June 5, 2025
City of Fort Worth
Jesica McEachern
200 Texas Street
Fort Worth, TX 76102
Re: Northside I II — Phase 11154 inch Water Transmission Main
City of Fort Worth CPN#104940-3
Dear Jesica McEachern:
It is Atmos Energy Corporation's (Atmos Energy) understanding that the City of Fort Worth
Water Department is proposing to install a water line crossing for the purpose of transmission
use per plans provided by Kimley Horn for the City of Fort Worth. The project's utility crossing
will cross Atmos Energy's 10" steel Transmission gas line and existing easement as shown in
the attached drawings and included exhibits.
Atmos Energy has determined that the construction of the 54" water main line in 78" steel casing
will not present a significant conflict given a minimum clearance of 9.8' is achieved based on the
given design criteria/information. Atmos Energy will not object to the construction of the proposed
utility crossing project, provided that the following additional criteria are followed:
Please contact Texas 811 for line locates 72 hours prior to excavation. A representative
with the Atmos Energy Damage Prevention team will then contact you to schedule an
onsite meeting in advance of excavation activities within the vicinity of Atmos Energy
facilities.
Atmos Energy's facilities have been determined to currently be approximately 5' (feet)
deep with respect to existing grade for the 10" steel gas Transmission line and 2' (feet)
deep with respect to existing grade for the 18" steel gas Transmission line at the
proposed water line crossing with a vertical clearance of at least 9.8' according to plans
provided. No additional cover will be allowed to be removed. The minimum clearance of
9.8' will be maintained during the utility crossing of the gas line during construction. If
sinking of construction equipment begins due to wet weather or compaction, then all
work over the pipeline location will cease until it can be worked without sinkage to avoid
damage to the pipelines and maintain depths of cover stated above. During
construction and final finished depths of cover will not be less than 5' of soil over the
pipeline. An Atmos Energy Representative must be on site during any excavation over
the pipeline.
• Once Atmos' pipe is visually identified through the potholing referenced above,
mechanized excavation may be utilized up to 3 feet of any direction of the circumference
of the pipe.
• Within 3 feet of any direction of the circumference of the pipe, any excavation must be
done by vacuum excavation or hand digging.
OFFICIAL RECORD
CITY SECRETARY
FT. WORTH, TX
Docusign Envelope ID: 69A67DE5-4F28-4CC5-90E6-FD4140819E75
City of Fort Worth continued
• At no time may cover be removed from the easement or right-of-way or over the
pipeline other than what has already been approved without the prior written approval
of Atmos Energy.
• Atmos Energy's line will be protected from washing and erosion during construction
and/or repairs.
• Equipment, materials, or excess dirt will not be stored on top of the pipeline during
construction without the prior written approval of Atmos Energy.
• Notification to Atmos must be made prior to crossing our pipelines with construction
equipment to allow time for load calculations to be performed. The curb weight and
type of equipment will be required to perform calculations. Load isolation structures
may be required at the requestor's expense.
• Atmos Energy will not be responsible for damage to any allowed encroachments.
• Atmos Energy reserves the right for future uses of this easement (if an easement
exists), including but not limited to, ingress and egress, reconstructing, removing,
relocating, maintaining, operating, etc., of any of its facilities.
• Impact/conflict analysis was based on and is limited to any drawings and documents
submitted to Atmos Energy, as referenced above AND changes in scope of work
contained in these drawings must be resubmitted for re -review and approval.
• If construction equipment is to cross any Atmos Energy pipeline, the City of Fort Worth,
or contractor equivalent, shall submit a list of equipment (with weights) to Atmos
Energy personnel for weight distribution loading review prior to construction.
Docusign Envelope ID: 69A67DE5-4F28-4CC5-90E6-FD4140819E75
City of Fort Worth continued
Please:
1. Sign and fill out the information below which signifies that you agree to the terms
of this letter.
2. Return this signed scanned document to Betty. Daugherty@atmosenergy.com prior
to your construction.
For further assistance please call Talon Tucker at 469-841-2598.
Sincerely,
DocuSigned by:
E230BAC95AE9450...
Saul Balcazar
Engineering Manager
Atmos Energy Corporation
901 Altamesa Blvd signature: �
Fort Worth, TX 76134
Name: Jesica McEachern
cc: Talon Tucker
Betty Daugherty Company: City of Fort Worth
Title: Assistant City Manager
Date: 06/18/2025
EXISTING I6" WATER LINE
a '(EXISTING 35' GAS EASEMENT
INST.Ao.0zD3oozlsa
°\, cEXISTNG 16" GAS LINE BY ENLINK
`MIDSTREAM SERVICES. LLC
_ -'MIDSTREAM SERVICES. LLC
EXISTING FENCE
\\ SEE NOTE 4
-25'X20'
\ORE PIT /
<NORTHSIDE III
54" WATERS-20'x20'
TRANSMISSIONONE
MAIN PHASE 2THy(SEEN NOTE'IT
0+00
(BY OERS) :
BEGIN 54" WATER LINE
/ (SEPARATE CONTRACT -
/ CPN 104940-2, 8274)
INSTALL
(1) FLANGE CONNECTION W/ Pa
IB-ON FLANGE ASSEMBLY
RE: D146/16 / ^
SEE NOTE 3 )
N: 7021923.]4
E.230195J.92
STA: 0+13 F�
END 54" WATER CARRIER\ /
PIPE IN 78" STEB_ CASING,\\
OR 78" TUNNEL LINER PLATE \ \
BY OTHER THAN OPEN CUT'\\\\
RE: D106M D107M D108M D109M 17�\
STA: D+81 I
BEGIN 54" WATER CARRIER
4 EL� ¢
PIPE IN JB" STEEL CASING i
BY OTHER THAN OPEN CUT
RE- ODBM, D1D7M, ODBM, D109M/17
N. 7021980.52
E:2302015.67
STA: D+B9 68
INSTALL:
¢
() ROLLED 4].10' ROD BEND e
I
1
Ni = 44.97' RT I''I
NV = 15.J8' UP
E:23D 986.61
E:2302021 BJ
PROPOSED 45' / ¢
TEMPORARY
CONSTRUCTION • II
EASEMENT ¢ /
-PROPOSED lGI I
E:2301987.19�'.� STA' 1+40
INSTALL (1) 12" DUAL AIR REIN=ASE
VALVE W/ EXISTING 1O" GAS
AND PROTECTIVE FRAME \ 1 LINE BY ATIM
RE: 2/20 \ \ EXISTING 1B" ABANDONED �� q
N:]021 72.18 GAS LINE BY A1M05 /y NOR
E: 23020]2.18 r -
JOINT RESTRAINT LENGTH
(A, C303):
845 / LfD SEEDIP^)
D EN B BACK-1�J
E 1, D Dl Y 1, U75, (.) "Vl
A EXISTING 16" 1 �
LJ E STING 10
- -ENLINK G85 LINE -ATM( CAS LINE
840 (T/P = 835.69') (ELECTRONIC
A 1 30RE 0'1 i DEP1H. 83].34')
O EXISTING LINE
30RE IT 1
ENLINCT�pK GAS LINE \I _
BORE PIT
835 I I
I
830-•2o'X2D'
BORE PIT
I I I
I I
825
IF
9 I
820 I —
?C +
PRROBED
NORTHSIDE III
- PHASE II C200
54" WATER
i 815 TRANSMISSION fJ
a MAIIM BY
- OTHERS. —[
- X-28274) /
810
Ilk
2020
805
al
1 I
—
_-�>
d r OFF fa.
801 �ma . Ni3Emxcl Nlm3%II"
x O+Oo 1+00 z 2+00
EXISTING 16' GAS EASEMENT
INST No.Dz03ooz1 sa TN' MARD"
AIWT�A` TOR su"B
END 54" WATER CARRIER Irvs
rvoaooeauo
oo
PIPE IN 75" STEEL CASING
OR 78" TUNNEL LINER PLATE
BY OTHER THAN OPEN CUT
RE: D106M. D10JM, D108M, D109M/17
N: 7021985.48
/
E'230215418
M
STA. 2+71
q
\\% _\ SFFHCAA'F
PIPENIN 78WATER STEELCARRIERCASING
OR 7E' TUNNEL LINER PLATES�/yFFr3Tq
BY OTHER THAN OPEN CUT
/ / ••/I/fir J0 Op
RE: 3106M, D107M, D10BM, D109M/17
N:]0219851]
E. 2302203.15
/ 12,51
STA. 2+90.14
/
INSTALL:
(1) 47.76' HORIZ.
NH = 4J.J6' LT
N: ]02198532
BEND
PROPOSED 20' / (/
TEMPORARY
E.2302222.33
/
CONSTRUCTION
EASEMENT
PROPOSED T / /
--------
PERMANENT /
EASEMENT A /
/ I /
_---_---_--- I /
4+00, ��C\ / J
STA: 9 A,-.
INSTALL
\ (1) 23 B4- HORIZ BEND
N3 = 23 B4' RT
\ E.2302305.6'
TIDE III 54-INCH WATER
MAIN
STA 01 TO STA. 6+10
Sq �7 2
/ / N15
PROPOSEDIt LSI OF 54—INpi
WATER TRANSMISSION PAIN A
STA: 4+91.40
INSTALL
/45.02' BEND
AH
Ni = 45.02' LT LT
/ N:7D22115.11
/ E:230�369.3J
TA: 4+81.62
INSTALL:
/ AH 45.00' 'LT BEND
)SET Ni _ 45.5.9 LT
MAIN N: J022105.94
MAIN E:2}02385 94
LEGEND
NOTES
NNRE BONDS RANCH
ROAD PAVING (BY OTHERS)
1. ALL REFERENCED DETAILS SHOULD BE CITY OF FORT WORTH
STANDARD DETAILS UNLESS NOTED OTHERWISE
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL
UTILITIES WHETHER PUBLIC OR PRIVATE PRIOR TO EXCAVATOR.
THE INFORMATION AND DATA SHOWN WITH RESPECT TO
MAP # 2024-460
EXISTING UNDERGROUND FACILITIES AT OR CONTIGUOUS TO THE
SITE IS APPROXIMATE AND BASED ON INFORMATION FURNISHED
BY THE OWNERS OF SUCH UNDERGROUND FACILITIES OR ON
PHYSICAL APPURTENANCES OBSERVED IN THE FIELD THE
OWNER AND ENGINEER SHALL NOT BE RESPONSIBLE FOR THE
ACCURACY OR COMPLETENESS OF ANY SUCH INFORMATION OR
DATA THE CONTRACTOR SHALL HAVE FULL RESPONSIBILITY
FOR RENEWING AND CHECKING ALL SUCH INFORMATION AND
DATA, FOR LOCATING ALL UNDERGROUND FACILITIES, FOR
COORDINATION OF THE WORK WITH THE OWNERS OF SUCH
UNDERGROUND FACILITIES DURING CONSTRUCTION, AND FOR ME
MAP N 2024-456
SAFETY AND PROTECTION THEREOF AND REPAIRING ANY
DAMAGE THERETO RESULTING FROM THE WORK THE COST OF
ALL WILL HAVE BEEN CONSIDERED AS HAVING BEEN INCLUDED
IN ME CONTRACT PRICE ME CONTRACTOR SHALL NOTIFY ANY
SHEET NOTES:
1. CONTRACTOR SHALL REPAIR EXISTING DITCH
AFFECTED UTILITY COMPANIES OR AGENCIES IN WRITING AT
LEAST 45 HOURS PRIOR TO CONSTRUCTION.
WARNING
ALONG BONDS RANCH ROAD TO EXISTING
CONDITIONS. THE COST OF REPAIRS SHALL BE
THE LOCATION AND DIMENSIONS 0- E%STING L-I ITIES SHOWN ON
THE PLANS ARE APPROXIMATE AND W RE OBTAINED FROM LTLITY
CONSIDERED SUBSIDIARY TO THE COST OF THE
PROJECT.
2. SHALL CENTER GAS LINES ON A
COMPANY RECORDS. IT 15 THE CONTRACTOR'S SOLE RESPONSIBILITY
TO VERIFY LOCATION. DEPTH AND DIMENSION OF EXISTING UTILITIES
PRIOR TO CONSTRUCTION
SCONTRAEGMENT 0
SEGMENT OF PIPE. PIPE JOINTS SHALL NOT BE
PLACED UNDER GAS CROSSINGS
3. FOR THE CONNECTION TIT NGONTRDE III,
WARNING. LNDERGROUND UTILITIES IN ME AREA OF CONSTRUCTION.
CONTACT THE FOLLOWING OFFICES AT LEAST 48 HOURS PRIOR TO
PHASE II AI
WATER MAIN, THE CONTRACTOR
EXCAVATION AT THIS LOCATION
TA
SHALL INSTALL TEMPORARY BLIND FLANGE.
TEST WATER LINE. REMOVE THE EXISTING
BIGMSS(800) 344-83]]
TUCKER
NICKER TALON A11J05 CAS ((469))) 841-2598
BOND FLANGE, AND CONNECT WITH A
FRIGHT ENUNA MIDSTREAM (337) 25]-3223
LAT
FLANGE CONNECTION WITH FLANGE ISOLATION
ASSEMBLY AND INSTALL ISOLATION JOINT TEST
JAMESNICHOLAS
NAMES KAPKA ENERGY TRANSFER ((817)) 240-0506
CHAD EAD ONCOR 817 215-6288
( )
STATION X (SEE SHEET
CITY OF FORT WORTH WATER DEPARTMENT (Bi J) B]i-6296
F FOR
AIR
4. CONTRACTOR SHALL REPAIR OR REPLACE
EXISTING BARBED WIRE FENCE TO EXISTING
BENCHMARKS
CONDITIONS.
5. CONTRACTOR SHALL MAINTAIN A MINIMUM
By-
CLEARANCE OF 5' FROM THE PROPOSED BORE
PIT TO THE EXISTING 16" WATER DNE ALONG
BONGS RANCH ROAD.
AN %-CUT WAS SET IN THE VDWESTSIDEALSO ROW AND THE EDGE OF
ALSO BEING GIN SOUTHEAST FROM
PAVME GMENTET LI N SAGINAW' BOX
ME CENTERLINE OF A J'X2' BOX CULVERT BEGINNING AT THE
INTERSECTION OF BONDS RANCH RD AND N SAGINAW BLED, I
NORTHWEST APPROXIMATELY 968' ALONG THE CENTER LINE OF N.
SAGINAW RD AT A RIGHT ANGLE FROM THE CENTER LINE. GO
SOUTHWEST APPROXIMATELY 24' FROM THE CENTERLINE TO AN
— - - X-CIT
Jr+ EXISTING 18" ABANDONED 8� am"a
ATMOS GAS LINE �qFlJ AN X-CUT WAS SET ON THE WESTSIDE R.0 W AND THE EDGE OF
U1Jf6 PAVEMENT OF N SAGINAW BLVD ALSO BEING 17' NORTHWEST FROM
__ THE CENTERLINE OF A 3'X2' BOX CULVERT BEGINNING AT THE
�r F
`_ -INTERSECTION OF BONDS RANCH RD AND N. SAGINAW BLVD, GO
_NORTHWEST APPROXIMATELY 2060' ALONG THE CENTER LLNE OF N.
ISTING - SAGINAW BLVD Ai A RIGHT ANGLE FROM ME CENTER THE, GO
OUND 840 SOUTHWEST APPROXIMATELY 20' FROM THE CENTERLINE TO AN
RROPOSED 24" X-CUT.
I �NSIV WATER LINE SHEET LD7�F:.
%.-25'x20'(SEE P
/ BORE PIT I '+IEETS)RT 1 RESTRAINED PIPE LENGTH SHOWN IS �AZ55/8 IRON ROD WITH CAP STAMPED "TAP RANDOM" SET ON THE
P F
F� f�'00
' APPROXIMATE AND BASED ON C303 NORTHWEST SIDE OF THE INTERSECTION BETWEEN PEDEN RD AND
BAR WRAPPED CONCRETE CYLINDER ROSINESS HIGHWAY 287. APPROXIMATELY 429' SW OF A LLGHi
PIPE FOR BIDDING PURPOSES. 835 POLE ON THE NORTHWEST SIDE OF SAD INTERSECTON.
CONTRACTOR SHALL SUBMIT
CALCULATIONS FOR RESTRAINT
LENGTHS REQUIRED BASED ON
ACTUAL VALUES FOR SELECTED PIPE
WITH SHOP
DRAWINGS.
_ 830
I_
825
820
I_
I_
_ 615
I_
I_
I_
I_
810
I_
F 805
+� o —
m _ Sol
H m 4+00 5+00 6+00 7+00
vROFI_e 4so; AH E:
0 _ AD 80 120 P [
SCALE1" = 40' Dp E pY a
REV. COMMENTS BY DATE
I I
I I
11yyy\yyy��� I
CITY OF FORT WORTH, TEXAS
WATER DEPARTMENT
PART 2:
NORTHSIDE III - PHASE III
544NCH WATER TRANSMISSION MAIN
PROPOSED 54-INCH WATER MAIN
STA. 0+00 - 7+00
Kimlex»)Horn
ml a."r sI. uW x aMM un Tx lrroa finaae-een
DESIGN: SOW DATE SCALE PROJECT NO. SHEET
DRAWN RAS MAY 1"=4D'H CITY PROJECT
CHECKED: JRT 2025 1"-4'V MI04940-3
Letter of No Objection
PROJECT NAME: Northside III - Phase II 54 Inch. (CPN: 104940-2)
ADDITIONAL ROUTING SIGNATURES
CITY OF FORT WORTH
CONTRACT COMPLIANCE MANAGER:
By signing, I acknowledge that I am the person responsible for the monitoring and
administration of this contract, including ensuring all performance and reporting requirements.
By: �� a.2t /)C
Preeti KC, P.E.
Sr. Project Manager
Email: Preeti.KC@fortworthtexas.gov
APPROVAL RECOMMENDED:
By: Christopher H rder (Jun 13, 2025 13:09 CDT)
Chris Harder, P.E., Director
Water Department
Email: Chris.Harder@fortworthtexas.gov
CONTRACT AUTHORIZATION
M&C: N/A
Date Approved: N/A
APPROVED AS TO FORM AND LEGALITY:
By: Douglas Black (Jun 13, 202517:53 CDT)
Douglas W. Black
Senior Assistant City Attorney
Email: Douglas.Black@fortworthtexas.gov
FORM 1295: N/A
ATTEST AS TO CITY MANAGER SIGNATURE:
Fopr.yd°aa
By.
ems°° 0
Jannette Goodall
City Secretary
a,°°aaa5a
Email: Jannette.Goodall@fortworthtexas.gov
OFFICIAL RECORD
CITY SECRETARY
FT. WORTH, TX