU IN N
MODULE •A• wEIGHt = �.9 LBS.
CUSTOMER
P.O. #
MSA ik
LOCATION
TA� #
TOTAL N0. OF UNITS
�
,�
SENSOR INLET
SOFT6TUBIN6
�
�+- 1.000 --�
[1�1,601
_ -� 1
� � �-� iiii�se�
3,000 2.250
t16.20) (51.IS1
._[_� � �
��
LEARANCE HOLES FON
1/4-20 SCREWS
11 PLACESf
�
�- �. 150
[120.657
�:,�. • - .L- i -�i...-�i
'1� �11.�`.'��lin���a 1: ! :
t�:�i!.7n
° i' 1
LEARANCE HOIES FOR
3,000 I/1-20 SCREN'S
t76.20] II PLACE51
,�
1
� -�
I . D00 _ �
[IOI.601
1 �,�, �-
- i�-�
-� 2.250 �+-
[57.151
: n il:��"�3- =;:.'t,l
.r,i'-i,`'��ii?'�ai. �:�
%)iiG7.. T
10.259
c2so.se�
i
_�
SENSOR INLET
SEE NOTE a
s.312 -�-
[160.321
SEE NOTE 5 _ „P�A1S LIST
('NO � � N�4$�Tf R f N0. �OTfi�.A � ---
� i .�--- 5.333 - -
t135./i1
�
�-3.9f1
f99.3/l
MATE81�lVL: I S AINLESS3TEEL �
MODULE 'B' WEIGHT : e.i L83.
_� ,
�
�-a
-MOUNT 1I I r SENSON YI I TH
ORIENTATION AS SHOWN
LL'i11� 70! TAA119/TfF71-- -
��� _ ��
wEicN i3, ie
i
�.750
(120.851
DESCRIPTION
� a�i
MODUIf '9' M IGH = f.1/ l83
�►--- 5. I OG ---�►
[ 129.5U
CLEARANGE HOlES fOR �_ �,100
f/�-20 SCREWS� �10�,1/)
N PLACES!
I�i
O o
0 0
6.724 � �
I110.79I p
�►- 3. ! I I -�
[91.311
I I
r,�►,
� �I�
f �
-
��
�
i
_f
O
0
O O
0 0
( �-
i � I� -
•.
', � .11 � YI' a�,!.�
�� �;irt..
�
0
0 7,1T1
t18Y.81)
NOTE:
1. DIMENStONS SHOWN Ik INCHES (MILLIMETERSI.
3. CAL18RATION TUBING IS SUPPtiED iN CAU BRATION NIT.
4. PtN 100�17562 IS REMOSE OPTIONAI MOUNTING STRAP.
S. CHECK THIS TAG FOR HA2ARDOUS RATING.
6. P/N IOQ11561 IS IW$TRUMENT OPTIONAL MOUNTING STAP.
7. CHECK SENSOR LABEI fOR GAE TYPE, NANGE, AND Ai0
ORDERING NUNBER.
6. SEMS08 tNIET MUST FACE DOwN.
�
AEVISiONS "
NOV 19 2004
AUTH0�11E6 � NII[ WLT1 AMLI�KE� CO �Xtf Glatip If I�E 11101CA�� Or Mi11 a�D +3 �aM Fra��qtE i0 iW ��
CO�f�O(KC ��C fusXU 10 Tw{ lOttOmO: �0 �(1�iSUdl i3 4�K��[0 �
CWMTAT trttwrna�. �� �>ta. ¢a �0 NOLISN, US{. �CfR00UC( 111MfY11 01 DISCt01f iNl� GIIM�M9, NOT
„�iit� caiu:i a�«s�i [ictn;a iw[�u�r��iYu:a�u�ci[iyia�rii, sDjg�'
MSA STANDARD SMOP PRACTICES APPIY SCMVp1[t�� uq 6i� 11 14JCMi[�. p1 M[I fiy�f.
CODE SI'Itfi��l� �01 �6. Jaoa�te ra1U -tr/fpv►� �6F�Q COOE: w0 MIOSN AIIA. OOC.: .
--�C�lTIC4. [.� Clllf p� Ol1I
rr��ot � t� ��"�m°p�iui BaC�u �r td-22-200/.
��«� s �.�p�tE ����2-Zoo� INSTALLATION OUTLINE,
' U! � I�it[CTIpi � ( �fOJ- [K!.
ta���.��, ��,�,a S.IURMEA �� ��.too, �ODBUS, ULTIMA XE
at�p���y�SHt�fqC W41tl4/f0.1AKC
F�uTiorK � iiee l.oew�x��oi w•�t�taa�
2 M. Nt. t o.o� u�arx�uuM
s n xc. f e,eea ID.Al1AND II-15•2D01 CADD REP: i0000021203
""°�`" t'=°°� I I�000002�zo3
�t� �sA irx�a� i D YR
r���a�E�aiu►ci�a�
�SCALE: i.000
�SHEET
I OF 4
c1 PIACES)
� �2,86�
[321.721
PAIiE 115T
ITCMI MAT� Ut �n��• DESCRIPTION
NO_ MAFTr.A N0.
ALARM
CONNECTION
NORMAILY CLOSED ENERGIZED• — — — —�
�
COMMON •— — — � �`
\ �
\ �
NORMALLT CLOSED DE-ENERGIiED`— — � \ �
� � \
� �` �
� � \
� , �
� \ \
� ` \
\ ` \
�\ ,�
ALAN
CONNECTI
SEE NOTE I
r---�----
SHIEID—
CONNECTiONS
�
i- - - - -•NORMALL'f CLOSED DE-ENERGIZED
,
- - - - -COMMON
i
j i- - -NORMALl1' CL�SEC ENERGIZED
I I
1 I
� � — — — � NONMALIY CLOSED DE-ENERGIIED
I I �
I I � �--��OMMON
1 I � /
� � � � — —NORMALLY CLOSED ENENGiZED
� � � I
/
I I � / �
f �
\—!J
o❑a o0
H
'� �P�� � � � ►�o�"�u�l��
����ca
AGQ�OwLm�
PUSFBUTTON � �� C,1
� � � O
� �� �
ra �
l "1°'�'��� o�o POYVEJt .ls
��rT
LAAM 3 CONNFCTIONS
— — — — — — — — — — •NORMALIY OPEN ENERCIZED
----------•COMMON
�------�--•NORMALLY CLOSED ENEHGIZED
TROUBLE RELAY
CONNECTIONS
—POWEfl ANO
CUMMUNICATIONS
tOroNECTI0N5
.v , ��� •' L �
\'�� I�! ' �� •
�
\ O� ��
� � •• �
`,�+ -= �,�
.��Il.�..;..11�•�. . , .
LOCAI SENSOR AND
STANDARD REMOTE
SEHSOR CONNECTIONS
,l .
, i '. T��.'.�: � =-'f I!. � '�
TABLE I
TtAMiMITTCII i0�C1 CONSUM�TIOY I1-]IVpt iY�►L�I
I CONFIGURATION NAX PONER�MAX PONER�
I CATALTTIC YIR ECnEM �ITM AFtATf I�ITMOYI RUTiI
� o o -3 z.sw i.sw �
I 0 z � B.SW I B.SW
� o � 2 �w sw I
I � p 2 6W SW
� i I I 6.SW S.SW
I p 0 I 8W 7ri I
� 3 0 o iow sw
�
�U
�
L N
I I
I I
� I
I
� —, I
' I
�� •••• i
�� O Q� 'i
��iI!i� ��i1��iI�i, �
f/ I
( I
I �
�,
I I--- (BI(T-/H-!
1
��
I I
I 1
I 1
K---
i
(�IOOI210 4AC>w-----�
�-----
I
TO GROUND SCREMI �
INSIDE HOUSING
I 1 � � - - - - fAl(T}/R*1
I 1 I I
I I t I
1 I I I
I I I 1
I I I I
I I I I
I I I I
I I I I
I I I f
I I I —" f-OC1
I I I (l2 ON 21 VDC NOMINAL)
I I �--------- f�Dt)
i 1----------- I-DCl
i _ _ _ _ _ _ _ _ _ _ _ _ ��p��fl2 OA 21 VDC NOMINALI
NOTE:
I. NORNAILY OPEN PUSH BUTTON S'MITCH IOPTIONALI.
COLOR CODE
BLACK = K GREEN
BROWN = N BLUE
RED = R VIOLET
ORANGE = d GRAY
YELLOW = Y WHITE
PINH = P TAN
'. .;I1.
JI-�..�.��.�_.��:�.:.� �.JI.�.
�,i.:r,=h�;�
kt�r�4iues
Nov �e zoo4
�11[ IAIITI MILI�KFI CQ �N�� OIA�I� 1{ fM[ IIOfE11T Or MS► �W 1S �AD( !Y{IIRttL IO 1Gq ��
AUTHOAIIED � tarrotrtt u�1 suutu io txt ro:tw��c: m rtR�istia �s eu�iFD �
COUMTRT lit�l�uN�, �� i3tA. us� i0 ru0i�sr, ust, oE��oouc( IR��{M11 0� D�fCLO![ IM�f oe����c. NOT
01 /�I I�fWM�f10� CO�I�IIIb IMI�(IY IO 01M(!{ ��IMOV! TN( P�i�� SCAIE
��u�c. cacui a Ms� crcur �a r�i �wr.ciac a uncus ra �s�. n�.
MSA STANDANU SHOP PAACTIGES APPL1' sceuurtuu� �uM eu �� e[uM�n +u �uu w�.
CODE S►MBOLS �ae �o. ��eeuu r.nu ►rrRoru FG[�(1 CODI: MO �MIOSN Alq. DOC.:
�u�ncuQ w�wn urc
WJO�� � �p���� BPao�r10-22•100�.
��� � o.ap��E ��-�Z-Zoo� . INSTALLATION OUTLINE,
11� � IYl![CTlpr� /10J. f�l.
_ � �a�,���, �.�E„ S TVANER ��-�z-�oa� MODBUS, ULTIMA XE
OTMCI�Ii[ 3/[CIIIIO Ou�Ult q1YUKt
- � FAKTIDIAI f U11 ),pANINA�Ot II�Ii�7G01
- V � IL DEC. * 1.01 �KIMiM
= A �rte[c. to.o�s D.ALtAAD 11:15•2001 �CAOD REF: IOOD0021203 �SCALE: I.000
= W AM6Yt�R t"'+� I'O00002�203 SHEET
,« .« =,��„R ,� D SK
= T /�KTICC r c i i 2 OF 4
wac ran..cc�
� �,. �.a •�i�.,
� . � .� ..., , =.y�!.;-
\
app ❑ o 0 000
Nm c) �Ka um ej 0� umpcpia! I
� �3
I� . . . �
�� a Ii��ii�l/I� 3
�..� . ..� � ... .
. Por� .�s
60TAR 0;9 ,L
� I a0� I °�
SIGNI�L BOOS1
CONNECIOR
REkOVE JUMPER
CONNECTION FON
LOCAL SENSOR OR
SiANDARD REMOTE
SENSON CONNECTIONS
TA�E 2
REMOTE SENSOR POWER CONSUNPTION
fAC OR DC VEPSIONI
.�QdfiOR TYPE MAi(IAIR�IA POWEA
�oNsu�wriau
CATALYTIC 4.5 WATTS
IXlr 5 WATTS
I E-CHEM 1.5 WATTS
_ '` � •` `
� � � � �
\ � \
\ � \ � \ O
� � \ � \
\ \
SHIELD �� � �� � ��
CONNECT IONS � � � � � O �
�������
\\ � \\ �`-f�3V)---------------------- --- �
� \ � ----�GND>-------------------- e.►
� � '----------IRXI----------------
� \------------- ��r .ns�
--(T%T----------- �s� ee0
�•-------------- ---(rSYI------ m. n
I I I 1 I �
I i I I I I
I I t 1 I i
�---(COM1-�i-I-' I I �--------------ICOM)------------------�
I I i 1 I �
I I I I 1 �
i i--tSIG-F-J-� � L---------------cSIG-}-----------
------- i -7
I � I I
I I I I
I I r�SIGi}-- -----------------(SIG+►------------------�--�--
� � � I I I
I I I I I�
I I � I I�
��� o� ���
��� oqo ���
� i i Q i i i
� � � a � I I
� � � . I ��
I 1 � � o o, � I I
o i i
; ;_� oB � ---�o�,� ; , �
� -(DC-) I L_
�-- - a• � -- �---
.DO o 0 0 0
�� �
�� OC POMER
CONMEC710N5
(7-30 VDC1
CONNUNICATIONS
CONNECTIONS
I3000 FEET MAKI
�' ��: ..,... mC V9t61p�1
�,
�
� �r� ��ll
eQ �x _�—PRE-WIRED
tro .r> O SENSOfl
CONNEC710NS
��q 00 . HDO �YAb
AC POWEH
�CONNECTIONS
f85-256 VAC)
� ------cceouHo�
- -----(NEUTRAL)
� - - - - - - -(LINE)
O
;�.�
�'� .
, �� /
�■ ��
�
0
�
�' 0
u .�
COMMUNICATIOHS— �—SENSOR
COHNCC1i0N5 CONHECTOR
(3000 FEET MA111
.� -c, :��.I i•� .��
G�.3 1!.�_� la'�,'.��
_r
`� �_ll
PAAiS IISi
if[M NAIERIAL tlT1.
N0. I MAS]�TR Np�oo.l
TAO.! 4
TRAHSMITTER POWER CONSUMPTIOM
TRANSMITTER
WITHOUT RELAVS
TRANSMITTER
WITH RELAYS
0.5 WATTS
1.5 WATTS
DESCRIPTIOM
�OTE:
I. ------ INOICATES FIELD CONNECTIONS B1' QTNENS.
Z. MAKIMUM TRANSNITTER•SENSON DISTANCE IS 100 FT WITHOUi THE
SIGNAL BOOST OPTION.
3. USE OF THIS OPTION flEOUIHES THE SENSOR TO 9E POWERED IOCAILY.
REVISIOXS
NOV td 2004
,Nu o��n.n �s n� r�au�, a Y1� ��� If MA7( ,.��wi� w rou ��
AUTHOAl2ED � MIYE !1lCT1 A►�U1KR CO3 �OII�DiK( ��0 lUlJ(Cl f0 ��[ f011O�l�fi� �O IUMISNN i3 W�ULOI �
COUNiRY r�meara, n �stn. ua ro rueusn, uit. ��o�aouc[ r���tnt o� o�uiof[ iN�t oa��i�G. NOT
01 A�T I�fp��ITIQ� CMTRII[j IM[R(1� f0 Oir[�S ��1h0ut IM[ /�101 $(AL(
��nin cas[�� a■a ucvi �a �.� r��urKma a.�nnis ra rs�. p�,
MSA SiANDARD SHOP PRACTILES APPLI gxuitrt�r[t� ��(� 0�� ll !(�CMI[�. �S� AOU 4YM.
CODE S1M80L5 I� p �����+u rrn� AP1�OV�C AGCMCI C00[: 10 IMIOSM �il/. OOC.;
cnnut Q ne�w �r o�ic
WJO�� � YIMQI I4P ��'2�'2���
'� "'"" ID BRUCE ��-�Z.�oo� INSTALLATION OUTLINE,
.ua � �
. w� � �.traria� na. [r�.
TOLCAAKE! YlilEli S.TUAAEA ��-��-zoo� MODBUS, ULTIMA XE
OTXG�Ii[ S/[CIFI[D o.•LL�tr �uiud
FII�C7101�1 t ull .I.DIA�NAi01 II•12•2001
i rl OEC. t 0.01 ►W�CIWiM
� n xc. to.oas u.AIIAAD II•IS•200� CADD REF: 10000021203 ISCALE: I.000
a�suw t i �.�. D� oau,��r w. SHEET
i�Mi'ui �a aiiu i 10000021�1 111 � 3 OF 4
. �q� ta���cu
�
MODBUS '
MASTER
DEVICE
COM LINE
TERMINATION DEYICE
SEE NOTE I
DC QR AC �
POWER �
SOURCE I
TABLE 3
MARIMUM POWER CABLE LEMGTH
COMMUNICATIONS
CABLE BRANCH
(UP TO 60 FT.I
DEYICE I
MAXIMUM POWER CABLE
CONfiGURATfON LENGTH IN FEET
(tITN Mp1lMlll i1 YDC TAAMSMITTE� fW�lTl
IB AWG I� AWG 12 AWG
iri� Y�� LHfY �ABLE CABLE CABLE
(�,2 OHM tEA fi.� OHN �fR (I.! OHM IEII
IM FT.) IK t'T.1 Ill FT.1
� REIATi O�TIOM IIELATS IOtTIONf �
NO AELAYS NO RELATS NO AElA1'S
REIAri OPTION
0� 0 ( 7 1500 3500 I 1200 5500 i0000 7300
1
( o I i � i000 isoo � nso I:soo I �oo0 3soo
Ia I � I: �oa (::so I�soe 3500 �zso s000
� t 0 2' 3500 I 2150 5500 ,/2S0 I 7500 I f000
i� � � r ( z000 isoo , a�so I:soo �oao asoo
t' o ' i l esoe , nso I�soa �aoo � s000 �oos
� � o � o � t000 ( isoa ( t�so ' :soo � �1so asoo
� il ���• ► � �ii �:il� i:i/s
COMMUNICATIONS CABLE TRUNK
(UP TO 3000 fT.)
/
��
LOCAL DC OR AC I
POWER SOURCE 1
ITEM MATiNIA1 �OT1•
NQ. ( NASTER M0. d76�N3,�
�
PARTE'.liSi . ...
DESCRiPT10N
_I
� �COM LINE
TERMINATION DEVICE
5EE NOTE I
/��� �
`�%
r
�
�
\
COMMUNICATIONS AND
POWER CA8lE5
IUP TO 100 fT,)
�
�COMMUNtCATIONS CABLE
(UP TO 3000 FT. WITH
SIGNAL BQOST OPTIONI
LOCAL OC OR AC �
PQWER SOl1RCE
0
NOTE:
I. IINE TERMINATION OENICE MUST NATCN CON LINE
fTrPICALLY 120 OHMSD.
2. TYPICAI R51E5 CONMUNICATIONS iNIRING SCHENE
IS 3 WINE CABIE, 22dWG, IABELED U i Tt/pF,
I8) T-/R- ANO (C) COMMON.
�
REVISIONS ` �
POlOV 16 2004 �
AuiNOAIZC� --- �i�[ iWttr �nu�Kc� coI'•�s o�"��� �4 r�c r�acur a w� ►.e �s �uot .r►�ueu w ra ��
COUNTRI ` �D���DEKE AMO SYOJ[Ct io i�t ra�pnw�: w r[�•�ss�a is c�.ricol �
►tTtf1YNM, fF Ift7�, YM �0 1UIUtN, W(, 1[I�ODUCF. ����SMIi pt DIfCIOiC INlf DNA�ilt6, NOT
OR q! �Yf WM�i10� CO�IAI�E� IN[�(iM 10 OINp{ �ItvOYT fME ��Id SCALE
MSA STANDARO SHOP PRACTICES APPL1' ����� C01s[�r a �u ucv� ra i�c w�wMiuu a unati �a �7i- D�.
st•aurn.E�c� wuM ot� �� eucMtn, Mu �rn wM,
WDE SIMBOlS I�p� 10���2N►Wl� �1N11pVA1 �GEMti CODE: w0 IM�03N �Ilt�. pOC.: .
UI11C1�L � OII� It NTf
.,� � A ■� 8P 10-22-2001
'p'�"' `�°"'" INSTALLATION OUTLINE,
""�' � D.BIIU�E 11•12•2001
IN i IMilCLTIO�� I 10J. [M�.
10lEtMCE: YREt{ iS.TURNEA ��-,�-�oo� �ODBUS, ULTlMA XE
OTN[dli[3�CCIfI[9 w�UtiNiu�uCt
rutnorAt 3vu J.DAMMXAApT It-It4011
i K DEC. t L01 +�wKnu�
7 n. DEt. ta.o�s D.ALMAR9 II•IS-200/ CADD HEF: 10000021203 �SCALE: I.000
��eut�� t��,�, �y oau.r�r m. SHEET
ii�C�`wciaa,Kr�i ° D JI� I�0000O����i I� ( 4 OF 4
9
DEVICE 2
New features & EXtreme design , now with HART Protocol and DuraSource ™ Technology .
----------X Factors----------
• OuraSource Technology prov idin g extended
infrared sensor li fe
• HART fi eld commun ications protocol option for
improved asset management.
• Patented sensor disconnect -under-powe r allo ws sensor
change-out without declass ify ing a hazardous area
• Interchangeable smart sensors : pre-calibrated.
in sta llat io n-ready sensor modules, field-replaceable
with out tools
• New sensor type quick recogn iti on and reconfigurat ion
of alarm and re lay sett ings
• LCD conven iently alternates between sensor reading
an d gas type plus scro ll ing messag ing for ongoing
diagnostic checks
• Single -b oard des ign for ultimate re liab ility and
serv iceabi li ty
The Safety Company
Ultima® X Series Gas Monitors
Ultimate Features ... EXtreme Design
Ultima XE Gas Monitor -Explosion-Proof,
Stainless Steel Gas Detector with Display
The Ultima XE Gas Mon itor offe rs:
• Explosion-proof 316 sta inless steel
• Mul ti ple-entry mounting enc losure
• Type 4X, IP66
Ultima XA Gas Monitor -Water-and Corrosion-
Resistant. All-Purpose, Polycarbonate Gas Detector
with Display
The Ult ima XA Gas Monitor offers :
• Nema 4X rat ing
• light weight (only 1.5 lbs)
Ultima XIR Gas Monitor -Explosion-Proof,
Stainless Steel, Infrared Gas Detector with Display
The Ultima XIA Gas Moni tor offers :
• DuraSource Technology for improved IR sensor life
• 316 Stainless steel
• Multiple -entry mounting enclosure
• Fast response ti me
• Opera ti on based on dua l-wave length , heated-opt ics techno logy,
prov iding def init ive compensation for temperatu re. humidity
and ag ing effects
• IA technology wh ich offe rs excel lent long -term stab ility, eli minat ing
the need for fr equent calibrations
• A sintered-d isk-free des ign for opt imum perfo rm ance in harsh
environments
• Na -gas calibrat ion . On ly a zero adjustment is required for ful l
cali brat ion .
• Type 4X. IP 66
Tht Saftty Company
Ultima® X Series Gas Monitors
With a number of new and exciting features, Ultima X Series Gas Monitors
are suitable for indoor and outdoor applications in virtually any type of
industry including offshore, refineries, chemical and petrochemical facilities,
steel mills, water and wastewater plants, mining, and general industry.
MSA 's U/tima X Series Gas
Monitors are microprocessor-based
transmitters, engineered with the
customer in mind.
Ulti ma X Ser ies Gas Mon itors. avai lab le in either
sta inless steel or po lycarbonate enclosure housings.
prov ide continuous monitor ing of combust ible and
toxic gases , and oxygen de ficiency. Insta ll ation is both
simple and flex ible . Ultima X Series Gas Monitors are
suitable for indoor and outdoor applicat ions in
virt ually any type of industry inc luding off shore.
refiner ies , chemical and petrochem ical facilities . steel
mills . water and wastewater plants . mining, and
general industry.
MSA 's Ult ima X Ser ies Gas Mon itors. engineered
using microprocessor -based technology and des igned
for var ied gas de tect ion needs . prov ide HART
protocol. Ultima XIA and XI Gas Mon itors offer
DuraSource Techno logy, a new and improved light
source prov idi ng extended sensor life .
HART Field Communicat ions Protoco l provides
increased sensor da ta. part of cost -effec t ive asse t
management. HART also prov ides conven ient setup.
cal ibrat ion . and diagnosti cs . Cal ibrate . set up or
perform diagnostics with HART from any point
along the 4-20mA line . HART all ows for exist ing
component insta ll and wiri ng to be used . re ducing
installation cos ts.
Installation and Operation
Installation is both simple and flexible . Ultima X Series
Gas Mon it ors :
• Operate in diffus ion mode. with factory-calibrated sensors
ready to perform immed iately aft er installation
• Offer HART upgrade of ex ist ing un its via replacement
PCBA
• Are available for remote sensing applicat ions . where
installations requ ire the sensor to be separated from
electronics
• Can operate completely stand -alone with a large LCD
display, optional qu ick -check LEDs and four relay outputs
(three alarm and one faultl . or connected with a standard
4-20mA output to a control system (PLC . DCS. etc)
• Have an adjustable full -scale range
• Prov ide for easy installation with the two-piece.
fi eld-wiring connectors
Calibration
As with all gas monitors . Ultima X Series Gas Moni tors must
be calibrated per iod ically with the gas of interest to ensure
proper operat ion . The ca libration process offe rs:
• Automat ic adjustments
• Date stamp ing
• Ca li bration instruct ions displayed on mon itor
• Se lectable lockout of output signal during cal ibrat ion
• Abil ity to calibra te at the insta ll at ion locat ion or remotely
wit hout sys tems interrupt ion
• Accessory ca li brator, controller. or pushbutton for
cal ibrati on ini ti at ion
Ultima X3® Technology
[ X to the Power of 3 ]
Up to 3000 ft .
. . .
Ultima X3 Technology for Ultima X Series Gas Monitors features :
• Multi-sensing
• Up to 31 monitors with up to 3 sensors inputted per monitor for 93-sensor total
• Combinat ion of electrochemical-. catalytic-. and infrared-type sensors is available
• Scro lling disp lay-moni tor scrolls through type and read ing for all attached sensors
• Operation of monitor as network slave dev ice
• Signal boost
• Each sensor is remotely observable up -to 3000ft. from the monitor
• Universal 85-256VAC or 8-30VDC power supply avai lable at remo te condulet
• ModBUS RTU output
• Industry-standard format
• RS -485 half -duplex commun icat ion interface
• PLC/OCS systems integration
PLC/DCS
[ProSoft· Tested]
Connect the X3 unit to PLC/DCS
control systems . X3 technology
is ProSoft-certified . It has been
tested and found to be
compatible with Allen-Bradley
PLC/ModBUS connectiv ity by
ProSoft Technology, Inc.
Accessories
Power Supply
Ul tim a X Ser ies exte rn al power supply can power sensors remo tely; one re mote powe r
supp ly modu le can power :
• up to 5 electrochemical or oxygen se nsors
• up to 3 combust ible sensors
• internal power supply opt ion also ava ilable
Pushbutton
Pu shbutton feature lets users view var ious funct ions without ca li brator :
• alarm acknow ledge
• zero cal ibra ti on ini tializati on
• SPAN ca li brat ion init iali za ti on
• iCAL ca li brat ion initi alizat ion
• cal ibration abort
Duct-Mount Kit
Duct-mount Kit all ows the user to monitor air within ductwork usi ng the Ul ti ma XE, XA
or XIA sensor. Qu ick-disconnect f itt ing enables ca li brat ion gas to reach sensors without
duct-mounted sensor remova l.
Pump
Samp li ng pumps br ing remote samples to sensors . Sampling modules are ava ilab le in
GP and XP versions of aspirated and pumped modules .
Calibrator
Ulti ma Moni t or Ca li brator offers the industry's simplest ca li bration method , a three -button
dev ice allowing Ultima X Ser ies cal ibrat ion and address changes .
Controller
Ul ti ma Mon itor Contro ll er provides comp lete access to all features through its full -funct ion
keypad : alarm level set , span gas va lue changes , and last calibrat ion date display.
HART Port
Intrin sica ll y safe co nnectio n fo r a HAR T comm unica tor.
~
id
I
:11-1 I . I ..
Th~ Safety Company
Gases
Acetylene IR-0-2.5%
Ammonia-0-50 PPM
Ammonia-0-100 PPM
Ammonia-0-1000 PPM
Arsine-0-2 PPM
Bromine-0-5 PPM
Sptciflc1tion1 (for Ultim1 XE. Ultlm1 XA and Ultlma XIR)
G11 Typ11 XE. xA Com bus1161es. oxygen <1nd toxics
XIA Cc mbust ibles : O· 100%LEL
Temp1ratur1 Rana, -WC to +s o0c l-40°F to+ 140°F)
Carbon Dioxide IR· 0-0 .5%
Carbon Dioxide IR-0-2%
Carbon Dioxide IR· 0-5%
Carbon Monoxide-0-100 PPM
Carbon Monoxide-0-500 PPM
Carbon Monoxide-0-1000 PPM
Chlor ine-0-5 PPM
Chlorine-0-10 PPM
Chlorine-0-20 PPM
Chlorine Dioxide-0-3 PPM
IR Combustible Gas -Methane-
0-100% LEL
IR Combustible Gas· Non-Methane-
0-100% LEL
Combustible Gas-0-100% LEL Natural
Gas and H•
Combustible Gas-0-100% LEL
Petroleum Vapors
Combustible Gas-0-100% Solvents
Diborane-0-50 PPM
Ethylene Oxide-0-10 PPM
Fluorine-0-5 PPM
Hydrogen Fluoride-0-10 PPM
Hydrogen-0-1000 PPM
Hydrogen Chloride-0-50 PPM
Hydrogen Cyanide-0-50 PPM
Hydrogen Sulfide-0-10 PPM
Hydrogen Sulfide-0-50 PPM
Hydrogen Sulfide-0-100 PPM
Hydrogen Sulfide-0-500 PPM
Nitric Oxide-0-100 PPM
Nitrogen Dioxide-0-10 PPM
Oxygen-0-10% -compensated
Oxygen-0-25% -compensated
Oxygen -C01 Tolerant-0-25%
Oxygen -Solvent Tolerant-0-25%
Phosgene-0-1 %
Phosphine-0-2 PPM
Silane-0-25 PPM
Sulfur Dioxide-0-25 PPM
Sulfur Dioxide-0-100 PPM
rt
Zero Dr ift
Sp an Dr ift
Noise
Accuracy
Repe ata bility
Lin earity
Rnpons1Tlmn
T20 O, & toxics
TSO o, & toxics
r 50 com bust.
f90 combust.
T90 combust
Humidity
Sanso, Ufi
Oxygen & Tox ics
Combust
Combust.
Warranty
Power Input
Wiring Requlremenu
Com bust.
Oxyg en & Toxics
Oxyg en & Toxics
S1gnel Output
R,la Contact Rating
Housing ntr,u
Pfiysical
Approval Ratings
XE. XA
XIA
XE, XA
XE. XA . XIA
XE.XA
XIA
XE,XA
XE. XA. XIA
XE.XA
XE,XA
XE.XA
XE .XA
XE.XA
XIA
XE.xA
XIA
XE .XA
XE. XA
XIA
XE. xA
XE.XA
XIA
XE .XA .XIR
XE .XA
XE.XA
XE.xA
XE. XA. XIA
XA
XE
XA
XIA
Olt1ma X Series
XA
Ultima X Series
Ultima X Ser ies
(n ot including XJ
Techn ology or Hart)
( fy pical -range for some gases may differl
<5%/year. typ ical
.t 2%/year. typ ical
<1 0%/year. ~ical
<1 % Full Sea
.t I %Full Scale or 2ppm. typ ical
±2%Full Scale or 2ppm . (0,, CO)
t2%Full Scale (~50% LEL)
.t 3%Full Scale (<50% LEL combust ibles)
t 5%Full Scale (>50% LEL combust ibles)
t 10%Full Sca le or 2ppm, (non -CO tox ics)
<12 seconds (typically 6 secondsl
<3 0 seconds (typically 12 seconds)
<8 se conds
<3 0 seconds
<2 seconds
15%-95% RH , mn-co ndensmg
0%-95% AH , non-condensing
2 years typical
3 ye ars typical
10 years typical
1 year XE. XA : 2 years XIR; 10 years XIA . XI (IA SOl.ft:e on ly)
1-JOVDC (oxygen and toxics)
7-JOVOC@ 450mA maximum (combustibles)
7-JOVDC @7SOmA maximum (combustibles)
3-wire
2-wire: no LEDs or relays
3-wire : LEDs and/or relays
4-20mA 2-wire current sink
4·20mA 3-wire current source
our conduit entnes. 4 or m
One entJy
316 Stainless Steel; 10 416s (4.7kg)
6.3'W x 3.9'0 x 10.J'L (160 x 99 x 261mm)
Polycarbonate; 1.51bs (0 .68kg)
5.1 "W x 2.9"0 x 9.4'L (130 x 76 x 239mml
316 Stainless Steel: 10 .Blbs (4 . 9kg)
12.6'W x 3.9'0 x 5.7'L (320 x 99 x 144mml
OsAJt1n1d1
cFMus. cULu,. CSA
Class I, Div. 1 and 2. Groups A. B. C. D
Class II. Div. 1. Groups F & G. Class Ill
Type 4X , 11'66
AN SI/ISA 12 13 .01
CSA C22 .2 No .152
Class I. Div. 1. Groups A.B .C.O
CSA C22 .2 No . 152
Class I, Div. 1, Groups B.C .D (XIAI
Nema 4X rat ing
Europe
CE Low Voltage/EMC/ATEX. EN 60079 · 1
@1 1 2G Exd 11C T4
IP66
SIL C111ific11ion
SIL 2@ HFT ={] (Oxygen . catalytic co mbust ible and IA)
SIL 1 @ HFT = 0: SIL 2@ HFT = 1 (Toxic)
Nott: Th it Bull eti n contain, only a gentrol
description oftha product, shown . While u111
ana p1rform1nc1 capabiliti u art desc ri bed,
und er no circumstances sha ll th, producll bt
used by untrained or unqua lifitd individua ls and
not until tha product instru ction , includ in g any
warn ings or cautions providad hava been
th oroughly read and un derstood . Only they
cont ain th t co mplete and
Corpor91aHN .........
P.O. Box 42!, Pittsburgh, PA
1mousA
MIAM11ice
?hon , 52 -55 21 22 mo
Offlc11 and rtpr111ntativ11 wor1dwld1
Fo r furth er info rmation:
concem ing proper use and 1: , detailed info""ation ®~
cart ofthtu products. \•,. -
ID 07-2051-MC / April 2009
~ MIA-Priot..i It U.U.
Phone 412-9'7 ·3000
www.MIAHt.o..,
U.L Cu11omw l,mo1 C1-
Phon1 1·!!00-MSA -I NST
Fu 1-724·771 ·32 IIO
MIAClfttft
Phan, 1-aao-m -2222
Fax 1-Bll0 -951 -0J!III
Fu 52·55 5359 4330
MIAl0-11i1ul
Pll ont 412-967-3354
FAX 412 ·967 ·34S1
The Safety Company
,ARK
Contractin g
S e 1· \.' i C c= S
Re: Village Creek Bar Screen & Junction Box Rehab
-Gas Detectors Change Order
Ark is requesting an addit ional 6 weeks for the installation of the Gas Detectors.
Todd Smith , PM