HomeMy WebLinkAboutOrdinance 11268£~, ~~
~:
P /~,
ORDINANCE NO. 1~1{
AN ORDINANCE ADOPTING THE 1991 EDITION OF THE
UNIFORM MECHANICAL CODE AS AMENDED, REGULATING
THE DESIGN, QUALITY OF MATERIALS,
CONSTRUCTION, LOCATION, AND MAINTENANCE OF
HEATING, COMFORT COOLING AND VENTILATING
SYSTEMS IN THE CITY OF FORT WORTH, TEXAS;
PROVIDING FOR THE ISSUANCE OF PERMITS AND
COLLECTION OF FEES THEREFOR; PROVIDING FOR THE
INSPECTION OF BUILDINGS; PROVIDING PENALTIES
FOR THE VIOLATIONS THEREOF; PROVIDING A
SEVERABILITY CLAUSE; PROVIDING FOR THE REPEAL
OF CONFLICTING ORDINANCES AND CODE SECTIONS;
PROVIDING A SAVINGS CLAUSE; AUTHORIZING
PUBLICATION IN PAMPHLET FORM, DIRECTING
PUBLICATION OF THE CAPTION, PENALTY CLAUSE AND
EFFECTIVE DATE; AND NAMING AN EFFECTIVE DATE.
WHEREAS, it is deemed necessary to provide minimum standards
to regulate the design, construction, materials, locations and
maintenance of heating, comfort cooling, refrigeration, ventilating
and exhaust systems and other miscellaneous heat producing
appliances within the City to protect and promote the public
safety, health and welfare; and,
WHEREAS, the present codes are in need of amendments in order
to protect and promote the public safety, health and welfare under
modern conditions; and,
WHEREAS, the Mechanical Board of Appeals of the City of Fort
Worth has recommended the adoption of the 1991 edition of the
Uniform Mechanical Code of the International Conference of Building
Officials, with certain amendments; NOW, THEREFORE,
BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF FORT WORTH,
TEXAS:
OF~'f~~! R~'~~D
C~~Y ~~~~~'~~Y
0-1 ~T. ~~~~'~~, TAX.
SECTION 1.
That the 1991 edition of the Uniform Mechanical Code of the
International Conference of Building Officials, appended hereto
marked Exhibit "A" and incorporated herein by reference for all
purposes, as the same is hereby amended by amendments appended
hereto and marked Exhibit "B", is hereby adopted as the Mechanical
Code of the City of Fort worth, Texas, from the effective date
hereof.
SECTION 2.
That it shall be unlawful for any person to construct,
enlarge, alter, repair, move, improve, convert, equip, use or
maintain any heating, comfort cooling, refrigeration, ventilating
or exhaust systems or other miscellaneous heat producing appliances
in the City of Fort worth or cause the same to be done, contrary to
or in violation of any of the provisions of this ordinance; and
that a person violating any of the provisions of this ordinance
shall be deemed guilty of a separate offense for each day or
portion thereof during which any violation of any provision of this
ordinance is committed, continued or permitted, and each violation
shall be punishable by a fine not to exceed Two Thousand Dollars
($2,000.00) for all violations involving fire safety or public
health and sanitation and shall be fined not more than Five Hundred
Dollars ($500.00) for all other violations of this ordinance.
SECTION 3.
That it is hereby declared to be the intention of the City
Council that the sections, paragraphs, sentences, clauses and
phrases of this ordinance are severable, and if any phrase, clause,
sentence, paragraph or section of this ordinance shall be declared
void, ineffective or unconstitutional by the valid judgment or
final decree of a court of competent jurisdiction, such voidness,
ineffectiveness or unconstitutionality shall not affect any of the
remaining phrases, clauses, sentences; paragraphs and sections of
this ordinance, since the same would have been enacted by the City
Council without the incorporation herein of any such void,
ineffective or unconstitutional phrase, clause, sentence, paragraph
or section.
~Ffl~~~~ ~~~~~
C~` ~~~~~'A~~
~~. ~t ~um~~~f ~~d8a
r« .e
SECTION 4.
That Ordinance No. 10744 and all ordinances amendatory thereto
are hereby expressly repealed and superseded by the terms of this
ordinance. All other prior ordinances and City Code sections in
conflict herewith are hereby repealed but only insofar as such
ordinances and code sections are in conflict with the provisions of
this ordinance.
Mechanical permits heretofore issued under then existing
ordinances shall be valid for the time for which they were issued
under said ordinances; but upon expiration of such permit, the same
shall be void.
SECTION 5.
That all rights and remedies of the City of Fort Worth, Texas,
are expressly saved as to any and all violations of the provisions
of Ordinance No. 10744 or any other ordinance affecting heating,
comfort cooling or ventilation systems which have accrued
violations and all pending litigation, both civil and criminal,
whether pending in court or not, under such ordinances, same shall
not be affected by this ordinance but may be prosecuted until final
disposition by the courts.
SECTION 6.
That the City Secretary of the City of Fort Worth, Texas, is
hereby authorized to publish Exhibits "A" and "B" to this ordinance
in pamphlet form for general distribution among the public, and the
operative provisions of this ordinance as so published shall be
admissible in evidence in all courts without further proof than the
production thereof, as provided in Section 3, Chapter XXV of the
Charter of the City of Fort Worth, Texas.
SECTION 7.
A complete copy of Exhibits "A" and "B" shall be filed
herewith and maintained wherever a complete copy hereof is required
for permanent record and inspection.
~~~~~~'~~ ~~Q
~~TY ~~C~~T~RY
~T. ~~RT~, TAX.
,.
SECTION 8.
That the City Secretary of the City of Fort Worth, Texas, is
hereby directed to publish the caption, penalty clause and
effective date of this ordinance for two (2) days in the official
newspaper of the City of Fort Worth, Texas, as authorized by
Section 2, Chapter XXV of the Charter of the City of Fort Worth,
Texas and by Section 52.013 (a) of the Texas Local Government Code.
SECTION 9.
That this ordinance shall be in full force and effect from and
after the date of its passage and publication as required by law,
and it is so ordained.
APPROVED AS TO FORM AND LEGALITY:
City Attorney ~,.
ADOPTED: ~ ~ ~/~~
/-~ -,.
r:~- ~ ~'
EFFECTIVE: ~~-;~~~`' ~~S r'
J%.
OFFIClRL ~FCQQ
CITY SFC~TA~Y
FT. WQ~~'!~, TAX.
•
SECTION 101
Title
E~~IIBIT "B"
Sec. 101. These regulations shall be known as the "Fort Worth
Mechanical Code," may be cited as such, and will be referred to
herein as "this code."
SECTION 103
Scope
Sec. 103. The provisions of this code shall apply to the
erection, installation, alteration, repairs, relocation,
replacement, addition to, use or maintenance of any heating,
ventilating, cooling, refrigeration systems, incinerators or other
miscellaneous heat-producing appliances within this jurisdiction.
Additions, alterations, repairs and replacement of equipment
or systems shall comply with the provisions for new equipment and
systems ei~cept as otherwise provided in Section 104 of this code.
Where, in any specific case, different sections of this code
specify different materials, methods of construction or other
requirements, the most restrictive shall govern. Where there is a
conflict between a general requirement and a specific requirement,
the specific requirement shall be applicable.
The Uniform Mechanical Code Standards and Uniform Building
Code Standards contained in Appendix A shall be considered as part
of this code.
Appendix B, Chapter 21, shall be considered as part of this
code, except Section 2127.3, which shall serve only as a guide.
Appendix B, Chapters 22, 23 and 24 contain recommended practices
which shall serve only as a guide.
Appendix C contains gas-venting tables and a list of
recommended standards and is intended to serve only as a guide.
The design and testing of equipment regulated by this code shall be
subject to the approval of the Building Official.
-1-
Q~F~~~~. ~~~
CITY ~~~~~~~y
fT. ~~~TN, TEX.
~~
SECTION 104
Sec. 104(x) unchanged.
(b) Add exceptions as follows:
• EXHIBIT "B"
EXCEPTION No. 1. The following chapters, sections and
paragraphs of this code as amended shall be applicable to all
mechanical installations within the City of Fort Worth, regardless
of when they were installed: 508, 601(a), 701 (second paragraph),
807, Chapter 9, 1104.
EXCEPTION No. 2. A kitchen exhaust system with a Type I hood
for collecting and removing grease and smoke and a fire
extinguishing system shall be installed at or above all existing
cooking equipment in commercial food processing establishments as
required by Chapter 20 of this code.
(c) (d) and (ej unchanged.
SECTION 201
Sec. 201(aj unchanged.
(b) Deputies. In accordance with the prescribed procedures of
this jurisdiction and with the concurrence of the appointing
authority, the Building Official may appoint a Chief Mechanical
Inspector and other related technical officers and inspectors and
other employees as shall be authorized from time to time.
(c) (d) (e) (f) (g) (h) and (i) unchanged.
SECTION 203
Board of Appeals
Sec. 203 (a) General. In order to determine the suitability of
alternate materials of construction and to provide for reasonable
interpretations of the provisions of this code, there shall be and
is hereby created a Mechanical Board of Appeals, hereafter referred
to as the "Board", or as "Mechanical Board", consisting of nine
members who are qualified as set forth below. The Building
Official or his designated representative shall ~a-ee~c~f-f' io
QFFICI~L RFCO~A~
• EXHIBIT "B"
member and shall act as Secretary of the Board.
{b) Appointment. The Mechanical. Board shall be appointed by
the City Manager with the consent of the Cfty Council and shall
hold office at its pleasure. The Board shall adopt reasonable
rules and regulations for conducting its investigations and shall
render all decisions and findings in writing.
(c) Board Compositfoa. The Board shall consist of:
Place Qualifications
1. Citizen not in Building Industry
2. Registered Mechanical Engineer
3. Registered Mechanical Engineer
4. Licensed Air Conditioning Contractor
5. Licensed Air Conditioning Contractor
6. Licensed Mechanical Contractor
7. Citizen in the Air Conditioning Industry
8. Architect
9. Citizen not in Building Industry
(d) Tenure. The members shall hold office for a term of two
(2) years unless relieved for cause prior to that time. Members in
even-numbered places shall be appointed in even-numbered years.
Members in odd-numbered places shall be appointed in odd-numbered
years. Members shall not serve more than three (3) consecutive
two-year terms.
(e) Removal. The City Council may remove any member of the
Board during the term for which he may be appointed.
(f) Vacancy. Should a vacancy occur, the City Manager, by
and with the advice and consent of the City Council, shall appoint
a person having the prerequisite qualifications of the place
vacated to fulfill the unexpired term of said place.
(g) quorum. Any five (5) members of the Board shall
constitute a quorum to transact business but no decision shall be
handed down unless concurred in by not less than five (5) members.
The Board shall hold meetings at such time and place as called by
the Chairman or one acting lawfully in that capacity
-3-
Q~~«~~I~ ~~~~
C~'~Y S;~'~~~~
• E~-iIBIT "B"
(h) Advisors. In addition to the members set out in Section
203(c) of this code, the following City officials shall be advisors
to the Board.
1. City Attorney
2. Director of Health
3. Fire Marshal
When required by the Board, the advisory members shall attend
and furnish necessary special reports and inspections.
(i) Bylaws. It shall be the duty of the Board to meet as
soon after their appointment as is practicable and organize by
selecting one of their members as Chairman and another as Vice-
Chairman to serve as such for a period of one (1) year.
(j) Secretary. The Building Official, who serves as
Secretary of the Board, shall perform the following services:
Keep the minutes, books, files and
other records of the Board.
Issue all licenses in the name of
the Board.
Send out all notices and attend to
all correspondence under the
direction of the Board.
Collect fees for which provision is
made by ordinance; same to be
deposited with the Building
Official.
He shall perform such other duties
as are incidental to his office and
as may be required by the Board.
(k) Rules. The board shall have the power to make and
promulgate its .own rules governing its meetings and proceedings,
subject to the provisions of this ordinance.
(1) Enforcement. The Building Official shall execute and
OFfIC~A1 flECORD
CITY SECRETARY
fT. WORTN, iE1(.
-4-
• EXHIBIT "B"
enforce all legally endowed decisions of the Board.
SECTION 204
Violations
Sec. 204 (a) IIalawful Installation. It shall be unlawful for
any person, firm or corporation to erect, install, alter, repair,
relocate, add to, replace, use, or maintain heating, cooling,
refrigeration, ventilating or exhaust systems, incinerators or
other miscellaneous heat-producing appliances in the City, or cause
the same to be done, contrary to or in violation of any of the
provisions of this code. Maintenance of equipment which was
unlawful at the time it was. installed and which would be unlawful
under this ordinance if installed after the effective date of this
ordinance, shall constitute a continuing violation of this
ordinance.
(b) Penalty. Any person, including a firm or corporation,
violating any of the provisions,of this code shall be deemed guilty
of a misdemeanor, and each such person shall be deemed guilty of a
separate offense for each and every day or portion thereof during
which any violation of any of the provisions of this code fs
committed, continued, or permitted, and upon conviction of any such
violation, such person shall be punished by a fine not to exceed
$500.00.
SECTION 205 (added)
Sec. 205(a)(1) Business Registration. Each business,
including self-employment shall be registered in the Department of
Development before installing equipment regulated by this code.
Such business shall have in its employ a licensed individual where
licenses are required by this code or an official of the business
listed on the business registration who will be designated for the
issuance of permits for installations of equipment regulated by
this code. Such individual/official shall hereby be referred to as
"Registered Official." The Licenses & Registrations Section of the
Department of Development shall be notified immediately and in
writing of any address or phone change of the registered business
or when the Registered Official terminates employment from the
registered business. Permits shall not be issued wher ~~,~~
registration or license has been suspended or revoked OFFI~IA! RECORD
-5- I cl~ sECe~r~~.~
. EXHIBIT "B"
Upon adoption of this code, it shall be mandatory for all
Mechanical Contractors registering a business in the Department of
Development to purchase a copy of this code.
(2) License Required. Only a person who possesses a valid
Fort Worth Mechanical Refrigeration and Air Conditioning
Contractor's License or a valid State of Texas Air Conditioning and
Refrigeration Contractor's License with proper endorsements may
register a business and be issued permits for the installation of
all forms of heating, cooling, heating and cooling duct systems,
refrigeration and other heat-producing appliances regulated by this
code. Such licensed contractors may extend to and connect thereto
any gas piping that may be required for the operating of such
equipment. All electrical connections are regulated by the Fort
Worth Electrical Code.
An electrical disconnect may be installed by a licensed HVAC
contractor with a valid business registration when replacing an
existing HVAC unit of the same or lesser amperage.
A maintenance electrician license shall be required for ail
persons who perform electrical service, repair or maintenance on
equipment regulated by the Mechanical Code when an electrical
permit is not required.
EXCEPTION: Those persons who possess a valid State of Texas
Air Conditioning and Refrigeration Contractor's License with proper
endorsements and having a business registered with the City of Fort
Worth; shall not be required to obtain nor shall employees under
their direct personal supervision be required to obtain a Fort
Worth Maintenance Electrical License to service and maintain the
internal part of the system as manufactured and listed.
Plumbing Contractors that hold a valid State of Texas Master
Plumber's License and a valid Plumbing Business Registration in the
Licenses & Registrations Section of the Department of Development
may obtain permits and install gas fired appliances which are not
considered "air conditioning contracting" by the State Air
Conditioning Licensing Law. All L.P. gas piping installations
shall conform to the applicable Texas Railroad Commission
regulations.
-6-
®FFICIA~ RECORp
C~1Y s~r,~ ~~~~ ~
Ft. ~~o ~~, ~~X.
® . E}Q-IIBIT "B"
(3j Boiler and Pressure vessels. Boiler installation or
repair contractors who have been certified by an approved testing
agency, testing to meet (A.S.M.E.) American Society of Mechanical
Engineers and (A.W.5.) American Welding Society codes, or licensed
as a State of Texas Air Conditioning and Refrigeration Contractor
or Fort Worth Mechanical Refrigeration and Air Conditioning
Contractor may make boiler and pressure vessel installation and
repair.
(4) Automatic Fire Extinguishing Installation. Automatic
Fire System Installation and Repair contractors who hold a valid
Class A Fire Extinguisher Servicing License or a Ffre Extinguishing
System Planning License issued by the State Fire Marshall and whose
business has been issued a valid certificate of registration for
installation and service of fire extinguisher systems by the State
Fire Marshall, are required to obtain permits for all automatic
fire extinguishing system installations regulated by this code.
(5) Prefabricated Fireplaces, Ventilation Svstems.
Commercial Kitchen Hood Systems. An owner
company whose primary business includes the
equipment, and who is proficient in the
equipment, may register for the purpose of
install such equipment.
or
or an oiticiat or a
installation of such
installation of such
obtaining permits to
(b~(1) License Testing Procedure. Every person desiring to
be licensed by the City to engage fn the mechanical heating and air
conditioning contracting business in a capacity for which a license
is required by this code shall take an examination.
(2) Eligibility. To be eligible for application to take an
examination for a Fort Worth Mechanical Refrigeration and Air
Conditioning Contractor's License, an applicant must be at least
eighteen (18) years of age and have a minimum of three (3) years
experience in the installation of heating, cooling, refrigeration
systems, or other approved miscellaneous gas fired appliances under
the supervision of a licensed mechanical and/or air conditioning
and heating contractor.
For purposes of the experience requirement, a degree or
diploma in air conditioning engineering, refrigeration engineering
or mechanical engineering from an institution of higher education
whose program is approved by the Texas State Board ohs rya ~a~,
• E~Q-IIBIT " B"
for Professional Engineers for the purpose of licensing
professional engineers is considered the equivalent of two years of
practical experience.
Credit for air conditioning and refrigeration courses
emphasizing hands-on training taken at schools accredited by the
Texas Education Agency, the Coordinating Board of the Texas College
and University System, and the National Association of Trade and
Technical Schools will be allowed at the rate of one month's credit
for each two months of successfully completed training.
Transcripts will be required.
(3) Application. Each person to be examined for a Fort Worth
Mechanical Refrigeration and Air Conditioning License to be issued
by the City of Fort Worth shall first f ile a written application
for such examination at least thirty (30) days prior to examination
date with the Chief Mechanical Inspector. Such application shall
be presented to the Mechanical Board for review and approval to
test. Proof of experience shall accompany the application and
shall be documented as follows:
"A typewritten letter from current
and/or former employers where
experience was obtained. Letter
shall be on company letterhead,
detailed a~s to dates of employment
and type of work experience, and
shall be notarized."
Where company letterheads are not available, a "Proof of
Experience" form furnished by the Department of Development,
completed by the employer and/or former employer, and notarized may
be acceptable documentation of work experience.
(4) License IIse. If an applicant is an owner, officer,
partner, association or supervisory employee of a firm,
partnership, association or corporation which intends to engage in
mechanical heating and air conditioning contracting under the
authority of the license applied for, the applicant shall also
provide such information regarding the firm, partnership,
association or corporation as the application form may require.
The applicant shall keep the office of the Licenses/ -~c3n$_.~.
Section informed of any change in this information. fICIAL RECORD
CITY S~C~4~~TARY
-$-
FT. WO:~T~~4 TAX.
• E~4iIBIT "B"
(5) Written Examination. A written examination shall inquire
into the applicant's knowledge of the Mechanical Code and be given
to those applicants who have eligibility approval. The examination
results shall be certified by the Board. Applicants passing the
examination may work prior to final certification by the Board.
(6) Examination Fee. Each applicant shall pay an examination
fee of twenty dollars ($20.00) to the City of Fort Worth at the
time the application is filed. A ten dollar ($10.00) re-
examination fee is required if re-examination is taken within six
(6) months of the first failure. The applicant is eligible for re-
examination after 30 days has expired from first failure and 60
days of failures thereafter.
(7) Location - Time. Examination may be held in the City
Hall or at such other place as may be designated and limited to the
hours between 8:00 a.m. and 5:00 p.m. The time of the holding of
such examination shall be set by the Chief Mechanical Inspector and
each applicant shall be notified of the time and location thereof.
The applicant shall be notified of his grade in writing after
certification by the Mechanical Board.
(c) Granting Licenss. The Chief Mechanical Inspector shall
grant a license to each applicant who has satisfactorily passed the
written examination with a grade of 70 or more and pays the
specified license fee within sixty calendar days following the date
of certification by the Mechanical Board or the applicant shall
forfeit his/her right to obtain such license until again passing
the examination.
(d)(i) Fees. Licensing fees shall be as follows:
First year or portion thereof: $100.00
Yearly renewal: $ 50.00
Delinquency fee for yearly
renewal: $ 25.00
(d)(2) Business registration fees shall be as follows:
First year or portion thereof: $100.00
Yearly renewal: $ 50.00
Delinquency fee ~ for yearly 0~'fICIAL RECORD
renewal: $ 25.00 ~'~ SE~~~~~RY
• E~{E-IIBIT "B"
Reinstatement of suspended, repealed or revoked
registration: $ 25.00
{e) Yearly Expiration. Business registration and licenses
shall expire on December 31 following the date of issuance or
renewal. Business registration and license fees are due January 1
and shall be renewed annually on or before February 1 upon payment
of the required fee. Permits will not be issued and inspections
will not be made after January 1 until renewal fees are paid and
files are updated.
Any license which has lapsed not more than one (1) year may be
renewed upon payment of the delinquency fee. A license which has
lapsed for more than (1) year shall not be renewable and re-
examination shall be required.
(f) Restrictions of License. Licensees shall not be
simultaneously employed by, or work for more than one business for
the purpose of obtaining permits under this code or for the purpose
of doing or supervising work that can only be done by authority-of
a permit obtained under the provisions of this code.
Only one licensee for each business registration will be
recognized for the purpose of obtaining permits. The licensee
shall keep the Licenses & Registrations Section in the Department
of Development notified of any change in his employment.
(g) Termination of License. Licenses shall not be assigned
or transferred, but a license of any owner, officer, partner,
association or corporation with a business registration shall be
sufficient to qualify .such firm, partnership, association or
corporation to engage in the business of mechanical heating and air
conditioning contracting if a licensee is solely employed by or
associated with such firm, partnership, association or corporation
in a permanent, full-time capacity. In the event all holders of
valid licenses terminate their relationship for any reason, with
such registered business, the business may continue in mechanical
heating and air conditioning contracting and will be held
responsible for those permits obtained prior to such termination,
provided, however, that such permits shall not be valid for more
than ninety (90) days from the date of termination. Ne~.,,pe_~rm~ its ,~
shall not be issued. I OIy~ICIAL RECORD
CIS S~CRI;'~'AlRY
-10- , I•~ il~t1.4 eiVei. dQ~pFi^
• F.~Q-iIBIT "B"
Thereafter, in order for a firm partnership or corporation to
continue operations as a mechanical heating and air conditioning
contractor, another owner, officer, partner, associate or
supervisory employee of said entity must either hold a valid
license or pass the examination, or the business shall engage the
full-time services of a valid license holder and a new business
registration shall be required.
(h) Temporary Work Permit. When approved by the Building
Official or enforcing authority, a Temporary Work Permit may be
issued to a person qualifying for a Fort Worth Mechanical
Refrigeration and Air Conditioning License and a business
registration. The time period for this permit shall not exceed
three (3) months.
This Temporary Work Permit will entitle the holder to obtain
one permit to begin installation of equipment regulated by the Fort
Worth Mechanical Code. During the three-month time period, or
before the installation is complete and before a final inspection
has been made; the person who has been issued a Temporary Work
Permit shall be required to take the licensing examination and
obtain a valid Fort Worth Mechanical Refrigeration and Air
Conditioning Contractor's License and a business registration.
A fee for this Temporary Work Permit shall include an
examination fee, a licensing fee, and a business registration fee.
This fee shall be paid in full before the issuance of a permit. No
additional fee will be required when the requirements for a valid
mechanical, heating and air conditioning license have been
certified and the business is registered.
(i) Vehicle. All vehicles operated in connection with the
installation, erection, alteration, relocation and replacement of
any equipment regulated by this code shall be identified on each
side with registered business name. Where a license is required by
Sec. 205(a), the licensee's license number shall be added for
identification. Letters of identification shall be a minimum of 2
inches in height, visible and legible at all times that the vehicle
is in use for contracting of regulated equipment.
(j) Chaage of Contractor. If, after a permit is issued to a
Registered Official of a registered business under the
hereof, said Registered Official abandons the job, a~ e
c~~r ~~~~~r~~~
-11-
• F~-IIBIT "B"
incapacitated or his services are terminated prior to final
inspection and approval thereof by the Building Official or
enforcing authority, the permit holders, the person engaging the
services of the Registered Official shall immediately notify the
office of the Building Official in writing. Upon such
notification, the Building Official or the enforcing authority
shall immediately have an inspection made of the work completed to
that time, and he may revoke the outstanding permit and require
that a new permit be obtained before the work is allowed to resume.
(k) License or Business Registration Revoked. A license, a
business registration or permit may be suspended, repealed or
revoked by the Building Official or enforcing authority by reason
of the occurrence of one or more of the following:
1. Adjudication of insanity;
2. Fraud or misrepresentation in obtaining a license,
a business registration or permit;
3. Violation of any provision of this ordinance, the
Plumbing, Electrical or Building Codes or any other
regulatory ordinances of the City applicable to the
installation or alteration of appliances, equipment
or systems as set forth in the Mechanical
Ordinance;-
4. Defraudation of any person for whom he has rendered
or contracted to render service;
5. Failure to obtain a permit or the attempted
assignment of a permit for others;
6. Failure to pay permit fees or the voluntary or
involuntary filing of bankruptcy proceedings by or
against the firm, partnership, association or
corporation with a business registration with the
City of Fort Worth;
7. The sending of six notifications within a six month
period that the licensee or registered business is
in violation of the Mechanical Ordinan dFFICI~~ R~CDRD
~I~'Y S~~RET~RY
-12-
~ ~
• EXHIBIT "B"
8. When a state license is suspended for any reason.
(1) License and Registration Suspension. Upon suspension or
revocation of said mechanical and air conditioning contracting
license, or business registration, same shall be null and void and
no work thereafter may be performed thereunder.
Board Affirmation. Upon appeal to the Board, the Board
may affirm, revise or modify such suspension or revocation.
"A business registration suspended for failure to maintain
state-required insurance may be reinstated at no fee."
SECTION 206 (added]
Board Powers
Sec. 206(a) Certification. The Board is hereby authorized to
investigate methods, materials, equipment and appliances to
determine their compliance with Section 102. Those complying shall
be certified by the Board for the information of the public.
(b) Authorization. The powers of the Mechanical Board are
hereby extended so as to authorize the Mechanical Board to make
reasonable interpretations or rulings in matters properly before it
as to the suitability of alternate materials and/or methods of
installation and, upon appeal, authorize such variance in the
application of the terms of this code as will not be contrary to
the public interest, where owing to special conditions, a literal
enforcement of the provision of this code will result in
unnecessary hardship.
(c) Limitation. The Board of Appeals shall have no power to
otherwise change in writing or by general application the text of
this code.
-13-
OFF~C~AL RECORD
CITY ~~'C~~F~',4'RY
SECTION 207 (added)
Method of Filing Appeal
EXHIBIT "B"
Sec. 207(a) Rigbt of Appeal. Any person, firm, company or
corporation aggrieved by any decisions of the Building Official
under this Chapter may appeal such decision or order to the Board
as set out herein.
(b) Appeal Procedure. Appeals to the Board must be filed in
writing within thirty (30) days from date of the decision or order
appealed from and shall be filed in duplicate with the Secretary of
the Board. Such notice shall contain appropriate reference to the
decision or order appealed from as well as the grounds of the
appeal. It shall be the duty of the Secretary to notify the
Chairman of the Board of Appeals filed and the details thereof.
(c) Appeal Fee. At the time of filing an appeal, the
appellant shall be required to pay a non-refundable appeal fee of
fifty dollars ($50.00) .
(d) Records. The Secretary shall transmit to the Board all
relevant records and data upon which the appeal was taken.
(e) Hearing. The Board shall fix a reasonable time, not to
exceed thirty (30) days, for the hearing of an appeal, giving
notice in writing to the parties in interest and shall reach its
decision within a reasonable time thereafter. Parties may appear
before the Board in person, by agents, or by attorney. The Board
may require additional data and tests necessary for adequate
decision of the appeal.
SECTION 208 (added)
Code Change Recommendations by Board
Sec. 208. The Board shall review all proposed amendments to
the Mechanical Code and shall recommend such changes or amendments
as they deem appropriate.
OfF~~I~~. R~CORO
~iTY ~~~R~T~RY
U
SECTION 302
Sec. 302(a) unchanged.
Add exception to #5 to read as follows:
EXHIBIT "B"
Applications may be called in over the phone by the Registered
Official of a company having a valid business registration with an
active status on file in the Department of Development.
Sec. 302 (b) Plans and Specifications.
"The Building Official may require plans and specifications
for any project to be prepared by or under the direction of a
registered professional architect or engineer licensed by the State
of Texas. When the plans and specifications are not sealed by an
architect or engineer, the Building Official may require that the
applicant demonstrate that state law does not require the plans or
specifications to be sealed by an architect or engineer. The
Building Official may waive the submission of all or any portion of
the plans and specifications if the nature of the work applied for
is such that reviewing those documents is not necessary to obtain
compliance with this code. All plans, specifications and
accompanying data involved with the practice of engineering or
architecture shall comply with all state and local laws governing
the practice of engineering or architecture."
Sec. 302(c) unchanged.
Sec. 302(d) added.
Sec. 302(d)
Administrative Hold. Any administrative discrepancy including
but not limited to, delinquency in payments, returned checks,
failure to pay for reinspection, investigation or registration
fees, and failure to keep registration, insurance or bond up-to-
date, may result in a hold being placed on issuance of permits and
performance of inspections of existing permits until the
administrative discrepancy is corrected. For the purpose of this
section, the term "up-to-date" shall mean that whenever any of
these items is required by this or any other code -tosobta,in„-a_..
permit covered by this code, it shall be maintained c ~~a(D
effect until the permit is finaled. ~~ ~~~~~,~~~~
-15- ` ~j. ~~~i~~, ~~X.
• EXHIBIT "H"
Sec. 304 (a) unchanged.
(b) Permit F®es. The fee for each permit shall be as set
forth in Table No. 3-A.
Any person obtaining a permit application required by this
code shall, at the time of filing, pay a permit and application fee
as required by this section for the installation, relocation or
replacement of any of the listed items.
EXCEPTION NO. 1. Where the fees for the new structures and
additions to structures have been collected on a building permit,
additional fees are not required but the permit application shall
be filed before work is commenced by the person doing the work.
EXCEPTION NO. 2. Where these permit fees are being invoiced
monthly and the account is past due, a fee of $15.00 or 10 percent
(10$) of the total, whichever is more, shall be assessed. The
above assessed fee shall be paid before additional permits will be
issued or additional inspections performed.
EXCEPTION N0. 3. Buildings or structures owned and occupied
by a Federal, State, or County entity on property owned by the
Federal, State, or County entity shall be exempt from the permit
fees. This exception does not apply to public school districts or
county community colleges.
EXCEPTION N0. 4. Work by non-City personnel on property under
the control of the City of Fort Worth shall be exempt from the
permit fees only if the work is for action under a contract
approved by City Council with notes in the contract packages
stating the fee is waived.
EXCEPTION NO. 5 Work by City personnel on property under the
control of the City of Fort Worth shall be exempt from the permit
fees only if the application is accompanied by a copy of the work
order for the project.
(c) deleted.
(d) and (e) unchanged.
OfE~CIAI RECORD
CI`t~ SE~ETAR~'
EXHIBIT "B"
(f) Fee Refunds. The Building Official may authorize the
refunding of any fee paid hereunder which was erroneously paid or
collected. Where work for which a permit has been issued does not
commence, and a request is made for a cancellation of such permit
within a 60-day time limit, the permit fee may be returned, upon
request, minus an administration charge of $5.00. After the 60
days, no fee shall be returned.
EXCEPTIONS:
1. When the investigation fee of Section 304(e) has been
collected, it shall not be refunded unless paid by another party.
2. No refund will be given for the application fee.
Sec. 304 (g) added
304 (g) Change of Record. Any request for a record change, or
any mistake made by an applicant that requires a record change,
including but not limited to name or address changes, whether
computer or paper record, must be required in writing by the
original applicant with a fee as specified in Table No. 3-A.
EXCEPTIONB:
1. For record changes that affect the permit fee, such as
adding equipment, fixtures or square footage, the Building Official
may require a separate permit for the extra. items with the
appropriate fee.
2. The fee will not be required for those applicants meeting
exception 5 of Section 304(b).
SECTION 305
Sec. 305(aj and (b) unchanged.
(c) Add to middle paragraph:
Chilled water and other piping used to convey fluids for
transferring heat shall be tested and approved as required by Sec..
2127 of Appendix B.
(d) (e) and (fj unchanged. OFFICIAL RECORD
CIfiY SECRETARY
-17- ~~. d~~~l, ~EX.
TABLE NO. 3-A - MECHANICAL PERMIT FEES
Permit Issuance
Permit Application Fee
$10.00
EXHIBIT "B"
Forced Air Heating~Furnaces Including Ducts and/or Vents Attached
Thereto:
Capacity to and including 100,000
BTU input or 20 KW $ 3.00
Over 100,000 BTU or 20 KW and
including 400,000 BTU or 40 KW $ 5.00
Heating Appliances Non-Ducted Air
Gas Unit or Room Heater, including vent $ 3.00
Gas Wall Heater, including vent $ 3.00
Gas Floor Furnace, including vent $ 3.00
Gas Infra-red Heating Unit $ 3.00
Electric Heater, Wall, Space, Unit, etc. $ 3.00
Energy-Using Heat Appliance Other Than Above
Per 1,000 BTU Input - $0.04
Minimum $ 3.00
Per 1 KW - $0.14
Minimum $ 3.00
Each Low or High Pressure Steam or Hot Water Boiler Rated in either
BTU's Input, Boiler Horsepower Output, or KW
Per 1,000 BTU's Input - $0.04
Minimum
Per Boiler HP Output - $1.30
Minimum
Per KW - $0.14
Minimum
$ 3.00
$ 3.00
$ 3
utal6~~t RECORD
~~~' SECRE~""~R~
~'t ~~IQ~~R, ~°~.
-18-
• E~iIBIT "B"
Each Absorber Unit, Electrical Reciprocating, Centrifugal, or
Rotary Compressor, Condensing Unft, or Chiller Unit, Each on its
Normal Capacity Rating
Up to and including 2 tons $ 3.00
Over 2 and including 3 tons $ 5.00
Over 3 and including 5 tons $ 8.00
Over 5 and including 7-1/2 tons $11.00
Over 7-1/2 and including 10 tons $14.00
Over 10 and including 30 tons, per ton $ 1.30
Over 30 and including 100 tons, per ton $ 1.20
Over 100 and including 320 tons, per ton $ 1.00
Over 320 and including 520 tons, per ton $ 0.80
Over 520 tons, per ton $ 0.60
Each Roof-Top or Combination Unit, Including Ducts and Drains
Heating
Cooling and
Only Coolfna
Up to and including
3 tons $ 5.00 $10.00
Over 3 and including
5 tons $ 8.00 $14.00
Over 5 and including
?-1/2 tons $11.00 $19.00
Over 7-1/2 and
including 10 tons $14,00 $22.00
Over 10 tons, per ton $ 2.00 $ 2.50
Roof-Top Heating Only
Unit per 1,000 BTU - $0.04
Minimum
Through-the-Wall A/C Units
All Sizes, Each
$ 3.00
$ 4.00
O~~~G(AL ~~GQ~D
C8~' S~C~-~~AR~
f~'. ~~d ~ti~~ ~'~X.
-19-
•
EXHIBIT "B"
Cooling Tower, Evaporative or Afr-Cooled Condensor, Tonnage Based
on Local Design Conditions
All size units, per ton
refrigeration capacity - $0.50
Minimum $ 3.00
Cooling-Heating Coils
D.E. or Chill Water
per ton - $0.50
Minimum $ 3.00
Steam or Hot Water,
per 1,000 BTU - $0.04
Minimum $ 3.00
Fan and Coil Units including Drains and Ducts
Cool and Heat, per ton - $1.00
Minimum $ 3.00
Cool only, per ton - $0.50
Minimum ~ $ 3.00
Heating Unit only, per
1,000 BTU - $0.04
Minimum $ 3.00
Electrical Heat Strips for Units or Duct Installations
Per KW - $0.14
Minimum
Mixing Box - Conditioned Air
Mixing Box - Forced Air
Duct Addition or System not
included elsewhere, per outlet - $0.50
Minimum
Miscellaneous
Commercial food preparation
hood - Grease Type I
Commercial food preparation
hood - Heat or Moisture Type II
Commercial hood exhaust fan - Grease
-20-
$ 3.00
S i.oo
$ 2.00
$ 3.00
S 8.00
$ 6.0
$ 5.0
~ OFFICIAL R~CQRD
CITY ~~CR~~°ARY
pps ~,~.,, .•~-u
di~lr,:eaK ~~~{,~
• ExHIBIT "B"
Commercial hood exhaust fan - Heat
or Moisture $ 4.00
Commercial hood exhaust duct - Grease $ 5.00
Commercial hood exhaust duct - Heat
or Moisture $ 4.00
Commercial kitchen make-up air unit $ 5,00
Commercial hood automatic
electronic smoke extractor $16.00 `~
Automatic fire-extinguishing
equipment system $16.00
Range hood exhaust duct, for
R Occupancy $ 1.00
Toilet exhaust fan and/or
duct (per inlet) $ 1.00
Ventilation fan and duct system $ 4.00
Industrial hood $ 6.00
Mechanical ventilator $ 4.00
Flue replacement - U.L. labeled $ 4.00
Flue or stack for commercial
and industrial appliances ,$ 5.00
Humidifier $ 2.00
Vented decorative appliance $ 4.00
Commercial clothes dryer exhaust duct $ 5.00
Domestic clothes dryer exhaust duct $ 1.00
Incinerator, per 1,000
BTU - $0.04
Minimum $ 3.00
Incinerator modification $50.00
Condensate drain-French sump $ 3.00
Fire or smoke damper $ 1.00
Circulating water pump $ 1.00
Evaporative cooler $ 4.00
Automatic shutoff - products
of combustion $ 5.00
Solar energy system $30.00
Heat recovery devices
per 1,000 BTU - $0.04
Minimum $10.00
Gas Extension Test $ 5.00
For each appliance or piece of
equipment by this ordinance for Of~~CIA~, RECORD
which no other fee is listed $ 5.00
~~~ s~~~-~TA~~
FT. ~~~~ ~T, TAX.
-a 1-
® •
Change of Record
Re-Inspection Fee
Inspection outside normal business hours
(minimum charge - 2 hrs.)
SECTION 404
$io.oo
$20.00
EXHIBIT "B"
$30.00/hr.
Sec. 404. Building Off icial - is the officer charged with the
administration and enforcement of this code, or a regularly
authorized deputy. For the purpose of this code the regularly
authorized deputy shall be the Chief Mechanical Inspector.
SECTION 510
NOTE: This section has been revised in its entirety.
Sec. 510(a) Condensate Waste Condensate from air cooling
coils shall be collected and discharged to an approved plumbing
fixture with an open sight air gap or to an approved disposal area.
The drain shall have a slope of not less than 1/8 inch per foot and
shall be non-ferrous metal pipe at least 3/4 inch inside diameter.
EXCEPTIONS:
1. The condensate piping material from an air cooling coil
may be of rigid schedule 40 PVC or CPVC pipe provided:
a. Type of construction will permit the use of plastic
piping, material per the FWBC;
b. Piping is not exposed within any duct or plenum
space except for residential type. construction;
c. Piping is permanently supported, not more than 5
feet on centers;
d. Any piping exposed to the ultraviolet rays of the
sun shall be composed of U.V. resistant materials.
e. Colored primer and cement is used on all glue type
fittings.
2. The inside diameter of the piping from a condensate pump
may be the same size but not smaller than that of the pump
discharge.
-22-
DFFiCI~L RECORD
C!~'Yp ~E'CFRE1'~RY
~! a N~~~!M 9 ~~r F
F~iIBIT "B"
3. Cooling unit condensate drains may discharge into a roof
drain if the roof drain connects directly into a storm sewer.
4. In the event sanitary sewer connections are not readily
available, the Building Official may permit air conditioning units
of no more than 7-i/2 tons to discharge their condensate drainage
into an approved disposal area.
5. Piping for drain lines from Group II refrigeration
equipment may be of galvanized ferrous metal.
6. Condensate waste from air conditioning coils may be
discharged by direct connection to a lavatory tailpiece or to an
approved accessible inlet on a bathtub overflow, provided the
connection is located in the area controlled by the same person
controlling the air conditioned space.
Condensate drain pipes shall be permanently supported not more
than 10 feet on centers, except PVC piping shall be supported not
more than 5 feet on centers. Supports must be of a permanent
material extending on either side of the drain pipe. Pipe exposed
to weather shall be secured to the supports with galvanized iron
strips and screws.
(b) Approved Condensate Disposal Area. Approved disposal
area may be a French sump having a minimum dimension of 2' x 2' x
1-i/2' deep, a minimum distance of 3 feet from a foundation, filled
with small crushed rock or washed gravel to within 6" of the top
and covered with dirt and turf to a depth of not less than 6". The
condensate pipe shall terminate into an approved non-metallic,
bottomless container having perforated side walls.
(c) vacuum Breaker. Condensate drains from draw through
cooling units shall have an open pipe vacuum breaker in the pipe
connection at the unit.
(d) Drain Pipe Length and Siring. The overall developed
horizontal length of a piping system collecting condensate drains
shall not exceed 200' in length.
Condensate drains for air-cooling coils shall be sized.~in .~..
accordance with equipment capacity as follows: 4 ~~~g~~~~ ~E~~~~
EXfiIBIT "B"
foment Caoacit
Minimum Condensate
Drain Diameter
Up to 20 tons of refrigeration
21 to 40 tons of refrigeration
41 to 90 tons of refrigeration
91 to 125 tons of refrigeration
126 to 250 tons of refrigeration
3/4 inch
1 inch
1-1/4 inch
1-1/2 inch
2 inch
Size of condensate drains may be for one unit or a combination
of units, or as recommended by the manufacturer. Drain capacity is
based on i/8 inch per foot slope, drains running three-quarters
full.
(e) Emergency Overflow. An emergency overflow from a cooling
coil condensate collector pan or an additional watertight pan of
corrosion resistant metal shall be installed in connection with a
cooling coil which is located above an occupied space.
The overflow condensate shall be discharged at a point which
can be readily observed by the occupant. Emergency overflow outlet
and piping shall be the size of the condensate drain and may be
uninsulated.
EXEMPTION: Equipment in a room with a waterproof floor having
a floor drain need not have an emergency overflow.
(f) Condensate Drain Pipe Insulation. All condensate drain
lines located above a ceiling, in stud spaces, furnace enclosures,
or any other spaces where condensed moisture from a drain line
could cause damage, shall be insulated in accordance with Section
2502(d).
EXEMPTION: (1) Insulation will not be required where PVC or
CPVC pipe is allowed.
(g) Equipment Drains. Drains from equipment discharging
unpolluted water, such as cooling tower overflow or drainage,
processing system or other systems, which require periodic or
continuous draining as a means of disposing liquid wastes, shall be
discharged into an approved disposal area as permitted by the Fort
Worth Water Pollution code, latest edition. ~ ~~~~C~A~
RECQ~D
EXHIBIT "B"
Above equipment drains may be of approved corrosion resistant
pipe.
(h) Humidifier Drains. Drains from humidifiers shall
discharge into a sanitary sewer. Piping materials may be ferrous
or nonferrous. Where humidifier discharges into a condensate drain
pipe; it must not decrease the pipe size or create a potential
overflow.
(i) Public Ways. Condensate or waste water shall not drain
over a public way.
(j) Fuel-burning Appliance Condensate Drains. Condensate
drain lines from individual fuel-burning condensing appliances
shall be sized according to the manufacturer's recommendations.
Condensate drain lines serving more than one appliance shall be
approved by the Building Official prior to installation.
SECTION 602
Sec. 602(a)~ Location. Approximately one-half of the required
combustion air opening area shall be located within the upper 12
inches of the enclosure and approximately one-half of the opening
area shall be located within the lower 12 inches of the enclosure.
All combustion air openings in an enclosure may be located within
the upper 12 inches of the enclosure provided the floor area of the
appliance compartment is more than twice the floor area of the
appliance therein and there is an unobstructed area equal to the
required opening area extending to the fire box.
See Table No. 6-A for combustion air requirements.
(b) and (c) unchanged.
OFF9C~Al R~CDRD
-25-
C~ ~`Y ~CR~IARY
Y~. SQ ,i~,Y 4~p Flan
S~CTIQ~6Q4
Sec 604 (a) and (b) unchanged.
• F~iIBIT "B"
(c) Screen. Top end of ducts which terminate in an attic may
be screened.
SECTION 607
Sec. 607 (a) deleted.
(b) Designed Installations. With prior approval, compliance
with the requirements of Table No. 6-A will not be required for an
installation which has been designed and sealed by an engineer
licensed by the State of Texas to practice as such and proficient
in Mechanical Engineering.
-26-
6F~'9ClAL RECORD
C~ ~C~~~°ARY
~~. ~~~INAp ~e
' • EXHIBIT "B"
Table No. 6 - To read as follows:
COMBUSTION AIR REQUIREMENTS FOR FUEL
BURNING EQUIPMENT
MINIMUM TOTAL FREE AREA MINIMUM TOTAL FREE AREA
OF DUCTS/OPENINGS, OF DUCTS/OPENINGS,
WHERE FLOOR AREA OF WHERE FLOOR AREA OF
COMPARTMENT IS LESS COMPARTMENT IS MORE
THAN TWICE THE FLOOR THAN TWICE THE FLOOR
AREA OF THE APPLIANCES AREA OF THE APPLIANCES
THEREIN THEREIN
INPUT
0 through 2 sq. in. for each 1 sq. in. for each
500,000 1,000 BTU/h (200 sq. 1,000 BTU/h (100 sq.
BTU/h in. min.) in. min.)
500,000 1,000 sq. in. plus 2 500 sq. in. plus 1 sq.
through sq. in. for each 1,500 in. for each 1,500
1,000,000 BTU/h over 500;000 BTU/h over 500,000
BTU/h BTU/h BTU/h
Over 1,666 sq. in. plus 2 833 sq. in. plus 1 sq.
1,000,000 sq. in. for each 2,000 in. for each 2,000
BTU/h BTU/h over 1,000,000 BTU/h over 1,000,000
BTU/h BTU/h
SECTION 701
Sec. 701, Paragraph 1, unchanged.
Add Paragraph 2 as follows:
Every dwelling unit, guest room and congregate residences
shall be provided with heating facilities capable of maintaining a
room temperature of 70°F at a point 3 feet above the floor in all
habitable rooms. RE: Building Code Sec. 1212
SECTION 703
Sec. 703, unchanged, except add Exemption #5 as f
-27-
~~~~~~~~~ R~~~4D
~I ~ ~~~~~T~RY
~~a l~~~~°s~, T~..
• EXHIBIT "B"
EXEMPTION No. 5: In existing construction, a room may be used
for a new or,replacement furnace, providing the door is not smaller
than eighteen (18) inches in width and provided access for unit
removal and installation is adequate.
SECTION 708
Sec. 708, add the following as Paragraph ~`4:
Access to the furnace shall be provided by a retractable or
fixed stair or ladder constructed of nominal 2 by 4's with steps
not over 11" centers.
EXCEPTION: An area above a suspended removable ceiling which
is not over l0' above the floor below and where a portable ladder
is permanently available.
SECTION ?10
Sec. 710(a) (b) (c) (d) (e) (f) and (g) unchanged.
Sec. 710(h), change Paragraph #2 to read as follows:
Every furnace located on the roof of any building shall be
readily accessible.
EXCEPTIONS:
1. Permanent exterior ladders providing roof access need not
extend closer than 8 feet to the finish grade.
2. A portable ladder may be used for access for furnaces on
the single-story portion of a Group M or R Occupancy.
3. For appliances located on roofs of the buildings where
the minimum height does not exceed eighteen (18) feet from the
finish grade, a portable ladder may be used.
SECTION 803
Sec. 803, add Paragraph #~3 as follows:
.Approved factory built wood burning fireplaces
-28-
• EXHIBIT "B"
shall be installed as required by the listing from an approved
testing agency and by the manufacturer's instructions. See Table
No. 5-A for clearances on unlisted appliances.
SECTION 807
Sec. 807(a) and (b) unchanged.
(cj revise the second sentence and add exception as follows:
This subsection shall not apply to portable oil-fired
unvented heating appliances used as supplemental heating
in Groups B, Divisions 1 and 3, and Group M Occupancies
and regulated by the Fire Code.
EXCEPTION: Unvented fuel-fired room heaters, excluding fuel-
fired bathroom heaters, may continue to be used in existing Group
R-3 Occupancies when approved by the Building Official unless
remodeling or rehabilitation of fire damage is in excess of 50
percent of the value of the structure.
SECTION 905
Sec. 905(a), add exception to Paragraph #1 as follows:
EXCEPTION: One 90° off-set from the
adjacent to a horizontal draft hood collar.
SECTION 910
Sec. 910, add note #4 as follows:
horizontal may be used
4. The venting system materials used must be of the same
manufacture and style as the existing venting system, or
replacement materials shall be of one manufacture. Installation
shall conform to the U.L. listing requirements for the materials.
SECTION 1002
Sec. 1002(a), add exceptions to Paragraph ~2 as follows:
EXCEPTION: 1. Existing buildings where hour
construction does not exist may have the use of the corri
-29-
• ~I-IIBIT "B"
integral part of a duct system when:
A. Ionization products of combustion detectors are installed
in an approved location so as to provide detection for each
inhabited room or exit way. The detector shall be connected to the
circulating air system controls; or
B. The circulating air system shall be designed and
controlled so a's to reverse the air flow from the corridor into the
inhabited room using all outside air when activated by-the product
of combustion detectors; or
C. An approved air release shall exist so as to assure a
constant flow from the corridor into the inhabited room; or
D. Any other approved system that will accomplish the intent
of the above subsections.
Sec. 1002(b) Factory-made Air Ducts. Factory-made air ducts
shall be approved -for use intended or shall conform to the
requirements of U.M.C. Standard No. 10-1. Each portion of a
factory-made air duct system shall be identified by the
manufacturer with a label or other suitable identification
indicating compliance with U.M.C. Standard No. 10-1 and its class
designation. These ducts shall be listed and shall be installed in
accordance with the terms of their listing, the requirements of
U.M.C. Standard No. 10-5, and the following requirements.
Metal volume-reducing fitting shall be used for branch take-
offs. Factory attached or shop made metal connectors shall be used
to connect flexible ducts. All metal connecting collars shall
incorporate a smooth standing bead or equivalent to positively
secure flexible duct.
EXCEPTION: Each individual flex duct circulating air system
designed and sealed by an engineer licensed by the State of Texas
to practice as such and proficient in Mechanical Engineering.
Sec. 1002 (c) add to first paragraph as follows:
All round metal duct f fittings such as starting co~.~azs~..f<er~-~-~-=-
plenums, reducers, branch take-offs, elbows, stack a~,~~c~,rll~~~`~QRQ
heads, etc., shall be of approved factory or shop ma ufact ~
~~~~ `~~~~~T~RY
• EXHIBIT "B"
Starting collars shall be used for all round metal duct and ceiling
outlets.
Sec. 1002(d) unchanged.
(e) Tin. Existing tin ducts may be used when cooling coils
are added to a heating system, provided the first 10 feet of the
duct or plenum measured from the cooling coil discharge are
constructed of metal of the gauge thickness set forth in Table No.
10-A, No. 10-B or No. 10-C of this chapter or are of approved
material and construction. Tin ducts completely enclosed in
inaccessible concealed areas need not be replaced. All accessible
ducts shall be insulated to comply with Table 25D of this code.
For the purpose of this subsection, ducts shall be considered
accessible where the access space is 30 inches or greater in
height.
Sec. 1002 (f) unchanged.
SECTION 1005
Sec. 1005 deleted. Replaced by Chapter 25 herein.
SECTION 1009
Sec. 1009(a) unchanged.
Sec. 1009(b) Changes to read as follows:
(b) Smoke Detection. Smoke detectors required by Subsection
(a) shall be installed in the main return-air duct ahead of any
outside-air inlet or they may be installed in each room or space
served by the return-air duct. Additional deteetors may also be
installed in the supply duct, downstream of the filters.
Activation of any detector shall cause the air-moving equipment to
automatically shut down.
TABLE NO. 10-C
Table No. 10-C, add note:
NOTE: Round ducts 10" diameter or less may be .010 z~. ess'
or 32 gauge material. D~~~~~. ~~.~DRD
~I~ SL~~~TADY
L
TABLE NO. 10-D
• EXHIBIT "B"
Table No. 10-D deleted. See Table No. 25-D for insulation of
ducts.
SECTION 1104
Sec. 1104 add exceptions 1 and 2 after the first paragraph to
read as follows:
EXCEPTIONS:
1. In all occupancies except "H", bathrooms which contain
only a water closet or lavatory or combination thereof, and similar
rooms may be ventilated with an approved mechanical recirculating
fan or similar device designed to remove odors from the air.
2. In "B" occupancies bathroom exhaust ducts may terminate
in a warehouse or shop area when infiltration of outside air is
present.
Sec. 1104 delete the last sentence of paragraph 3.
SECTION 1205
Sec. 1205 deleted. See Sec. 510.
SECTION 1207 (added)
Chilled and Hot Water Piping Material
Sec. 1207. Materials shall be as follows:
(a) Copper Pipe. Copper piping or tubing for chilled-hot
water piping shall have a weight of not less than that of Type L.
Underground copper joints shall be made with high temperature
solder equal to silfos.
EXCEPTION: Type M copper pipe or tubing may be used when
piping is not located under a concrete slab or underground and the
maximum pressure does not exceed 60 psi and the working
does not exceed 210°F.
-32-
~~~D~Q
~G. ~~'68 RW~~ ~~.fIIe
EXi-IIBIT "B"
r(b) Steel Pipe. Steel piping shall be seamless or electric
butt-welded black or hot-dipped galvanized. The minimum strength
shall be "Standard Weight", Schedule 40 or 80 as necessary to meet
pressure requirements.
1. For one and one-half (1-1/2) inch or smaller, use not
less than Schedule 40 if pipe is to be threaded. For working
pressures in excess of 300 psi use Schedule 80 for all sizes.
2. All underground pipe, also pipe sizes two and one-half
(2-1/2) inch IPS and larger, shall have welded joints or be an
approved fitting.
Piping change of direction shall be made with seamless welding
fittings or of Weldolet type. Mitered fittings are not permitted
unless approved by the Building Official.
(c) underground Pipe. Cement fiberglass and pre-insulated
Schedule 40 PVC pipe may be installed underground for chilled water
only. ,All pipe and joints shall be insulated in an approved manner
(Sec. 2502).
(d) Isolatfos Valves. Structures served by multiple building
chilled-hot water distribution systems shall have all chilled-hot
water connections to each structure or space valved in such a
manner as to afford isolation of the structure or space from the
system. Gate valves shall be installed approximately two (2) feet
outside of the structure unless otherwise approved by the Building
Official and shall be properly labeled. Valves shall be accessible
through a concrete or cast iron box, with top mounted flush with
final grade when underground.
SECTION 1701
Section 1701, add sentence and exception to third paragraph to
read:
Materials shall comply with Sec. 2127 of this code.
EXCEPTIONS:
V
1. Underground pipe material may be PVC Sched -e, ew ~ ,
outside of building perimeter. ~ ~~~~~~~ ~~~'~~~
-33-
~~TY S~~~Y~T~RY
~T. ~°a~T T~.
•
EXHIBIT "B"
2. Above ground pipe material when outside the building, may
be U.V. resistant PVC Schedule 40 or may be shielded from the
sunlight by an approved method.
SECTION 1702 (added)
Sec. 1702. All drains shall be installed as specified in
Section 510 of this code.
SECTION 1903
Sec. 1903(a) unchanged.
Sec. 1903(b) deleted.
Sec. 1903(c) and (d) unchanged.
SECTION 2002
Sec. 2002(a) through (c) unchanged.
Sec. 2002(d) add exception as follows:
EXCEPTION: That portion of a duct directly above the food
preparation area, from the ceiling penetration through a roof or
exterior wall and which does not penetrate a floor above or
adjacent tenant wall may be protected by insulating with a material
having a temperature rating with a minimum of 1200°F.
Sec. 2002 (e) through (j) unchanged.
SECTION 2003
Sec. 2003 (a) add exception as follows:
EXCEPTION: Those establishments using cooking equipment
designed for domestic use, excluding griddles and deep fat fryers,
are required to meet only those requirements for domestic equipment
in Sec. 1901 and 1902.
Sec. 2003(b) add the following after last paragr
Thermal recovery units or other devices may be
-34-
~~~~~~Q~ ~~~~~
stalled in
~~ ~~~r.~a:~~~b~
~ t~~~sEu, ~~.
-,ter.:--
•
E~{i-IIBIT "8"
ducts or hoods or located in the path of travel of exhaust products
when specifically approved or listed for such use. Such devices
shall not increase the fire hazard, nor shall it allow an
accumulation of grease buildup.
Sec. 2003 (c) and (d) unchanged.
Sec. 2003(e) add exception as follows to first paragraph:
EXCEPTION: Grease filters in a non-canopy hood, located above
the cooking surface having less clearance than required by Table
No. 20-A shall be tested and listed for its clearance and shall be
approved by the Building Official.
Sec. 2003 (f) unchanged.
Sec. 2003(8)(4) add second exception as follows:
EXCEPTION: Type I and Type II commercial hood exhaust systems
may have a minimum of two-thirds of the listed air quantity when
designed by an engineer, registered by the State of Texas, and
approved by the Building Official. The air quantity must be of
sufficient amount to provide for capture and removal of all grease,
heat and moisture laden vapors. Test data or performance or both,
acceptable to the Building Official, shall be provided upon
request.
Sec. 2003 (h) unchanged.
Sec.. 2003(i) add the following after first paragraph:
Tempered Air. Kitchens with exhaust systems in excess of 2500
cfm shall be provided with tempered makeup air.
For this purpose, tempered air means a temperature of not less
than 60°F at the discharge diffuser in the room.
EXCEPTION: Kitchen ventilation systems which furnish their
own makeup air independent of the air furnished to the kitchen or
other areas of the building are excluded.
Sec. 2003(j) through (k) unchanged.
-35-
o~~PC~~~ R~eo~fl
Cdr S~C~~~~,~~
fT. ~~~C:~ ~ ®~, a~~.
.,,
• E~-IIBIT " B"
SECTION X004
Sec. 2004 (a) unchanged.
Sec. 2004(b) (1) through (3) unchanged.
Sec. 2004 (b) (4) (A) through (E) unchanged.
Sec. 2004 (b) (4) (F) (added)
F. Oneratit~q Test
Upon completion of the installation of an automatic fire
extinguishing system or an addition thereto, the
certified firm shall, before the system is placed in use,
perform an operating test in conformance with the
requirements of the Building Official.
Sec. 2004(b) (4) (G) (added)
G. portable Extinguishers
In addition to the fixed system, portable fire
extinguishers shall be installed near the food-processing
equipment in accordance with U.F.C. Standard No. 10-1 (40
B:C - 5 lb. min.).
Sec. 204(b) (4) (H) (added)
H. Service
Extinguishing systems shall be serviced at least every
six months or after activation of the system. Inspection
shall be by a qualified individual of a firm certified
through the State Fire Marshal's office.
A new service tag shall be attached each time an
inspection or service is performed. Should system fail
to pass service inspection and a red tag is attached, the
certified firm shall notify the Building Official.
Sec. 2004(b) (5) unchanged.
-36-
OE'f{CBE RECORq
CITY SEC~ET~RY
ET. WQR~°Q, TEX.
~~
Sec. 2004(c) unchanged.
CHAPTER 25 (added)
Insulation - Mechanical Installations
,SECTION 2500
• EXHIBIT "B"
Sec. 2500. Certain words and terms used in this section shall
means as follows:
Thermal Conductivity (R-Factor) - The time rate of heat flow
through one square foot of homogenous material one inch thick; when
there is a temperature difference of one degree F between the
opposite faces of the material expressed in BTU/Hr., per square
foot, per degree F, per inch.
Thermal Conductance (C-Factor) - The time rate of heat flow
through a homogenous material of other than one inch thickness; or
through a non-homogenous construction such as an air space,
expressed in BTU/Hr., per square foot, per degree F temperature
difference.
K = C-Factor for a specific thickness
Inches of nominal thickness
Thermal Resistance (R) - The measure of the resistance of a
material or building component to the passage of heat. The
resistance value (R) of masstype insulations shall not include any
value for reflective facing. The "R" factor is the reciprocal of
the conductance "C" or the "U" factor.
I
R - -
C
Q Factor - The total heat flow through a given construction
assembly; air to air, expressed in BTU/Hr., per square foot, per
degree F temperature difference.
Perm Rating - The water vapor permeance of a sh e~~F~~~~an~~CORD
thickness (or assembly between parallel surfaces) is th ~ii~~~~~ ~~~
-37- ' Fr. W~R~e~, ~~.
• EXHIBIT "B"
water vapor flow to the vapor pressure difference between the
surfaces, measured in perms.
SECTION 2501
Sec. 2501(a) Duct Insulation. Every supply and return air
metal duct and/or plenum system of a heating and/or cooling system
shall be insulated with not less than the amount of .insulation set
forth in Table No. 25-D.
EXCEPTION: Duct and plenum systems used exclusively for
evaporative cooling systems.
1. All insulation, ducts, tapes and adhesive material shall
have a mold, humidity and erosion resistance face, where
applicable, meeting the requirements of U.M.C. Standard No. 10-1.
All such materials shall have aflame-spread rating of not greater
than 25 and a smoke developed rating of not greater than 50. They
shall be so labeled or identified with printing, acceptable to the
Building Official, on the facing of the fiberglass insulation
products and on the product or container of accessory items.
Sec. 2501(b) deleted.
(c) Duct Arap-Faced Fiberglass Insulation. Installation of
duct wrap-faced fiberglass products shall conform with the
following:
1. All duct wrap-faced fiberglass type insulation applied
externally to a duct system, which is located in or on a building
and provides air supply for heating and/or cooling, shall be faced
with a permanent vapor barrier composed of a foil scrim kraft
material having a maximum perm rating of 0.05.
2. Insulation on rectangular ducts over 24" wide shall be
provided with suitable mechanical fasteners at no more than 18
O.C., to secure insulation on the bottom of the duct.
3. All duct wrap on round duct shall not be more than 1/2"
less than labeled thickness after application. The same insulation
thickness applies to rectangular duct except on the corners,,in
which area 3/4" thickness is acceptable.
-38-
OfFlC~AC R~CO~~D
CtiY S~C~~"AY
~". WO~'~p ~'~.
E~~'-iIBIT "B"
4. The facing shall have a minimum 2" tab on the
longitudinal and circumferential joints for lapping and stapling.
Facing tabs shall be sealed with adhesive and stapled on not over
3" centers. All punctures and tears in the vapor barrier facing
shall be sealed with an approved adhesive and covered with facing
material.
5. Insulation of the duct systems which are exposed to
weather shall be vapor sealed and additionally weatherproofed as
follows. Apply a coat of weatherproof mastic and embed into the
wet tack coat a layer of open weave glass cloth. Smooth membrane
to avoid wrinkles and overlap all seams at least 2". Apply a
finish coat of the mastic to a minimum thickness of iJ8".
6. Duct wrap shall be interrupted at fire or smoke dampers.
Also shall be interrupted at heat sources in a duct system
involving electric resistance or fuel-burning heaters.
External duct wrap insulation shall not extend through those
walls, floors or roofs required by the Build~inq Code to have afire
resistance rating. The insulation shall be sealed to the wall,
floor or roof to form a vapor-proof connection.
(d) Duct Liner. All duct liner shall be coated on the air
flow side with afire-resistant coating tightly bonding the surface
fibers .
Duct lining, when used as insulation, shall be continuous in
all portions of the duct except at fire or smoke dampers and at
heating appliances.
Application of liner to duct shall be by means of 100-percent
coverage with adhesive and the use of mechanical fasteners in
accordance with SMACNA Standard. All leading edges and transverse
joints shall be coated with adhesive.
OEfICIAL RECORD
CITY ~ECRE~'R'~
-39- , I:T. ~Q~~ ~~X.
TABLE 25-D
E~-iIBIT "B"
Minimum Insulation Requirements
for Plenum Spaces, Metal Fitting and
~eta1 Air Conditioning Duct Systems
DUCT LUCATION ACCEPTABLE
1. SUPPLY and RETURN 3", 0.75 lb/cu ft
DUCT systems FSK WRAP
exterior of building ~ 1-i/2", 1.5 lb/cu ft
and exposed to Duct Liner
outside temperature 1-1/2", Type 475 or
and weather. 800 Duct Board
or equivalent to
provide an installed
conductance = 0.16
2. SUPPLY and RETURN ~ 2", 0.75 lb/cu ft
DUCT systems located FSK WRAP
in attic spaces 1", 1.5 lb/cu ft
outside the building Duct Liner
insulation envelope. 1", Type 475 or 800
SUPPLY and RETURN Duct Board
DUCT systems located or equivalent to
in mechanical provide an installed
equipment rooms, conductance = 0.24
furnace enclosures,
shaft enclosures,
and any other spaces
connecting or
ventilated with
unconditioned air.
SUPPLY and RETURN
DUCT systems located
outside of the
building insulation
envelope but inside
the building other
than attic spaces.
-40-
OFEICIA! RECORD
C~~ SEC~~~~~~
FT. w~~~~4 ~~~.
EXHIBIT "B"
3. SUPPLY DUCT systems 1", 0.75 lb/cu ft
located inside of the FSK WRAP
building insulation 1/2", 2.0 lb/cu ft
envelope (Min. R-11). Duct Liner
` 1/2", Type 475 or
Examples: 800 Duct Board
or equivalent to
A. Equipment provide an installed
rooms, shaft conductance = 0.48
enclosures, and
floor or roof
ceiling spaces.
8. Floor or roof
ceiling spaces
when used as a
duct or plenum
(See Note 1).
SUPPLY DUCT systems
located in under floor
crawl spaces.
4. SUPPLY and RETURN
DUCT systems located
in non-concealed
conditioned spaces.
RETURN DUCT SYSTEM
in all locations not
listed above NONE REQUIRED
(including) return
ducts in under-floor
crawl spaces).
NOTE 1: Insulation may be omitted on a maximum of
six (6) feet length of branch or run-out
ducts to a ceiling air diffuser and on the
diffuser when located in building spaces
used as a return air duct or plenum.
-41-
OfElClAL RECORD
CITY SEGR~E~'ARY
ET. WORTl~, ~~,X.
SECTION 2502
Piping Insulation
EXt-IIBIT "B"
Sec. 2502(a) Pipe In Buildiags. All piping requiring
insulation installed to serve buildings and within buildings shall
be thermally insulated in accordance with Table 25-G and this
section.
Pipe insulation or jackets used on steam or hot-water pipes
shall be of noncombustible materials. Composite of insulation or
jackets and lap-seal adhesives shall have a flame spread of not
greater than 25 and a smoke developed rating of not greater than
50. (See Table 5-A, Footnote No. 6j.
EXCEPTION: Piping underground or outside the structure need
not meet the 25/50 flame and smoke requirement.
O~~IGIAL REGDRD
G(~1( SEGR~TARY
-42- ~ F~. W~e~~ ~~X.
` ~ ~ EXHIBIT "B"
iJ
O
N ~ \ M N N N ri
N
.C p
~7 1 j
~ ~ M ~ ~
1
H H
O N ~
•rl 41
N -.~ ~ \ ~"~ N rl N
~ ~..~ N
~
O N ~ j i ;
,sC fL ~ M ~ rl
U •~
•.~
~+
H a
~ ~
I
N
N
~
N
~
N
\
ri
N
~
,..I
~
w
O
.,~ 1
N N N H ~
~"~ dl
~ H
y
}~
d ro
e-~1
N
N
d'
N
N
N
H
rl
i
sr ~
-r~
N
G)
H
.-i ~
H
I \
c'1 \
ei N
.
~
r•i I H
H
~ ~
y
a •.~i
~
~ O ~ to ~ ~ .~ ~ rl N
~ ,.~ U
k
N ~ b ~ ei ~ ~ ~
o`~o ~ ~
a a --
E~ H
N
~ ~ O
H N N
~ e-i N
\ r-I '
N ~
r•i •rl
•
a O =
N H ~ ~ ~m
~
a ~ ,~ ~ ~+ a,
~ ~
~ ~ m
5E: ~
a w o an o o •oa H w
~ ~ b ~ ~ ca
w ~ +
ro ~
° .~
'~ .~
o o
N
~
°~ ~ b
a b o
a N N e-1
~
H •~ GJ
'd U1
O ~
~
m O
~ ~
d
to
>'+
O H
O A
~
C~! i~ Gf 3.1 Cl ~ Q1 O ~
~ N
0 b
3 y ~ ~
~
N ao
~ ~
b ~
IA f'a
~ m
Q) fr
~ ~
~ m
1.1
>`I a
i
b
b N
?r ~
b +~
~ ~ ~
~
~ tn 3 u1 ~ fr y to ~ m O O ~ 3 b Or
~+
~
m a
•~
~ a a~ ~ a~ ~ :a d ~ ~ ~
~ ~Q
a a s a m H ~ ~ •~ ~ '~°
'~ ~+ ~ ~ •~ H ~ H O ~ O ~ ~ O ~ C1 (~ ~~~~~~e~1.~a!
a x cn x ~ a H a ~ v v a
FT. i~Y9\~.ls N~e
- 43-
s
t
• E~i-IIBIT "B"
NOTE: Piping insulation is not required in any of the
following cases:
1. Factory piping installed, within HVAC equipment.
2. Piping at temperatures between 65°F and 120°F.
3. Piping installed under slabs, in basements, cellars or
unventilated crawl .spaces with insulated walls in one and two-
family dwellings.
(b) Other Pipe Insulation Thicknesses. Insulation
thicknesses in Table 25-G are based on insulation having thermal
resistances in the range of 4.0 to 4.6 per inch of thickness on a
flat surface at a mean temperature of 75°. Minimum insulation
thickness shall be increased for materials having R values less
than 4.0 or may be reduced for materials having R values greater
than 4.6 per inch of thickness.
1. For materials with thermal resistance greater than R -
4.6, the minimum insulation thickness may be reduced as follows:
4.6 X Table 25-G Thickness = New Minimum Thickness
Actual R
2. For materials with thermal resistance Iess than R = 4.0,
the minimum insulation thickness shall be increased as follows:
4_ 0 X Table 25-G Thickness New Minimum Thickness
Actual R
(c) Vapor Barrier. Chilled water, refrigerant, and brine
lines shall be insulated with a material which will have a
continuous vapor barrier, to eliminate condensation in an ambient
air temperature of 90°F, 80 percent relative humidity in zero air
velocity. Barrier shall not be penetrated by pipe supports.
1. Except as otherwise noted, underground piping conveying
a vapor or fluid which will be used to provide heating or cooling
shall be insulated, vapor sealed and water-proofed.
2. Underground pipe insulation shall be coat ith an
a roved fibrous mastic coatin g °'""~"
pp g, at a rate of 1 a z
FT. ~V~~~' ~~a
~ ~-
6
square feet of outer insulation surface. Apply with spray, glove
or brush. After four hours, apply a second coat at the same rate
--and embed a layer of glass fabric into the mastic. After 3-4
hours, a final coating of mastic shall be applied at the same rate
to completely cover the glass fabric.
(d) Condensate Drain Pipes. Condensate drain lines shall be
insulated with a minimum of 3/8 inch thickness of foamed plastic,
rubber based foam or other approved insulation which shall be
installed on ~7iping material without longitudinal cuts. Circular
joints shall be sealed with an approved adhesive.
(e) Humidifier Water Lines. Humidifier water supply pipe
installed in spaces exposed to outside air temperature shall be
insulated with a minimum of 3/8 inch thickness of foamed plastic,
rubber based foam, or other approved insulation. All joints shall
be sealed.
OF~IC~AL RE CCCC RA
CIS SE~'~~'~~R~
-45-
FT. W~ ~ ~, ~ ~~.
C~~y of Fort Worth, texas
Mayor and' Council C~crrrtmunication
DATE REFERENCE NUMBER LOG NAME PAGE
02/23/93 G-10061 06MECH 1 of 1
SUBJECT ORDINANCE ADOPTING 1991 UNIFORM MECHANICAL CODE AND AMENDMENTS THERETO
t
4
RECOMMENDATION:
It is recommended that the City Council adopt the attached ordinance (constituting the
1991 Uniform Mechanical Code with local amendments) as the Mechanical Cade of the City
of Fort Worth.
DISCUSSION:
Attached is the proposed ordinance adopting the 1991 Uniform Mechanical Code. This is
in keeping with the policy of regularly updating the Mechanical Cade of the City of
Fort Worth..
The Mechanical Board .has revised the ordinance to include changes primarily for the
purpose of clarification and,to gain a closer uniformity with the Uniform Mechanical
Code.
All during their review of the UMC, the Board considered each item in the basic code
to insure:
a) that requirements are necessary to provide a minimal level of safety, and
b) the most economical way to ach ieve the minimal level of safety was reached,
and
c) consideration was given to optimize the desires of Council to encourage
development and construction.
A Public Hearing was held by the Mechanical Board of Appeals on Tuesday, January 12,
1993. No one appeared in apposition to the proposed ordinance, therefore, the
Mechanical Board recommends City Council adoption.
MG:z
QFFlCIAI RECORD
C1~Y SF,CR~TARY
~'. WORTN, ~E~.
Subtoitted for City Manager's FUND ACCOUNT CENTER AMOUNT CITY SECRETARY
Office by: to
APp~~V
Mike Groomer 6140 IVV~
CITY G Q U L
Originating Department Head
F
MAR 11 T993
Joe Bilardi 8901 from
i
'
Adop ed. Qcd
and
For Additional Inforlpation
City Seca~taa<ry of the
Contact ~; Citp of Fort Worih, Vexes
Joe Bilardi 8901
~~ Printed on recycled papgr