HomeMy WebLinkAboutContract 29731-(1 of 2) EXECUTED COPY CITY SECRETARY CONTRACT NO. CITY OF FORT WORTH, TEXAS WATER DEPARTMENT SPECIFICATIONS AND CONTRACT DOCUMENTS FOR CONSTRUCTION OF ROLLING HILLS WATER TREATMENT PLANT 40MGD PLANT EXPANSION - PHASE 4 NEW HIGH SERVICE PUMP STATION PROJECT No. PW77-060770510050 2003 FORTWORTH WATER MIKE MONCRIEF GARY JACKSON MAYOR CITY MANAGER ti DALE FISSELER,P.E. CHARLY ANGADICHERIL DIRECTOR, WATER DEPARTMENT ASSISTANT DIRECTOR, WATER DEPARTMENT S. FRANK CRUMB,P.E. ASSISTANT DIRECTOR, WATER DEPARTMENT Freese and Nichols CDM00507 l CITY OF FORT WORTH, TEXAS WATER DEPARTMENT SPECIFICATIONS AND CONTRACT DOCUMENTS FOR CONSTRUCTION OF ROLLING HILLS WATER TREATMENT PLANT 40MGD PLANT EXPANSION - PHASE 4 NEW HIGH SERVICE PUMP STATION PROJECT No. PW77-060770510050 2003 FORTWORTH WATER MIKE MONCRIEF GARY JACKSON MAYOR C=AIANAGER DALE FISSELER, P.E. CHARLY ANGADICHERIL DIRECTOR, WATER DEPARTMENT ASSISTANT DIRECTOR, WATER DEPARTMENT S. FRANK CRUMB,P.E. ASSISTANT DIRECTOR, WATER DEPARTMENT `..1t11�tttk "5�,E•QFyrF�t ��E 0� r�4 -HOMAS W.HASTER ALAN C.HUTSON Freese and Nichols �i�s e C,E M Sri CDM00507 vti� ;:1ASiC��VAL Page 1 of 2 City of Fort Worth, Texas Mayor and Council Communication COUNCIL ACTION: Approved on 3/23/2004 DATE: Tuesday, March 23, 2004 LOG NAME: 60ROLLING REFERENCE NO.: C-20011 SUBJECT: Award of Contract to Archer Western Contractors, Ltd. for Rolling Hills Water Treatment Plant - Facilities Upgrade and 40 MGD Expansion, Phase 4 — New High Service Pump Station RECOMMENDATION: It is recommended that the City Council authorize the City Manager to execute a contract with Archer- Western Contractors, Ltd. in the amount of $5,391,000.00 for the Rolling Hills Water Treatment Plant - Facilities Upgrade and 40 MGD Expansion, Phase 4 — New High Service Pump Station. DISCUSSION: On June 6, 2000 (M&C C-18062), the City Council authorized an engineering agreement with Camp, Dresser & McKee, Inc. for design of the Rolling Hills Water Treatment Plant 40 MGD (million gallons per day) facility upgrade. As part of this agreement, the engineer prepared plans and contract documents to add a new high service pump station, in order to increase the pumping capacity by 100 MGD. Within this construction contract, Archer-Western Contractors, Ltd. will build a new high service pump station, together with related electrical and control system. The new station will initially house two 30 MGD, and two 20 MGD vertical turbine pumps with space for additional pump installation in the future. This project is the fourth phase of an overall plan to upgrade and expand the Rolling Hills Plant in order to meet present demands, and future growth in the rapidly developing areas of Fort Worth, and the wholesale customer cities. The project was advertised for bid in the Commercial Recorder on January 8 and 15, 2004. On February 5, 2004, the following bids were received: BIDDER TOTAL BID CONTRACT Aracher Western Contractors $5,391,000.00 535 Calendar Days Bar Constructors $5,562,675.00 Eagle Contracting $5,774,000.00 Craig, Sheffield &Austin $6,058.000.00 Holloman Corporation $6,237,576.96 Martin K. Eby Construction $6,793,275.00 This project is located in COUNCIL DISTRICT 8. http://www.cfwnet.org/council_packet/Reports/mc_pnnt.asp 03/24/2004 Page 2 of 2 Archer-Western Contractors, Ltd. is in compliance with the City's M/WBE Ordinance by committing to 15% M/WBE participation. The City's goal on this project is 15%. In addition to the contract cost, $269,550.00 is provided for project contingencies. FISCAL INFORMATION/CERTIFICATION: The Finance Director certifies that funds are available in the current capital budget, as appropriated, of the Water Capital Projects Fund. TO Fund/Account/Centers FROM Fund/Account/Centers P163 541300 060163051005 $5,391,000.00 Submitted for City Manager's Office b Marc Ott (8476) Originating Department Head: Dale Fisseler(8207) Additional Information Contact: Dale Fisseler (8207) http://www.cfwnet.org/council_packet/Reports/mc_print.asp 03/24/2004 F CITY OF FORT WORTH,TEXAS ROLLING HILLS WATER TREATMENT PLANT PHASE 4—NEW HIGH SERVICE PUMP STATION � f b PROJECT No. PW77-060770510050 X ALAN HC UTSON ADDENDUM NO. 1 ����s 80179 January 28, 2004 .�1 �!C.FNgEd `�4►�;+► 4;4 y0WAl BID DATE: Thursday, February 5, 2004, 2:00 pm / The following additions, deletions, modifications, or clarifications shall be made to the appropriate sections of the plans and specifications and shall become a part of the Contract Documents. Bidders shall acknowledge receipt of this Addendum in the space provided on the Bid form. BIDDING REQUIREMENTS: Al-1 PART A—NOTICE TO BIDDERS A. Reference Page A-4, Paragraph 1. Modification: Modify the paragraph by deleting"For additional information contact Peter Fu, Fort Worth Water Department at(817)871-8438 (FAX 817-871-8195)."and adding the following"For additional information contact Peter Fu, Fort Worth Water Department at(817)392-8438(FAX 817-392-8195)." A1-2 PART B-PROPOSAL Modification: Delete the bid proposal and replace it with the Proposal included with this Addendum. The revised form is to be attached to the contract documents and submitted with the Bid. The allowance for the Owner selected Applications Engineer work has been added. Also, a line has been added for the Contractor to list the pump and motor supplier that will be used on the project. TECHNICAL SPECIFICATIONS: A1-3 SECTION 01025—MEASUREMENT AND PAYMENT A. Reference Page 01025-3, Paragraph 1.04.D.2 Delete"(To be added by addendum)"from the last sentence. B. Add the HSQ letter dated January 23, 2004, attached to the end of this Addendum No. 1, to the end of Section 01025. A1-4 SECTION 02490—LOAMING, HYDROSEEDING AND EROSION CONTROL A. Reference Page 02490, Paragraph 3.04,A. Modification: "All seeded areas shall be guaranteed by the Contractor for not less than ene two full years from the time of acceptance" Al-5 SECTION 02614—BAR-WRAPPED CONCRETE CYLINDER PIPE A. Reference Page 02614, Paragraph 2.03, A. Clarification: The working pressure for the discharge piping is 200 po Thisia,the same as the rated pressure noted in the drawings. All pipe, flanges, valves adurter�r� be designed for a pressure of 200 psi. Addendum No. 1 0U -1 CDM00507—Rolling Hills WTP—High Service Pump Station I B. Reference Page 02614, Paragraph 3.01,C,4. Addition: Pipe larger than 36"shall be welded from the inside. Al-6 SECTION 08342—Fiberglass Reinforced Door and Frame System A. Reference Page 2, Paragraph 2.01. Modification: Modify the paragraph by deleting'Substitutions: Refer to Section 01600— Product Requirements", and adding"Substitutions: Refer to Section 01610—MATERIAL AND EQUIPMENT" Al-7 SECTION 11212—VERTICAL TURBINE PUMPING UNITS A. Reference Page 11212, Paragraph 1.02,A. Addition: Flowserve shall be added to the list of acceptable pump manufacturers. Al-8 SECTION 13300 DISTRIBUTED CONTROL SYSTEM A. Reference Page 13300-1 Paragraph 13300 1.01 B. 1. Add the following: 'k. Provide equipment and services for the setup of a new fiber optic communications link from the Laboratory to the East Communications Hub. The monitoring PLC(PLC 23)shall be constructed from the PLC Development System included in this contract." B. Reference Page 13300-1 Paragraph 13300 1.01 B. 2. Add the following: 'g. Provide services to support the setup of a new fiber optic communications link from the Laboratory to the East Communications Hub. This would include configuration of the monitoring PLC (PLC 23)being constructed from the PLC Development System included in this contract.' C. Reference Page 13300-14 Paragraph 13300 1.08 B. Add the following: '4. The project includes addition of a Fiber Optic link from the East Communications Hub to the Laboratory and implementation of a monitoring PLC(PLC 23)from the Development System provided in this contract. 5. The Unwitnessed Factory Test(UFT)shall be conducted at the PCSI and AES sites respectively. The Witnessed Factory Test(WFT)shall be a joint test conducted at the Rolling Hills Plant. The WFT shall use simulated inputs to fully test the PLC system prior to ORT" D. Reference Page 13300-14 Paragraph 13300 1.08 D.3. Delete the paragraph. Replace with the following: Addendum No. 1 00900-2 CDM00507—Rolling Hills WfP—High Service Pump Station "3. Participate in all witnessed tests at the Rolling Hills Plant and in general startup activities. In addition, provide the services of a trained field technician to assist the PCSI for a minimum of 10 days (up to 2 separate trips)of field support, including all travel, per diem, and lodging costs associated therein." Al-9 SECTION 13305 APPLICATION ENGINEERING SERVICES A. Reference Page 13305-1 Paragraph 13305 1.01: Add the following: "H. Support Implementation of the Laboratory to East Communications Hub link. 1. In coordination with PCSI subcontractor, reconfigure the development PLC into a monitoring PLC for the East Communications Hub. PLC shall monitor the UPS using Modbus RS 485 physical link and Modbus protocol. 2. In coordination with the PCSI subcontractor, configure the PLC and SCADA system to monitor up to 20 parameters to be identified by the owner after the first coordination meeting. Parameters shall be displayed on a dedicated graphic. Up to five alarms shall be configured in addition to the 20 parameters." Al-10 SECTION 13310-DISTRIBUTED CONTROL SYSTEM A. Reference Page 13310-2, Paragraph 13310 1.09 C. 1. a. Replace"development system" with"Development System" B. Reference Page 13310-8, Paragraph 13310 2.05. Delete the paragraph in its entirety. Replace with: "2.05 LAB AND EAST COMMUNICATION HUB HARDWARE A. General 1. A communications link is being added between the Laboratory and East Communications Hub. Equipment and software shall be provided by the PCSI and configuration services will be supplied by the AES to help make the link operational. Installation shall be coordinated with Fort Worth Water Department Information Technology Group(FWWDIT). New equipment to be provided includes: Racks, uninterruptible power supplies (UPS),fiber optic patch panels, and fiber optic cable. Refer to section 13320 for specification of the fiber optic cable. PLC 23 will consist of the Development system specified earlier in this section and referenced in this subsection. In order to maintain compatibility with existing equipment used by FWWDIT or the Plant SCADA system, no substitutions will be permitted for items on this list. B. Hardware 1. Provide new equipment listed in table below: Manufacturer Part Number DESCRIPTION QTY 72/144/288-port Rack Mount Interconnect SIEMON RIC72-F-01 Center 4RMS 2 Addendum No. 1 00900-3 CDM00507—Rolling Hills WTP—High Service Pump Station SIEMON RIC-F-SA6-01 3 duplex ST adapters 6 fiber, iconpockets) 12 SIEMON RIC-F-BLNK-01 Blank adapter plate 12 ORTRONICS OR-60400159 MIGHTY MO RACK 7'X 6.5" 43RD 2 Powerware model PW 700 VA/490 Watts Rack Mount UPS with 4 9125 700 05146012-5501 Post Mounting Rail Kit. 2 Powerware Power Pass module to permit replacement model PPDM or upgrade of UPS. (Equivalent to a bypass 700-1500VA 05146519-001 switch) 2 X-Slot Modbus Card for Powerware UPS Powerware monitoring by PLC 23 in the East Modbus Card 103002510-5501 Communications Hub 1 Powerware Connect UPS- X-Slot Web Card for Powerware UPS X Card 103002974-5501 monitoring by FWWDIT in the Laboratory 1 RS485 4 wire conductor and accessories to connect UPS to PLC 23 Modbus port 1 Rack mounting hardware to secure Modicon/ Development system Six-Slot Chassis to Square D See earlier sections Rack for PLC 23 1 2. Reuse the Development System equipment listed in table below: Manufacturer Part Number DESCRIPTION QTY Modicon/ Development System six-slot chassis (use IF Square D See earlier sections for PLC 23) 1 PLC and Power supply from Development Modicon/ System to be commissioned as PLC 23 Square D See earlier sections During functional Demonstration Test. 1 Ethernet communications module to be Modicon/ supplied by Owner from spare modules Square D See earlier sections provided under Phase 3. 1 Power cable from Development System connected to UPS. 1 Spare fiber optic jumper connecting Ethernet module to port in switch. 1 C. Services I 1. Install Racks, Patch Panels, and other equipment as shown on drawings and under the direction of Owner and Engineer. 2. Coordinate installation with Owner personnel. 3. In coordination with AES subcontractor, reconfigure the Development PLC into a monitoring PLC(PLC 23)for the East Communications Hub. PLC 23 shall monitor the UPS using Modbus RS 485 physical link and Modbus protocol. 4. In coordination with the AES subcontractor, configure PLC 23 and SCADA system to monitor up to 20 parameters to be identified by the owner after the first coordination meeting. Parameters shall be displayed on a dedicated graphic. Up to five alarms shall be configured in addition to the 20 parameters." Addendum No. 1 00900-4 CDM00507—Rolling Hills WTP—High Service Pump Station C. Reference Page 13310-9, Paragraph 13310 2.06 A 2. Delete the paragraph in its entirety. Replace with: "1.The following Uninterruptible Power Supplies shall be provided: Size Tag ID Location/Description kVA Power Input/Output UPS-1 Electrical Room for New High 5.3 kVA 120-VAC/40 Amp Single- Service Pump Station, will Phase Input/ service PLC 22 in addition to 120-VAC/40 Amp Single- other loads. Provide Phase Output EXTERNAL Bypass Switch per Division 16 and Electrical Drawings. Internal bypass switch is not acceptable. UPS-2 Individual spare, shown on 0.5 kVA Hardwired 120 VAC input with System Architecture in PLC 22 Hardwired/ 120 VAC output. cabinet. Provide EXTERNAL Bypass Switch asspecified. Al-11 SECTION 13315- INSTRUMENTATION SUBSYSTEM A. Reference Page 13315-1 Paragraph 13315 2.01 A. 1. a. 1) Delete the paragraph in its entirety. Replace with attached section 13315 2.01 A. 1.a. 1) 41) Diagonally traversing transit time type. Multiple paths (four to eight transducers) depending on vault and supplier. See item h, below and drawing 1-6 details A, B, C, D." B. Reference Page 13315-2, Paragraph 2.01 A. 1, d, 5). Delete paragraph 5) in entirety. Replace with attached paragraph: 'S) Dimension confirmation. The meter vaults have been designed around an 84 inch total length spool piece for the 48 inch lines and a 92 inch total length spool piece for the 54 inch line.There is a side clearance of 48 inches from pipe outer diameter to walls of each vault. Confirm that spool piece length, and sensor side protrusion with removal jack will fit in the meter vault. Confirm that there will be adequate space to remove and replace sensors in the meter vault when the pipe is at a pressure of 200 psig." C. Reference Page 13315-3, Paragraph 2.01 A. 1. Add the following paragraph: 'h. Minimum Acceptable Configurations: 1) Vaults 14, 15, 17, Configuration 1: Four transducers arranged in a single plane with two parallel paths. (Accusonics, Rittmeyer) 2) Vaults 14, 15, 17, Configuration 2: Four transducers arranged in two non- parallel paths. (Eastech Badger) 3) Vault 16, Configuration 1: Eight transducers arranged in two planes with two parallel paths per plane. (Accusonics, Rittmeyer) 4) Vaults 16, Configuration 2: Six transducers arranged in three non-parallel paths. (Eastech Badger) Addendum No. 1 00900-5 CDM00507—Rolling Hills WTP—High Service Pump Station Al-12 SECTION 13320 FIBER OPTIC COMMUNICATIONS SEGMENTS A. Reference Page 13320-1 Paragraph 13320 1.01 B. Delete the paragraph in its entirety. Replace with: "B. Furnish fiber optic cable for the communications segments (indoor/outdoor cable rated ONFR)for the following locations as described in the specifications and Drawings: 1. PLC 22 to Network Room—Multimode, see 2.02 A. 3 2. Laboratory Building to East Communications Hub—Multimode, see 2.02 A. 4. 3. Laboratory Building to East Communications Hub—Single mode, see 2.02 A. 5.' B. Reference Page 13320-4 Paragraph 13320 2.02 A. Add the following: Add the following: `4. Cable-Multimode for Laboratory to East Communications Hub link a. Manufacturer/Make:COMSCOPE R-024-LN-6F-F12BK Indoor/Outdoor. b. 24 fiber(twelve pair)cable c. 62.5/125um High Performance Fiber. d. Or Engineer/Owner approved equal. 5. Cable—Single mode for Laboratory to East Communications Hub link a. Manufacturer/Make: COMSCOPE R-012-LN-8W-F12BK Indoor/Outdoor. V b. 12 fiber(six pair)cable c. 8.3/125um High Performance Fiber. d. Or Engineer/Owner approved equal." C. Reference Page 13320-7 Paragraph 13320 2.06 A. Delete the paragraph in its entirety. Replace with: 'A. Spare Parts—2 spare Single Mode Fiber Jumper Cables and 2 spare Multimode Fiber Jumper Cables (2 strands)with ST connectors 3 meters in length' Al-13 SECTION 15103—BUTTERFLY VALVES A. Reference Page 15103-4, 3.03 Addition: Add the following line to the valve schedule: Location/ Number Size and Rated Position of Valve Service Required Ends Pressure Type Operator Shaft HSP S17 2 36"Flg. 200 Handwheel Horz. Exposed Outside Addendum No. 1 00900-6 CDM00507—Rolling Hills WTP—High Service Pump Station "Note: This change reflects the actual number of valves shown on Sheet P-1 of the drawings." Al-14 SECTION 15110—PUMP CONTROL BALL VALVES A. Reference Page 15110-5, Paragraph 2.02.A. L Modification: Delete the first sentence of paragraph A: "The ball valves shall be metal seated or resilient seated type valves with flanged ends." Replace with the following sentence: "The ball valves shall be metal seated type valves with flanged ends." B. Reference Page 15110-6, Paragraph 2.02.F. Delete paragraphs 2 and 3 in their entirety. Al-15 SECTION 16000—ELECTRICAL—GENERAL PROVISIONS B. Reference Page 4, Paragraph 1.06.A Modification: Delete the existing paragraph A. Replace with the following new paragraph A: "A. Power for the pump station will be obtained from Switchgear SG1 as shown." C. Reference Page 4, Paragraph 1.06.B. Delete Paragraph B. D. Reference Page 4, Paragraph 1.06.H. Delete the first sentence of paragraph H. Al-16 SECTION 16110—RACEWAYS, BOXES, FITTINGS,AND SUPPORTS A. Reference Page 3, Paragraph 3.01.6 Modification: Delete the table in its entirety and replace with the following table: Conduit Type Location 1. Rigid Galvanized Conduit Not acceptable for use. 2. PVC Coated Rigid Galvanized Steel All embedded conduit bends(except underground duct banks)and all conduit stub-ups ` to a minimum of 6 above finished floor or grade. All RTD circuits above or below grade, exposed or concealed. 3. Liquidtight Flexible Aluminum Raceway connection to motors or vibrating equipment in all areas. Connections to light fixtures. 4. Rigid Non-metallic, Schedule 40 Underground encased in red dyed reinforced concrete. Addendum No. 1 00900-7 CDM00507—Rolling Hills WTP—High Service Pump Station 5. Aluminum Rigid Metal Conduit All above grade areas, except for concrete embedded and those areas described in Locations 2 through 5 above. All medium voltage conductor circuits above grade, exposed or concealed. Al-17 SECTION 16121 —MEDIUM VOLTAGE CABLES B. Reference Page 3, Paragraph 2.02 CABLE RATINGS AND TYPE Modification: Delete Paragraph A in its entirety and replace with the following Paragraph: "A. General 1. Multi-conductor or armored multi-conductor medium voltage cable shall not be used. 2. The Contractor shall provide three single conductor 5 kV cables as specified in Paragraph B, and ground conductor, each sized as shown on the drawings from the medium voltage starters to each motor. 3. Each cable and ground shall be installed in the cable tray laid side by side per the NEC and secured with tie wraps every 24-inches. 4. The cable shall enter a 4-inch 90 degree long-sweep elbow from the tray and leave the valve building to terminate on the motor. 5. The orientation of the end of the long sweep elbow shall be rotated down a few degrees to point toward the tray to eliminate a any sharp bends as the cable exits the tray and enters the conduit. 6. Provide a grounding type conduit bushing on the end of the elbow per the NEC. Bond the bushing to the cable tray. 7. Provide seal tight flexible conduit with grounding jumper to complete the raceway connection to the motor terminal box." C. Reference Page 5, Paragraph 3.01 GENERAL Addition: Add the following paragraph C: "Splices in medium voltage cables are prohibited. Medium voltage cables shall be continuous from the line side of the protective device to the load terminals of the device served." Al-18 SECTION 16170—METAL FRAMING A. Reference Page 1, Paragraph 2.01.A Modification: Delete paragraph A in its entirety and replace with the following paragraph: "A. Stainless Steel" B. Reference Page 1, Paragraph 3.01.A and 3.01.13 Modification: Modify the paragraph as follows: "A. Use 316 stainless steel components for all applications. B. Use stainless steel channels with all aluminum conduits. The aluminum channel shall not come in direct contact with concrete. Install a spacer or coat the channel as per manufacturer's recommendation." Addendum No. 1 00900-8 CDM00507—Rolling Hills WTP—High Service Pump Station Al-19 ADD THE FOLLOWING SECTIONS: 01610—MATERIAL AND EQUIPMENT 16115—CABLE TRAYS APPENDIX A—SUPPLEMENTAL DATA FOR EXISTING 48"AND 54"WATER MAINS APPENDIX B—PRE-BID CONFERENCE MEETING MINUTES DRAWINGS: Al-20 SHEET C-8, VALVE VAULT AND METER VAULT DETAILS A. Reference: Section 3. Delete the meter vault plan, section and schedule and replace with the attached Exhibit C-8(A). Al-21 SHEET P-2, PIPING SECTION A. Add the following note: '11. The concrete cradle for the 60" suction pipe entering the wet-well shall extend to the bottom of the wet-well excavation to property support of the pipe." Al-22 SHEET S-10, VAULT PLANS AND SECTIONS A. Delete the meter vault top plan, meter vault sectional plans and schedule and replace with the attached Exhibit S-10(A). Al-23 SHEET A-8, DOOR DETAILS FINSH SCHEDULE DOOR SCHED. A. SCHEDULE'DOOR& FRAME TYPE" Eliminate column labeled 'UL LABEL". UL rated doors not required. Al-24 SHEET H-1, 1 OF 2 H SHEETS A. HVAC PLAN The heaters in the valve room will now be controlled separately from the heaters in the electrical room by an additional identical thermostat. Each of these thermostats shall be mounted directly onto their respective heater control panel (furnished by the electrical contractor). See electrical drawings for these locations. Al-25 SHEET H-2 OF 2 H SHEETS A. Reference: Section 1 Provide and install a 12"x12" hinged and latched access door onto the ducts of both supply fans adjacent to motorized damper motor inside. Al-26 SHEET E-7 A. Reference: Electrical Building Lighting Plan: a. Add one type F fixture in the middle of the north wall of the electrical room. The fixture shall face the pump and wet well area. Aim the flood light toward the center of the line up of pumps. Circuit the light fixture on LA-9 and switch the fixture using the two three-way switches described in"b" below. b. Add two 3-way light switch inside pump building on the north and south ends on the west wall by the north door and south doors in that wall. The switch will switch the all of the type F fixtures (four installed on the west wall of the valve room and the new type F fixture installed under'a"above. Addendum No. 1 00900-9 CDM00507—Rolling Hills WTP— High Service Pump Station c. Redesignate all type F fixtures to be on LA-9. d. Add two three-way light switches in the electrical room next to each of the exit doors. These light switches shall be circuited to switch all of the type D outdoor fixtures. e. Re-circuit all of the Type D, D1 and F1 fixtures to be from LA-18. f. The type D1 and F1 fixtures shall not be switched with the three-way switches described in"d"above. The D1 and F1 fixtures shall all be switched with their internal photocell switches. g. Change all electrical room receptacles to be GFI type. Al-27 SHEET E-8 A. Reference: Electrical Building Lighting Plan a. Show SV-7380-2 to be served on circuit LA-13 and the conductors shall be type BT3. Al-28 SHEET E-9 A. Reference: Electrical Building Lighting Plan: a. Show SV-7380-1 to be served on circuit LA-12 and the conductors shall be type BT3. b. Change Note 1 to read as follows: "Receptacles for heat trace shall be rated 20 A,WP-GFI and served from LA-35 through 39 for HSP-S13 through HSP-S14 respectively." Al-29 SHEET E-9 A. Reference: Multilin 496 Relay Typical Wiring Diagram. a. Change the title to read "Multilin 396 Relay Typical Wiring Diagram b. Remove the 120 volt power connection to H11 and H12 from the CPT and show the relay to be powered from Panel UPS per Sheet E-5 and EY-1. Al-30 SHEET E-10 A. Reference: High Service Pump Station Power and Control Section a. Add note to designate sealtight flex between end of power conduit and motor terminal box Al-31 SHEET EY-5 A. Reference: Schematic 1. a. Change the enclosure to NEMA 12. b. Change the dotted line showing the limit of the enclosure to show the heaters to be located outside the enclosure. c. Add the feeder designation to be Panel LA-25,27,29. d. Change CRA*to a thermostat in rung 2. B. Reference: Schematic 2. a. Change the dotted line showing the limit of the enclosure to show the heaters to be located outside the enclosure b. Add the feeder designation to be Panel LA-26,28,30. c. Change CRA*to a thermostat in rung 2. OP"' C. Reference: Schematic 3. a. Change the enclosure to NEMA 12. Addendum No. 1 00900-10 CDM00507—Rolling Hills WTP—High Service Pump Station b. Change the Stop to an E-Stop in rung 4. c. Remove the MA switch, M seal-in and Start pushbutton in rung 4 and 6 �- Al-32 SHEET EY-6 A. Reference: Sump Pump Schematic 1. a. The receptacle is WP-GFI. B. REFERENCE: WET WELL LEVEL RELAY PANEL(WWRLP)SCHEMATIC 1 a. Change feed to Panel UPS-3 b. Change enclosure to NEMA 12 C. REFERENCE EXHAUST FAN SCHEMATIC 3 a. Change the Stop to an E-Stop in rung 4. b. Remove the MA switch, M seal-in and Start pushbutton in rung 4 and 6. D. REFERENCE BLOW DOWN STATIONS SCHEMATIC 4 a. Add the abbreviation (BIDS)to the title b. Show BDS 1 fed from LA-12 Mir C. Show BDS 2 fed from LA-13 Al-33 ADD THE FOLLOWING EXHIBITS TO THE DRAWINGS: L E-2A DETAIL A TELEPHONE&FOC ROUTE E-2AA DETAIL I, M, N AND O DUCT BANK SECTIONS E-2AB WIRE SCHEDULE TABLE AND NOTES E-3A DETAIL A E4A PARTIAL PLAN SHOWING THE EXISTING SWITCHGEAR SG1 AND CONNECTION TO NEW ONCOR SUBSTATION E-6A 50 MGD HSPS ELECTRICAL BUILDING PLAN, NOTES AND CIRCUIT TABLE E-8A VIBRATION DECTCTOR DIAGRAM 3 AND WETWELL LEVEL RELAY PANEL DIAGRAM E-1 OA HIGH SERVICE PUMP STATION POWER AND CONTROL DETAIL 1 EY-1A PANEL LA SCHEDULE EY-1 B PANEL HA AND PANEL UPS SCHEDULES EZ1-A DETAIL K—CABLE TRAY DETAIL Al-34 REPLACE THE FOLLOWING SHEETS: � REPLACE SHEET WITH SHEET E-2 Addendum Drawing E-2 E-5 Addendum Drawing E-5 E-11 Addendum Drawing E-11 1-2 Addendum Drawing 1-2 1-6 Addendum Drawing 1-6 1-8 Addendum Drawing 1-8 END OF ADDENDUM NO. 1 Addendum No. 1 00900-11 CDM00507—Rolling Hills WTP—High Service Pump Station PROPOSAL (This Proposal shall be attached to this volume of the Contract Documents and submitted with the appropriate supporting documents.) TO: Gary W.Jackson City Manager Municipal Office Building 1000 Throckmorton Fort Worth,Texas 76102 PROPOSAL FOR: The furnishing of all materials and equipment and labor and all necessary appurtenances and incidental work to provide a complete and operable project designated as: Rolling Hills Water Treatment Plant Facilities Upgrade and 40 MGD Expansion Phase 4—New High Service Pump Station Project No. PW77-060770510050 Pursuant to the foregoing Notice to Bidders, the undersigned Bidder, having thoroughly examined the Contract Documents,including plans,special contract documents,and the General Contract Documents and General Specifications for Water Department Projects,the site of the project and understanding the amount of work to the done, and the prevailing conditions, hereby proposes to do all the work, furnish all labor, equipment and material except as specified to be furnished by the City,which is necessary to fully complete the work as provided in the Plans and Contract Documents and subject to the inspection and approval of the Director of the Fort Worth Water Department of the City of Fort Worth, Texas; and binds himself upon acceptance of this Proposal to execute a contract and furnish an approved Performance Bond,Payment Bond, Maintenance Bond, and such other bonds, if any, as may be required by the Contract Documents for the performing and completing of the said work. Contractor proposes to do the work within the time stated and for the following sums: BASE BID: Item Estimated Brief Description of Item Unit Bid Price Amount No. Quanti With Unit Bid Price in Words in Fig res in Figures 1 1 Construction of the Rolling Hills WTP L.S. Phase 4—New High Service Pump Station, complete, excluding Bid Items 2,3,and 4. Dollars $ $ and Cents per Lump Sum 2 * Design, Installation and Removal of L.F. Trench Safety System Dollars and Cents per Linear Foot $ $ *Maximum linear footage to be determined by Bidder and entered here. Linear footage shall not be less than 1,000 L.F. Part B -Proposal B-1 CDM00507—Rolling Hills WTP High Service Pump Station Item Estimated Brief Description of Item Unit Bid Price Amount No. Quanti With Unit Bid Price in Words in Figures in Figures 3 400 Drilled Shafts L.F. Dollars Cents per Linear Foot 4 1 ALLOWANCE for Owner selected L.S. Applications Engineer (AES) work including PLC and HMI software programming services Ninety-nine thousand, two hundred seventy-five Dollars and no Cents $ 99,275.00 $ 99,275.00 TOTAL BASE BID (ITEMS 1 through 4) (in words) (in figures) Bidder shall list below the subcontractor firm that will be used on this project as the Process Control System Integrator(PCSI). The PCSI will be Bidder shall list below the pump and motor manufacturer that will be used on this project. The pump manufacturer will be The motor manufacturer will be Part B-Proposal B-2 CDM00507—Rolling Hills WTP High Service Pump Station Y' Within ten(10)days after acceptance of this proposal,the undersigned will execute the formal contract and will deliver an approved Surety Bond and such other bonds as required by the Contract Documents, for the faithful performance of this contract. The attached bid security in the amount a 5%is to become - the property of the City of Fort Worth,Texas,in the event the contract and bond or bonds are not executed and delivered within the time above set forth,as liquidated damages for the delay and additional work caused thereby. The undersigned bidder certifies that he has been furnished at least one set of the General Contract Documents and General Specifications for Water Department Projects dated January 1, 1978, and that he has read and thoroughly understands all the requirements and conditions of those General Documents and the Specific Contract Documents and appurtenant drawings. The undersigned assures that its employees and applicants for employment and those of any labor organization, subcontractors,or employment agency in either furnishing or referring employee applicants to the undersigned are not discriminated against as prohibited by the terms of City Ordinance No. 7278 as amended by City Ordinance No. 7400. The Bidder agrees to begin construction within 10 Calendar Days after issue of the work order, and to complete the contract within 535 Calendar Days, and to meet the Substantial Completion requirements specified in Paragraph D-15 of the Special Conditions(Part D). (Check A or B as appropriate and fill in blanks where applicable.) A. The principal place of business of our company is in the State of Nonresident bidders in the State of , our principal place of business, are required to be percent lower than resident bidders by state law. A copy of the statue is attached. Nonresident bidders in the State of , our principal place of business, are not required to underbid resident bidders. B. The principal place of business of our company or our parent company or majority owner is in the State of Texas. Addendum No. 1 (Initials) Addendum No. 2 (Initials) Addendum No. 3 (Initials) Addendum No. 4(Initials) Respectfully submitted, By: Title: Address: Telephone: (S E A L) If Bidder is Corporation Date: Part B -Proposal B-3 CDM00507—Rolling Hills WTP High Service Pump Station � � � Mailing Address: Shipping Address: '� P.O.Box 4557 26227 Research Road Hayward,California 945404557 Hayward,California 94545-3725 TECHNOLOGY Telephone: (510)259-1334 ♦ Facsim fie: (510)259-1392 ♦ saies®hsq.com ♦ hUy://www.hso.rnm Via e-mail January 23,2004 City of Fort Worth Attention: Peter Fu Reference: Rolling Hills Water Treatment Plant Facilities Upgrade& 40-MGD Expansion Phase 4—High Service Pump Station Project City of Fort Worth,Texas Project No. PW77-060770510050,HSQ No. 0401-02-A Gentlemen: HSQ Technology is pleased to provide you a quotation to supply the software,configuration,and testing as specified in Specification Section 13300,Process Instrumentation and Controls— General Provisions, Section 13305,Application Engineering Services, and as shown on the Jow- Contract Drawing: Included • Provide programming,configuration,integration,including but not limited to loading of software on computers,operating system software configuration, Ethernet configuration, and communication between servers and PLCs. • Provide the PLC and control programming. • Provide two site visits that will total 10 days, for testing,training,and startup services as specified. • Perform the Unwitnessed Factory Tests(UFT)at HSQ's Hayward Factory before the Witnessed Factory Tests(WY1). • Provide assistance in the Witnessed Factory Tests(WFT)at the Rolling Hills Treatment Plant. • Supply RS232 to RS485 converter and jumper for Modbus link from PLC to PLC23. • Coordinate with the PCSI in delivering a complete PCS,to include 3 mandatory coordination meetings and two workshops. • Engineering and submittals, as required by the Specifications. • Payment and Performance Bonds Excluded • Supply and installation of all instruments. • Conduit and wire. • Jobsite receiving, storage, or protection. ,ow- • Sales tax. • Bonds. Pronate Safety, . . E►+eryCay/ An Equal Opportunity Employer California Contractor's License 378393 COME] TECHNOLOGY Page 2 January 23,2004 Re: Rolling Hills Water Treatment Plant Facilities Upgrade&40-MGD Expansion Phase 4—High Service Pump Station Project City of Fort Worth,Texas Project No.PW77-060770510050,HSQ No. 0401-02-A Our lump sum price for the above scope is$99,275.00. The pricing is valid for 120 days after the bid date. The payment terms are in accordance with Specification Sections 13300-1.14.13. On January 15,2004,John Robinson of CDM and Alan Nelson and Gary Waters of HSQ, completely discussed the Specifications and agreed that HSQ understands and can comply with the requirements. A paragraph-by-paragraph review will not be required by HSQ. If you have any questions,please call the undersigned at 800/486-6684. Very truly yours, HSQ TECHNOLOGY Pte_ Alan T.Nelson Estimating Manager ATN:rm cc: J.Dan Shannon,P.E.—CDM—via e-mail John Robinson,CDM—via e-mail An Equal Opportunity Employer California Contractor's License 378393 01610 MATERIAL AND EQUIPMENT 1.00 GENERAL 1.01 ACCEPTANCE OF MATERIALS AND EQUIPMENT A. Only new materials and equipment shall be incorporated in the Work, except for Owner furnished equipment and materials listed on the Drawings. Materials and equipment furnished by the Contractor shall be subject to the inspection and approval of the Owner. No material shall be delivered to the Work without prior approval of the Owner. B. Material and equipment incorporated into the Work shall: 1. Be new or listed on the Drawings as Owner furnished, in current production, and conforming to applicable specifications and standards. 2. Comply with size, make, type and quality specified, or as specifically approved in writing by the Engineer. C. Manufacture like parts of duplicate units to standard sizes and gages, to be interchangeable. D. Two or more items of the same kind shall be identical, by the same manufacturer. E. Products and equipment shall be suitable for service conditions F. Equipment capacities, sizes and dimensions shown or specified shall be adhered to unless variations are specifically approved in writing. G. Do not use material or equipment for any purpose other than that for which it is designed or is specified. H. The materials and equipment used on the Work shall correspond to the approved samples or other submitted data. 1.02 REUSE AND REPLACEMENT OF EXISTING MATERIALS AND EQUIPMENT A. Except as specifically indicated or specified, materials and equipment removed from any existing structure shall not be used in the completed Work. B. For the pieces of equipment to be reused in the work: 1. Use special care in removal, handling, storage and reinstallation, to assure proper function in the completed Work. 2. Arrange for transportation, storage and handling of products which require off-site storage, restoration or renovation. Pay all costs for such work. 1.03 TRANSPORTATION AND HANDLING A. Arrange deliveries of products and equipment in accord with construction schedules, coordinate to avoid conflict with work and conditions at the site. B. Deliver products in undamaged condition, in manufacturers original containers or packaging, with identifying labels intact and legible. C. Pipe and other materials delivered to the job shall be unloaded and placed in a manner which will not hamper the normal operation of the existing plant or interfere with the flow of necessary traffic. D. Immediately on delivery, inspect shipments to assure compliance with requirements of Contract Documents and approved submittals, and that products are properly protected and undamaged. Material and Equipment `' ��1�-�;va�1 0-1 CDM00507—Rolling Hills WTP High Service Pump Station 1.04 INSPECTION AND TESTING FOR ACCEPTANCE Owl A. Furnish all materials or specimens for testing and all labor and facilities for inspection of equipment and materials. B. Furnish suitable evidence that the materials proposed to be incorporated into the Work are in accordance with the Specifications. Mill tests for reinforcing stell and cement will be acceptable if it is definite that the test sheets apply to the material being furnished. Manufacturer's or supplier's test results will be acceptable for such items as pipe, valves, hydrants when it is definite that the material being furnished is in accordance with the manufacturer's or supplier's specifications to which the test results apply. Should the Contractor fail to provide the above information, the Owner shall have the right to require tests to be made by the Owner's laboratory to obtain the information and the cost therefore shall be borne by the Contractor. The Owner may have further inspection and tests made by the laboratory or may make tests himself, to ensure that the Contractor is complying with the Specifications. C. Details for testing equipment and materials are found in the individual Sections of these Specifications. D. If the Owner requires, either prior to beginning or during the progress of the Work the Contractor shall submit samples or materials for such special tests as may be necessary to demonstrate that they comply with the Specifications. Such samples shall be furnished, stored, packed, and shipped as directed at the Contractor's expense. Except as otherwise noted, the Owner will make arrangements for and pay for the tests. E. Delay of approval resulting from the Contractor's failure to submit samples or data promptly shall not be used as a basis of a claim against the Owner or Engineer. 1.05 STORAGE AND PROTECTION OF EQUIPMENT AND MATERIALS ON SITE A. Materials and equipment to be incorporated in the Work shall be handled and stored by the manufacturer,fabricator, supplier and Contractor before, during, and after shipment in a manner to prevent warping, twisting, bending, breaking, chipping, rusting, and any injury, theft or damage of any kind whatsoever to the material or equipment. B. Special attention shall be given to the storage and handling of equipment on site. Equipment storage will be approved by the Owner. As a minimum, the procedure outlined below shall be followed: 1. Equipment shall be shipped as late as possible to assure its availability when required by the Contractor's schedule. The intent of this requirement is to reduce on-site storage time prior to installation and operation. Under no circumstances shall equipment be delivered to the site more than one month prior to installation without prior written authorization from the Owner. Equipment shall not be shipped until the Contractor has received an approved submittal from the Owner. 2. Equipment having moving parts such as gears, electric motors, and instruments shall be stored in a temperature and humidity controlled building approved by the Owner, until such time as the equipment is to be installed. All space heaters in equipment shall be energized during construction. 3. Equipment shall be stored fully lubricated with oil or grease, unless otherwise instructed by the manufacturer. 4. Manufacturer's storage instructions shall be carefully studied by the Contractor and reviewed with the Owner. These instructions shall be carefully followed and a written record shall be kept by the Contractor. 5. Moving parts shall be rotated a minimum of once weekly to insure proper lubrication and to avoid metal-to-metal "welding". Upon installation of the equipm ; tractor ` shall start the equipment, at least half load, once weekly for an ad quperiod, i ensure that the equipment does not deteriorate from lack of use. ; P Material and Equipment 010- �"sae CDM00507—Rolling Hills WTP High Service Pump Station - 6. Lubricants shall be changed upon completion of installation and as frequently as required AM, thereafter during the period between installation and acceptance. New lubricants shall be put into equipment at the time of substantial completion. 7. Prior to acceptance of the equipment, the Contractor shall have the manufacturer inspect the equipment and certify in writing to the Owner that its condition has not been detrimentally affected by the long storage period. Such certification by the manufacturer shall be deemed to mean that the equipment is judged by the manufacturer to be in a condition equal to that of equipment that has been shipped, installed, tested and accepted in a minimum time period. As such, the manufacturer will guarantee the equipment equally in both instances. If such a certification is not given, the equipment shall be judged to be defective. It shall be removed and replace at the Contractor's expense. C. Store materials in accordance with manufacturer's instructions, with seals and labels intact and legible. 1. Store products subject to damage by the elements in weathertight enclosures. 2. Maintain temperature and humidity within the ranges required by manufacturer's instructions. D. Exterior Storage: 1. Store fabricated products and equipment above the ground, on blocking or skids, to prevent soiling or staining. Cover products which are subject to deterioration with impervious sheet coverings; provide adequate ventilation to avoid condensation. 2. Store loose granular materials in a well-drained area on solid surfaces to prevent mixing with foreign matter. 3. Cement and lime shall be stored under a roof and off the ground and shall be kept completely dry. Structural, miscellaneous, and reinforcing steel shall be stored off the ground or otherwise to prevent accumulations of dirt or grease, and in a position to prevent accumulations of standing water and to avoid rusting. 4. Beams shall be stored with the webs vertical. Precast concrete shall be handled and stored in a manner to prevent accumulations of dirt, standing water, staining, chipping or cracking. Brick, block and similar masonry products shall be handled and stored in a manner to prevent breakage, chipping, cracking, and spalling. E. Mechanical equipment subject to corrosive damage by the atmosphere if stored outdoors (even though covered)shall be stored in a building to prevent injury. The building may be a temporary structure on the Site or elsewhere, but it shall be satisfactory to the Owner. F. Arrange storage in a manner to provide easy access for inspection. Make periodic inspections of stored materials and equipment to assure that they are maintained under specified conditions and free from damage or deterioration. G. Protection After Installation: 1. Provide substantial coverings as necessary to protect installed materials and equipment from damage from traffic and subsequent construction operations. Remove when no longer needed. H. Off-site Storage: 1. Contractor may store materials and equipment off-site with Owner's approval. I. Rejection of Materials and Equipment: 1. Materials and equipment which, in the opinion of the Owner, have become so damaged as to be unfit for the use intended or specified shall be promptly removed from the site of the Work. The Contractor shall recveive no compensation for the damaged material or its removal. 2. Damaged material and equipment shall be replaced at the Contractor's expense. Material and Equipment 01610-3 CDM00507—Rolling Hills WTP High Service Pump Station 1.06 INSTALLATION STANDARDS A. Handle, store and install equipment in accordance with the manufacturer's drawings and recommendations. B. When Contract Documents require that installation of work shall comply with manufacturer's printed instructions, obtain and distribute copies of such instructions to parties involved in the installation. Maintain one set of complete instructions at the job site during installation and until completion. C. Handle, install, connect, clean, condition and adjust products in strict accord with such instructions and in conformity with specified requirements. Do not omit any preparatory step or installation procedure unless specifically modified or exempted by Contract Documents. 1. Should job conditions or specified requirements conflict with manufacturer's instructions, consult with Owner for further instructions. 2. Do not proceed with work without clear instructions. D. New equipment and existing equipment to be relocated shall be carefully aligned on the new foundations after their sole plates have been properly shimmed to true alignment at the .anchor bolts. The anchor bolts shall be set in place and the nuts tightened against the shims. After the foundation alignments have been approved by the Owner, the bed plates or wing feet of the equipment shall be securely bolted in place. The alignment of equipment shall be further checked after securing to the foundations, and after confirmation of alignments, the sole plates shall be finally grouted in place. E. Provide wedges, shims,filling pieces, keys, packing, red or white lead, grout, or other materials necessary to properly align level, and secure apparatus in place. Parts intended to be plumb or level shall be proven exactly so. Grinding necessary to bring parts to proper bearing after erection shall be done. F. Special care shall be taken to ensure proper alignment of sluice gates, operating mechanisms, stems, stem guides, and accessories. Care shall be taken to avoid warping the gate frames and to maintain tolerances between seating faces. Gates, stems, and operators shall be plumbed, shimmed and accurately aligned. G. Provide openings, channels, and chases, and install anchor bolts and other items to be embedded in concrete, as required to complete the Work under this Contract and do all cutting and patching as required. H. Furnish sleeves, inserts, hangers, and anchor bolts, required for the execution of the electrical, HVAC, and plumbing work specified and shown on the Drawings. In no case shall beams, lintels, or other structural members be cut without the approval of the Owner. 1.07 SUBSTITUTIONS AND PRODUCT OPTIONS A. Substitution of Equipment: 1. The Contractor shall note that the Engineer's design is based upon the first listed manufacturer for items of equipment, though not necessarily the manufacturer's "standard" product. 2. If the Contractor chooses other manufacturer's equipment he shall be responsible for the total cost, including engineering design, of modifications, alterations, adjustment, and coordination necessary to make the proposed equipment compatible with the treatment process and with the specified equipment, structures, spaces, and other features of the original design. If the specification list of approved manufacturers states"no equal"or .no substitutions will be allowed", the Contractor shall choose equipment from the approved manufacturer's list. B. Products List: 1. Within 30 days after Contract Date, submit to Owner a complete list of major products proposed to be used, with the name of the manufacturer and the installing subcontractor. Material and Equipment 01610-4 CDM00507—Rolling Hills WTP High Service Pump Station C. Substitutions: Aowl 1. For a period of 90 days after Contract Date, Engineer will consider written requests from Contractor for substitution of products. After that time period, no substitutions will be allowed and listed manufacturers shall be provided. 2. Submit a separate request for each product, supported with complete data, with drawings and samples as appropriate, including: a. Comparison of the qualitites of the proposed substitution with that specified. b. Changes required in other elements of the Work because of the substitution. c. Effect on the construction schedule. d. Cost data comparing the proposed substitution with the product specified. e. Any required license fees or royalties. f. Availability of maintenance service, and source of replacement materials. 3. Engineer shall be the judge of the acceptability of the proposed substitution. D. Contractor's Representation: 1. A request for a substitution constitutes a representation that Contractor: a. Has investigated the proposed product and determined that it is equal to or superior in all respects to that specified. b. Will provide the same warranties or bonds for the substitution as for the product specified. c. Will coordinate the installation of an accepted substitution into the Work, and make such other changes as may be required to make the Work complete in all respects. d. Waives all claims for additional costs, under his responsibility,which may subsequently become apparent. E. Engineer will review requests for substitutions with reasonable promptness, and notify Contractor, in writing, of the decision to accept or reject the requested substitution. 2.00 PRODUCTS (NOT USED) 3.00 EXECUTION (NOT USED) END OF SECTION Material and Equipment � " v�16 0-5 CDM00507—Rolling Hills WTP High Service Pump Station1E SECTION 16115-CABLE TRAYS 1.00 GENERAL 1.01 SCOPE OR WORK A. Furnish and install complete cable tray systems,with all accessories, fittings, supports, as indicated specified, and in accordance with the latest applicable NEMA and ASTM standards. B. Cable tray runs outline the general routing of raceways. Select actual routing in the field to follow Drawings as closely as possible and to avoid interfering with pipes, ducts, structural members, or other equipment. Deviations in routing from that shown on the Drawings must be approved by the Engineer, at no additional cost to the Owner. 1.02 RELATED WORK A. Submittals are included in Section 01300. B. Division 16 Electrical 1.03 SUBMITTALS A. Submit to the Engineer, in accordance with Section 01300, the following: 1. Shop Drawings: Indicate tray type, dimensions, support points and finishes. 2. Product Data: Provide data for fittings and accessories. 3. Manufacturer's Instructions: Indicate application conditions and limitations of use stipulated by product testing agency specified under Regulatory Requirements. Include instructions for storage, handling, protection, examination, preparation, installation and starting of product. 1.04 REFERENCE STANDARDS A. National Fire Protection Association (NFPA) 1. NFPA 70-National Electric Code. B. American Society for Testing and Materials (ASTM) 1. ASTM B633 SC1 -Standard Specification for Electrodeposited Coatings of Zinc on Iron and Steel. C. National Electrical Manufacturers Association(NEMA) 1. NEMA VE-1 - Metallic Cable Tray Systems 2. NEMA FG-1 -Fiberglass Cable Tray Systems. D. Canadian Standards Association (CAN/CSA) 1. CAN/CSA C22.2-No. 126-M91 Cable Tray Systems E. Underwriters Laboratories (UL) F. Where reference is made to one of the above standards, the revision in effect at the time of Cable Trays 16115-1 CDM00507—Rolling Hills WTP—High Service Pump Station bid opening shall apply. 1.05 REGULATORY REQUIREMENTS A. Conform to the requirements of NFPA 70. B. Furnish products listed and classified by UL as suitable for the purpose specified herein and as shown on the Drawings. 2.00 PRODUCTS 2.01 MANUFACTURERS A. T.J. Cope Allied. B. B-Line C. Acceptable Equal 2.02 LADDER-TYPE CABLE TRAY A. Description: NEMA VE 1, Class 20C ladder type tray. B. Material:Aluminum C. Finish: N/A. D. Inside Width:As indicated. E. Inside Depth: 6-in. F. Straight Section Rung Spacing: 6-in on center. G. Inside Radius of Fittings: 24-in. H. Provide stainless steel clamps, hangers, brackets, splice plates, reducer plates, blind ends, barrier strips, connectors, nuts, bolts,washers, lock washers, all thread and grounding straps. I. Covers: None. 2.05 WARNING SIGNS A. Permanent warning label shall appear on all straight sections and fittings and shall have the following wording: WARNING! DO NOT USE CABLE TRAY AS A WALKWAY, LADDER OR SUPPORT. USE ONLY AS A MECHANICAL SUPPORT FOR CABLES. 3.00 EXECUTION 3.01 INSTALLATION A. Install in accordance with manufacturer's instructions. B. Install metallic cable tray in accordance with NEMA VE 1. C. Install fiberglass cable tray in accordance with NEMA FG 1. Cable Trays 16115-2 CDM00507—Rolling Hills WTP—High Service Pump Station D. Provide supports at each connection point, at the end of each run, and at other points to . maintain spacing between supports of 8-ft maximum. E. Use expansion connectors where required. F. Ground and bond cable tray under provisions of NEC Article 318. 1. Provide continuity between tray components. 2. Install a bare 1 AWG copper cable through entire length of each tray(both medium voltage power and low voltage power and control)and bond to each section and ground connect to the Pump Station ground grid at both ends. 3. Use anti-oxidant compound to prepare aluminum contact surfaces before assembly. G. Provide cable tray angle brackets and supports to keep cable tray from swaying or moving horizontally. Mount on each side every 24-ft. END OF SECTION N� Cable Trays 16115-3 CDM00507—Rolling Hills WTP—High Service Pump Station APPENDIX B PRE-BID CONFERENCE MEETING MINUTES i I Memorandum To: Distribution From: Danny Shannon Camp Dresser& McKee Date: January 22, 2004 Subject: Rolling Hills WTP— Facilities Upgrade and 40 MGD Expansion Phase 4— High Service Pump Station Pre-Bid Conference Minutes The Pre-Bid Conference for the Rolling Hills WTP—Facilities Upgrade and 40 MGD Expansion,Phase 4—High Service Pump Station Project was conducted on January 20,2002. The Pre-Bid Conference was held at the Rolling Hills WTP. The agenda and attendance sheet for the conference are attached. These minutes provide a record of,the Pre-Bid Conference proceedings only,and do not change the contract documents as written. Any changes to the contract documents prior to the bid will only be made through written addenda. INTRODUCTIONS/ATTENDANCE 1. Danny Shannon,project manager for Camp Dresser&McKee Inc. (CDM)introduced personnel from the FWWD,the Fort Worth M/WBE Department,Freese&Nichols(F&N) —Project Engineer,and F&N —Construction Manager. 2. An attendance sheet was distributed for sign-in. A copy is attached. 3. Unless covered by addenda,items discussed during this meeting or prior to the bid are not binding. f PROJECT BACKGROUND 1. The Rolling Hills WTP is a 160 mgd facility constructed in two phases,the fust in early 1970's and the second in the early 1980's. It is the City's largest water treatment plant and therefore it is critical that the plant remain in operation throughout construction. Rolling Hills WTP PreBid Conference Minutes January 20,2004 h Distribution 01/22/04 Page 2 2. The Rolling Hills WTP—Facilities Upgrade and 40-MGD Expansion project may consist of six phases to upgrade the plant and expand its capacity to 200 MGD. This project, Phase 4—High Service Pump Station,will include construction of a new high service pump station,upgrade the existing sedimentation basins and filters to increase capacity and improve performance;increase the capacity of the plant sewer and sludge piping;and modify the existing washwater recovery system. Construction of Phase 1 -Ozonation Facilities(Eagle Contracting)and Phase 2—Backwash Supply System(BAR Constructors) have both been completed. Phase 3—Plant Process Improvements is currently under construction. Archer Western is the General Contractor for Phase 3. This project includes upgrades to the existing sedimentation basins and filters to increase capacity and improve performance;increase the capacity of the plant sewer and sludge piping; and modify the existing washwater recovery system. The Phase 3 project is scheduled to be substantially completed by May 2005 with final completion in August 2005.The Contractor may elect to finish earlier. The Phase 4 contractor will be required to coordinate with Archer Western during the construction. 3. The potential upcoming project phases include: ■ Phase 5—Flocculation Basins,Chemical Facilities,and Paving Improvements. This project may include modifications to upgrade the existing flocculation basins and chemical building and site grading and paving; and landscaping. Estimated advertisement date of Summer 2004. ■ Phase 6—Security Enhancements and Building Improvements project. This project will include modifications to the administration building and old chlorine building;implementation of an in-plant telecommunications system; implementation of plant security features;site grading and paving;and landscaping. Estimated advertisement date of Fall 2004. M/WBE GOALS AND REQUIREMENTS 1. Tom Jordan of the City's M/WBE Department presented the M/WBE requirements for this project. The City's goal for this project is 15%M/WBE participation. 2. Contractors must submit the paper work presented in the contract documents within 5 City business days after the bid. Failure to provide necessary documentation may render the bid non-responsive. The contractors will need to submit their Good Faith Effort documents within 10 calendar days of the bid,if they elect to go that route. 3. Mr.Jordan indicated that the M/WBE fors must be filled out listing both M/WBE and Non-M/WBE contractors. If listed on the forms,the subcontractors must be used To I obtain a list of M/WBE subcontractors,check the City website. Rolling Hills WTP PreBid Conference Minutes January 20,2004 Distribution 01/22/04 Page 3 4. It was recommended that contractors begin the process of M/WBE documentation now. If bidders have any questions,contact Mr.Jordan at 817-392-8509 or e-mail to thomas.jordan®fortworthgov.org. SCOPE OF WORK 1. Alan Hutson presented a brief summary of work for the project. The major items of the project include the following: ■ Construction of a below ground wetwell ■ Construction of a new high service pump station consisting of 4 pumps,pump control valves located in a new building and two header pipes and valves. ■ Buried and non-buried piping,valves and appurtenances ■ New process instrumentation and controls. ■ Electrical,instrumentation equipment and systems. Mr 2. The instrumentation and control system work will include work by a prequalified process control system integrator(PCSI). The PCSI work is outlined in Section 13300.A list of pre-approved PCSI firms are provided in Section 13300,paragraph 1.06.F. The PCSI will be a subcontractor to the General Contractor. The instrumentation and control system work will also include work by a prequalified applications engineer(AES). The AES will be HSQ Technology. The AES will also be a subcontractor to the General Contractor. Their scope and fee will be incorporated into the bid form,as an allowance,by addendum. This list may be revised by addendum,should other subcontractors submit prequalification statements and be deemed qualified for the work. The General Contractor shall select one of the PCSI firms. Section 13300 presents a division of work for the PCSI and AES. 3. If Contractors desire to review design plans for the existing Rolling Hills WTP or set up visits to the plant,they should contact Mr.Bob Arms,(817)999-6344. BIDDING REQUIREMENTS 1. The Bid Date is scheduled for February 5,2004. Bids must be received by 1:30 pm and will be opened at 2:00 pm in City Council chambers. 2. The Special Prequalification Requirements specific for this project,as presented in the M Special Instructions to Bidders were discussed. Current prequalification for City projects does not apply for this project. 3. The prequalification information must be received by two weeks prior to the bid date. Rolling Hills WTP PreBid Conference Minutes I January 20,2004 Distribution 01/22/04 Page 4 4. The electrical subcontractors must also meet qualification requirements presented in Section 16000 of the specifications. 5. The Proposal Form was discussed. Item 1 includes a majority of the work Item 2—Trench Safety requires the Contractor to determine the amount of trench safety required.Item 3 is a unit price item for drilled shafts below the pump station.Item 4 is the allowance for the AES(HSQ)work. Item 4 is the allowance for furnishing REXA Valve Actuators. A revised Proposal Form with the allowance numbers included will be provided with the addenda. A 5%bid security must be provided with the bid. 6. The proposal form must be attached to and submitted with the specification book Since the proposal form will be revised and included in an addendum,the Contractors should staple the proposal form to the original proposal form. 7. Wage rates are presented in Part D. If two rates for the same labor classification conflict, the higher rate shall be used. 8. Bidders should take no exceptions in their Bid submittal or include exceptions from any suppliers or subcontractors. A bid that includes any exceptions will be rendered non- responsive and will be rejected. CONTRACTSCHEDULE l� 1. The estimated date for Notice to Proceed construction is approximately two months following bid openings. The timing of the notice to proceed is dependent upon the M/WBE requirements and associated documentation provided.If the M/WBE documentation is submitted properly and approved quickly,the notice to proceed may be given earlier. The City desires to start construction as soon as possible,and it is their intent to expedite contract execution. 2. The time of completion for the project(Part D,Item D-15)is 535 Calendar Days. Substantial completion of the project is defined as completion of all process structures, pipelines,buildings and equipment,including electrical and instrumentation and control system so that water can be pumped. Work must be substantially complete with 420 calendar days,but no later than May 31,2005. This is substantial completion. 3. Liquidated damages for final and substantial completion dates are$3,000 per calendar day. Rolling Hills WTP PreBid Conference Minutes January 20,2004 Distribution 01/22/04 Page 5 4. The construction sequence for work was discussed per Section 01040. Tie-ins to existing waterlines must occur between November 1,2004 and April 1,2005. Only one line may be taken out of service at a time. A new fiber optic cable and telephone cable will be installed to serve the Laboratory Building.This work must be in operation for a period of 2 weeks prior to removing the existing fiber optic and telephone lines. The Owner and Engineer will not dictate the Contractor's means of construction,but the Contractor shall take the construction constraints presented into account in developing his on schedule. 5. The Contractor will be responsible for obtaining building permits and coordinating electrical inspections. The cost of the building permit will be waived. The City and CDM are currently proceeding with preparing building permit submittal and review with Development Department to insure that the Contractor will be able to obtain the building permit soon after award of contract. A building-permit will also be required for the construction trailer. This permit will be the responsibility of the contractor to obtain. 6. Security issues were discussed The Contractor will be responsible for following the City's security requirements. Check-in,with appropriate identification,at the back gate will be required for entry by contractor employees,suppliers,and other visitors. Contractor shall provide names to security staff prior to arrival. Under orange or red status,the security requirements will be more stringent. The contractor and his subcontrators,vendors,and suppliers shall use the rear gate for entrance and exit. ADDENDA 1. Addendum No. 1 will be completed by the end of this week and sent out no later than the first of next week. A second addendum will follow later in the week. 2. CDM and F&N asked that written questions be faxed to Freese&Nichols at(817)735- 7491,attention Alan Hutson. CDM and F&N will respond appropriately or cover through addendum. 3. A revised Proposal Form will be included with the second addendum to include allowances for HSQ Technology. LC Rolling Hills WTP ' °'Pr�eBid 4 eq e Mi es Jaritiatq'20I Distribution 01/22/04 Page 6 QUESTIONS AND ANSWERS No questions were asked at the Pre-Bid Conference. FACILITY TOUR A tour of the site was conducted following the meeting. END OF MEETING MINUTES Rolling Hills WTP PreBid Conference Minutes January 20,2004 CITY OF FORT WORTH ROLLING HILLS WATER TREATMENT PLANT FACILITIES UPGRADE AND 40-MGD EXPANSION PROJECT PHASE 4—HIGH SERVICE PUMP STATION PRE-BID CONFERENCE AGENDA January 20, 2004 1. INTRODUCTIONS/ATTENDANCE 2. PROJECT BACKGROUND 3. M/WBE GOALS AND REQUIREMENTS 4. SCOPE OF WORK E Below Ground Wetwell ■ High Service Pump Station ■ Buried and Non-Buried Piping and Valves ■ Process Instrumentation and Control ■ Electrical ■ Site Work 5. BIDDING REQUIREMENTS ■ Bid Date—Time ■ Special Prequalification Requirements ■ Proposal Form and Security ■ Allowances ■ Wage Rates ■ M/WBE 6. CONTRACT SCHEDULE ■ Estimated Notice to Proceed 0 ■ Sequence of Work and Constraints ■ Substantial Completion Dates ■ Liquidated Damages p ■ Building Codes/Building Permits 7. ADDENDA 8. QUESTIONS AND ANSWERS 9. FACILITY TOUR 4- 0 W N q L r 7; CP0� N � tx� cr QD N l`n D00 0 oz CL LU v� az ..� w N a- a � H ~ N - odA � o U � © w00 U c w W � oma tzi w fi s `^ LU zc v L J N d -.Q t7 .,. C2 U N m M m � X00 I Do � T'LLI O 74D[ 00 O O ff ' N N I r r Z o W m� t� m tip o a CA w ti `) M t r c 00 Pk rn w T`►• 1 /-� 0- i 1 r-• 1 qg � z J w d v� wzw C.9 O3wCx�7 w F- w OW u x o - � cn Wv cn y 3 � ahA4 w LLI Z z � ? � � Z ! -D Ej M 0 M rn O LL r 1 � I► 0 Lu r- l� o (Z "' X r az w CLw z 14 0o M �. w IN w 003 0 0 U dLUo x O w �Q p (� a vi �if w w 9 � t z S 0 J 0) Jam_ DIMENSIONS ELEVATIONS PIPELINE METER VAULTS CENTER [ L M DIAMETER EL "N" METER VAULT NO.14 19'-6" 673 653.5 48" 658 METER VAULT NO. 15 II'-6" 673 661.5 48" 666 METER VAULT N0.16 22'-0" 67 51.5 48" 656 METER VAULT NO.17 13'-6" 673.5 660.0 54" 66 5'-0" 1-4- 15'-0" V-4- 5--0- /-Sump PUM ONTROL PANEL.SEE ELECTRICAL 2'-0" DE SUMP W/I"FIBER LASS iv '-p" GRATING 2"x2"x "H 1 CONCR TE SPLASI I PAD 11/2" .roc I SCHED LE 80 ALUM. P.V.C. IPE WALL PENETRATION, LADDER TO I I/2"R .0 . HANDRAIL RE:H P-8 12" 4' -k'' io WALL FLAN iE M 71 _ FLOW in io r HARNESSED 4�K ADJUSTABLE PSE HARNESSED `D DRESSER SUPPORT(3 TYP) DRESSER COUPLING h COUPLING I ti N LIFTING LUGS(2 TYP) RE: D/C-10 • LAY LENGTH OF FLOW METER 3 SPOOL PIECE TO BE VERIFIED W/FLOW METER SUPPLIER. METER VAULT PLAN NOT TO SCALE V-2"� 6'-6" 6'-6" PIPE TO 2'x2'x4'H CONCRETE I 1/2"R AIIUM.HANDRAIL~i SPLASH PAD INSTALL PIPE ( I HANGERS AND SUPPORTS TO ADEOUATELY ATTACH DISCHARGE SLOPE TO DRAIN PIPING TO METER VAULT M ALL DIRECTIONS AROUND VAULT. EL L W W 1 1/2" ALUM LARD R ;•Y SCHEDULE 80 ''. m P.V.C.PSE •° RE: S io i 11/2" a ,! i0 . a _ BALL VALVE j••' CHECK VALVE ;. S 11/2" FL N ; �Q PVC UNION ooN 0 a �t z g o a ADJUSTABLE SEE GRATING 3 c= SUPPORT PIPE SUPPORT no, DETAILS c M mNc '�:���' '.i•+'�J•r.•. :t.. �a:%:H } 6"PVC fj WATERSTOP p a C - - NOTES: >N� a HYDROMATIC SUBMERSIBLE �a SUMP PUMP MODEL OSP33 >Nz I METER VAULT L SEE SHEET S-10 FOR STRUCTURAL.LADDER,AND HANDRAIL DETAILS. < —' co 2. INSTALL FLEXIBLE JOINTS WITHIN 5 FEET OF WALLS OF VAULT ON <o SECTIQN 3 BOTH SIDES.BACKFILL UNDER PIPE ADJACENT TO VAULT WITH m z^ NOT TO SCALE LEAN CONCRETE TO UNDISTURBED MATERIAL. .oNa _N j= 3. FLOW METER SPOOL PIECES TO BE MANUFACTURED BY THE FLOW METER MANUFACTURER. THE CONTRACTOR SHALL VERIFY THE LAY LENGTH, 10. Z AND PIPE MATERIAL W/ THE MANUFACTURER. floss 1Mernoliond Plum,Sults 200 .*�. ROLLING HILLS WATER TREATMENT PLANT Fort Worth,Tm 78100-4MS �i •—�. FACILITIES UPGRADE 8 40 MGD EXPANSION =a n w Pl a - (817)735-7300 c��LL � x: 111 Fm - (a,7)73s-7+e1 PHASE 4 - NEW HIGH SERVICE PUMP STATION V SOU w 90170 Date: Reference Addendum Exhibit: moo'zLL 4 1' * Sheet No. No. < » 26/ AN. 26, 2004 C-8 1 C-8 (A) At '-2" If 5'-0" '-2" CHAIN GUARD RE:A/S-10 2 ALUM M.,ALUM O LADDERHANDRAIL 2 SV RE:A/S-10 o (L P1PE F. � 44i in v'3` e N fV p}e i 5 METER VAULT METER VAULT TOP PLAN SECTIONAL PLAN NOT TO SCALE NOT TO SCALE 1 DIMENSIONS ELEVATIONS PFELWE REINFORCEMENT METER VAULTS I L M DIAMETER CENTER DD EE FF GG m EL "N" 0 METER VAULT N0. 14 t9'-6" 673 653.5 48" 658 +6 a 12"C/C +6 0 6"C/C +6 0 12"C/C +6 a 12'C/C o/ oz METER VAULT N0.15 11'-6" 673 661.5 48" 666 +6 0 12"C/C +6 a 12"C/C +6 a 12"C/C +6 0 12"C/C a O`o METER VAULT N0.16 22'-0" 673.5 651.5 48" 656 +6 a 12"C/C +6 0 6"C/C +6 a 12"C/C +6 a 12"C/C O J ✓ O� c/ METER VAULT N0.17 I 13'-6" 673.5 660.0 54" 665 1 +6 0 12"C/C +6 0 12"C/C +6 0 12"C/C +6 o 12"C/C CA O= O! C/ a C; Ow Ca 11// O/ pgZ 5`V2 OO"-N S4A � ; �g/i g _. .. OLLING HILLS WATER TREATMENT PLANT ■ „ FACILITIES UPGRADE 8 40 MGD EXPANSION Is 1�-(SM>�7+01 , PHASE 4 - NEW HIGH SERVICE PUMP STATION S/ FrNso+na Nichols i eo+�.uN i - '•tii7lstZE�,opi�= Date: Reference Addendum Exhibit: � r ►�� L Sheet No. No. W JAN. 26, 2004 S-10 1 S-10 (A) Iabv EXISTING 2'C EXISTING 2'C EXISTING 2'C IN DUCTBANK IN DUCTBANK IN DUCTBANK EMH EMH EMH EMH 18 19 20A 20B 1 1 1 _/;l 1 EXISTING YC :� IN DUCTTy1NKLAB NEW 2'C ----- ------ 1 EXISTING 2'C BUILDING I j IN DUCTBANK NEW TELEPHONE EXISTING 2'C 5 Q BOARD i---- --------- ---------- 3 L----- —� EXISTING 2-4"C 1 1 I 1 EMH-21 I ADMINISTRATION ADMINISTRATION ADMINISTRATION I BUILDING CMH 2 BUILDING BUILDING I I 1 MECHANICAL HUB ROOM 1 0 EXISTING 2"C L--RDO -----------------J NEW 2'C E-2A IN DUCTBANK EXISTING 2 RACK 2 NEW RACK EMH-23 EAST EXISTING 2'C COMMUNICATIONS IN DUCTBANK BUILDING TELEPHONE do FOC RE—ROUTE A NOTES Q INSTALL 100 PAIR DB TELEPHONE CABLE (GENERAL CABLE E-010024DFC). Q INSTALL 1-24 FIBER MULTIMODE FOC AND 1-12 FIBER SINGLE MODE FOC. SEE DIV. 13. Q PROVIDE ATT 100 PAIR PROTECTOR BOX (189ECT1-100) AND ATT GAS FUSE PROTECTORS (106945538) ON EACH END. PROVIDE NEW 4' X 8' X 3/4- FIRE RESISTANT PLYWOOD TELEPHONE BACKBOARD AT EACH END. CONTACT DALE STEWART CITY OF FT. WORTH AT 817-329-7664 TO COORDINATE. Q4 LAB ELECTRICAL ROOM. Q LAB MECHANICAL ROOM. ruin4055 Warnu u" Plow. AiB, zoo ROLLING HILLS WATER TREATMENT PLANT Fort Morft Tara 78109-4= _ FACILITIES UPGRADE & 40 MGD EXPANSION Phom 17) 735 Fox - (677) 735-7491 �+.� •~ ��/ PHASE 4 - NEW HIGH SERVICE PUMP STATION �RO6QiT A NWAYS Jti '� 553041 Date: Reference Addendum Exhibit: Sheet No. No. NAL 6 JAN. 26, 2004 E2 E-2A SECTION L E-2 • (EXISTING) •38 ? 37 Q s .31 .• -; 3 34 •. SECTION M SECTIO N 42� Q, m Nis E-2 NM —2 � ) SECTION 0 E-2 4055 bA nwew„d P,®a Suft 200 . ROLLING HILLS WATER TREATMENT PLANT Fat Woed%(Tena.7e,0�,a®s }�I. FACILITIES UPGRADE & 40 MGD EXPANSION Fm» (517) 73:F7401 ?*•.. +/0 ��..A. PHASE 4 — NEW HIGH SERVICE PUMP STATION �ROBE1tT A KfJ.lA115 Ai 55304 Date: Reference Addendum Exhibit: Sheet No. No. i z� JAN. 26, 2004 E-2A E-2AA CONDUIT FROM TO CONTAINS SIZE COMMENTS A 0 SPARE CONDUIT SWILL FOLLOW THE ROUTE SHOWN 1 EMH-19 HSPS SPARE 2' lO FROM EMH-19, NEAR AIV-17, MV-16, EMH-20A, AIV-15, MV-14, THROUGH VALVE VAULT 9, VALVE 2 EMH-19 HSPS SPARE 2' 10 VAULT 8 AND INTO HSPS. PROVIDE NEW 2' X 2' X 2' HANDHOLE OUTSIDE OF MV-14, MV-15, MV-16 AND 3 EMH-19 HSPS SPARE 2' O MV-17. PROVIDE 4-27C FROM HAND HOLE TO EACH METER VAULT. SEE METER VAULT PLAN ON E-11. 4 EMH-19 HSPS SPARE 2' Q CONDUITS SHALL BE ROUTED THROUGH EACH EMH AND THROUGH VALVE VAULTS 8 AND 9. CONDUITS SWILL BE 5 AIV-17 MV-16 A1.A3 2' 1 SPARE STUBBED UP INSIDE HSPS IN THE SOUTHWEST CORNER NEXT TO THE WALL AND ROUTED AS SHOWN. 6 AIV-17 MV-16 F2.C2 2' 2 SPARE 7 AIV-16 EMH-20A A t 2' 2 SPARE 8 AIV-16 EMH-20A F2,F2,C2 C4 4 SPARE 9 EMH-20A MV-15 A t 2' 2 SPARE 10 EMH-20A MV-15 F2,F2,C4 2' 4 SPARE 11 MV-15 MV-14 A9 t 2' 3 SPARE 12 AIV-15 MV-14 1`2.1`2,1`2,C6 2' 6 SPARE 13 IAV-14 V V-9 t 2' — 14 AIV-14 V V-9 F2,F2,F2,F2 2' — 15 V V-9 V V-8 S t 2 — 16 V V-9 V V-8 F2.F2,F2,F2 2' — 17 V V-8 HSPS t 2' ROUTE TO TC 18 V V-8 HSPS F2.F2,F2,F2 2' ROUTE T t PANEL—HA 19 V V-8 EMH-24 FO t 2' 3 20 V V-9 EMH-24 SPARE 2' EMPTY 21 EMH-24 EAST COM. FO CABLE 2' — BLDG 22 EMH-24 EAST COMM ' SPARE 2' — LDG 23 EMH-24 EAST COM. SPARE 2' — BLDG 24 EMH-24 BT COM. SPARE 2' — LDG 25 AIV-14 CMH-2 Al2 2' 4 SPARE O 26 AIV-14 CMH-2 CT19 2' 11 SPARED 27 MV-14 CMH-2 SPARE 2- 28 AIV-14 CMH-2 SPARE 2- 29 ADMIN CMH-1 FO & PHONE 4' EXIST 30 ADMIN CMH-1 — 4' EXIST 31 CMH-1 LAB FO R PHONE 4' EXIST 32 CMH-1 LAB — 4' EXIST 33 ADMIN CMH-1 FO R PHONE 4' 34 ADMIN CMH-1 — 4' O4 35 HSPS V V-8 FO CABLE 36 PS — 36 CMH-1 EMH-21 FO CABLES 2' t 36 CMH-1 EMH-21 TELEPHONE 2' 36 CMH-1 EMH-21 SPARE 2' SPARE 36 CMH-1 EMH-21 SPARE 2' SPARE 36 CMH-1 EMH-21 SPARE 2' SPARE 36 CMH-1 EMH-21 SPARE 2' SPARE 36 CMH-1 EWH-21 SPARE 2' SPARE 36' CMH-1 EMH-21 I SPARE 2' SPARE 405,,Wwraftid Pka,,5iw 200 ROLLING HILLS WATER TREATMENT PLANT Fwt '"oftww r6�a;�j, 5 <;.• s� FACILITIES UPGRADE & 40 MGD EXPANSION 1-=- (617)las-7401 �,;• � ���'';✓�,35-7300 PHASE 4 — NEW HIGH SERVICE PUMP STATION lYttxtssQslOs�sle :soaem�ti wu.iws .i 55304 % Date: Reference Addendum Exhibit: .. Sheet No. No. JAN. 26, 2004 E-2A 0 E-2A6 i { € i t I "4 rNA H U U Ll U U U U H H U U U I G1, 4\ Q 0 P 10 p N, loe \ I i Ilei Ile- DETAIL GDETAIL A 1._4-0. NOTES: O1 EXTEND EXISTING DUCT13ANK AND TURN UP UNDER SWITCHGEAR. 02 EXTENT OF EXISTING DUCT BANK STUB OUTS. EXISITNG DUCTBANK IS INSTALLED APPROXIMATELY 10 FEET BELOW GRADE. 30 PROVIDE (8) SETS OF 3-500 KCMIL 5KV 1338 AIV-105, /4/0 GROUND IN 6- CONDUITS SHOWN. EXTEND 6" CONDUITS AS SHOWN. CONTRACTOR SHALL TERMINATE CONDUCTORS. COORDINATE WITH ONCOR FOR EXACT TERMINATION LOCATION AND CONDUCTOR TESTING. PROVIDE 6' LONG RADIUS PVC COATED RGS ELBOWS AND EXTEND UP ABOVE GRADE TO CONNECT TO ONCOR SUBSTATION EQUIPMENT. SEE E-4. Q EXISTING 6' STUBOUTS (8 EACH). SO SWITCHGEAR SG-1 INSTALLED UNDER EXISTING PHASE III CONTRACT. REFER TO SHT E-4 AIM h,I,,,,,Um Pla,, S„a, 2W ROLLING HILLS WATER TREATMENT PLANT fat Wath,T7�B. 76109-+ms5 ,..».,,.� FACILITIES UPGRADE & 40 MGD EXPANSION Fwt — (a1» 735-7300ass— ao _y;••' Fac- (a+;)735--7491 �; % .',� PHASE 4 - NEW HIGH SERVICE PUMP STATION .ROBERT ti..A,AMS.R., Date: Reference Addendum Exhibit: �'4F`•' �° Sheet No. No. II�'ONAL�� I t� r JAN. 26, 2004 E-3 0 E-3A ! ONCORE SUBSTATION r------------------------------------ _------------------- --------------- � E E E 3 Q i 1 E i S I ; E i E I E ; ! i t I -- ---�-- --�—_ _ ------�--- -- —_.—� 8 FIaQQ&F 21 2500AT 7 9 —t 52' 52 5 6 12 10 it 1200AT 120OAT NOTES OROVIDE (8) SETS OF 3-500 KCMIL 5KV 1335 MV-105, /4/0 GROUND IN EXISTING 6' CONDUITS. EXTEND 6' CONDUITS TO ONCOR METERING POINT. CONTRACTOR SHALL TERMINATE CONDUCTORS IN SG-1. COORDINATE WITH ONCOR FOR EXACT TERMINATION LOCATION AND FOR SUBSTATION TERMINATIONS AND CONDUCTOR TESTING. PROVIDE 6' LONG RADIUS PVC RGS ELBOWS TO CONNECT TO ONCOR SUBSTATION EQUIPMENT. SEE E-3. 2�HORT CIRCUIT AND PROTECTIVE DEVICE COORDINATION `'STUDY SHALL INCLUDE SETTINGS FOR THESE EXISTING CIRCUIT BREAKERS. CONTRACTOR SHALL COORDINATE WITH PHASE IN CONTRACTOR. SWITCHGEAR SG-1 INSTALLED UNDER EXISTING PHASE IN `CONTRACT. CONTRACTOR SHALL COORDINATE WITH PHASE IN CONTRACTOR. AIM k,,,,,s,,,,I Plmo, Su. 2W ROLLING HILLS WATER TREATMENT PLANT PFwt horma.u`T7. 5-7300ees ..•.�,�� FACILITIES UPGRADE & 40 MGD EXPANSION �. — (e17) 73s-7300 .�:• s Fm - (817)735-74011 �;� � PHASE 4 — NEW HIGH SERVICE PUMP STATION �R0--MT—NIWAMS JLC ss'3oa Date: Reference Addendum Exhibit: '4;S� CENS��•.- Sheet No. No. 1G p ``��•� JAN. 26, 2004 E-4 A E-4A O3 PLG-22 Q A2 TJB-O• MSG1 LS- (SEE PANEL SCHEDULE SHEET EY-1) Bi 3 2 Ci 5 O ® PNL-UPS VTT-7330-+B MFG. CABLE MFG. CABLE VIT-7330-+A VE-7330-+A VE-7330-+8 VIBRATION DETECTOR DIAGRAM 3 NTS • 1-4 (NO 5 FUTURE) C4 MFG. CABLE PLC-22 LSHHH-7325 CIO CIO LSHH-7325 TJB-07 WWLRCP MSCI LSLL-7325 LSLLL-7325 Bt PNL-UPS 0 WETWELL LEVEL RELAY PANEL (WWLRP) WIRING DIAGRAM 4 NTS - NOTES O /4/0 BARE COPPER. TIE TO EXISTING GROUND GRID. 0 SEE NOTE 3 ON SHEET E-9. O ROUTE VIA CABLE TRAY. O RUN THROUGH WET WELL ROOF SLAB. O TERMINATE CONDUCTORS IN TJB. © PROVIDE NEMA 20C ALUMINUM 18- WIDE WITH 6- SIDE RAIL LADDER BOTTOM WITH RUNGS EVERY 6 © INCHES. SUPPORT TRAY EVERY 8 FEET. Foss mt.moeaw Plmo zao ROLLING HILLS WATER TREATMENT PLANT Fat - ( Togo7 5-73 Fear .rte, FACILITIES UPGRADE & 40 MGD EXPANSION Pna,.- (e,� ass-rano ;e:•' ,fit F= - (817) 735-701 ���, PHASE 4 — NEW HIGH SERVICE PUMP STATION .ROON,A..WA16 Jto 55304 " s Date: Reference Addendum Exhibit: � _ Sheet No. No. 1 26 o'L°"AL JAN. 26, 2004 E-8 E-8A CONDUR 4' LONG CLAMP SWEEP ELBOW TO MOTOR POWER d. TERMINAL BOX SEE DETAIL A THIS SHEET L' 1 ALUMINUM CABLE TRAY (TYP) 316 SS FASTENING HARDWARE STAINLESS STEEL CANTILEVER ! SUPPORT, ANCHORS, CLAMPS AND ALL HARDWARE (TYP) i i 316 SS ANCHORS (TYP) ALL RTD AND 4-20mA CONDUCTORS SHALL BE to IN CONDUIT ROUTE TO MOTOR, DOWN WALL 6c THROUGH SLAB i HIGH SERVICE PUMP STATION POWER AND CONTROL DETAIL 1 NTs - roll ,= P� �,,,zoo ROLLING HILLS WATER TREATMENT PLANT Fart Wkwlk Tem. 76109-+ens ;�� ........f � FACILITIES UPGRADE & 40 MGD EXPANSION Phw — (811) 7_35-MWy.•' �e"wd Fax - (817)735--7491 � PHASE 4 — NEW HIGH SERVICE PUMP STATION %mom&eau a m% 55304 ' s Date: Reference Addendum Exhibit: Sheet No. No. 1 Zfj a �•� JAN. 26, 2004 E-10 E-10A 120/208V, 30, 4W PANEL LA NEMA 12 t00A/3P MAIN SURFACE MOUNTED CIRCUIT# SERVES C/B WIRE CONDUIT 1,2 ELECTRICAL ROOM LIGHTS 20A/1P 2#12 3/4' 3,4 ELECTRICAL ROOM RECEPTACLES (GFl) 2OA/1P 2#12 3/4- 5,6 VALVE ROOM LIGHTS 2OA/1P 2#12 3/4' 7 VALVE ROOM RECEPTACLES (GFl) 2OA/1P 2#12 3/4' 8,9 OUTSIDE LIGHTS 3OA/1P 2#10 3/4' 10,11 OUTSIDE RECEPTACLES (GFI) 2OA/1P 2#12 3/4' 12 BLOW DOWN STATION-1 20A/lP 2#12 3/4' 13 BLOW DOWN STATION-2 2GA/1P 2#12 3/4' 14 SPARE 3OA/1P — — 15 SPARE 3OA/1P — — 16 WETWELL DEWATERING PUMP RECPTICLE 3OA/1P 2#10 3/4- 17 TCP-1 20A/1P 2#12 3/4' 18 OUTSIDE LIGHTS 3OA/1P 2#10 3/4- 19 AIR DRYER 3OA/1P 2#10 3/4' 20 AIR FILTER 20A/lP 2#12 3/4' 25,27,29 ELECTRICAL ROOM HEATERS 30A/3P 2#10 3/4' 26,28,30 PUMP ROOM HEATERS 30A/3P 2#10 3/4- 31 UPS 60A/iP 2#6 1' 35-39 HEAT TRACE 2OA/113 2#12 3/4' 21-24, 32-34 & 40-42 SPACE — — — 4055 Kmalional P,® sun. zoo ROLLING HILLS WATER TREATMENT PLANT pFwt1m Womb, 70109-4895 tE•,, 1 ,,, _ (81»17) 735-7300 _y:*..• ••�..t�� FACILITIES UPGRADE & 40 MGD EXPANSION Fm - (817)735-7491 � ��,� PHASE 4 — NEW HIGH SERVICE PUMP STATION �s5'" soa`:Q',' Date: Reference Addendum Exhibit: Sheet No. No. JAN. 26, 2004 EY-1 EY-1A 277/480V, 3 PH, 4W [PANEL HA NEMA 12 225A/3P AWN BREAKER SURFACE MOUNTED CIRCUIT# SERVES C/B WIRE CONDUIT 1,3,5 AIR COMPRESSER 3OA/3P 3110 3/4' 2,4,6 DRAIN SUMP PUMP 2OA/3P 3110 3/4' 7,9,11 WETWELL DEWATERING 2OA/3P 3110 3/4' 8,10,12 SF-1 STARTER 20A/3P 3112 3/4' 13,15,17 SF-2 STARTER 20A/3P 3112 3/4' 14,16,18 EF-1 STARTER 20A/3P 3112 3/4' 19,21,23 EF-2 STARTER 20A/3P 3112 3/4' 20,22.24 AIV-14 2OA/3P 318 3/4' 28,28,30 AIV-15 20A/3P 318 3/4' 32,34,36 AIV-16 20A/3P 318 3/4' 38,40,42 AIV-17 20A/3P 318 3/4' 25,27,29, 31,33,35, SPACE - - - 37,39,41 240/12OV, 1 PH, 3W PANEL UPS NEMA 12 6OA/1P MAIN BREAKER SURFACE MOUNTED CIRCUIT# SERVES C/B WIRE CONDUIT I LIT 7330 20A/1 P 2112 3/4' 2 PLC-22 20A/1P 2112 3/4' 3 WWLRP 20A/1P 2112 3/4' 4 VIT 7330-01/MULTIUN 369 20A/1 P 2112 3/4' 5 VIT 7330-02/MULTIUN 369 20A/1P 2112 3/4' 6 VIT 7330-03/MULTIUN 369 20A/1P 2112 3/4' 7 VIT 7330-04/MULTIUN 369 20A/1P 2112 3/4' 8 FUTURE 20A/1P - - 9 AWN 1 MULTIUN 750 20A/1P 2112 3/4' 10 MAIN 2 MULTIUN 750 20A/1 P 2112 3/4' 11,12 SPARE 20A/lP - - rill 4= I,t,,,,+onW P+mm• Suft zoo ROLLING HILLS WATER TREATMENT PLANT Fort Worft Taw 76109-4895 t, . ., t,4 FACILITIES UPGRADE & 40 MGD EXPANSION F= — (e+>)735-740+ PHASE 4 — NEW HIGH SERVICE PUMP STATION 55304�Ws Date: Reference Addendum Exhibit: Sheet No. No. JAN. 26, 2004 EY-1 EY-1 8 D 316 SS 3/6'BEA, CLAMP(TYP) 316 SS TALL ALUMININ THREAD ROD CABLE TRAY (Typ) 316 SS FASTENING HARDWARE 316 SS NUTS. WASHERS(TYP) STSL STEEL SLOTTED CHANNEL K CABLE TRAY DETAIL NTS TRAPEZE TRAY SUPPORT ,ox h,tm„Ba„i Pte®.Suft Zoo ROLLING HILLS WATER TREATMENT PLANT Fat Worth,Toes 761109-40115FACILITIES UPGRADE & 40 MGD EXPANSION Rear x (017)715-7300 q;:•• 1 I= (817)735-7411 PHASE 4 NEW HIGH SERVICE PUMP STATION /R06ERY A.11wAMs Jt; 04 Date: Reference Addendum Exhibit: � 553 '�S Sheet No. No. / JAN. 26, 2004 EZ-1 EZ-1A OF CITY OF FORT WORTH TEXAS '��tE '� ROLLING HILLS WATER TREATMENT PLANT -47 F° �`p* PHASE 4—NEW HIGH SERVICE PUMP STATION ,•,» ° PROJECT No. PW77-060770510050 • ALAN C. HUTSON ADDENDUM N0.2 �`� 'O 90179 a;y• l�� January 30,2004 o�E��CENSE� g'10NAL BID DATE: Thursday, February 5, 2004, 2:00 pm The following additions, deletions, modifications, or clarifications shall be made to the appropriate sections of the plans and specifications and shall become a part of the Contract Documents. Bidders shall acknowledge receipt of this Addendum in the space provided on the Bid form. TECHNICAL SPECIFICATIONS: A2-1 SECTION 02202—PIPELINE EXCAVATION AND BACKFILL A. Reference Page 02202-8, Paragraph 3.02.G.1. Delete paragraph c in its entirety and replace with the following paragraphs: 'c. Place the third lift of granular embedment material in the trench simultaneously and evenly on both sides of the pipe for the full width of the trench to a depth of 0.7 times the outside diameter of the pipe using internal vibration or mechanical tamping. Compaction of granular embedment in this zone shall be to a minimum of 95% maximum density as measured by ASTM D 4253. d. Place the fourth lift of granular embedment material in the trench simultaneously up to the top of the pipe zone. Compaction of granular embedment in this zone shall be to a minimum of 95% maximum density as measured by ASTM D 4253.° A2-2 SECTION 11212—VERTICAL TURBINE PUMPING UNITS A. Reference Page 11212-2, Paragraph 1.04 SUBMITTALS Addition: Add Paragraph E as follows: 'E. Design Information. For each motor specified under this Section, provide the following design information on the Electric Motor Questionnaire included at the end of this Specification. 1. Manufacturer. 2. Rated full load horsepower. 3. Rated volts. 4. Number of phases. S. Frequency in hertz. 6. Full load amperes(FLA). 7. No load amperes. 8. Locked rotor amperes(LRA)at rated voltage or NEMA code letter. 9. Synchronous speed (SRPM). 10. Guaranteed maximum slip at full load in percent. 11. NEMA insulation system classification and description of manufacturer's method of application. 12. Temperature rise at rated full load, by resistance tIm per13. Maximum ambient temperature for which motor is 1000, 14. Maximum air flow through motor in cfm at maximuAMU 15. Service factor.Addendum No. 2 2-1 CDM00507—Rolling Hills WTP—High Service Pump Station 16. Frame size, outline dimensions, net weight and weight of rotating element. For all motors include surge protection dimensions and weight. 17. The limiting temperature rise shall be by resistive temperature detector method. 18. NEMA machine type(ODP, WP-1,TEFC, etc.). 19. Bearing size and calculation. 20. Lubrication (compatible with pump manufacture). 21. Safe stall time. 22. Maximum acceleration time with NEMA standard Wk2 value, at rated voltage and at 90% of rated voltage. 23. Number of safe starts in succession when starting from a 50 degree Celsius ambient, intermediate waiting periods and other conditions for driving equipment with a NEMA standard wk2 value. 24. Efficiency at 1/4, 1/2, 3/4,full load, and service factor. 25. Power factor at 1/4, 1/2, 3/4,full load, and service factor. 26. Space heater voltage and wattage. 27. Surge protection information including mounting details. 28. Platinum resistance temperature detector(RTD) literature with wiring diagram. 29. Motor Damage Curve, safe stall time curve, and acceleration curve at 100%, 90% and 80%of motor rated terminal voltages applied. B. Reference Page 11212-2, Paragraph 1.04 SUBMITTALS Addition: Add Paragraph E as follows: 'F. Shop Drawings and Product Data. Provide the following information. 1. Data to be included on nameplate. 2. Dimensioned outline drawings. 3. Net weight of assembled motor and net weight of heaviest part to be handled ` during field assembly or disassembly. 4. Dimensions and internal arrangements of terminal boxes. 5. Stator and rotor thermal damage curves for motor located in a 50 C ambient. 6. Actual information on manufactured unit when in variance with information previously submitted under paragraph 1.04.E, Submittals." A2-3 SECTION 13315 INSTRUMENTATION SUBSYSTEM A. Reference Page 13315-5 Paragraph 13315 2.02 B. 5.b. Delete the paragraph in its entirety. Replace with following paragraph 13315 2.02 B. 5.b. 'b. Engineer-approved equal.Any engineer-approved equal must meet functional requirements and include Profibus DP interface.' h . A24 Section 15101 —GATE VALVES A. Reference Page 15101-1, Paragraph 1.03 Add the following lines to the paragraph: "AWWA C-515 'Reduced-Wall, Resilient-Seated Gate Valves for Water Supply Service" "Applicable standards of the Fort Worth Water Department's Specifications shall apply. In case of conflicts or discrepancies between this specification and the Water Departments Specifications, the Fort Worth Water Department's Specifications shall govern." B. Reference Page 15101-1, Paragraph 2.01.A. Addendum No. 2 00902-2 CDM00507—Rolling Hills WTP—High Service Pump Station Add the following paragraph: '4. Gate Valves 36"and larger may also be in accordance with AWWA C-515 and shall be rated for the pressure class as indicated. Resilient Wedge Gate Valves as manufactured by America Flow Control Series 2500 are acceptable for this project." C. Reference Page 15101-2, Paragraph 2.01,13. Add the following sentence to the paragraph: "Gate for resilient wedge valves shall be ductile iron,fully encapsulated with EPDM rubber." D. Reference Page 15101-2, Paragraph 2.01.C. Delete the first sentence in its entirety and replace with the following "Operators shall turn clockwise to open the valve." E. Reference Page 15101-3, Paragraph 3.03. Add the following lines to the gate valve schedule: PUMP STATION AND MAIN LINES . VALVEt,IUMBE f PRESSlR1 ��. .00tOI�F 0111ETR REQUIRED a Ij ,, lRAT Jr< Valve Vault# 16 48" 1 200 psi 2" Sq. Nut Drain Sump 3" 1 125 psi Handwheel Pre-cast Vault "Note: This change reflects the actual number of gate valves shown on Sheet C-4 and P- 9 of the drawings." A2-5 Section 15103—BUTTERFLY VALVES A. Reference Page 15103-2, Paragraph 1.04 Add the following line to the paragraph: 'Applicable standards of the Fort Worth Water Department's Specifications shall apply. In case of conflicts or discrepancies between this specification and the Water Departments Specifications, the Fort Worth Water Department's Specifications shall govern.' B. Reference Page 15103-3, Paragraph 2.01.C.1. Delete the last sentence in its entirety and replace with the following 'The direction of the manual rotation shall be clockwise to open the valve.' A2-6 Section 15110—PUMP CONTROL BALL VALVES A. Reference Page 15110-1, Paragraph 1.02.A.2. Addition: Miller shall be added to the list of acceptable air-over-oil actuator manufacturers. B. Reference Page 15110-4, Paragraph 1.05.A. Addendum No. 2 00902-3 CDM00507—Rolling Hills WTP—High Service Pump Station In the fifth paragraph, delete the last sentence in its entirety and replace with the following: "Rate of closings shall be manually adjustable from one(1) minute to ten(10) minutes for complete valve travel." In the sixth paragraph, delete the last sentence in its entirety and replace with the following: "The"different-than-normal"closing rate shall be manually adjustable from one (1) minute to ten(10) minutes for complete valve travel." C. Reference Page 15110-7, Paragraph 2.01.1. Modification: The required speed of operation shall be modified as follows: "Normal Open— 60 seconds minimum 600 seconds maximum Normal Close— 60 seconds minimum 600 seconds maximum Emergency Close— 60 seconds minimum 600 seconds maximum" A2-7 SECTION 15117—AIR RELEASE AND AIR AND VACUUM VALVES A. Reference Page 15117-2, paragraph.3.03 Delete the air valve schedule in its entirety and replace with the following: :- ------ Pump Discharge Piping 5 4" CAV 200 psi Pump Discharge Piping 4 6" CAVSC 200 psi SS 3 Main Piping 1 6" CAV 200 psi Valve Vault No. 15 1 2" AV 200 psi Valve Vault No. 11 1 2" AV 200 psi Valve Vault No. 13 1 2" AV 200 Valve Vault No. 14 1 2" AV 200 �si A2-8 SECTION 15126—PUMP CONTROL CONE VALVES A. Reference Page 15126-1, Paragraph 1.02.A.2. Addition: Miller shall be added to the list of acceptable air-over-oil actuator manufacturers. B. Reference Page 15126-4, Paragraph 1.05.A. In the fifth paragraph, delete the last sentence in its entirety and replace with the following: "Rate of closings shall be manually adjustable from one(1) minute to ten(10) minutes for complete valve travel." Addendum No. 2 00902-4 CDM00507—Rolling Hills WTP—High Service Pump Station In the sixth paragraph, delete the last sentence in its entirety and replace with the following: "The"different-than-normal"closing rate shall be manually adjustable from one (1)minute to ten(10)minutes for complete valve travel." C. Reference Page 15126-6, Paragraph 2.01.H. Modification: The required speed of operation shall be modified as follows: "Normal Open- 60 seconds minimum 600 seconds maximum Normal Close- 60 seconds minimum 600 seconds maximum Emergency Close- 60 seconds minimum 600 seconds maximum' A2-9 SECTION 15136-MISCELLANEOUS VALVES AND APPURTENANCES A. Reference Page 15136-2, Paragraph 2.08. Delete the paragraph in its entirety and replace with the following: '2.08 FLANGE INSULATION KITS A. Insulating flange kits shall be installed according to manufacturer's recommendations. All flange gaskets shall be 1/8" thick,Type E, full- faced flange gaskets made of rubber and suitable for the pressure class of the adjacent pipe. The insulating half sleeves (full-length sleeves cut in half)shall be polyethylene. The insulating washers shall be made of laminated fabric reinforced phenolic. Double washers (steel and phenolic)shall be used on each end. All insulating material shall be of a type designated by the manufacturer as suitable for use under the design conditions. B. Insulating Flange Resistance-After installation, the Contractor shall measure the electrical resistance across the flange with an ohmmeter. The minimum acceptable resistance shall be 50,000 ohms. The pipe shall be empty at the time of test. This test shall be made with at least one side of the flanged joint ungrounded, or if both sides of the flange joint are grounded, a test voltage of 20 millivolts shall be used. F C. Bypassing Insulating Flanges-Care shall be exercised to avoid bypassing(shorting)the insulating flanges with small diameter piping, instrumentation lines, miscellaneous cable,wire rope, or other metallic objects and electrical "grounds". Where such metallic piping or conduits are required, they shall be electrically insulated by use of nonmetallic conduits or with approved insulating flanges or bushings. In no case shall an electrical jumper be used across the insulating flange or joint." B. Reference Page 15136-2 Add the following paragraphs: "2.10 SWING CHECK VALVES A 3-inch Rubber flapper swing check valves shall be furnished at the wet well drain sump. The check valves used shall be rubber flapper swing check valves Addendum No.2 00902-5 CDM00507-Rolling Hills WTP-High Service Pump Station unless otherwise specified. The valve disc shall absolutely prevent the return of water or gas back through the valve when the inlet pressure decreases below the delivery pressure. The valve shall be tight-seating. Swing check valves shall be designed for 50 psi working pressure and be furnished with ANSI 125 pound flanges. The valves shall be suitable for buried service, in which case, stainless steel cover bolts must be furnished. The valve body and cover shall be ASTM A126, Class B heavily constructed cast iron with flow area equal or greater than nominal pipe flow area. Disc shall be Buna-N, meeting ASTM D2000. Rubber flapper valves shall be series 500 Swing Flex by Val-Matic or series 100 by APCO. 2.11 DUCKBILL CHECK VALVES A 4-inch Duckbill check valve shall be furnished at the sanitary sewer manhole tie-in as indicated on the drawings. Duckbill check valves shall be of the flow- operated check type with a slip-on end connection. Inlet port areas shall be 100% of the mating pipe port size. The port area shall contour down to a duckbill which shall allow passage of flow in one direction while preventing reverse flow. Valves shall open in the proper direction under two inches or more of pressure, and shall withstand up to ten feet of back pressure. Valves shall be designed to slip over the specified pipe outside diameter, and shall be attached to the pipe by means of clamps furnished by the valve manufacturer. Valves shall be of one piece neoprene rubber construction with a fabric reinforcement,with a protective EPDM exterior wrapping for protection against ultraviolet radiation. Valves shall be Red Valve Tide Flex Check Valves or approved equal." A2-10 SECTION 15145-SUBMERSIBLE SUMP PUMP A. Reference Page 15145-1, Paragraph 1.02.A. Addition: Add Barnes to the list of acceptable manufacturers B. Reference Page 15145-1, Paragraph 2.01.13. Delete Paragraph 2.01.13. in its entirety and replace with the following. "B. The sump pumps provided for the existing plant vaults shall be Hydromatic, or approved equal." C. Reference Page 15145-1, Paragraph 2.02.13. Delete Paragraph 2.02.13. in its entirety and replace with the following. "13. Seven Owner furnished sump pumps shall be removed from seven existing flow } meter vaults. Five of these sump pumps shall be installed in the five flow meter vaults constructed under this Contract. The two remaining sump pumps shall be turned over to the Owner. Furnish seven (7) new sump pumps as part of this contract and install in seven existing plant vaults. The new sump pumps shall have a capacity of not less than 20 gpm at 35 ft of total dynamic head.The pumps shall be equipped for automatic operation." D. Reference Page 15145-2, Paragraph 2.03.8. Delete"113 HP"and replace with"maximum% HP". A2-11 SECTION 16000—ELECTRICAL—GENERAL PROVISIONS h A. Reference Page 16000-2, Paragraph 1.03.B.6 Addendum No. 2 00902-6 CDM00507—Rolling Hills WTP—High Service Pump Station h Modification: Delete the paragraph. Shop drawings for Medium Voltage Motors are included under Section 11212. B. Reference Pagel 6000-4, Paragraph 1.06.C. Delete this paragraph in its entirety C. Reference Pagel 6000-4, Paragraph 1.06.D. Delete the last sentence of this paragraph in its entirety D. Reference Pagel 6000-4, Paragraph 1.06.G. Delete this paragraph in its entirety A2-12 SECTION 16110-RACEWAYS, BOXES, FITTINGS, AND SUPPORTS A. Reference Page 16110-4, Paragraph 3.04.F. Modification: Remove the reference to aluminum. All slotted channel shall be stainless steel. A2-13 SECTION 16170—METAL FRAMING A. Reference Page 16170-1, Paragraph 2.02.A Modification: Remove the reference to aluminum slotted channel. All slotted channel shall be stainless steel.. B. Reference Page 16170-1, Paragraph 3.01.6 Modification: Modify the paragraph to read as follows: Use stainless steel channels with all aluminum conduits. The aluminum conduit shall not come in direct contact with concrete A2-14 SECTION 16345—MEDIUM VOLTAGE SWITCHGEAR A. Reference Page 16345-1, Paragraph 1.01A Change"metal enclosed"to"metal clad" in the first and second sentence. B. Reference Page 16345-1, Paragraph 2.01A Change"metal enclosed"to"metal clad" in the first sentence. C. Reference Page 16345-7, Paragraph 3.04.A. Modification: The warranty shall start at final acceptance. A2-15 SECTION 16411- POWER SYSTEM STUDY A. Reference Page 16411-1, Paragraph 1.01 A. Modification: Replace the paragraph with the following: Addendum No.2 00902-7 CDM00507—Rolling Hills WTP—High Service Pump Station "General: This section specifies that the CONTRACTOR prepare a short circuit and coordination study for the Rolling WTP Hills Phase IV High Service Pump Station electrical power system. The electrical power system shall be deemed to include the following: • Utility company's substation transformer located in the new Oncor Group substation feeding the OWNER'S switchgear SG1, ■ Electric Utility Company's line side transformer protective device, ■ The OWNER'S 4160V-power Switchgear SG-1 main installed under Phase III • The OWNER'S 4160V-power Switchgear SGA feeder breakers installed under Phase III dedicated to feed the new High Service Pump Station constructed under this project • The two sets of power cables from SGA to the High Service Pump Station Main Switchgear ■ The medium voltage starters ■ The OWNER'S 416OV-480V dry-type transformer ■ The 480V power distribution system at the Pump Station. The CONTRACTOR shall obtain all required data fro the field or shop drawings provided under these specifications. The CONTRACTOR shall obtain a copy of the short circuit and coordination study completed for the Phase III project from the OWNER, and incorporate and coordinate the recommended protective device settings with the findings and protective device settings in this study. Include a copy of that report as an appendix in this study. The short circuit study shall include all motor contributions from the high service medium voltage motors and the 480 volt motors located in the High Service Pump Station. The short circuit and coordination study reports shall provide an evaluation of the electrical power systems and the model numbers and settings of the protective relays or devices and metering or motor monitoring devices for setting by the CONTRACTOR. The Study shall include settings for all motor protective relays and electric system monitoring devices, including all RTD alarm and trip settings. The Study shall include all settings for the Multilin 750 relays on the main and tie breakers, and all settings for the Multilin 369 motor protective relays specified under other sections. The study shall include circuits down to and including all 480 volt circuit breakers and motor overload devices, and the main breaker in the 208Y/120 volt lighting panel boards! A2-16 SECTION 16481 —MEDIUM VOLTAGE MOTOR CONTROL CENTERS A. Reference Page 16481-1, Paragraph 1.01.13 Addition: The switchgear specked under this section shall all be"metal enclosed"type switchgear. B. Reference Page 16481-7, Paragraph 3.03A. Modification: The warranty shall start at final acceptance. DRAWINGS: A2-17 SHEET C-1 ■ A. A new flexbase road shall be installed as shown in the attached Exhibit C-1(A). A description of required signage is also noted on the Exhibit. A2-18 SHEET C-2, SITE PLAN A. Addition: Regarding the proposed 8"thick flexbase road east of then new pump station to be constructed under this contract, the curb and gutter on the-north end will need to be removed. Curb, gutter and paving does not exist on the southern end of the road and will not be installed until Phase 5 of the Project. The centerline of the road is E5117.71. Addendum No. 2 00902-8 CDM00507—Rolling Hills WTP—High Service Pump Station A2-19 SHEET C-5, YARD PIPING PLAN III A. Reference Note for tie-in to the sanitary sewer manhole Delete the following sentence: "Install buried check valve 2'from the manhole." Replace with the following sentence: "Install a 4-inch Duckbill check valve on the end of the 4' pipe, inside the SS manhole. Reference Spec 15136.° A2-20 SHEET C-8, VALVE VAULT AND METER VAULT DETAILS A. Reference the Valve Vault Schedule Add the following line to the schedule: Valve Vault No. Size Elevations (P) Pipeline Centerline EI."N" 16 48" 674.0 663.0 A2-21 SHEET C-8(A), METER VAULT DETAILS Modification: The dimensions of the sump shall be 2'wide x 2'long x 2' deep. A2-22 SHEET C-9, MISCELLANEOUS PIPE DETAILS A. Reference Detail A Add the following general note: 'For areas where a new pipeline crosses under and an existing pipeline, contractor shall take necessary measure to protect the existing pipe. No shutdowns of the existing line will be allowed. Contractor shall place granular embedment in the new pipe zone and shall cavy the granular embedment up through the pipe zone of the existing pipe." B. Reference Detail D, Typical Trench Detail for Open Cut Asphalt Pavement Replacement Areas Delete the following note: "Backfill Material 95% standard proctor density" And replace with the following note: "Compacted Granular Embedment compacted to 95% Maximum Density" C. Reference Detail G, Typical Joint Detail—Welded Joint for Mortar Coated Steel Pipe Modification: The full circumferential fillet weld thickness is currently listed at 5/16". Delete this thickness and replace with the thickness Y, the thickness of the steel cylinder. Addendum No. 2 00902-9 CDM00507—Rolling Hills WTP—High Service Pump Station A2-23 SHEET P-1, PIPING FLOOR PLAN A. Addition: The concrete pipe support for the future pump control valve shall be installed in this contract. The support and base plate size shall be the same as required for the 30" pump control valves. B. Delete Sheet P-1 in its entirety and replace with the attached Sheet P-1. The drawing has been modified to remove several 30"and 36"flanges and to replace the buried 60" and 72' blind flanges on the end of the header pipes with welded dished head plugs. C. Modification: The contractor shall coordinate the dimensions for the leave-outs in the precast panels for the O.D. of the discharge piping. The leave-outs shall not be oversized, but shall provide only link-seal clearance. Some of the flanges have been eliminated, making it easier to install the pipe through the panels. Flanges must be shop applied; however, in line welds of the pipe will be permitted if necessary. A2-24 SHEET P-2, PIPING SECTION A. Add the following notes: '12. Gravel shall be 4'thick. Excavate the top 4"of topsoil and apply a soil sterilent. Lay the gravel on top of a 6 mil black poly liner with 8"overlap on all sides. The limits of the gravel are from the concrete driveway approach slab, the full length of the valve building, up to the edge of the sidewalk, approximately 69' in length and 30' in width. 13. A flange insulating kit shall be installed on the last flange before burial on the 36" pipes running vertically into the 60"and 72" header pipes. 10 total." B. Addition: A stainless steel ladder is shown on the north wall. Re:A/C-10. A stainless steel i ladder shall also be installed on the south wall below the hatch opening. A2-25 SHEET P-4, VALVE DETAILS A. Reference Detail A Modification: Steel vent pipe shall be schedule 40 B. Reference Detail B, Note 1 Modification: By-pass valves, piping and flanges shall be rated for 200 psi. C. Reference Detail C Delete note 3 in its entirety and replace with the following: '3. On air valve drain piping, contactor shall furnish steel pipe, anchors, and fasteners to securely attach pipe to the discharge pipe." A2-26 SHEET P-5, THRUST HARNESS AND PIPE SUPPORT DETAILS A. Reference Detail E Modification: Grout under pump control valve base plate shall be grouted with non-shrink epoxy structural grout as specified in Spec. 3300. Addendum No. 2 00902-10 CDM00507—Rolling Hills WTP—High Service Pump Station F A2-27 SHEET P-6, PVC PNEUMATIC SCHEMATIC Modification: The contractor shall provide a control panels, piping and cylinders for the 4 pump control valves to be installed in this contract. For the future pump slot,the contractor will provide a Y4"copper pipe, ball valve, union, and a capped end. A2-28 SHEET P-8, MISCELLANEOUS DETAILS A. Reference Detail K, Penetration for Precast Walls Delete Detail K in its entirety. Add the revised Detail K and new Detail L as shown on the attached Exhibit P-8(A). A2-29 SHEET P-9,WET WELL AND FLOOR DRAIN SUMP PUMP DETAILS A. Reference Section 1, Plan of Wet Well Sump Modification: Pipe shall be 4' Ductile Iron. The pipe material is shown correctly in the section view. B. Reference Section 3, Drain Sump Modification: In the precast vault, the contractor shall install a victaulic coupling, a 3'check valve as referenced in Spec 15346, and a 3"gate valve. A2-30 SHEET A-8, DOOR DETAIL, FINISH SCHEDULE, DOOR SCHEDULE " A. Reference Room Finish Key, Mark C1 Delete the sentence in its entirety and replace with the following sentence: "Paint the roof trusses, roof deck, and roof hatch curbs. Re: Section 09900." A2-31 SHEET E-11, METER VAULTS 14-17 PLANS AND DETAILS A. Reference: Detail 1 and Detail 2. Provide stainless steel sun shades to protect the sump pump and metering enclosures from direct exposure to sunlight.The sun shade shall consist of a back and top with triangle shaped sides that extend from the front of the top to the bottom of the back plate. Mount the enclosure on stainless steel slotted channel to provide an air gap between the back of the enclosure and the back plate of the sun shield to which it is mounted. Do NOT mount the enclosure directly to the back of the sun shade. The sun shades shall extend 18-inches beyond the front of the enclosure on top(including the spacing caused by mounting on the specified slotted channel)and shall angle down from the outer edge of the top cover to the back plate to which the enclosure is mounted. Provide 3-inch clearance on both sides and top of the enclosure. A2-32 SHEET EY-4, SCHEMATIC 1 A. General: Final timer ranges and setting shall be provided after shop drawing review for the pump control valves is completed. All timers shall be adjusted in the field during startup for proper startup, protection and shutdown operations. B. Rung 4: Change the range for TDE-1 to 10 minuets. The setting of 2 minutes shall remain the same to be adjusted in the field during startup. C. Rung 208: Change TDE-32 to CR-32 Addendum No.2 00902-11 CDM00507—Rolling Hills WTP—High Service Pump Station D. Rung 210: Change TDE-34 to TDD-34 A2-33 EXHIBIT E-2A,ADDENDUM 1 DETAIL A—TELEPHONE AND FOC RE-ROUTE A. Laboratory Building: General: There are two 4-inch conduits existing from CMH-1 into the Libratory Building Electrical Room. One of the conduits is presently empty with a pull string installed. The second conduit contains a 200-pair telephone cable and a fiber optics cable. The empty 4-inch conduit is to be used to install the new 100-pair telephone cable and the new fiber optics cables specified in Addendum No. 1. The CONTRACTOR shall provide the following: 1. Install a new telephone backboard consisting of a 2.5-foot X 5-foot X 3.4-inch sheet of fire proof plywood on the west wall next to the existing telephone backboard in the electrical room. 2. Relocate the thermostat mounted next to the wall switch to accommodate the new telephone backboard. 3. Install the new 100 pair telephone protector can on the new telephone backboard. 4. Terminate the 100 pair telephone cable at both ends and ring out all pairs. If more than 5% of the pair do not pass the ring-out test, remove and replace and reinstall the cable with no expense to the OWNER. 5. The existing 200 pair telephone cable that exists between the Libratory Building and .� the Administration Building shall remain in service a minimum of two weeks after the new 100 pair telephone cable is installed, terminated and tested. 6. After the City has switched over the Libratory Building telephone service to the new cable, the CONTRACTOR shall remove the existing 200 pair telephone cable and the associated termination enclosures, and remove from the project site. The CONTRACTOR shall coordinate with the City to prevent interruption to the Libratory Building telephone service. 7. Pull the 24-fiber multimode and the 12-fiber single mode cables from the East Hub into the Laboratory Building as specified under Addendum No. 1. 8. Extend the fiber optics cables to the rack in the mechanical room. 9. Install the new patch panels in the existing rack, terminate and test all fibers in accordance with the contract specifications. 10. Allow at least two weeks after installation and testing of the fiber optics cables before removing the existing fiber optics cables that exist between the Libratory Building and the Administration Building. 11. Remove the existing fiber optics cable between the Libratory Building and the Administration Building after the City has switched the Libratory network to the new fiber optics cable. B. Administration Building: The CONTRACTOR shall provide the following: 1. Install four 4-foot X 8-foot X 3.4-inch sheet of fire proof plywood on the west wall of the Hub Room. 2. Delete the 4-foot X 8-foot X 3.4-inch sheet of fire proof plywood specified in Addendum No. 1 to be installed in the Mechanical Room. 3. Mount the 100 pair protector can on the new telephone backboard in the Hub Room. Coordinate with the City for the exact location. Addendum No. 2 00902-12 CDM00507—Rolling Hills WTP—High Service Pump Station 4. Terminate and test all 100 pair as specified above. A2-34 EXHIBIT E-3A, ADDENDUM 1 DETAIL A(Shows connections between Switchgear SG-1 and the new Oncor Substation) A. The CONTRACTOR shall provide the following: 1. The underground portion of the conduits shall be PVC. 2. The tum up transition from underground to exposed shall be PVC-coated rigid steel. 3. Provide 10 feet of PVC-coated rigid steel above ground. 4. Provide cable seals at the end of the PVC coated steel riser to prevent rain and dirt entry. 5. Provide 5 kV outdoor cable terminators(3M or Raychem or equal as acceptable to Oncor)on each conductor at the Oncor Substation end and leave loose for final connection by Oncor to their equipment. Provide bolts, nuts and Bellville washers (or per Oncor's requirements)for their use in making the final connection. 6. Provide indoor 5 kV cable terminators, bolts, nuts and Bellville washers for connection to the incoming line terminals in the OWNER'S Switchgear SG-1. 7. Test the cables per manufacturer's requirements and Section 16121. A2-35 ADD THE FOLLOWING EXHIBITS TO THE DRAWINGS: C-1(A) FLEXBASE ROAD LAYOUT P-8(A) DETAIL K AND L—PENETRATIONS FOR PRECAST WALLS A2-36 REPLACE THE FOLLOWING SHEETS: REPLACE SHEET WITH SHEET P-1 Addendum Drawing P-1 S-5 Addendum Drawing S-5 S-6 Addendum Drawing S-6 S-7 Addendum Drawing S-7 S-8 Addendum Drawing S-8 END OF ADDENDUM NO. 2 Addendum No. 2 00902-13 CDM00507—Rolling Hills WTP—High Service Pump Station / 33WQ �I 1 1F1 1 1 cn C-) J cr O m aM mit CL z Z a a La ! �Ocr J co V)Q — QN 111 J 33�Z wry Q_jQ �� om pm �iwQ mu z — x a ,U. Tr 1 o o 3� Z ® �m c7 0 CO e mu o J z u WWW W O o o W � 0 Y �I LO C v Q U = UH z (n N Im IL, w — w 3 � z am =LI cn m= ~�o SCD m vi z .� w x " c3w � 0 wCD W J ZUzJ > w < < zin W 3 � p = `L0 LLJM LL ML, 0w 00� q 33� o: earn cn z W � z - z a- ~ z =_j LJ-J ,nw �wpw � cc i- CS J z Cc w u' >-o aa 'n w-jta�nD a m-- w N 0 ti <z CL m p h W w 0 in ? � x _ja�. wz w a � a � Z W xQa �a Co �o 0Z ON - 11 ON N wopz -i w cnC-� .9,Y31712 ! O L806E O' pcw`� mw�~gym am ~� am z v�cn _ -JLU Uj a0~ m a =� z�pw0a V) Zcn N V) ZMJ O 2 Sd U)o I y U a J ~= v O Q z w O 3 z cr << ro CL Q CO w H F-2 Z w w z U U)LU J 2 Z am � om N suft ROLLING HILLS WATER TREATMENT PLANT F°'t'"°'"�To'°'�°'°°'4°°°7°0 ;* FACILITIES UP NSION Fm ro 7)X74011 * PHASE 4 - NEW Ef S RVI TATION o% 1fft*...r MoNeb ami • 90179 Date: R feli�ice Adde7rt m Exhibit: moi S ee.i No. Not.- �„ Z x/ JAN. 30, 2004 6-1 2 C-1 (A) OPENING DIMENSION AND LINK SEAL LINK-SEAL INSTALLATION MODULAR MECHANICAL SHALL BE PER MFR'S. STAINLESS STEEL RECOMMENDATION EXPANDING RUBBER SEAL 36" PIPE a o FILL IN THE GAP W/ CAULK OR SEALANT PENETRATION FOR PRECAST WALLS (36" PIPE) DETAIL K NOT TO SCALE — LINK SEAL OPENING DIMENSION AND LINK-SEAL INSTALLATION MODULAR MECHANICAL V , a. ° SHALL BE PER MFR'S. STAINLESS STEEL a RECOMMENDATION EXPANDING RUBBER ° o ° 0 36" OD x 7 1/2" SEAL WIDE PIPE THIMBLE 30" PIPE F p s o FILL IN THE GAP W/ sod ° o CAULK OR SEALANT d� -° PENETRATION FOR PRECAST WALLS (30" PIPE) 3g A2DETAIL L Z_P- _ NOT TO SCALE - N f r-- ROLLING ILL 'WAT`ER_TREAT ENT PLANT rim �„6',-4ate FACILITI U� ADE,X-40 1' G EXPANSION Fm—<e+»�-7+a+ � PHASE 4 NE�V"11IOH-SE#$VICE MP STATION W eo,� Date: (�e'ferEnae jdum Exhibit: aRm� 0 3 � 3 s JAN. 30, 2004 P-8 2 P-8 (A) City of Fort Worth Rolling Hills Water Treatment Plant Phase 4- New High Service Pump Station TABLE OF CONTENTS PART A - NOTICE TO BIDDERS Notice to Bidders Instructions to Bidders PART B - PROPOSAL Proposal Minority and Women Business Enterprise Bid Specifications PART C - GENERAL CONDITIONS ° PART C1 - SUPPLEMENTARY CONDITIONS PART D - SPECIAL CONDITIONS PART F - BONDS Certificate of Insurance Contractor Compliance and Worker's Compensation Law Performance Bond w Payment Bond Maintenance Bond PART G- CONTRACT PART E - TECHNICAL SPECIFICATIONS DIVISION 1 GENERAL REQUIREMENTS 01005 Abbreviations 01010 Summary of Work 01011 Site Conditions 01025 Measurement and Payment 01035 Control of Work 01040 Construction Sequence 01110 Environmental Protection Procedures 01170 Special Provisions 01171 Electric Motors 01172 Pipe Penetrations 01179 OEM-Provided Control Panels 01200 Project Meetings 01300 Submittals 01315 Progress Schedule and Reports 01410 Testing and Testing Laboratory Services 01500 Temporary Facilities 01510 Construction Temporary Controls 01600 Delivery, Storage and Handling 01610 Material and Equipment Table of Contents Jy� "` " C CDM00507—Rolling Hills WTP—New High Service Pump Station :, , 01656 Disinfection of Potable Water Facilties 01665 Trench Safety Requirements 01666 Testing of Pipelines 01680 Water Tightness Test for Hydraulic Structures 01700 Contract Closeout 01710 Cleaning 01720 Project Record Documents 01730 Operation and Maintenance Data' 01740 Warranties and Bonds ,t DIVISION 2 SITEWORK 02202 Pipeline Excavation and Backfill 02210 Site Grading 02217 Trenching, Backfilling, and Pipe Embedment for Small Pipelines 02220 Trench Safety 02221 Structural Excavation and Backfill 02255 Earth Fill Classifications 02256 Aggregate Fill Classifications 02257 Controlled Low Strength Material (Flowable Fill) 02372 Drilled Shafts 02490 Loaming, Hydroseeding, and Erosion Control 02504 Flexible Base 02528 Concrete Curb and Gutter 02529 Concrete Sidewalks and Driveways 02614 Bar Wrapped Concrete Cylinder Pipe 02622 Polyvinyl Chloride Pipe and Fittings 02626 Steel Pipe 02930 Exterior Trees DIVISION 3 CONCRETE 03100 Concrete Formwork 03200 Concrete Reinforcement 03300 Cast-in-Place Concrete 03411 Precast Concrete Panels DIVISION 4 MASONRY 04270 Glass Unit Masonry DIVISION 5 METALS 05210 Steel Bar.foists 05300 Metal Deck 05500 Miscellaneous Metals 05520 Handrails and Guardrails and Steel Pipe Handrails DIVISION 7 THERMAL AND MOISTURE PROTECTION 07190 Water Repellents 07530 Modified Bituminous Membrane Roofing 07620 Sheet Metal Flashing and Trim 07720 Roof Accessories ' 07900 ,feint Sealers Table of Contents TOC-2 CDM00507—Rolling Hills WTP—New High Service Pump Station DIVISION 8 DOORS AND WINDOWS 08342 Fiberglass Reinforced Door and Frame System 08710 Door Hardware 08800 Glazing DIVISION 9 FINISHES 09900 Architectural Paints and Coating 09905 Protective Coatings DIVISION 11 EQUIPMENT 11212 Vertical Pumping Units-.Line Shaft Type DIVISION 13 SPECIAL CONSTRUCTION 13300 Process Instrumentation and Controls—General Provisions 13305 Application Engineering Services Attachment A—Process Control Loop Descriptions 13310 Distributed Control System 13315 Instrumentation Subsystem 13320 Fiber Optic Communications Segments 13325 Control Panels and Panel Mounted Equipment DIVISION 15 MECHANICAL 15050 Basic Mechanical Materials and Methods 15101 Gate Valves 15103 Butterfly Valves 15110 Pump Control Ball Valves 15117 Air Release &Air and Vacuum Valves 15126 Pump Control Cone Valves 15136 Miscellaneous Valves and Appurtenances 15145 Submersible Sump Pump 15153 Reciprocating Air Compressor and Receiver 15170 Pressure Gauges and Cocks 15260 Pipe Insulation 15410 Compressed Air Pipe, Valves,and Fittings 15430 Plumbing Specifications 15769 Electric Infrared Heaters 15838 Power Ventilators 15950 HVACTest-Adjust-Balance 15975 Sequence of Operations DIVISION 16 ELECTRICAL 16000 Electrical -General Provisions 16110 Raceways, Boxes, Fittings and Supports 16120 Wires and Cables(600V Maximum) 16121 Medium Voltage Cables 16140 Light Switches and Receptacles 16170 Metal Framing 16191 Miscellaneous Equipment Table of Contents p � .� TOC-3 CDM00507—Rolling Hills WTP—New High Service Pump Station l